Heat & Glo 6000CLX-IPI-S User Manual

Models: 6000CLX-IPI-T 6000CLX-IPILP-T 6000CLX-IPI-S 6000CLX-IPILP-S 8000CLX-IPI-T 8000CLX-IPILP-T 8000CLX-IPI-S 8000CLX-IPILP-S
Owner’ s Manual
Installation and Operation
NOTICE
DO NOT DISCARD THIS MANUAL
• Important operating and maintenance instructions included.
WARNING: If the information in these instructions is not followed exactly, a fi re or explosion may result causing property damage, personal injury, or death.
DO NOT store or use gasoline or other fl am- mable vapors and liquids in the vicinity of this or any other appliance.
• What to do if you smell gas
- DO NOT try to light any appliance.
NOT use any phone in your building.
- Immediately call your gas supplier from a
neighbor’s phone. Follow the gas suppli­er’s instructions.
- If you cannot reach your gas supplier, call
the fi re department.
• Installation and service must be performed by a qualifi ed installer, service agency , or the gas supplier.
This appliance may be installed as an OEM installation in manufactured home (USA only) or mobile home and must be installed in accordance with the manufacturer’s instructions and the manufactured home construction and safety standard,
Title 24 CFR, Part 3280 or Standard for Installation in Mobile Homes, CAN/CSA Z240MH, in Canada.
This appliance is only for use with the type(s) of gas indicated on the rating plate.
• Read, understand and follow these instructions for safe installation and operation.
DO NOT
DISCARD
• Leave this manual with party responsible for use and operation.
WARNING
HOT SURFACES!
Glass and other surfaces are hot during operation AND cool down.
Hot glass will cause burns.
DO NOT touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other fl ammable materials.
• Keep clothing, furniture, draperies and other fl ammable materials away.
This appliance has been supplied with an integral barrier to prevent direct contact with the fi xed glass panel. DO NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one.
In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fi tter.
See Table of Contents for location of additional Commonwealth of Massachusetts requirements.
Installation and service of this appliance should be performed by qualifi ed personnel. Hearth & Home Technologies suggests NFI certifi ed or factory trained professionals, or technicians supervised by an NFI certifi ed professional.
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/09
1
Read this manual before installing or operating this appliance.
Please retain this owner’s manual for future reference.
A. Congratulations
Congratulations on selecting a Heat & Glo gas fi replace, an elegant and clean alternative to wood burning fi replaces. The Heat & Glo gas fi replace you have selected is designed to provide the utmost in safety, reliability, and effi ciency.
As the owner of a new fi replace, you’ll want to read and carefully follow all of the instructions contained in this owner’s manual. Pay special attention to all cautions and warnings.
Homeowner Reference Information
This owner’s manual should be retained for future reference. We suggest that you keep it with your other important documents and product manuals.
The information contained in this owner’s manual, unless noted otherwise, applies to all models and gas control systems.
Your new Heat & Glo gas fi replace will give you years of durable use and trouble-free enjoyment. Welcome to the Heat & Glo family of fi replace products!
We recommend that you record the following pertinent information about your fi replace.
Model Name: ___________________________________________ Date purchased/installed: __________________ Serial Number: __________________________________________ Location on fi replace: _____________________ Dealership purchased from: _______________________________ Dealer Phone: __________________________ Notes: _______________________________________________________________________________________ _____________________________________________________________________________________________
Listing Label Information/Location
This product may be covered by one or more of the following patents: (Nos produits sont couverts par un ou plusieurs des brevets suivants): (United States) 4593510,4686807, 4766876, 4793322, 4811534, 5000162, 5016609, 5076254, 5113843, 5191877, 5218953, 5263471, 5328356, 5341794, 5347983, 5429495, 5452708,5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237,5947112,5996575, 6006743, 6019099, 6048195, 6053165, 6145502, 6170481, 6237588, 6296474, 6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940, 6748942, D320652, D445174, D462436; (Canada)1297749, 2195264, 2225408; or other U.S. and foreign patents pending (ou autresbrevetsamericainsetetrangers en attente).
Type of Gas
NotNot for for use use withwith solid solid fuel.fuel. ((NeNe doitdoit pas pas entre entre utilise utilise avecavec un un combustible combustible solide).solide).
Type Type ofof Gas Gas (Sorte(Sorte DeDe Gaz)Gaz)::
NNAATURALTURAL GASGAS
Gas and Electric Information
Minimum Minimum Permissible Permissible Gas Gas SupplySupplyfor for PurposesPurposes ofof Input Input Adjustment.Adjustment. ApprovedApproved Minimum Minimum (De (De Gaz)Gaz)AcceptableAcceptable 0.00.0inin w.c.w.c. (Po.(Po.Col.Col. d’eau)d’eau) Maximum Maximum PressurePressure(Pression)(Pression) 0.00.0inin w.c.w.c. (Po.(Po.Col.Col. d’eau)d’eau) Maximum Maximum ManifoldManifoldPressurePressure(Pression)(Pression) 0.00.0 inin w.c.w.c. (Po.(Po.Col.Col.d’eau)d’eau) Minimum Minimum ManifoldManifold PressurePressure(Pression)(Pression) 0.00.0 inin w.c.w.c. (Po.(Po.Col.Col. d’eau)d’eau) Total Total ElectricalElectrical Requirements: Requirements: 000Vac, 000Vac, 00Hz.,00Hz.,lesslessthanthan0000AmperesAmperes
ALTITUDE:ALTITUDE: 0-0000 0-0000 FT.FT. 0000-0000FT.0000-0000FT. MAX.MAX.INPUT INPUT BTUH:BTUH: 00,00000,000 00,00000,000 MIN.MIN. INPUT INPUT BTUH:BTUH: 00,00000,000 00,00000,000 ORIFICE ORIFICE SIZE:SIZE: #XXXXX#XXXXX #XXXXX#XXXXX
The model information regarding your specifi c fi replace can be found on the rating plate usually located in the control area of the fi replace.
Heat & Glo, a brand of Hearth & Home Technologies, Inc. 7571 215th Street West, Lakeville, MN 55044
ThisThisappliance appliance mustmust bebeinstalled installed inin accordanceaccordance withwith local local codes,codes, ifif any;any; ifif not,not, follow follow ANSIANSIZ223.1Z223.1 ininthe the USA USA ororCAN/CGA CAN/CGA B149 B149 installation installation codes.codes.(Installer (Installer l’appareill’appareil selon selon leslescodes codes ouou reglementsreglements
locauxlocaux ou,ou, enen l’absencel’absence dede telstels reglements, reglements, selon selon les les codescodes d’installationd’installation CAN/CGA-B149.)CAN/CGA-B149.)
