Heatcraft Refrigeration Products TA, TL, VA, BBM, BBL User Manual

...
REACHIN UNIT COOLERS
Technical Guide
Models TA, TL, C, VA, BBM, BBL, KMK, RAMK, BTO & U
BNRITB
January 2004
(Replaces 107.2, 01/04)
Model TA Thin Prole Air Defrost ................................................................................................................... 3
Model TL Thin Prole Electric Defrost ..........................................................................................................
Model C High Prole ..........................................................................................................................................
Model VA Vee-Aire ..............................................................................................................................................
Models BBM/BBL Back Bar ...............................................................................................................................
Model KMK Kompact Mullion .........................................................................................................................
Model RAMK Reverse Air Flow Kompact Mullion ....................................................................................
Model BTO Twin Flow ......................................................................................................................................
Model U ................................................................................................................................................................
4
5
6
7
8
9
10
11
©2007 Heatcraft Refrigeration Products LLC
2
Model TA
Thin Prole Air Defrost Reach-In Unit Cooler
Features
• Textured aluminum cabinet
• Molded Lexan® guards and fans
• Drain tting mounted at 45-degree angle so drain can be run through back or bottom of refrigerator
• Room for expansion valve inside the unit
• Stainless steel screws
• Motors are thermally protected and permanently lubricated
• Convenient, moistureproof motor plug
• Compact design! Does a big job in a small space
• Optional Bohn-Kote® coated coil available (Model TAK) for optimum protection in corrosive environments
• Internal junction box for electrical connection
• All models are UL listed for the US and Canada
• UL classied to NSF standards
Sweat inlet connection to reduce leaks (are connection available as a ship loose option)
Application
Model TA is a thin prole unit which mounts in the top of
a refrigerator and makes the entire top shelf area usable. The attractive low silhouette makes the unit particularly desirable for display type refrigerators. It can also be used in back bars, under counter cabinets, or wherever space is at a premium.
For 35° to 45°F xtures at 10° to 15° TD applications with 16 hours maximum compressor run time per day.
Nomenclature
Thin Prole Air Defrost
TA (K) 17 B G
Bohn-Kote® Coil
(Optional)
Size
Vintage
Voltage A = 115/1/60 B = 208-230/1/60
Table 1. Performance and Electrical Data
Model
TA10 1,000 120 1 0.8 0.4 3/8 3/8 1/2 14 TA13 1,300 170 2 1.6 0.8 3/8 3/8 1/2 17 TA17 1,700 210 2 1.6 0.8 3/8 3/8 1/2 21 TA23 2,300 330 3 2.4 1.2 3/8 3/8 1/2 28
TA30 3,000 360 3 2.4 1.2 3/8 1/2 1/2 33 TA43 TA55
Models 43 and 55 use external equalized expansion valve
BTUH
10°F TD
4,300 540 4 3.2 1.6 1/2 5/8 1/2 44
5,500 650 5 4.0 2.0 1/2 5/8 1/2 53
CFM Qty.
Motor Data Connections (in.) Approx.
115/1/60
Total FLA
208-230/1/60
Total FLA
Coil Inlet
OD
SuctionIDDrain
OD
Table 2. Physical Data
Model
TA10 14-5/8 14 15/16 13-1/2 10-1/2 11-3/8 4-1/2 8-7/8 2-1/2 15/16 4-3/8 16-1/2 TA13 18-5/8 14 15/16 13-1/2 10-1/8 10-1/4 4-1/2 8-3/8 9-1/2 15/16 4-3/8 20-1/2 TA17 22-1/8 15 15/16 14-1/2 11-1/8 12 4-1/2 9-3/8 11-1/4 15/16 4-3/8 24 TA23 29-3/4 15 15/16 14-1/2 13 20-7/8 4-1/2 10-3/4 10-1/4 15/16 4-3/8 31-5/8 TA30 38-1/8 15 15/16 14-1/2 13 29-3/4 4-1/2 10-3/4 9-3/4 15/16 4-3/8 40 TA43 51-1/2 15 15/16 14-1/2 13 48-3/4 4-1/2 10-3/4 13-1/4 15/16 4-3/8 53-3/8 TA55 51-1/2 15 15/16 14-1/2 13 49 6-3/4 10-3/4 11 15/16 4-3/8 53-3/8
A B C D E F H J K L M W
Dimensions (in.)
