(QTY.4) 18 x 25 [45.74 x 63.5](QTY.8) 18 x 25 [45.74 x 63.5]
15 x 11 [38.1 x 38.1]
15 x 15 [38.1
x 38.1]
All units have grommet & spring compressor mountings, and 1/2" & 1-3/4" electrical knockouts.
3
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
ALL CONFIGURATIONS REQUIRE SERVICE ACCESS AREA SHOWN BELOW. (RR/FD)
HKV084-150 Dimensional Data
F
B
7.6
BSP
NRP
C
02
P
01
1
2
3
4
5
LEGEND
Water Inlet (See Note 2)
Water Outlet (See Note 2)
Condensate Drain (See Note 3)
High Voltage Access (See Note 4)
Low Voltage Access (See Note 4)
BSP - Blower Service Panel
CAP - Control Access Panel
CSP - Compressor Access Panel
MSP - Motor Service Panel
NRP - Non Removable Panel
Q
3
CAP+MSP
CSP
RETURN AIR
2
D
AIR OUT
1
Control Box
REAR RETURN TOP DISCHARGE
S
L
HKV084-120
TLV084-120
NRP
R
NRP
3
M
K
A
1-1/2” FPT
1-1/2” FPT
1” FPT
1-3/8” [3.49 CM]
7/8” [2.2 CM]
R
U
N
HKV150
TLV150
2” FPT
2” FPT
4
5
4
3
NRP
NOTES FOR LEGEND:
1. While access to all removable panels is not required, installer
should take care to comply with all building codes and allow
adequate clearance for future field service.
2. Water inlet and water outlet connections are available on either
side (left or right) of the unit. Qty (2x) MPT Plugs are shipped loose
in a plastic bag tied to the water leg in front of the unit. Installer must
plug water inlet/outlet side not being connected to.
3. Condensate drain is available on either side (left or right) of unit.
Drain hose and drain connection will be tied inside the unit. Installer
will untie the drain hose and connect to the condensate drain hole of
installer’s choice.
4. Electrical access is available on either side (left or right) of unit and
is also available (left or right) in the front of the unit.
7.6
NRP
AIR OUT
RETURN AIR
2
Control Box
4
1
CSP+CAP+MSP
FRONT RETURN TOP DISCHARGE
F
BSP
NRP
3
5
4
L
M
K
084
-120
150
Model
Overall Cabinet
A
DepthBWidthCHeightDSupply
in.
34.0
53.1
86.4
34.0
86.4
134.9
53.1
134.9
cm.
in.
cm.
SERVICE ACCESS
3’ (91 CM)
FRONT AND BACK
Discharge Connections
Width
79.0
17.5
200.7
44.5
79.0
21.4
200.7
54.4
1.7
F
D
RETURN AIR
E
BSP
NRP
4
5
4
AIR OUT
3
CAP+MSP
2
CSP
NOTES:
- All dimensions in inches (cm)
- Units require 3’ (9.1 cm) clearance for water connections, CAP, CSP, MSP and BSP service access.
- Overall cabinet height dimension does not include duct flange when in top discharge configuration.
- Overall cabinet width dimensions does not include filter rack and duct flange when on front or back discharge configuration.
- Side service access must be 3 feet (91 cm) on either side that connections are made. If no connections are made on a side
then service access can be 6 inches (1.5 cm) minimum.
Duct Flange
E
Supply
Depth
17.6
44.6
17.6
44.6
BSP
NRP
1
Control Box
REAR RETURN FRONT DISCHARGE
Water ConnectionsElectrical Knockouts
FK
1
Water
Inlet
17.8
31.0
45.1
78.7
17.8
31.0
45.1
78.7
4
4
NRP
5
L
1
Water
Outlet
3.0
7.6
3.0
7.6
3
densate
4
5
4
NRP
SIDE
SERVICE ACCESS
(SEE NOTE)
M
NO1O2PQRS
3
Con-
27.0
25.6
68.6
65.1
27.0
25.6
68.6
65.1
3
BSP
RETURN AIR
Control Box
CSP+CAP+MSP
31.0
78.7
31.0
78.7
AIR OUT
2
4
4
1
FRONT RETURN REAR DISCHARGE
38.0
34.6
96.4
87.7
38.0
34.6
96.4
87.7
F
NRP
3
5
Return Air Connections
Using Return Air Opening
T
UVW
Return
Return
Depth
Height
1.0
3.0
48.0
32.4
44.6
2.7
2.5
1.0
2.5
7.6
3.0
7.6
121.9
48.0
121.9
82.2
32.4
82.2
113.3
44.6
113.3
6.9
2.7
6.9
2.0
5.1
2.0
5.1
4
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
ALL CONFIGURATIONS REQUIRE SERVICE ACCESS AREA SHOWN BELOW. (RR/FD)
HKV168-300 Dimensional Data
3
(See Note)
7.6
RETURN AIR
3
Control Box
CSP+CAP
RETURN AIR
Control Box
CSP+CAP
AIR OUT
2
1
AIR OUT
2
1
V
7.6
NRP
C
02
BSP
Q
3
P
01
CSP
1. Water inlet (see note 2)
2. Water outlet (see note 2)
3. Condensate drain (see note 3)
4. High voltage access (see note 4)
5. Low voltage access (see note 4)
1.7
F
E
NRP
4
5
4
CSP
Service Access
3’ (91 cm)
Front and Back
(All Configurations)
F
D
AIR OUT
E
2
LEGEND
MSP
1
2
NRP
RETURN
1
NRP
BSP
CAP
CSP
G
AIR
NRP
CAP
NRP
CSP
RETURN AIR
S
MSP
BSP - Blower Service Panel
CAP - Control Access Panel
CSP - Compressor Access Panel
MSP - Motor Service Panel
NRP - Non Removable Panel
BSP
D
AIR OUT
3
NOTES:
- All dimensions in inches (cm)
- Units require 3’ (9.1 cm) clearance for water connections, CAP, CSP, MSP and BSP service access.
- Overall cabinet height dimension does not include duct flange when in top discharge configuration.
- Overall cabinet width dimensions does not include filter rack and duct flange when on front or back discharge configuration.
- Side service access must be 3 feet (91 cm) on either side that connections are made. If no connections are made on a side then
service access can be 6 inches (1.5 cm) minimum.
B
G
D
AIR OUT
E
RETURN AIR
S
Control Box
L
REAR RETURN TOP DISCHARGE
168-240
D
AIR OUT
Control Box
300
2½” FPT
2” FPT
21/2”FPT
21/2”FPT
2½” FPT
2” FPT
1” FPT
1
3/8” (3.49 cm)
7/8” (2.2 cm)
RETURN
AIR
REAR RETURN FRONT DISCHARGE
T
4
5
4
NRP
4
5
NRP
4
U
N
A
NOTES FOR LEGEND:
1. While access to all removable panels is not required, installer should
take care to comply with all building codes and allow adequate
clearance for future field service.
2. Water inlet and water outlet connections are available on either side
(left or right) of the unit. Qty (2x) MPT Plugs are shipped loose in a
plastic bag tied to the water leg in front of the unit. Installer must
plug water inlet/outlet side not being connected to.
3. Condensate drain is available on either side (left or right) of unit.
Drain hose and drain connection will be tied inside the unit. Installer
will untie the drain hose and connect to the condensate drain hole of
installer’s choice.