ANSIANSIZ21XX-XXXXZ21XX-XXXX · · CSA CSA 2.XX-MXX2.XX-MXX · · UL307BUL307B
ININCANADACANADA
Model:Model:
(Modele):(Modele):
SerialSerial
(Serie):(Serie):
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
MADEMADE ININ USAUSA
Model Number
Serial Number
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/092
Safety Alert Key:
• DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury.
• WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury.
• CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
• NOTICE: Used to address practices not related to personal injury.
Table of Contents
A. Congratulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
B. Limited Lifetime Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1 Listing and Code Approvals
A. Appliance Certifi cation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
B. Glass Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
C. BTU Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
D. High Altitude Installations . . . . . . . . . . . . . . . . . . . . . . . . . . 7
E. Non-Combustible Materials Specifi cation. . . . . . . . . . . . . . 7
F. Combustible Materials Specifi cation . . . . . . . . . . . . . . . . . 7
G. Electrical Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
H. Requirements for the Commonwealth of Massachusetts . . 8
User Guide
2 Operating Instructions
A. Gas Fireplace Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
B. Your Fireplace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
C. Fan Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
D. Clear Space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
E. Decorative Doors and Fronts . . . . . . . . . . . . . . . . . . . . . . 10
F. Fixed Glass Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
G. Remote Controls, Wall Controls and Wall Switches . . . . . 10
H. Before Lighting Fireplace . . . . . . . . . . . . . . . . . . . . . . . . . 10
I. Lighting Instructions (IPI) . . . . . . . . . . . . . . . . . . . . . . . . . 11
J. After Fireplace is Lit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
K. Frequently Asked Questions . . . . . . . . . . . . . . . . . . . . . . 12
3 Maintenance and Service
A. Maintenance Tasks-Homeowner . . . . . . . . . . . . . . . . . . . 13
B. Maintenance Tasks-Qualifi ed Service Technician . . . . . . 14
C. Refractory, Grate and Valve Assembly Removal . . . . . . . 15
D. Burner Identifi cation/Verifi cation . . . . . . . . . . . . . . . . . . . . 16
Installer Guide
4 Getting Started
A. Typical Appliance System. . . . . . . . . . . . . . . . . . . . . . . . . 17
B. Design and Installation Considerations . . . . . . . . . . . . . . 18
C. Tools and Supplies Needed . . . . . . . . . . . . . . . . . . . . . . . 18
D. Inspect Appliance and Components . . . . . . . . . . . . . . . . . 18
5 Framing and Clearances
A. Selecting Appliance Location . . . . . . . . . . . . . . . . . . . . . . 19
B. Constructing the Appliance Chase . . . . . . . . . . . . . . . . . . 20
C. Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
D. Mantel and Wall Projections . . . . . . . . . . . . . . . . . . . . . . . 21
6 Termination Locations
A. Vent Termination Minimum Clearances . . . . . . . . . . . . . . 22
7 Vent Information and Diagrams
A. Approved Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
B. Vent Table Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
C. Use of Elbows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
D. Measuring Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
E. Vent Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
8 Vent Clearances and Framing
A. Pipe Clearances to Combustibles . . . . . . . . . . . . . . . . . . 35
B. Wall Penetration Framing . . . . . . . . . . . . . . . . . . . . . . . . . 35
C. Install the Ceiling Firestop . . . . . . . . . . . . . . . . . . . . . . . . 36
D. Install Attic Insulation Shield . . . . . . . . . . . . . . . . . . . . . . . 37
E. Installing the Optional Heat-Zone-Gas Kit . . . . . . . . . . . . 37
9 Appliance Preparation
A. Top Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
B. Rear Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
C. Installing the Non-combustible Board. . . . . . . . . . . . . . . . 40
D. Securing and Leveling the Appliance . . . . . . . . . . . . . . . . 40
10 Installing Vent Pipe (DVP and SLP Pipe)
A. Assemble Vent Sections (DVP Pipe Only) . . . . . . . . . . . . 41
B. Assemble Vent Sections (SLP Pipe Only) . . . . . . . . . . . . 42
C. Assemble Slip Sections . . . . . . . . . . . . . . . . . . . . . . . . . . 42
D. Secure the Vent Sections . . . . . . . . . . . . . . . . . . . . . . . . . 43
E. Disassemble Vent Sections . . . . . . . . . . . . . . . . . . . . . . . 43
F. Install Decorative Ceiling Components (SLP only) . . . . . . 44
G. Install Metal Roof Flashing . . . . . . . . . . . . . . . . . . . . . . . . 45
H. Assemble and Install Storm Collar . . . . . . . . . . . . . . . . . . 45
I. Install Vertical Termination Cap . . . . . . . . . . . . . . . . . . . . 46
J. Install Decorative Wall Components (SLP only) . . . . . . . . 46
K. Heat Shield Requirements for Horizontal Termination . . . 46 L. Install Horizontal Termination Cap (DVP and SLP Pipe) . 47
11 Gas Information
A. Fuel Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
B. Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
C. Gas Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
D. High Altitude Installations . . . . . . . . . . . . . . . . . . . . . . . . . 48
12 Electrical Information
A. Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
B. IntelliFire Plus
C. Optional Accessories Requirements . . . . . . . . . . . . . . . . 49
D. Electrical Service and Repair . . . . . . . . . . . . . . . . . . . . . . 50
E. Junction Box Installation. . . . . . . . . . . . . . . . . . . . . . . . . . 50
F. Wall Switch Installation for Fan . . . . . . . . . . . . . . . . . . . . 50
G. Control Module Operation . . . . . . . . . . . . . . . . . . . . . . . . 51
TM
Ignition System Wiring . . . . . . . . . . . . . . 49
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/09
3
13 Finishing
A. Mantel and Wall Projections . . . . . . . . . . . . . . . . . . . . . . . 52
B. Facing Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
C. Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
D. Elevated Hearth Systems . . . . . . . . . . . . . . . . . . . . . . . . . 56
14 Appliance Setup
A. Remove Fixed Glass Assembly . . . . . . . . . . . . . . . . . . . . 57
B. Remove the Shipping Materials . . . . . . . . . . . . . . . . . . . . 57
C. Clean the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
D. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
E. Burner Top Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
F. Refractory Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
G. Ember Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
H. Teco-Sil Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
I. Install the Log Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . 61
J. Fixed Glass Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
K. Install Trim and/or Surround . . . . . . . . . . . . . . . . . . . . . . . 65
L. Air Shutter Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
15 Troubleshooting
A. IntelliFire Plus™ Ignition System . . . . . . . . . . . . . . . . . . . 66
16 Reference Materials
A. Appliance Dimension Diagram . . . . . . . . . . . . . . . . . . . . . 68
B. Vent Components Diagrams . . . . . . . . . . . . . . . . . . . . . . 70
C. Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
D. Contact Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Î = Contains updated information.
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/094
B. Limited Lifetime Warranty
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/09
5
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/096
1
1
Listing and Code Approvals
A. Appliance Certifi cation
MODELS: 6000CLX-IPI, 6000CLX-IPILP, 8000CLX-IPI, 8000CLX-IPILP
LABORATORY: Underwriters Laboratories, Inc. (UL) TYPE: Direct Vent Gas Appliance Heater
STANDARD:
This product is listed to ANSI standards for “Vented Gas Appliance Heaters” and applicable sections of “Gas Burn­ing Heating Appliances for Manufactured Homes and Recreational Vehicles”, and “Gas Fired Appliances for Use at High Altitudes”.