Diagram 1. Dimensions
Ship Wt.
(lbs.)
3
Model TL
Thin Prole Electric Defrost Reach-In Unit Cooler
Features
• Electric defrost insures positive heat source
• Built-in fan delay allows coil to be chilled before returning to the normal cooling cycle
• Defrost terminates on coil temperature eliminating excessive defrost period
• Textured aluminum cabinet
• Molded Lexan® guard
• Knockouts provided on sides for electrical connections - opening in rear for coil connections
• Stainless steel screws
• Motors are thermally protected and permanently lubricated
• Internal junction box for electrical connection
• Plate type aluminum ns with full collars on expanded copper tubes
• Coils are dehydrated and sealed
• Easy to install and maintain
• All models UL listed for the US and Canada
• UL classied to NSF standards
Sweat inlet connection to reduce leaks (are connection available as a ship loose option)
Application
Model TL low temperature unit cooler has a completely
automatic defrost system. Mounted in the top of a refrigerator, its extremely compact cabinet makes it possible to utilize the entire top shelf area for storage. Having a normal operating range of 15°F to -20°F, this unit is ideally suited for such applications as commercial freezers, ice cream boxes and bakery freezers.
Nomenclature
Thin Prole
Electric Defrost
Size
TL 12 B G
Vintage
Voltage A = 115/1/60 B = 208-230/1/60
Table 3. Performance and Electrical Data
BTUH 10˚F TD Motor Data Heater Data Connections (in.) Approx.
Model
TL09 1,050 900 110 1 0.8 0.4 475 4.1 2.1 3/8 3/8 1/2 14 TL12 1,380 1,200 210 2 1.6 0.8 600 5.2 2.6 3/8 1/2 1/2 19 TL16 1,780 1,600 210 2 1.6 0.8 700 6.1 3.0 3/8 1/2 1/2 23 TL21 2,400 2,100 240 1 1.0 0.5 1,100 9.6 4.8 3/8 1/2 1/2 24
TL28 3,200 2,800 335 3 - 1.2 1,430 - 5.7 3/8 1/2 1/2 27 TL35* 4,000 3,500 420 2 - 1.0 1,600 - 7.0 1/2 5/8 1/2 38 TL53* 6,100 5,300 595 3 - 1.5 1,950 - 8.5 1/2 7/8 1/2 53
* Models 35 and 53 use external equalized expansion valves
20˚F
SST
-10˚F SST
CFM Qty.
115/1/60
Total FLA
208-230/1/60
Total FLA
Watts
115/1/60
Amps
208-230/1/60
Amps
Coil InletODSuctionIDDrain
OD
Ship Wt.
Table 4. Physical Data
Model
TL09 14-5/8 14 15/16 13-1/2 10-1/2 11-3/8 4-1/2 8-7/8 2-1/2 15/16 4-3/8 - 1 16-1/2 TL12 18-5/8 14 15/16 13-1/2 10-1/8 10-1/4 4-1/2 8-3/8 9-1/2 15/16 4-3/8 - 1 20-1/2 TL16 22-1/8 15 15/16 14-1/2 11-1/8 12 4-1/2 9-3/8 11-1/4 15/16 4-3/8 - 1 24 TL21 22-1/8 16-1/2 15/16 16-1/2 14-1/2 18-7/8 6-3/4 11-7/8 17-1/4 15/16 4-3/8 - 1-1/2 24 TL28 29-3/4 15 15/16 14-1/2 13 20-3/4 6-3/4 9-3/4 9-7/8 15/16 4-3/8 - 1 31-5/8 TL35 35-3/4 16-1/2 15/16 16-1/2 14-1/2 33-1/4 6-3/4 11-5/8 18-3/8 15/16 6 5-1/8 1-1/2 38-3/8 TL53 46-1/2 16-1/2 1-1/8 16-1/2 14-1/2 44 6-3/4 11-5/8 30-3/8 1-1/2 6 5-1/8 1-1/2 49-1/8
A B C D E F H J K L M N P W
Dimensions (in.)
Diagram 2. Dimensions
(lbs.)
4
Loading...
+ 8 hidden pages