4. Electrical access is available on either side (left or right) of unit and
is also available (left or right) in the front of the unit.
NRP
4
5
4
3
Side Service Access
R
3
H
K
NRP
AIR OUT
RETURN AIR
NRP
CSP+MSP
FRONT RETURN TOP DISCHARGE
BSP
AIR OUT
RETURN AIR
NRP
CSP+MSP
FRONT RETURN REAR DISCHARGE
BSP
5
4
F
NRP
4
5
3
4
L
H
K
F
NRP
4
3
Discharge Connections
Width
79.0
17.5
200.7
44.5
79.0
21.4
200.7
54.4
Duct Flange
E
Supply
Depth
17.6
17.8
44.6
45.1
17.6
17.8
44.6
45.1
168-
240
300
Model
Overall Cabinet
A
DepthBWidthCHeightDSupply
in.
34.0
106.7
86.4
34.0
86.4
270.9
106.7
270.9
cm.
in.
cm.
FGK
Water
31.3
79.4
23.4
59.4
Water ConnectionsElectrical Knockouts
Inlet
31.0
78.7
31.0
78.7
L
1
1
Water
Outlet
3.0
7.6
3.0
7.6
M
3
Condensate
27.0
68.6
27.0
68.6
NO1O2PQRS
25.6
31.0
78.7
31.0
78.7
38.0
96.4
38.0
96.4
65.1
25.6
65.1
5
34.6
87.8
34.6
87.8
1.0
2.5
1.0
2.5
3.0
7.6
3.0
7.6
Return Air Connections
Using Return Air Opening
T
UVW
Return
Return
Depth
Height
48.0
32.4
82.2
32.4
82.2
44.6
113.3
44.6
113.3
121.9
48.0
121.9
2.7
6.9
2.7
6.9
2.0
5.1
2.0
5.1
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
General Information
Inspection
Upon receipt of the equipment, carefully check the
shipment against the bill of lading. Make sure all units
have been received. Inspect the carton or crating of each
unit, and inspect each unit for damage. Assure the carrier
makes proper notation of any shortages or damage on all
copies of the freight bill and completes a common carrier
inspection report. Concealed damage not discovered
during unloading must be reported to the carrier within
15 days of receipt of shipment. If not led within
15 days, the freight company can deny the claim
without recourse. Note: It is the responsibility of the
purchaser to le all necessary claims with the carrier.
4. Inspect all electrical connections. Connections must
be clean and tight at the terminals.
5. Remove any blower support packaging from mouth
of blower.
6. Loosen compressor bolts on units equipped with
compressor spring vibration isolation until the
compressor rides freely on the springs. Remove
shipping restraints.
7. Locate and verify any hanger, or other accessory kit
located in the compressor section and or the
blower section.
WARNING!
Storage
Equipment should be stored in its shipping carton in a
clean, dry area. Store units in an upright position at all
times. Stack units a maximum of 3 units high.
Unit Protection
Cover units on the job site with either shipping cartons,
vinyl lm, or an equivalent protective covering. Cap
the open ends of pipes stored on the job site. In areas
where painting, plastering, and/or spraying has not
been completed, all due precautions must be taken to
avoid physical damage to the units and contamination
by foreign material. Physical damage and contamination
may prevent proper start-up and may result in costly
equipment clean-up.
Examine all pipes, ttings, and valves before installing
any of the system components. Remove any dirt or trash
found in or on these components.
Pre-Installation
Installation, Operation, and Maintenance instructions
are provided with each unit. HKV units are typically
installed in a oor level closet or in a mechanical room.
The installation site chosen should include adequate
service clearance around the unit. Before unit startup, read all manuals and become familiar with the unit
and its operation. Thoroughly check the system before
operation.
Prepare units for installation as follows:
1. Compare the electrical data on the unit nameplate
with ordering and shipping information to verify that
the correct unit has been shipped.
2. Keep the cabinet covered with the shipping carton
until installation is complete and all plastering,
painting, etc. is nished.
3. Verify refrigerant tubing is free of kinks or dents and
that it does not touch other unit components.
DO NOT store or install units in corrosive environments or
in locations subject to temperature or humidity extremes
(e.g., attics, garages, rooftops, etc.) Corrosive conditions
and high temperature or humidity can signicantly reduce
performance, reliability, and service life. Always move units
in an upright position. Tilting units on their sides may cause
equipment damage.
To avoid equipment damage, DO NOT use these units
as a source of heating or cooling during the construction
process. The mechanical components and lters used in
these units will quickly become clogged with construction
dirt and debris which may cause system damage.
To avoid the release of refrigerant into the atmosphere,
the refrigerant circuit of this unit must be serviced only by
technicians who meet local, state, and federal prociency
requirements.
All refrigerant removed from this unit must be recovered
WITHOUT EXCEPTION. Technicians must follow industry
accepted guidelines and all local, state, and federal statutes
for the recovery and disposal of refrigerants.
If a compressor is removed from this unit, system refrigerant
circuit oil will remain in the compressor. To avoid leakage of
compressor oil, the refrigerant lines of the compressor must
be sealed after it is removed.
6
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
Installation
Figure 1: Typical Vertical Installation
Rear Return/Top Discharge shown
Refer to Dimensional Data pages for
other arrangements & dimensions
Ductwork not shown.
All components external
of unit are field supplied.
Supply
Water
Return
Water
Unions
Shutoff
Hoses
Optional
Drain
To
Water
Optional
Balancing
Valve
Return Air
In
Return Air
Supply
Supply
Air
Water
Out
Condensate Internally
Trapped. Do not trap externally.
Pitch horizontal runs ¼” per foot.
1
/4”
Air
24 V Remote
Thermostat
Plug water
in and out
connections
Control Box
Disconnect Box
Per NEC and
Local Codes
Vertical Location and Access
HKV units are not designed for outdoor installation.
Locate the unit in an indoor area that allows enough
space for installation and for service personnel to perform
typical maintenance or repairs. HKV units are typically
installed in a oor level closet or in a small mechanical
room. Refer to Figure 1 for an illustration of a typical
installation. Install units with adequate clearance to allow
maintenance and servicing. Conform to the following
guidelines when selecting
unit location:
1. Provide adequate clearance for lter replacement
and drain pan cleaning. DO NOT block lter access
with piping, conduit or other materials. Refer to
submittal drawing for Vertical Unit Dimensions.
2. Provide access for fan and fan motor maintenance
and for servicing of the compressor and coils without
removal of the unit.
3. Provide an unobstructed path to the unit within the
closet or mechanical room to enable removal of the
unit if necessary.
4. Provide access to water valves and ttings, and
screwdriver access to the unit side panels, discharge
collar and all electrical connections
Duct System Design & Installation Guidelines
The following application guidelines must be used when
installing HKV units. Failure to follow these guidelines
could result in unsatisfactory unit performance and/
or premature failure of some unit components. Heat
Controller will not warrant, or accept responsibility for
products which fail, have defects, damage or insufcient
performance as a result of improper application.
• The duct system must be sized to handle the
airow quietly and must not exceed the maximum
allowable External Static Pressure. To maximize
sound attenuation metal supply and return ducts
should include internal insulation or be of duct board
construction for the rst 10 feet or end of rst full-
sized elbow.
• Install a exible connector in all supply and return
air ducts close to the unit to inhibit sound transfer to
the ducts.