NOTICE: This installation must conform with local codes. In the absence of local codes you must comply with the National Fuel Gas Code, ANSI Z223.1-latest edition in the U.S.A. and the CAN/CGA B149 Installation Codes in Canada.
NOT INTENDED FOR USE AS A PRIMAR Y HEAT SOURCE.
This appliance is tested and approved as either supplemen­tal room heat or as a decorative appliance. It should not be factored as primary heat in residential heating calculations.
ANSI Z21.88b-2008 • CSA 2.33a-2008
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction.
When installing above 2000 feet elevation:
• In the USA: Reduce input rate 4% for each 1000 feet above 2000 feet.
• In CANADA: Reduce input rate 10% for elevations between 2000 feet and 4500 feet. Above 4500 feet, consult local gas utility.
Check with your local gas utility to determine proper orifi ce size.
E. Non-Combustible Materials Specifi cation
Material which will not ignite and burn. Such materials are those consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 ºC and UL763 shall be
considered non-combustible materials.
B. Glass Specifi cations
This appliance is equipped with 5 mm ceramic glass. Re­place glass only with 5 mm ceramic glass. Please contact your dealer for replacement glass.
C. BTU Specifi cations
Models
(U.S. or Canada)
6000CLX-IPI (NG)
6000CLX-IPILP
8000CLX-IPI (NG)
US
(0-2000 FT)
CANADA
(2000-4500 FT)
US
(0-2000 FT)
CANADA
(2000-4500 FT)
US
(0-2000 FT)
CANADA
(2000-4500 FT)
US
(0-2000 FT)
Maxi­mum Input
BTU/h
40,000 22,000
36,000 19,800 32
40,000 21,000 49
36,000 18,900 50
45,000 22,000 30
40,500 19,800 31
45,000 23,000 47
Mini­mum Input
BTU/h
Orifi ce
Size
(DMS)
0.124 in.
F. Combustible Materials Specifi cation
Materials made of or surfaced with wood, compressed pa­per, plant fi bers, plastics, or other material that can ignite and burn, whether fl ame proofed or not, or plastered or unplastered shall be considered combustible materials.
G. Electrical Codes
NOTICE: This appliance must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with National Electric Code ANSI/NFPA
70-latest edition or the Canadian Electric Code CSA C22.1.
• A 110-120 VAC circuit for this product must be protected with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks.
8000CLX-IPILP
CANADA
(2000-4500 FT)
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/09
40,500 20,700 48
7
Note: The following requirements reference various Massachuset ts and national codes not contained in this document.
H. Requirements for the Commonwealth of
Massachusetts
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above fi nished grade in the area of the venting, in- cluding but not limited to decks and porches, the following requirements shall be satisfi ed:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fi tter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the fl oor level where the gas equipment is to be installed. In addi­tion, the installing plumber or gas fi tter shall observe that a battery operated or hard wired carbon monoxide detec­tor with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualifi ed licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fu­eled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent oor level. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that dur­ing said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Inspection
The state or local gas inspector of the side wall horizon­tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector ob­serves carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fu­eled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
• Detailed instructions for the installation of the venting system design or the venting system components; and
• A complete parts list for the venting system design or venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not pro­vide the parts for venting the fl ue gases, but identifi es “special venting systems”, the following requirements shall be satisfi ed by the manufacturer:
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accor­dance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certifi ed.
Signage
A metal or plastic identifi cation plate shall be permanent- ly mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fu­eled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) in. in size, “GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB­STRUCTIONS”.
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/098
• The referenced “special venting system” instructions shall be included with the appliance or equipment in­stallation instructions; and
• The “special venting systems” shall be Product Ap­proved by the Board, and the instructions for that sys­tem shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Ap­proved side wall horizontally vented gas fueled equip­ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
See Gas Connection section for additional Common­wealth of Massachusetts requirements.
2
2
Operating Instructions
User Guide
A. Gas Fireplace Safety
WARNING
HOT SURFACES!
Glass and other surfaces are hot during operation AND cool down.
Hot glass will cause burns.
DO NOT touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other ammable materials.
• Keep clothing, furniture, draperies and other fl ammable materials away.
This appliance has been supplied with an integral barrier to prevent direct contact with the fi xed glass panel. DO NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one.
If you expect that small children or vulnerable adults may come into contact with this fi replace, the following precau- tions are recommended:
• Install a physical barrier such as:
- A decorative fi rescreen.
- Adjustable safety gate.
• Install a switch lock or a wall/remote control with child protection lockout feature.
• Keep remote controls out of reach of children.
• Never leave children alone near a hot fi replace, whether operating or cooling down.
• Teach children to NEVER touch the fi replace.
• Consider not using the fi replace when children will be present.
Contact your dealer for more information, or visit: www. hpba.org/staysafe.
T o prevent unintended operation when not using your fi re- place for an extended period of time (summer months, vacations, trips, etc):
• Remove batteries from remote controls.
• Turn off wall controls.
• Unplug 6 volt transformer plug and remove batteries on IPI models.
• Turn off gas controls valve on standing pilot models.
When lighting the pilot light on fi replaces with a standing pilot, remove the fi xed glass assembly so you can de- tect presence of residual gas build-up. See Standing Pilot Lighting instructions and Maintenance Tasks.
B. Your Fireplace
WARNING! DO NOT operate fi replace before read- ing and understanding operating instructions. Failure
to operate fi replace according to operating instructions could cause fi re or injury.
Figure 2.1 General Operating Parts
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/09
FAN KIT
SECTION 2.C.
DECORATIVE DOORS
(NOT SHOWN)
SECTION 2.E.
CLEAR SPACE
SECTION 2.D.
FIXED GLASS ASSEMBLY
(NOT SHOWN) SECTION 14.J.
HEARTH
SECTION 3.C.
GRATE
MANTEL
SECTION 5.D
9
C. Fan Kit
A fan is shipped with this appliance.
F. Fixed Glass Assembly
See Section 14.J.