• Do not install uninsulated duct in an unconditioned
space. The unit performance will be adversely
affected and damage from condensate can occur.
• On units with multiple fan outlets a “pair of pants”
duct connection must be used for proper air balance
and distribution and to prevent fan oscillation.
7
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
Installation
•
Include at least one 90-degree turn in supply air
ducts to reduce noise transmission.
• Existing ducts must be checked to insure proper
size and conguration prior to installation of any
replacement unit. Also inspect for and repair all air
leaks in existing ducts.
• Units may only be connected to a dedicated duct
system. Consult the factory BEFORE connecting
multiple units to a common duct system.
• Never connect a unit to a duct system with automatic
or modulating dampers, VAV boxes, etc. in the supply
air system. Never allow a situation where the total
unit CFM can drop below the minimum required for
proper unit operation.
•
Never connect a bypass damper from the supply air
duct to the return air duct. Never allow the return air
temperature to drop below the minimum allowable
normal temperature for proper unit operation.
• Do not use HKV units for 100% outdoor air treatment.
Do not add hot-gas-bypass to “convert” a unit for
outdoor air treatment. Always use a dedicated
outdoor air unit for outdoor air treatment.
• Do not exceed 10% of the total unit CFM with
untreated outdoor air.
8
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
Swivel
Piping Installation
Installation of Supply and Return Piping
Follow these piping guidelines.
1. Install a drain valve at the base of each supply and
return riser to facilitate system ushing.
2. Install shut-off / balancing valves and unions at each
unit to permit unit removal for servicing.
3. Place strainers at the inlet of each system
circulating pump.
4. Select the proper hose length to allow slack between
connection points. Hoses may vary in length by +2%
to -4% under pressure.
5. Refer to Table 1. Do not exceed the minimum bend
radius for the hose selected. Exceeding the minimum
bend radius may cause the hose to collapse which
reduces water ow rate. Install an angle adapter to
avoid sharp bends in the hose when the radius falls
below the required minimum.
CAUTION!
CAUTION! Piping must comply with all applicable codes.
Table 1: Metal Hose Minimum Bend Radii
Hoses in InchesMinimum Bend Radius
1” [25.4mm]5.5” [140mm]
1.25” [31.8mm]7.0” [178mm]
1.5” [38.1mm]8.5” [216mm]
Insulation is not required on loop water piping except
where the piping runs through unheated areas or outside
the building or when the loop water temperature is below
the minimum expected dew point of the pipe ambient.
Insulation is required if loop water temperature drops
below the dew point.
WARNING!
WARNING! Do not bend or kink supply lines or hoses.
Figure 2: Supply/Return Hose Kit
Rib Crimped
Length
(2 ft [0.6m] Length Standard)
Brass
Fitting
Note: When anti-freeze is used in the loop, assure
that it is compatible with Teon tape or pipe joint
compound employed.
Maximum allowable torque for brass ttings is 30 foot-
pounds [41 N-m]. If a torque wrench is not available,
tighten nger-tight plus one quarter turn. Tighten steel
ttings as necessary.
Optional pressure-rated hose assemblies designed
specically for use with Heat Controller units are available.
Similar hoses can be obtained from alternate suppliers.
Supply and return hoses are tted with swivel-joint ttings
at one end to prevent kinking during installation.
Refer to Figure 2 for an illustration of a Supply/Return
Hose Kit. External Pipe Thread (EPT) adapters secure
hose assemblies to the unit and risers. Install hose
assemblies properly and check them regularly to avoid
system failure and reduced service life.
Brass
Fitting
EPT
CAUTION!
Pipe joint compound is not necessary when Teon
threaded tape is pre-applied to hose assemblies or when
ared-end connections are used. If pipe joint compound
is preferred, use compound only in small amounts on the
male pipe threads of the tting adapters. Prevent sealant
from reaching the ared surfaces of the joint.
CAUTION! Corrosive system water requires corrosion
resistant ttings and hoses and possibly water treatment.
9
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
Remove knockout on side that drain will be connected.
Remove access panels. Inside of unit, untie and uncoil
drain hose. Form trap in hose, make sure hose is not
kinked or deformed. Connect plate assembly to side
frame with 2 screws.
Outside of unit, connect 1” EPT tting to plate assembly.
Run line to building drain. Horizontal runs must be pitched
¼” per foot (10 mm per 46 cm) toward drain. Do not trap
externally.
Figure 3 illustrates a typical trap and vent used with HKV
series equipment.
Figure 3: HKV
Each unit must be installed with its own individual line to
the building main condensate drain line or riser. Provide a
means to ush or blow out the condensate line. DO NOT
install units with a common trap and or vent.
Always vent the condensate line when dirt or air can
collect in the line or a long horizontal drain line is
required. Also vent when large units are working against
higher external static pressure than other units connected
to the same condensate main since this may cause
poor drainage for all units on the line. WHEN A VENT
IS INSTALLED IN THE DRAIN LINE, IT MUST BE
LOCATED AFTER THE TRAP IN THE DIRECTION OF
THE CONDENSATE FLOW and opening 46” (117 cm)
minimum from bottom of unit. (Vent per code)
WARNING!
WARNING! Ensure condensate line is pitched toward
drain 1/4" per foot [10mm per 46cm] of run.
Drain main or riser must be sized for all units connected
to it.
Open
Vent
1” EPT
46” Min
To Bottom
Of Unit
To main
drain, pitch
¼” Per foot
1” IPT
Fitting
2 Screws
All fittings and tubing outside of the unit are field supplied.
Condensate
Pan
After drain is connected to main and all drain connections
are secure and water tight, pour 1 gallon of water into
condensate pan. Water should drain out freely. Repair
any leaks.
10
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
Water-Loop Heat Pump Applications
Commercial systems typically include a number of
units plumbed to a common piping system. Any unit
plumbing maintenance work can introduce air into the
piping system, therefore air elimination equipment is a
major portion of the mechanical room plumbing. In piping
systems expected to utilize water temperatures below
50°F [10°C], 1/2" [13mm] closed cell insulation is required
on all piping surfaces to eliminate condensation. Metal
to plastic threaded joints should never be employed due
to their tendency to leak over time. All non-distributor
class units include a low temperature-soldered bracket-
supported FPT water connection. Teon tape thread
sealant is recommended to minimize internal fouling
of the heat exchanger. Do not overtighten connections
and route piping so as not to interfere with service or
maintenance access. Hose kits are available from Heat
Controller in different congurations as shown in Figure
4 for connection between the HKV Series and the piping
system. The piping system should be ushed to remove
dirt, piping chips, and other foreign material prior to
operation. See Piping System Cleaning and Flushing
Procedures. The ow rate is usually set between 2.25
and 3.5 gpm per ton [2.9 l/m and 4.5 l/m per kW] of
cooling capacity. Heat Controller recommends 2.5 gpm
per ton [3.2 l/m per kW] for most applications of water
loop heat pumps. To insure proper maintenance and
servicing, P/T ports are imperative for temperature and
ow verication, as well as performance checks.
Cooling Tower/Boiler Systems typically utilize a
common loop maintained 60-90°F [16-32°C]. The use
of a closed circuit evaporative cooling tower with a
secondary heat exchanger between the tower and the
water loop is recommended. If an open type cooling
tower is used continuously, chemical treatment and
ltering will be necessary.
Figure 4: Typical Water Loop Application
Supply
Air
Supply
Air
Return Air
Water
Control Valve
Thermostat
Wiring
Unit
Power
Field Supplied
Disconnect Box
TO Drain, See Fig. 4
Ball Valve with
integral P/T plug
Water In
Ball Valve with
integral P/T plug
Water Out
11
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
Electrical Data
WARNING!
To avoid possible injury or death due to electrical shock,
open the power supply disconnect switch and secure it in an
open position during installation.
Use only copper conductors for eld installed electrical
wiring. Unit terminals are not designed to accept other
types of conductors.
CAUTION!
Table 4A: HKV Electrical Data Standard
Model
HKV084
HKV096
HKV120
HKV150
HKV168
HKV192
HKV240
HKV300
HACR circuit breaker in USA only
All fuses Class RK-5 Created: 3/26/09B
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
Electrical - Power Wiring
WARNING!
WARNING! To avoid possible injury or death due to
electrical shock, open the power supply disconnect switch
and secure it in an open position during installation.
CAUTION!
CAUTION! Use only copper conductors for eld installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.
WARNING!
WARNING! Disconnect electrical power source to prevent
injury or death from electrical shock.
General Line Voltage Wiring
Be sure the available power is the same voltage and phase
as that shown on the unit serial plate. Line and low voltage
wiring must be done in accordance with local codes or the
National Electric Code, whichever is applicable.
HKV Power Connection
Line voltage connection is made by connecting the
incoming line voltage wires to the power block as shown in
Figure 6. Consult Table 4a and 4b for correct fuse size.
Thermostat Installation
The thermostat should be located on an interior wall in
a larger room away from supply duct drafts. Do NOT
locate the thermostat in areas subject to sunlight, drafts
or on external walls. The wire access hole behind the
thermostat may in certain cases need to be sealed to
prevent erroneous temperature measurement. Position the
thermostat backplate against the wall so that it appears
level and so the thermostat wires protrude through the
middle of the backplate. Mark the position of the backplate
mounting holes and drill holes with a 3/16" bit. Install
supplied anchors and secure plate to the wall. Thermostat
wire must be 18 AWG wire. Wire the appropriate thermostat
as shown in Figure 10 to the low voltage terminal strip
in the CXMControl as shown in Figure 7 using 18 AWG
thermostat wire of minimum length.
Figure 6: Typical HKV Series Line Voltage
Field Wiring
208 Volt Operation
All 208-230 Volt units are factory wired for 208 Volt. The
transformers may be switched to 230V operation as
illustrated on the wiring diagram by switching the Red
(208V) and the Orange (230V) at the contactor terminal L2.
All eld installed wiring, including electrical ground, must
comply with the National Electrical Code as well as all
applicable local codes.
Refer to the unit wiring diagrams for fuse sizes and a
schematic of the eld connections which must be made by
the installing (or electrical) contractor.
Consult the unit wiring diagram located on the inside of the
compressor access panel to ensure proper electrical hookup.
All nal electrical connections must be made with a length of
exible conduit to minimize vibration and sound transmission
to the building.
Figure 7: Low Voltage Field Wiring (CXM
board shown)
13
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
Electrical - Low Voltage
Low Water Temperature Cutout - FP1
The CXM control allows the eld selection of source uid low
temperature cutout points. The factory setting of FP1 is set for
water (30°F [-1.1°C]). In cold temperature applications jumper
JW3 (FP1- antifreeze 10°F [-12.2°C]) should be clipped as
shown in Figure 8 to change the setting to 10°F [-12.2°C], a more
suitable temperature when using antifreezes. It should be noted
that the extended range option should be specied to operate the
HB Series at entering water temperatures below 60°F [15°C].
Figure 8: FP1 Jumper
Figure 9: 24 Volt Accessory Wiring
CXM Terminal Strip
These terminals may be
used to power 24 volt
water valves on units
size 084-150. Refer to
Figure 9a for water valve
wiring to dual compressor units.
closing valve may be required to prevent water hammer.
When using an AVM -Taco Slow Closing valve on HKV
Series equipment Figure 10 wiring should be utilized. The
valve takes approximately 60 seconds to open (very little
water will ow before 45 seconds) and it activates the
compressor only after the valve is completely opened (by
closing its end switch). Only relay or triac based electronic
thermostats should be used with the AVM valve. When
wired as shown, the valve will operate properly with the
following notations:
1-The valve will remain open during a unit lockout.
2-The valve will draw approximately 25-35 VA through the
“Y” signal of the thermostat. Note: This can overheat the
anticipators of electromechanical thermostats. Therefore
only relay or triac based thermostats should be used.
Accessory Connections
A terminal paralleling the compressor contactor coil has been
provided on the CXM control board. “A” has been provided to
control accessory devices, such as water valves, electronic
air cleaners, humidiers, etc. Note: This terminal must be
used only with 24 Volt signals and not line voltage signals. This signal operates with the compressor contactor. See
Figure 9 or the wiring schematic for details.
Water Solenoid Valves
When using external solenoid valves on ground water
installations, a slow closing valve may be desired. Figure 9
illustrates a typical slow closing water control valve wiring
which will limit wasted water during a lockout condition. A slow
Figure 10: Well Water AVM Valve Wiring
CXM/DXM #1
C
1
2
Heater Switch
C
Y1
Thermostat
Y1
3
HKV Unit
AVM
Taco Valve
CAUTION!
CAUTION! For units with manual or electric water shut-off
valve. DAMAGE WILL OCCUR if shut-off valve is closed
during unit operation. A high pressure switch must be installed
on the heat pump side of any eld provided shut-off valves
and connected to the heat pump controls in series with the
built-in refrigerant circuit high pressure switch to disable
compressor operation if water pressure exceeds pressure
switch setting. The eld installed high pressure switch shall
have a cut-out pressure of 300 psig and a cut-in pressure of
250 psig.
14
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
CXM Control Operation
Note: See CXM operation manual for detailed information pertaining to controller operation.
Electrical - Thermostat
Typical Thermostat Selection and Wiring
Practically any multi-stage contact type thermostat will work with the HKV Series. Figure 11 shows typical thermostat
wiring. Thermostats with Triac outputs are not compatible with CXM boards.
Figure 11: Typical Manual Changeover 2 heat/
2 cool thermostat wiring with HKV unit & CXM
15
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
HKV084-150 with CXM Schematic
HKV084-150 with CXM
16
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
HKV168-300 with CXM Schematic
17
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
Blower Adjustment
CAUTION!
Always disconnect all power supply(s) to unit prior to
making belt or sheave adjustments. Inadvertently starting
of the motor can cause damage to the equipment and
personal injury.
Airow and External Static Pressure
Selection Adjustment
The HKV Series is available with standard, low, and high
static options. These options will substitute a different
blower drive sheave for each static range. In addition
certain static ranges may require the optional large fan
motor. Please specify static range and motor horsepower
when ordering. See model nomenclature.
Sheave Adjustment
The HKV Series is supplied with variable sheave drive
on the fan motor to adjust for differing airows at various
ESP conditions. Select an airow requirement on the left
side of the table, then move horizontally to right under
the required ESP. Note the sheave turns open, rpm and
horsepower for that condition. Fully closed the sheave
will produce the highest static capability (higher rpm). To
adjust sheave position: loosen belt tension and remove
belt, loosen set screw on variable sheave (on fan motor)
and open sheave to desired position. Retighten set
screw and replace belt and set belt tension as below.