D. Clear Space
WARNING! DO NOT place combustible objects in front of the fi replace or block louvers. High temperatures may start a fi re. See Figure 2.2.
A void placing candles and other heat-sensitive objects on mantel or hearth. Heat may damage these objects.
3 FT. IN FRONT OF FIREPLACE
CLE
AR SPACE
Figure 2.2 Clear Space
E. Decorative Doors and Fronts
WARNING! Risk of Fire! Install ONLY doors or fronts approved by Hearth & Home Technologies. Unapproved doors or fronts may cause fi replace to overheat.
This fireplace has been supplied with an integral barrier to prevent direct contact with the fi xed glass panel. DO NOT operate the fi replace with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one.
G. Remote Controls, Wall Controls and Wall
Switches
Follow the instructions supplied with the control installed to operate your fi replace:
For safety:
• Install a switch lock or a wall/remote control with child protection lockout feature.
• Keep remote controls out of reach of children.
See your dealer if you have questions.
H. Before Lighting Fireplace
Before operating this replace for the rst time, have a qualifi ed service technician:
• Verify all shipping materials have been removed from inside and/or underneath the fi rebox.
• Review proper placement of logs, ember material and/or other decorative materials.
• Ensure plastic fi nishing strips have been removed after use for incorporating fi nishing materials.
• Check the wiring.
• Check the air shutter adjustment.
• Ensure that there are no gas leaks.
• Ensure that the glass is sealed and in the proper position and that the integral barrier is in place.
WARNING! Risk of Fire or Asphyxiation! DO NOT op­erate fi replace with fi xed glass assembly removed.
For more information refer to the instructions supplied with your decorative door or front.
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/0910
I. Lighting Instructions (IPI)
FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a re or explosion
may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an
intermittent pilot ignition (IPI) device which automatically lights the burn­er. DO NOT try to light the burner by hand.
B. BEFORE LIGHTING, smell all around
the appliance area for gas. Be sure to smell next to the fl oor because some gas is heavier than air and will settle on the fl oor.
WHA T TO DO IF YOU SMELL GAS
DO NOT try to light any appliance.
DO NOT touch any electric switch; do not use any phone in your building.
WARNING:
DO NOT CONNECT LINE VOLT­AGE (110/120 VAC OR 220/240 V AC) TO THE CONTROL VAL VE.
Improper installation, adjustment, al­teration, service or maintenance can cause injury or property damage. Re­fer to the owner’s information manual provided with this appliance.
This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air.
If not installed, operated, and main­tained in accordance with the manufac­turer’s instructions, this product could expose you to substances in fuel or fuel combustion which are known to the State of California to cause cancer, birth defects, or other reproductive harm.
Keep burner and control compartment clean. See installation and operating instructions accompanying appliance.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas sup­plier, call the fi re department.
C. DO NOT use this appliance if any
part has been under water. Imme­diately call a qualifi ed service tech- nician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
CAUTION:
Hot while in operation. DO NOT touch. Keep children, clothing, furniture, gaso­line and other liquids having fl ammable vapors away.
DO NOT operate the appliance with xed glass assembly removed, cracked or broken. Replacement of the fi xed glass assembly should be done by a licensed or qualifi ed service person.
NOT FOR USE
WITH SOLID FUEL
For use with natural gas and propane. A conversion kit, as supplied by the manufacturer, shall be used to convert this appliance to the alternate fuel.
Also Certifi ed for Installation in a Bedroom or a Bedsitting Room.
For assistance or additional informa­tion, consult a qualifi ed installer, ser- vice agency or the gas supplier.
LIGHTING
INSTRUCTIONS (IPI)
1. This appliance is equipped with an ignition
device which automatically lights the burner.
DO NOT try to light the burner by hand.
GAS
VALVE
2. Wait ve (5) minutes to clear out any gas.
Then smell for gas, including near the fl oor. If you smell gas, STOP! Follow “B” in the Safety Information located on the left side of this la­bel. If you do not smell gas, go to next step.
3. To light the burner: Equipped with wall switch: Turn ON/OFF switch
to ON.
Equipped with remote or wall control: Press
ON or FLAME button.
Equipped with thermostat: Set temperature to
desired setting.
4. If the appliance does not light after three tries, call your service technician or gas supplier.
TO TURN OFF
GAS TO APPLIANCE
1. Equipped with wall switch: Turn ON/OFF switch
to OFF.
Equipped with remote or wall control: Press
OFF button.
Equipped with thermostat: Set temperature to
lowest setting.
2. Service technician should turn off electric power to the control when performing service.
593-913G
Hearth & Home Technologies fi replace, please refer to www.fi replaces.com.
For additional information on operating your
Final inspection by
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/09
11
J. After Fireplace is Lit
Initial Break-in Procedure
• The fireplace should be run three to four hours continuously on high.
• Turn the fi replace off and allow it to completely cool.
• Remove fi xed glass assembly. See Section 14.J.
• Clean fi xed glass assembly. See Section 3.
• Replace the fi xed glass assembly and run continuously on high an additional 12 hours.
This cures the materials used to manufacture the fi re- place.
NOTICE! Open windows for air circulation during fi re- place break-in.
• Some people may be sensitive to smoke and odors.
• Smoke detectors may activate.
K. Frequently Asked Questions
ISSUE SOLUTIONS
Condensation on the glass
Blue fl ames
Odor from appliance
Film on the glass
Metallic noise
Is it normal to see the pilot fl ame burn continually?
This is a result of gas combustion and temperature variations. As the appliance warms, this condensation will disappear.
This is a result of normal operation and the fl ames will begin to yellow as the appliance is al- lowed to burn for 20 to 40 minutes.
When fi rst operated, this appliance may release an odor for the fi rst several hours. This is caused by the curing of the paint and the burning off of any oils remaining from manufacturing. Odor may also be released from fi nishing materials and adhesives used around the appliance.
This is a normal result of the curing process of the paint and logs. Glass should be cleaned within 3 to 4 hours of initial burning to remove deposits left by oils from the manufacturing process. A non-abrasive cleaner such as gas fi replace glass cleaner may be necessary. See your dealer.
Noise is caused by metal expanding and contracting as it heats up and cools down, similar to the sound produced by a furnace or heating duct. This noise does not affect the operation or longevity of the appliance.
In an intermittent pilot ignition system (IPI), the pilot fl ame should turn off when appliance is turned off. Some optional control systems available with IPI models may allow pilot fl ame to remain lit.
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/0912
3
3
Maintenance and Service
Any safety screen or guard removed for servicing must be replaced prior to operating the fi replace.
When properly maintained, your fi replace will give you many years of trouble-free service. We recommend an­nual service by a qualifi ed service technician.