Notes:
- Motor position should not need adjustment.
- Motor sheave position is at mid position of each sheave.
Thus the motor sheave is typically 2.5 turns open on a 5
turn sheave.
Special Note for AHRI Testing
Note 1: All HKV084 ratings @ 2800CFM (1321 l/s)
w/21GPM (1.33 l/s). Sheave setting for ARI is
3.5 turns open.
Note 2: All HKV096 ratings @ 3200CFM (1510 l/s)
w/24GPM (1.51 l/s). Sheave setting for ARI is
3.0 turns open.
Note 3: All HKV120 ratings @ 4000CFM (1888 l/s)
w/30GPM (1.89 l/s). Sheave setting for ARI is
2.5 turns open.
Note 4: Cooling capacities based upon 80.6°F DB,
66.2°F WB entering air temperature.
Note 5: Heating capacities based upon 68°F DB, 59°F
WB entering air temperature.
Note 6: All ratings based upon operation at lower voltage
of dual voltage rated models.
Belt Tensioning
An overly loose belt will, upon motor start, produce a
slippage 'squeel' and cause premature belt failure and
or intermittent airow. An overly tight belt can cause
premature motor or blower bearing failure.
Belt Tensioning Procedure - HKV
Blower motors for HKV models are slide base mounted.
To adjust the belt tension:
1. Loosen the two (4) bolts that lock the base to the slide
rails.
2. Insert a socket into the opening at the front of the base
assembly.
3. Turn counter clock wise to tighten or clock wise to
loosen the belt.
4. The belt should be tensioned using a tension gauge
method such as the Browning Belt Tensioner to set
proper belt tension (see next page).
5. After belt tension is set secure the (4) locking bolts.
18
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
Tensioning V-Belt Drives
General rules of tensioning
1. Ideal tension is the lowest tension at which the belt will not slip under
peak load conditions.
2. Check tension frequently during the first 24-48 hours of operation.
3. Over tensioning shortens belt and bearing life.
4. Keep belts free from foreign material which may cause slip.
5. Make V-drive inspection on periodic basis. Tension when slipping.
Never apply belt dressing as this willl damage the belt and cause
early failure.
Tension Measurement Procedure
1. Measure the belt span (see sketch).
2. Position bottom of the large “O” ring on the span scale at the measured belt span.
3. Set the small “O” ring on the deflection force scale to zero.
4. Place the tension checker squarely on one belt at the center of the belt span. Apply a force on the
plunger and perpendicular to the belt span until the bottom of the large “O” ring is even with the
top of the next belt or with the bottom of a straight edge laid across the sheaves.
5. Remove the tension checker and read the forct applied from the bottom of the small “O” ring on
the deflection force scale.
6. Compare the force you have applied with the values given in the table below. The force should be
between the minimum and maximum shown. The maximum value is shown for “New Belt” and
new belts should be tensioned at this value to allow for expected tension loss. Used belts should
be maintained at the minimum value as indicated in the table below.
NOTE: The ratio of deflection to belt span is 1:64.
Sheave Diameter - Inches
Smallest
Sheave
Cross
Section
A, AX
B, BX
Diameter
Range
3.0 - 3.6
3.8 - 4.8
5.0 - 7.0
3.4 - 4.2
4.4 - 5.6
5.8 - 8.6
RPM
Range
1000-2500
2501-4000
1000-2500
2501-4000
1000-2500
2501-4000
860-2500
2501-4000
860-2500
2501-4000
860-2500
2501-4000
Deflection Force - LBS
Super Gripbelts and
Unnotched Gripbands
Used
Belt
3.7
2.8
4.5
3.8
5.4
4.7
5.3
4.5
6.3
6.0
New
Belt
5.5
4.2
6.8
5.7
8.0
7.0
7.9
6.7
9.4
8.9
Belt Deflection Force
Gripnotch Belts and
Notched Gripbands
Used
Belt
4.1
3.4
5.0
4.3
5.7
5.1
4.9
4.2
7.1
7.1
8.5
7.3
New
Belt
6.1
5.0
7.4
6.4
9.4
7.6
7.2
6.2
10.5
9.1
12.6
10.9
19
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
Use original table to find correct turns based upon new rpm
Blower Sheave Information
Table 5: HKV Blower Sheave and Belt Information
Model
084
096
120
150
168
192
240
300
Conguration
Return/Supply
Back or Front/Top
Back/Front
Front/Back
Back or Front/Top
Back/Front
Front/Back
Component
Blower Sheave
Motor Sheave
Motor
Belt
Blower Sheave
Motor Sheave
Motor
Belt
Blower Sheave
Motor Sheave
Motor
Belt
Blower Sheave
Motor Sheave
Motor
Belt
Blower Sheave
Motor Sheave
Motor
Belt
Blower Sheave
Motor Sheave
Motor
Belt
Blower Sheave
Motor Sheave
Motor
Belt
Blower Sheave
Motor Sheave
Motor
Belt
Drive Package
ABCDE
BK95 X 1”
1VP40 X 7/8”
1HP
BX79
BK95 X 1”
1VP40 X 7/8”
1.5HP
BX79
BK95 X 1”
1VP44 X 7/8”
2HP
BX80
BK95 X 1”
1VP50 X 7/8”
3HP
BX81
BK95H X 1-3/16”
1VP44 X 7/8”
2HP
BX80
BK95H X 1-3/16”
1VP40 X 7/8”
3HP
BX80
BK90H X 1-3/16”
1VP44 X 1-1/8”
5HP
BX76
BK105H X 1-3/16”
1VP60 X 1-1/8”
5HP
BX80
BK110 X 1”
1VP34 X 7/8”
1HP
BX81
BK110 X 1”
1VP34 X 7/8”
1.5HP
BX81
BK110 X 1”
1VP40 X 7/8”
2HP
BX81
BK110 X 1”
1VP50 X 7/8”
3HP
BX83
BK110H X 1-3/16”
1VP40 X 7/8”
2HP
BX81
BK110H X 1-3/16”
1VP40 X 7/8”
3HP
BX81
BK110H X 1-3/16”
1VP44 X 1-1/8”
5HP
BX80
BK110H X 1-3/16”
1VP50 X 1-1/8”
5HP
BX80
BK95 X 1”
1VP50 X 7/8”
1HP
BX81
BK95 X 1”
1VP50 X 7/8”
1.5HP
BX81
BK95 X 1”
1VP60 X 7/8”
2HP
BX82
BK95 X 1”
1VP65 X 7/8”
3HP
BX83
BK95H X 1-3/16”
1VP50 X 7/8”
2HP
BX81
BK95H X 1-3/16”
1VP50 X 7/8”
3HP
BX81
BK95H X 1-3/16”
1VP60 X 1-1/8”
5HP
BX78
BK95H X 1-3/16”
1VP60 X 1-1/8”
5HP
BX78
BK95 X 1”
1VP40 X 7/8”
1.5HP
BX79
BK95 X 1”
1VP40 X 7/8”
2HP
BX79
BK95 X 1”
1VP44 X 7/8”
3HP
BX80
BK95 X 1”
1VP50 X 1-1/8”
5HP
BX77
BK95H X 1-3/16”
1VP44 X 7/8”
3HP
BX80
BK95H X 1-3/16”
1VP44 X 1-1/8”
5HP
BX76
N/A
BK105H X 1-3/16”
1VP60 X 1-3/8”
7.5HP
BX80
BK95 X 1”
1VP50 X 7/8”
1.5HP
BX81
BK95 X 1”
1VP50 X 7/8”
2HP
BX81
BK95 X 1”
1VP60 X 7/8”
3HP
BX82
BK95 X 1”
1VP65 X 1-1/8”
5HP
BX79
BK95H X 1-3/16”
1VP50 X 7/8”
3HP
BX81
BK95H X 1-3/16”
1VP50 X 1-1/8”
5HP
BX77
BK95H X 1-3/16”
1VP60 X 1-3/8”
7.5HP
BX78
BK95H X 1-3/16”
1VP60 X 1-3/8”
7.5HP
BX78
Note 1: D-drive is not available because standard sheave is not available in 1-3/8”.