A. Maintenance Tasks-Homeowner
Installation and repair should be done by a qualifi ed service technician only. The fi replace should be inspected before use and at least annually by a professional service person.
The following tasks may be performed annually by the homeowner. If you are uncomfortable performing any of the listed tasks, please call your dealer for a service ap­pointment.
More frequent cleaning may be required due to lint from carpeting or other factors. Control compartment, burner and circulating air passageway of the fi replace must be kept clean.
CAUTION! Risk of Burns! The fi replace should be turned off and cooled before servicing.
Glass Cleaning
Frequency: Seasonally By: Homeowner Tools Needed: Protective gloves, glass cleaner, drop
cloth and a stable work surface.
CAUTION! Handle fi xed glass assembly with care.
Glass is breakable.
• Avoid striking, scratching or slamming glass
• Avoid abrasive cleaners
DO NOT clean glass while it is hot
• Prepare a work area large enough to accommodate fi xed glass assembly and door frame by placing a drop cloth on a fl at, stable surface.
Note: Fixed glass assembly and gasketing may have res­idue that can stain carpeting or fl oor surfaces.
• Remove door or decorative front from fi replace and set aside on work surface.
• See Section 14.J for instructions to remove fi xed glass assembly.
• Clean glass with a non-abrasive commercially available cleaner.
- Light deposits: Use a soft cloth with soap and water
- Heavy deposits: Use commercial fireplace glass
cleaner (consult with your dealer)
• Carefully set fi xed glass assembly in place on fi replace. Hold glass in place with one hand and secure glass latches with the other hand.
• Reinstall door or decorative front.
Doors, Surrounds, Fronts
Frequency: Annually By: Homeowner Tools needed: Protective gloves, stable work surface
• Assess condition of screen and replace as necessary.
• Inspect for scratches, dents or other damage and repair as necessary.
• Check that louvers are not blocked.
• Vacuum and dust surfaces.
Remote Control
Frequency: Seasonally By: Homeowner Tools needed: Replacement batteries and remote con-
trol instructions.
• Locate remote control transmitter and receiver.
• Verify operation of remote. Refer to remote control operation instructions for proper calibration and setup procedure.
• Place batteries as needed in remote transmitters and battery-powered receivers.
• Place remote control out of reach of children.
If not using your fi replace for an extended period of time (summer months, vacations/trips, etc), to prevent unin­tended operation:
• Remove batteries from remote controls.
• Unplug 6 volt transformer plug on IPI models.
• Remove battery backup from control module.
Venting
Frequency: Seasonally By: Homeowner Tools needed: Protective gloves and safety glasses.
• Inspect venting and termination cap for blockage or obstruction such plants, bird nests, leaves, snow, debris, etc.
• Verify termination cap clearance to subsequent construc­tion (building additions, decks, fences, or sheds). See Section 6.
• Inspect for corrosion or separation.
• Verify weather stripping, sealing and fl ashing remains intact.
• Inspect draft shield to verify it is not damaged or missing.
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/09
13
B. Maintenance Tasks-Qualifi ed Service
Technician
The following tasks must be performed by a qualifi ed ser- vice technician.
Gasket Seal and Glass Assembly Inspection
Frequency: Annually By: Quali ed Service Technician T ools needed: Protective gloves, drop cloth and a stable
work surface.
• Inspect gasket seal and its condition.
• Inspect fi xed glass assembly for scratches and nicks that can lead to breakage when exposed to heat.
• Confi rm there is no damage to glass or glass frame. Replace as necessary.
• Verify that fi xed glass assembly is properly retained and attachment components are intact and not damaged. Replace as necessary.
Logs
Frequency: Annually By: Quali ed Service Technician Tools needed: Protective gloves.
• Inspect for damaged or missing logs. Replace as neces­sary . Refer to Section 14 for log placement instructions.
• Verify correct log placement and no fl ame impingement causing sooting. Correct as necessary.
Firebox
Frequency: Annually By: Quali ed Service Technician Tools needed: Protective gloves, sandpaper, steel wool,
cloths, mineral spirits, primer and touch-up paint.
• Inspect for paint condition, warped surfaces, corrosion or perforation. Sand and repaint as necessary.
• Replace fi replace if fi rebox has been perforated.
Burner Ignition and Operation
Frequency: Annually By: Quali ed Service Technician T ools needed: Protective gloves, vacuum cleaner, whisk
broom, fl ashlight, voltmeter, indexed drill bit set, and a manometer.
• Verify burner is properly secured and aligned with pilot or igniter.
• Clean off burner top, inspect for plugged ports, corrosion or deterioration. Replace burner if necessary.
• Replace Glowing embers with new dime-size pieces. DO NOT block ports or obstruct lighting paths. Refer to Section 14 for proper ember placement.
• Verify batteries have been removed from battery back­up IPI systems to prevent premature battery failure or leaking.
• Check for smooth lighting and ignition carryover to all ports. Verify that there is no ignition delay.
• Inspect for lifting or other fl ame problems.
• Verify air shutter setting is correct. See Section 14 for required air shutter setting. Verify air shutter is clear of dust and debris.
• Inspect orifi ce for soot, dirt and corrosion. Verify orifi ce size is correct. See Service Parts List for proper orifi ce sizing.
• Verify manifold and inlet pressures. Adjust regulator as required.
• Inspect pilot fl ame pattern and strength. See Figures 3.1 for proper pilot fl ame pattern. Clean or replace orifi ce spud as necessary.
• Inspect IPI fl ame sensing rod for soot, corrosion and deterioration. Clean with emery cloth or replace as required.
• Verify that there is not a short in fl ame sense circuit by checking continuity between pilot hood and fl ame sensing rod. Replace pilot as necessary.
Control Compartment and Firebox Top
Frequency: Annually By: Quali ed Service Technician Tools needed: Protective gloves, vacuum cleaner, dust
cloths
• V acuum and wipe out dust, cobwebs, debris or pet hair. Use caution when cleaning these areas. Screw tips that have penetrated the sheet metal are sharp and should be avoided.
• Remove all foreign objects.
• Verify unobstructed air circulation.
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/0914
(Either cobrahead or SIT)
Figure 3.1 IPI Pilot Flame Patterns
C. Refractory, Grate and Valve Assembly
Removal
It may become necessary to remove the refractory, grate and valve assemblies. This task should be performed by a qualifi ed service technician. the refractory, grate and base refractory do not need to be removed to service the burner assembly.
Note: Refractory is Fragile.
Handle with care.
Figure 3.2 Side Refractory Removal
To remove the top refractory panel, lift the top refractory panel up using both hands, slide it forward as much as possible and carefully lower it.
To remove the side refractory panels, slide the panel for­ward as shown in Figure 3.2. Rotate the panels and re­move as shown in Figure 3.3. Remove the back refractory panel by lifting it over the burner assembly.
NOTICE: Remove refractory before removing grate. If grate is removed fi rst, damage to refractory will occur.
Figure 3.3 Side Refractory Removal
Note: The refractory must be removed
before removing the grate.
Figure 3.4 Grate Removal
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/09
15
Note: The base refractory must be removed to access screws.
BASE REFRACTORY
Figure 3.5 Base Refractory Removal
Figure 3.6 Valve Assembly Removal
D. Burner Identifi cation/Verifi cation
The burner may be accessed for identi cation and veri- cation purposes. This task should be performed by a
qualifi ed service technician. The base refractory, valve plate, refractory and grate do not need to be removed to access the burner assembly. The logs and fi ber burner top need to be removed to access the burner. Disconnect the pilot from the burner before removal. See Figure 3.7 for burner identifi cation chart. Notch patterns are located on bottom side of burner.
BURNER BOTTOM
NOTCH LOCATION
NG LP
6000C
6000CL
6000CLX
6000CBV
8000C
8000CL
8000CLX
8000CBV
Figure 3.7 Burner Identifi cation
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/0916
HORIZONTAL
TERMINATION CAP
(SECTION 10.L )
4
4
A. Typical Appliance System
NOTICE: Illustrations and photos refl ect typical installations and are for design purposes only . Illustrations/diagrams are not drawn to scale. Actual product may vary from pictures in manual
Getting Started
Note: Dual venting configurations ARE NOT allowed. Appliance MUST
be vented EITHER vertically OR horizontally.
VERTICAL TERMINATION CAP
(SECTION 10.I)
NON-COMBUSTIBLE ROOF FLASHING MAINTAINS MINIMUM CLEARANCE AROUND PIPE (SECTION 10.G)
STORM COLLAR (SECTION 10.H)
Installer Guide
VENT PIPE (SECTIONS 7 and 8)
CEILING FIRESTOP ON FLOOR OF ATTIC (SECTION 8.C)
FRAMING/HEADER (SECTION 5.B)
VENT PIPE PENETRATES ROOF PREFERABLY WITHOUT AFFECTING ROOF RAFTERS (SECTION 8.C)
ATTIC INSULATION SHIELD (NOT SHOWN) MUST BE USED HERE TO KEEP INSULATION AWAY FROM VENT PIPE IF ATTIC IS INSULATED (SECTION 8.D)
FRAMING HEADED OFF IN CEILING JOISTS (SECTION 8.C)
WALL SWITCH SECTION 12.C.
MANTEL AND MANTEL LEG (SECTION 5.D)
SURROUND
OPTIONAL
GAS LINE (SECTION 11)
Figure 4.1 Typical System
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/09
HEARTH EXTENSION
17
B. Design and Installation Considerations
Heat & Glo direct vent gas appliances are designed to operate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside. No additional outside air source is required.
Installation MUST comply with local, regional, state and national codes and regulations. Consult insurance carrier, local building inspector, fi re offi cials or authorities having jurisdiction over restrictions, installation inspection and permits.
Before installing, determine the following:
• Where the appliance is to be installed.
• The vent system confi guration to be used.
• Gas supply piping requirements.
• Electrical wiring requirements.
• Framing and fi nishing details.
• Whether optional accessories—devices such as a fan, wall switch, or remote control—are desired.
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. For assistance or additional information, consult a qualifi ed service technician, service agency or your dealer.
C. Tools and Supplies Needed
Before beginning the installation be sure that the following tools and building supplies are available.
Tape measure Framing material Pliers High temperature caulking material Hammer Phillips screwdriver Gloves Framing square Voltmeter Electric drill and bits (1/4 in.) Plumb line Safety glasses Level Reciprocating saw Manometer Flat blade screwdriver Non-corrosive leak check solution 1/2 - 3/4 in. length, #6 or #8 Self-drilling screws One 1/4 in. female connection (for optional fan).
D. Inspect Appliance and Components
• Carefully remove the appliance and components from the packaging.
• The vent system components and decorative doors and fronts may be shipped in separate packages.
• If packaged separately, the log set and appliance grate must be installed.
• Report to your dealer any parts damaged in shipment, particularly the condition of the glass.
Read all of the instructions before starting the instal-
lation. Follow these instructions carefully during the installation to ensure maximum safety and benefi t.
WARNING! Risk of Fire or Explosion! Damaged parts could impair safe operation. DO NOT install damaged, in­complete or substitute components. Keep appliance dry.
Hearth & Home T echnologies disclaims any responsibility for , and the warranty will be voided by, the following actions:
• Installation and use of any damaged appliance or vent
system component.
• Modifi cation of the appliance or vent system.
• Installation other than as instructed by Hearth & Home
Technologies.
• Improper positioning of the gas logs or the glass door.
• Installation and/or use of any component part not approved
by Hearth & Home Technologies.
Any such action may cause a fi re hazard.
WARNING! Risk of Fire, Explosion or Electric Shock! DO NOT use this appliance if any part has been under
water. Call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and/or gas control which has been under water.
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/0918
5
5
Framing and Clearances
A. Selecting Appliance Location
When selecting a location for the appliance it is important to consider the required clearances to walls (see Figure 5.1).
WARNING! Risk of Fire or Burns! Provide adequate clearance around air openings and for service access.
Due to high temperatures, the appliance should be locat­ed out of traffi c and away from furniture and draperies.
NOTE: THE REAR STANDOFF MAY NEED
TO BE REMOVED WHEN VENTING AT 45º
A
1/2 IN.
G
ALCOVE
INSTALLATION
A
B
C
TOP VENT
ONE 90º ELBOW
NOTICE: Illustrations refl ect typical installations and are FOR DESIGN PURPOSES ONLY. Illustrations/diagrams are not drawn to scale. Actual installation may vary due to individual design preference.
B
E
REAR VENT,
HORIZONTAL TERMINATION
TWO ELBOWS
B
D
H
ABCD E F G H
6000
8000
Figure 5.1 Appliance Locations - 6000 Models
in. 51 42 72 56-5/8
mm 1295 1067 1829 1438 559 451 203
in. 55-7/8 49 79 61-1/2
mm 1419 1245 2007 1562 559 502 254
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/09
REAR VENT
NO ELBOWS
B
Mantel Projections
Mantel Projections
ONE ELBOW
F
See Section D.
See Section D.
REAR VENT
B
D
D
22 17-3/4 8
22 19-3/4 10
19
B. Constructing the Appliance Chase
A chase is a vertical box-like structure built to enclose the gas appliance and/or its vent system. In cooler climates the vent should be enclosed inside the chase.