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For dry coil performance rst calculate the face velocity of the air coil (Face Velocity [FPM] = Airow [CFM] / Face Area [sqft]). Then use preceding wet coil to dry coil conversion table.
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions. Do not operate in black
regions. All airow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For dry coil performance rst calculate the face velocity of the air coil (Face Velocity [FPM] = Airow [CFM] / Face Area [sqft]).Then use preceding wet coil to dry coil conversion table.
Table Continued on Next Page
22
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For dry coil performance rst calculate the face velocity of the air coil (Face Velocity [FPM] = Airow [CFM] / Face Area [sqft]). Then use preceding wet coil to dry coil conversion table.
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions. Do not operate in black regions. All airow in rated at lowest Volt-
age if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For dry coil performance rst calculate the face velocity of the air coil (Face Velocity [FPM] = Airow [CFM] / Face Area [sqft]).Then use preceding wet coil to dry coil conversion table.
Table Continued on Next Page
24
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions. Do not operate in black regions. All airow in rated at lowest
Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For dry coil performance rst calculate the face velocity of the air coil (Face Velocity [FPM] = Airow [CFM] / Face Area [sqft]).Then use preceding wet coil to dry coil conversion table.
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions. Do not operate in black regions. All airow in rated at lowest Volt-
age if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For dry coil performance rst calculate the face velocity of the air coil (Face Velocity [FPM] = Airow [CFM] / Face Area [sqft]).Then use preceding wet coil to dry coil conversion table.
Table Continued on Next Page
26
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For dry coil performance rst calculate the face velocity of the air coil (Face Velocity [FPM] = Airow [CFM] / Face Area [sqft]). Then use preceding wet coil to dry coil conversion table.
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For dry coil performance rst calculate the face velocity of the air coil (Face Velocity [FPM] = Airow [CFM] / Face Area [sqft]). Then use preceding wet coil to dry coil conversion table.
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions. Do not operate in black regions. All airow in rated at lowest Volt-
age if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For dry coil performance rst calculate the face velocity of the air coil (Face Velocity [FPM] = Airow [CFM] / Face Area [sqft]).Then use preceding wet coil to dry coil conversion table.
Table Continued on Next Page
29
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For dry coil performance rst calculate the face velocity of the air coil (Face Velocity [FPM] = Airow [CFM] / Face Area [sqft]). Then use preceding wet coil to dry coil conversion table.
30
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions. Do not operate in black regions. All airow in rated at lowest Volt-
age if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For dry coil performance rst calculate the face velocity of the air coil (Face Velocity [FPM] = Airow [CFM] / Face Area [sqft]).Then use preceding wet coil to dry coil conversion table.
Table Continued on Next Page
31
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For dry coil performance rst calculate the face velocity of the air coil (Face Velocity [FPM] = Airow [CFM] / Face Area [sqft]). Then use preceding wet coil to dry coil conversion table.
776798822844865885908928948967988100710261044
32
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions. Do not operate in black regions. All airow in rated at lowest Volt-
age if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For dry coil performance rst calculate the face velocity of the air coil (Face Velocity [FPM] = Airow [CFM] / Face Area [sqft]).Then use preceding wet coil to dry coil conversion table.
Table Continued on Next Page
33
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For dry coil performance rst calculate the face velocity of the air coil (Face Velocity [FPM] = Airow [CFM] / Face Area [sqft]). Then use preceding wet coil to dry coil conversion table.
32.5213.52.521.5
34
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
Unit Commissioning & Operating Conditions
Environment – This unit is designed for indoor
installation only. Do not install in an area subject to
freezing or where humidity levels can cause cabinet
condensation.
Power Supply – A voltage variation of +/- 10% of
nameplate utilization voltage is acceptable.
Operation and performance is primarily dependent
upon return air temperature, airow, water temperature,
water ow rate and ambient air temperature. This water
to air heat pump is capable of operating over a wide
temperature range and with ow rates of between 1.5
GPM (.1 l/s) and 3 GPM (.19 l/s) per ton, however usually
no more than one of these factors may be at a minimum
or maximum level at a time.
Table 6: Building Commissioning
BUILDING COMMISSIONING
ALL HKV MODELS
Cooling °F [°C]Heating °F [°C]
AMBIENT MIN - MAX DB45-110 [7-43]40-85 [4.5-29]
RETURN AIR MIN DB/WB50/45 [10/7]40 [4.5]
RETURN AIR MAX DB/WB110/83 [43/28]85 [29]
STANDARD UNIT ENTERING
WATER MIN* - MAX
EXTENDED RANGE UNIT** EN-
TERING WATER MIN* - MAX
*- Requires optional insulation package when operating below the dew point
**- Requires antifreeze, optional insulation package and jumperclipped.
40-120 [4.5-49]60-90 [16-43]
30-120 [-1-49]20-90 [-6.7-43]
The commissioning table indicates air and water
temperatures which are suitable for initial unit
commissioning in an environment where the ow rate and
water temperature is not yet stable and to avoid nuisance
shut down of the units freeze and refrigerant pressure
safeties.
The operating table indicates the maximum and
minimum ranges of the unit.
For more specic unit performance reference the product
catalog, the submittal data sheets or contact your
supplier for assistance.
Table 6A: Unit Operating Limits
UNIT OPERATING LIMITS
All HKV Models
Cooling °F [°C]Heating °F [°C]
AMBIENT MIN - MAX DB50-100 [10-38]50-85 [10-29]
RETURN AIR MIN DB/WB65/60 [18/15.5]50 [10]
RETURN AIR MAX DB/WB95/75 [35/24]80 [27]
STANDARD UNIT ENTERING
WATER MIN* - MAX
EXTENDED RANGE UNIT** EN-
TERING WATER MIN* - MAX
*- Requires optional insulation package when operating below the dew point
**- Requires antifreeze, optional insulation package and jumper clipped.
50-120 [10-49]60-90 [16-43]
30-120 [-1-49]20-90 [-6.7-43]
35
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
Piping System Cleaning & Flushing
CAUTION!
CAUTION! To avoid possible damage to a plastic (PVC)
piping system, do not allow temperatures to exceed 110°F
[43°C].
CAUTION!
CAUTION! DO NOT use 'stop leak' or any similar chemical
agent in this system. Addition of these chemicals to the loop
water will foul the system and inhibit unit operation.
Note:
Heat Controller strongly recommends all piping
connections, both internal and external to the unit, be
pressure tested for leakage by an appropriate method
prior to any nishing of the interior space or before
access to all connections is limited. Heat Controller
will not be responsible or liable for damages from water
leaks due to inadequate or a lack of pressurized leak
testing during installation.
Cleaning and ushing of the WLHP piping system is the
single most important step to ensure proper start-up and
continued efcient operation of the system.
Follow the instructions below to properly clean and ush
the system:
1. Verify electrical power to the unit is disconnected.
2. Install the system with the supply hose connected
directly to the return riser valve. Use a single length of
exible hose.
3. Open all air vents. Fill the system with the water. DO
NOT allow system to overow. Bleed all air from the
system. Pressurize and check the system for leaks
and repair appropriately.
4. Verify all strainers are in place. (Heat Controller recommends a strainer with a #20 stainless steel wire mesh.)
Start the pumps, and systematically check each vent
to ensure all air is bled from the system.
5. Verify make-up water is available. Adjust make-up water appropriately to replace the air which was bled from
the system. Check and adjust the water/air level in the
expansion tank.
6. Set the boiler to raise the loop temperature to approximately 85°F [29°C]. Open the a drain at the lowest
point in the system. Adjust the make-up water replacement rate to equal the rate of bleed.
7. Rell the system and add trisodium phosphate in a
proportion of approximately one pound per 150 gallons
[1/2 kg per 750 L] of water (or other equivalent approved cleaning agent). Reset the boiler to raise the
loop temperature to about 100°F [38°C]. Circulate the
solution for a minimum of 8 to 24 hours. At the end of
this period, shut off the circulating pump and drain the
solution. Repeat system cleaning if desired.
8. When the cleaning process is complete, remove the
short-circuited hoses. Reconnect the hoses to the
proper supply, and return the connections to each of
the units. Rell the system and bleed off all air.
9. Test the system pH with litmus paper. The system
water should be slightly alkaline (pH 7.5-8.5). Add
chemicals, as appropriate, to maintain acidity levels.
10. When the system is successfully cleaned, ushed,
relled and bled, check the main system panels,
safety cutouts and alarms. Set the controls to properly maintain loop temperatures.
BEFORE POWERING SYSTEM, please check
the following:
Unit Checkout
qBalancing/Shutoff Valves: Ensure all isolation
valves are open, water control valves wired and
open or coax may freeze and burst.
qLine Voltage and Wiring: Ensure Voltage is
within an acceptable range for the unit and wiring
and fuses/breakers are properly sized. Low
voltage wiring is complete.
qUnit Control Transformer: Ensure transformer
has properly selected control voltage tap. 208230V units are factory wired for 208V operation
unless specied otherwise.
qEntering Water and Air: Ensure entering water
and air temperatures are within operating limits of
Table 6.
qLow Water Temperature Cutout: Verify low
water temperature cut-out on CXM is properly set.
qUnit Fan: Manually rotate fans to assure free
rotation and ensure blower wheel is secured to
motor shaft. Be sure to remove any shipping
supports if needed. DO NOT oil motors upon
start-up. Fan motors are pre-oiled at factory.
Verify unit fan speed selected is correct.
qCondensate Line: Condensate line is open and
properly pitched toward drain.
qWater Flow Balancing: Verify inlet and outlet
water temperatures are recorded for each heat
pump upon startup. This check can eliminate
nuisance trip outs and high velocity water ows
that can erode heat exchangers.
qUnit Air Coil & Filters: Ensure lter is clean and
accessible. To obtain maximum performance and
avoid possible condensate blow-off the coil should
36
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
Unit & System Checkout
be cleaned using a 10% solution of dish washing
detergent.
qUnit Controls: Verify CXM eld selection options
are proper and complete.
System Checkout
q
q
q System Flushing: Verify all hoses are connected
q Cooling Tower/Boiler: Check equipment for
System Water Temperature: Check water
temperature for proper range and also verify
heating and cooling setpoints for proper operation.
System pH: System water pH is 7.5 - 8.5. Proper
pH promotes longevity of hoses and ttings.
end to end when ushing to ensure debris
bypasses unit heat exchanger and water valves
etc. Water used in the system must be potable
quality initially and clean of dirt, piping slag, and
strong chemical cleaning agents. Verify all air is
purged from the system. Air in the system can
cause poor operation or system corrosion.
proper setpoints and operation.
WARNING!
WARNING! Verify ALL water controls are open and allow
water ow prior to engaging the compressor. Freezing of
the coax or water lines can permanently damage the heat
pump.
qStandby Pumps: Verify the standby pump is
properly installed and in operating condition.
qSystem Controls: Verify system controls function
and operate in the proper sequence.
qLow Water Temperature Cutout: Verify low
water temperature cut-out controls are provided
for the outdoor portion of the loop or operating
problems will occur.
qSystem Control Center: Verify control center and
alarm panel for proper setpoints
and operation (if used).
qMiscellaneous: Note any questionable aspects of
the installation.
qLog Data: Record data on startup log sheet in
this manual or on web site. keep log for future
reference.
WARNING!
WARNING! To avoid equipment damage, DO NOT leave
system lled in a building without heat during the winter
unless antifreeze is added to system water. Condenser
coils never fully drain by themselves and will freeze unless
winterized with antifreeze.
37
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
Unit Start Up Procedure
WARNING!
WARNING! When the disconnect switch is closed, high
voltage is present in some areas of the electrical panel.
Exercise caution when working with energized equipment.
WARNING!
WARNING! Verify ALL water controls are open and allow
water ow prior to engaging the compressor. Freezing of
the coax or water lines can permanently damage the heat
pump.
1. Turn thermostat fan position to “ON”. Blower should start.
2. Balance air ow at registers.
3. Adjust all valves to their full open position. Turn on the
line power to all heat pump units.
4.
Operate unit in cooling cycle. Room temperature should
be approximately 45-100°F [7-38°C] DB. For Start-up
check, loop water temperature entering the heat pumps
should be between 45°F [7°C] and 110°F [43°C].
5.
Two factors determine the operating limits of a Heat
Controller HKV System– (a) return air temperature, and
(b) water temperature. When any one of these factors is at
a minimum or maximum level, the other factor must be at
normal levels to ensure proper unit operation.
a. Adjust the unit thermostat to the warmest position.
Slowly reduce thermostat setting until the
compressor activates.
b. Check for cool air delivery at the unit grille within a
few minutes after the unit has begun to operate.
Note: Units have a ve minute time delay in the control
circuit that can be eliminated on the CXM PCB as
shown below in Figure 14. See controls description for
detailed features of the control.
c. Verify that the compressor is on and that the water
ow rate is correct by measuring pressure drop
through the heat exchanger using the Pete’s
plugs and comparing to Table 7.
d. Check the elevation and cleanliness of the
condensate lines. Dripping may be a sign of a
blocked line. Check that the condensate trap
includes a water seal.
e. Refer to Table 9. Check the temperature of both
supply and discharge water. If temperature is within
range, proceed with test. If temperature is outside
operating range, check cooling refrigerant pressures
in Table 8. Verify correct water ow by comparing
unit pressure drop across the heat exchanger
versus the data in Table 9. Heat of rejection can be
calculated and compared to specication catalog.
f. Check air temperature drop across the coil when
compressor is operating. Air temperature should
drop between 15°F [8°C] and 25°F [14°C].
g. Turn thermostat to “OFF” position. A hissing noise
indicates proper functioning of the reversing valve.