NOTICE: Treatment of ceiling restops and wall shield restops and construction of the chase may vary with the
type of building. These instructions are not substitutes for the requirements of local building codes. Therefore, you MUST check local building codes to determine the requirements to these steps.
Chases should be constructed in the manner of all out­side walls of the home to prevent cold air drafting prob­lems. The chase should not break the outside building envelope in any manner.
Walls, ceiling, base plate and cantilever fl oor of the chase should be insulated. Vapor and air infi ltration barriers should be installed in the chase as per regional codes for the rest of the home. Additionally, in regions where cold air infi ltration may be an issue, the inside surfaces may be sheetrocked and taped for maximum air tightness.
To further prevent drafts, the wall shield and ceiling fi re- stops should be caulked with high temperature caulk to seal gaps. Gas line holes and other openings should be caulked with high temperature caulk or stuffed with un­faced insulation. If the appliance is being installed on a cement surface, a layer of plywood may be placed under­neath to prevent conducting cold up into the room.
C. Clearances
NOTICE: Install appliance on hard metal or wood surfaces extending full width and depth. DO NOT install directly on carpeting, vinyl, tile or any combustible material other than wood.
WARNING! Risk of Fire! Maintain specifi ed air space clearances to appliance and vent pipe:
• Insulation and other materials must be secured to prevent accidental contact.
• The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fi replace or chimney.
• Failure to maintain airspace may cause overheating and a fi re.
B
C
D
A B C** D E F G H I J
Models
6000
8000
Rough
Opening
(Width)
in. 10 40-1/8 22 42 25 0 0 1/2 1/2 36
mm 254 1019 559 1067 635 0 0 13 13 914
in. 10 42-1/8 22 49 25 0 0 1/2 1/2 36
mm 254 1019 559 1245 635 0 0 13 13 914
* Adjust framing dimensions for interior sheathing (such as sheetrock)
C** Add 12 inches for rear venting with one 90º elbow.
Figure 5.2 Clearances to Combustibles
A
Rough Opening (Height)
F
* MINIMUM FRAMING DIMENSIONS
Rough
Opening
(Depth)
Rough
Opening
(Width)
Clearance
to Ceiling
Combustible
Floor
J
G
Combustible
Flooring
Behind
Appliance
I
Sides of
Appliance
E
H
Front of
Appliance
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/0920
D. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear­ances as specifi ed. Framing or fi nishing material closer than the minimums listed must be constructed entirely of noncom­bustible materials (i.e., steel studs, concrete board, etc).
Combustible Mantel Legs or Wall Projections
INTERIOR WALL
Combustible Mantels
3
2-1/2
Note: All measurements in inches.
12
11
10
9
8
7
6
5
4
13
12
11
10
5
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
16
15
14
18
17
TO CEILING
25
19
18
32
TOP VIEW
A
FIREPLACE OPENING
MANTEL LEG OR WALL PROJECTIONS
B
If A minimum is ____, then B maximum is_____.
Inches
A
B
Millimeters
Millimeters
2-7/16 3-7/16 4-7/16 5-7/16 6-7/16 7-7/16
62 87 113 138 164 189
Inches
12345
25 51 76 102 127
Figure 5.4 Clearances to Mantel Legs or Wall Projections (Acceptable on both sides of opening.)
Note: Measurement is taken from top of the
opening, NOT the top of the fi replace.
Figure 5.3 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/09
21
6
6
Termination Locations
A. Vent Termination Minimum Clearances
WARNING
Fire Risk. Maintain vent clearance to combustibles as
specifi ed.
DO NOT pack air space with insulation or other materials.
Failure to keep insulation or other materials away from vent pipe may cause overheating and fi re.
HORIZONTAL
OVERHANG
2 FT. MIN.
GAS DIRECT VENT TERMINATION CAP
20 INCHES MIN.
LOWEST
DISCHARGE
OPENING
H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING
X
12
ROOF PITCH
VERTICAL
WALL
IS X/ 12
6in.(minimum)upto20in.
AB
152mm/508mm
20 in. and over 0 in. minimum
18 in. minimum
457 mm
Gas, Wood or Fuel Oil
Termination Cap
B
A*
Gas
Termination
Cap **
If using decorative cap cover(s), this distance may need to be
*
increased. Refer to the installation instructions supplied with the decorative cap cover.
In a staggered installation with both gas and wood terminations, the
**
wood termination cap must be higher than the gas termination cap.
Roof Pitch H (Min.) Ft.
Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0
* 3 foot minimum in snow regions
Figure 6.1 Minimum Height From Roof To Lowest Discharge Opening
Figure 6.2 Staggered Termination Caps
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/0922
O
N
P
E
C
V
B
J
V
B
V
i
D
V
A
V
B
V
A
F
U.S
(3 FT.)
M
G
X
V
H or i
R
Q
(See Note 2)
Measure vertical clearances from this surface.
V
L
K
K
Electrical
V
Service
V
C
V
Measure horizontal clearances from this surface.
= VENT TERMINAL
V
X
= AIR SUPPLY INLET
A = 12 inches.................clearances above grade, veranda,
(See Note 1)
porch, deck or balcony
B = 12 inches.................clearances to window or door
that may be opened, or to perma­nently closed window. (Glass)
C = 18 inches.................vertical clearance to unventilated
soffi t or to ventilated soffi t located above the terminal
30 inches .................for vinyl clad soffi ts and below
electrical service
D = 9 inches...................clearance to outside corner
E = 6 inches...................clearance to inside corner
F = 3 ft. (Canada) ..........not to be installed above a gas
meter/regulator assembly within 3
feet (90 cm) horizontally from the
center-line of the regulator
G = 3 ft ...........................clearance to gas service regulator
vent outlet H = 9 inches (U.S.A.)
12 inches (Canada) clearance to non-mechanical
(See Note 2)
air supply inlet to building or the
combustion air inlet to any other
appliance i = 3 ft. (U.S.A.)
6 ft. (Canada) ...........clearance to a mechanical (pow-
(See Note 2)
** a vent shall not terminate directly above a sidewalk or paved driveway
which is located between two single family dwellings and serves both dwellings.
*** only permitted if veranda, porch, deck or balcony is fully open on a
minimum of 2 sides beneath the fl oor, or meets Note 2.
Note 1: On private property where termination is less than 7 feet above a sidewalk, driveway, deck, porch, veranda or balcony, use of a listed cap shield is suggested. (See vents components page)
Note 2: Termination in a covered alcove space (spaces open only on one side and with an overhang) are permitted with the dimensions specifi ed for vinyl or non-vinyl siding and soffi ts. 1. There must be 3 feet minimum between termination caps. 2. All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below the termination cap. 3. All gravity air intakes within 3 feet of a termination cap must be a minimum of 1 foot below the termination cap.
Figure 6.3 Minimum Clearances for Termination
ered) air supply inlet
= AREA WHERE TERMINAL IS NOT PERMITTED
J** = 7 ft. ......................... clearance above paved
(See Note 1)
sidewalk or a paved driveway located on public property
K = 6 inches................. clearance from sides of electri-
(See Note 5)
cal service
L = 12 inches................ clearance above electrical
(See Note 5)
service
Covered Alcove Applications
M*** = 18 inches .............clearance under veranda, porch,
42 inches ......... vinyl
N = 6 inches ........... non-vinyl sidewalls
12 inches ......... vinyl sidewalls
O = 18 inches ......... non-vinyl soffi t and overhang
42 inches ......... vinyl soffi t and overhang
P = 8 ft.
1 cap 3 feet 2 x Q 2 caps 6 feet 1 x Q 3 caps 9 feet 2/3 x Q 4 caps 12 feet 1/2 x Q
Q
= # termination caps x 3 R
MIN
Note 3: Local codes or regulations may require different
clearances. Note 4: Termination caps may be hot. Consider their proximity to
doors or other traffi c areas. Note 5: Location of the vent termination must not interfere with
access to the electrical service. In the U.S and Canada: Vent system termination is NOT permitted
in screened porches. Vent system termination is permitted in porch areas with two or more
sides open. You must follow all side walls, overhang and ground clearances as stated in the instructions.
Heat & Glo assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements.
deck, balcony or overhang
Q
MIN
= (2 / # termination caps) x Q
MAX
R
MAX
ACTUAL
ACTUAL
ACTUAL
ACTUAL
ACTUAL
CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED.
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/09
23
7
7
Vent Information and Diagrams
A. Approved Pipe
This appliance is approved for use with Hearth & Home T echnologies DVP or SLP venting systems. Refer to Sec­tion 16B for vent component information.
DO NOT mix pipe, fi ttings or joining methods from differ- ent manufacturers.
The pipe is tested to be run inside an enclosed wall. There is no requirement for inspection openings at each joint within the wall.
WARNING! Risk of Fire or Asphyxiation. This appli­ance requires a separate vent. DO NOT vent to a pipe serving a separate solid fuel burning appliance.
Vertical
12 in.
8-1/2 in.
8-1/2 in.
B. Vent Table Key
The abbreviations listed in this vent table key are used in the vent diagrams.
Symbol Description
First section (closest to appliance) of vertical length
V
1
Second section of vertical length
V
2
H H
First section (closest to appliance) of horizontal length
1
Subsequent sections of horizontal length
2
C. Use of Elbows
Diagonal runs have both vertical and horizontal vent as­pects when calculating the effects. Use the rise for the vertical aspect and the run for the horizontal aspect (see Figure 7.1).
Two 45º elbows may be used in place of one 90º elbow. On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216 mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A length of straight pipe is allowed between two 45º elbows (see Figure 7.1).
Horizontal
Figure 7.1
D. Measuring Standards
Vertical and horizontal measurements listed in the vent diagrams were made using the following standards.
• Pipe measurements are shown using the effective length of pipe (see Figure 7.2).
• Horizontal terminations are measured to the outside mounting surface (fl ange of termination cap) (see Figure
6.3).
• Vertical terminations are measured to bottom of termination cap.
• Horizontal pipe installed level with no rise.
Effective Length
Inches Millimeters
Effective
Height/Length
Pipe
DVP4 4 102
DVP6 6 152 DVP12 12 305 DVP24 24 610 DVP36 36 914 DVP48 48 1219 DVP6A 3 to 6 76 to 152
DVP12A 3 to 12 76 to 305 DVP12MI 3 to 12 76 to 305 DVP24MI 3 to 24 76 to 610
Figure 7.2 DVP Pipe Effective Length
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/0924
E. Vent Diagrams Top Vent - Horizontal Termination
Note: The 6000/8000 series fi replaces can adapt to SLP series
vent pipe, if desired.
When venting off the top of the unit, use a DVP-2SL adapter and a minimum 48 inch vertical section of SLP series vent pipe.
A DVP-SLP24 adapter may also be used with a 24 inch vertical section of SLP series vent pipe.
After the 48 inch vertical section, the venting table rules must be followed. The fi rst 48 inch vertical section is NOT counted as part of the vertical components in the table. It is still counted as part of the overall maximum run. All venting table rules for the vent run must still be followed.
Example: DVP pipe 3 ft. min. vertical = 11 ft. max. horizontal SLP pipe 7 ft. min. vertical = 11 ft. max. horizontal
Top Vent - Horizontal Termination
One Elbow
6000 MODELS
WARNING
Fire Risk. Explosion Risk. Do NOT pack insulation or other combustibles
between ceiling fi restops.
• ALW A YS maintain specifi ed clearances around venting and fi restop systems.
• Install wall shield and ceiling fi restops as speci- ed.
Failure to keep insulation or other material away from vent pipe may cause fi re.
WARNING
Fire Risk.
• When using DVP-HRC-SS and DVP-HRC-ZC­SS termination caps on top vented fi replaces, a 6 inch minimum vertical vent section is required before installing fi rst elbow.
8000 MODELS
V1 Minimum H1 Maximum
Elbow only 2 ft 610 mm 1 ft. 305 mm 3 ft. 914 mm 2 ft. 610 mm 6 ft. 1.8 m 3 ft. 914 mm 11 ft. 3.4 m 4 ft. 1.2 m 16 ft. 4.9 m 5 ft. 1.5 m 20 ft. 6.1 m
+ H1 = 40 ft. (12.2 m) Maximum
V
1
H1 = 20 ft. (6.1 m) Maximum
Note: For corner installations: A 6 inch (152 mm) section of straight pipe may need to be attached to the appliance before a 90º elbow, to allow the vent pipe to clear the top standoffs.
V
Minimum H1 Maximum
1
Elbow only 1 ft 305 mm 1 ft. 305 mm 3 ft. 914 mm 2 ft. 610 mm 6 ft. 1.8 m 3 ft. 914 mm 11 ft. 3.4 m 4 ft. 1.2 m 16 ft. 4.9 m 5 ft. 1.5 m 20 ft. 6.1 m
+ H1 = 40 ft. (12.2 m) Maximum
V
1
H1 = 20 ft. (6.1 m) Maximum
V
1
H
1
Figure 7.3
Heat & Glo • 6000CLX-IPI-S, 6000CLX-IPI-T, 8000CLX-S, 8000CLX-IPI-T • 2166-900 Rev. G • 12/09
25
Loading...
+ 57 hidden pages