6. Operate the heat pump in the heating cycle immediately
after checking cooling cycle operation. Allow ve (5)
minutes between tests for pressure to equalize or cycle the
reversing valve to equalize.
a. Turn thermostat to lowest setting and set thermostat
switch to “HEAT” position.
b. Slowly turn thermostat to a higher temperature until
the compressor activates.
c. Check for warm air delivery at the unit grille within a
few minutes after the unit has begun to operate.
d. Check the temperature of both supply and discharge
water. Refer to Table 8. If temperature is within
range, proceed with test. If temperature is outside
operating range, check heating refrigerant pressures
in Table 8.
e. Check air temperature rise across the coil when
compressor is operating. Air temperature should
rise between 20°F [11°C] and 30°F [17°C]. Heat
of extraction can be calculated and compared to
specication catalog.
f. Check for vibration, noise, and water leaks.
7. If unit fails to operate, perform troubleshooting analysis
(CXM manual). If the check described fails to reveal the
problem and the unit still does not operate, contact a
trained service technician to ensure proper diagnosis and
repair of the equipment.
8. When testing is complete, set system to maintain desired
comfort level.
9. BE CERTAIN TO FILL OUT AND FORWARD
ALL WARRANTY REGISTRATION PAPERS
TO HEAT CONTROLLER, INC.
Note: If performance during any mode appears
abnormal, refer to the troubleshooting section of CXM
manual. To obtain maximum performance the air coil
should be cleaned before start-up. A 10% solution of
dishwasher detergent and water is recommended.
Figure 11: Test Mode Pins
Short test pins together to
enter Test Mode and speedup timing and delays for 20
minutes.
CXM Board
38
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
Unit Start Up Procedure
Table 7: Coax Water Pressure Drop
ModelGPM
10.5
HKV084
HKV096
HKV120
HKV150
HKV168
HKV092
HKV240
HKV300
15.75
21
12
18
24
15
22.5
30
19
28
38
21
31.5
42
24
36
48
30
45
60
38
56
76
30°F50°F70°F90°F
2.4
5.5
9.2
3.8
8.0
13.0
2.1
5.3
9.4
2.7
6.2
11.0
2.7
6.1
10.4
4.2
9.0
14.6
2.4
5.9
10.5
3.1
7.0
12.4
Pressure Drop
2.0
4.6
7.9
3.1
6.8
11.2
1.7
4.4
8.1
2.1
5.2
9.5
2.2
5.2
8.9
3.5
7.6
12.6
1.9
4.9
9.2
2.4
5.9
10.7
1.2
3.4
6.2
2.3
5.3
9.2
1.2
3.5
6.7
1.5
4.1
7.7
1.4
3.8
6.9
2.6
6.0
10.3
1.3
3.9
7.5
1.7
4.6
8.7
1.1
3.0
5.7
2.0
4.8
8.6
1.0
3.2
6.2
1.3
3.7
7.2
1.2
3.4
6.4
2.3
5.5
9.6
1.1
3.6
7.0
1.5
4.2
8.1
CXM Safety Control Reset
Lockout - In Lockout mode, the Status LED will begin fast
ashing. The compressor relay is turned off immediately.
Lockout mode can be soft reset via the thermostat “Y”
input or can be hard reset via the disconnect. The last fault
causing the lockout will be stored in memory and can be
viewed by going into test mode.
Fault Retry - In Fault Retry mode, the Status LED begins
slow ashing to signal that the control is trying to recover
from a fault input. The CXM control will stage off the
outputs and then “try again” to satisfy the thermostat "Y"
input call. Once the thermostat input calls are satised,
the control will continue on as if no fault occurred. If 3
consecutive faults occur without satisfying the thermostat
"Y" input call, then the control will go to Lockout mode. The
last fault causing the lockout will be stored in memory and
can be viewed by going into test mode.
Consult the CXM manual for complete descriptions.
CAUTION!
CAUTION! Do not restart units without inspection and
remedy of faulting condition. Equipment damage may occur.
39
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
Start-up Sheet Log
Installer: Complete unit and system checkout and follow unit start-up procedures in the IOM. Use this form to record
unit information, temperatures and pressures during start-up. Keep this form for future reference.
Job Name: ________________________________ Street Address: _____________________________________
Model Number: ____________________________ Serial Number: ______________________________________
Unit Location in Building: _______________________________________________________________________
Date: ________________________________ Sales Order No: __________________________________________
In order to minimize troubleshooting and costly system failures, complete the following checks and data entries before
the system is put into full operation.
Temperatures: F C
Pressures: PSIG kPa
Cooling ModeHeating Mode
Entering Fluid Temperature
Leaving Fluid Temperature
Temperature Differential
Return-Air TemperatureDBWBDBWB
Supply-Air Temperature
Temperature Differential
DB
WBDBWB
Water Coil Heat Exchanger
(Water Pressure IN)
Water Coil Heat Exchanger
(Water Pressure OUT)
Pressure Differential
Compressor
Amps
Volts
Discharge Line Temperature
(After 5 Minutes)
Motor
Amps
Volts
Do not connect gage lines
40
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
Unit Operating Conditions
Table 8: Typical Unit Operating Pressures and Temperatures
*Based on Nominal 400 cfm per ton airow and 70°F EAT htg and 80/67°F EAT cooling
**Cooling air and water numbers can vary greatly with changes in humidity
Subcooling is based upon the head pressure at compressor service port
Table 9: Water Temperature Change Through Heat Exchanger
Water Flow, gpm [l/m]
For Closed Loop: Ground Source or
Closed Loop Systems at 3 gpm per ton
[3.9l/m per kw]
For Open Loop: Ground Water Systems
at 1.5 gpm per ton [2.0l/m per kw]
Rise, Cooling
°F, [°C]
9-124-11
18-237-20
Drop, Heating
°F, [°C]
41
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
Preventive Maintenance
Water Coil Maintenance –
Generally water coil maintenance is not needed however,
if the installation is located in a system with a known
high dirt or debris content, it is best to establish with
the owner a periodic maintenance schedule so the coil
can be checked regularly. These dirty installations are
a result of the deterioration of iron or galvanized piping
or components in the system or open cooling towers
requiring heavy chemical treatment and mineral buildup
through water use. Should periodic coil cleaning be
necessary, use standard coil cleaning procedures which
are compatible with both the heat exchanger material
and copper water lines. Generally, the more water owing
through the unit, the less chance for scaling, however
ow rates over 3 gpm per ton can produce water (or
debris) velocities that can erode the heat exchanger wall
and ultimately produce leaks.
Compressor
Conduct annual amperage checks to ensure amp draw
is no more than 10% greater than that indicated by serial
plate data.
Fan Motors
All units have lubricated fan motors. Inspection should be
performed for proper tension and excessive wear of drive
belts every three months.
Air Coil
The air coil must be cleaned to obtain maximum
performance. Check once a year under normal operating
conditions and, if dirty, brush or vacuum clean. Care must
be taken not to damage the aluminum ns while cleaning.
CAUTION: Fin edges are sharp.
Filters
Filters must be clean to obtain maximum performance.
They should be inspected every month under normal
operating conditions and be replaced when necessary.
Units should never be operated without a lter.
Washable high efciency electrostatic lters, when dirty,
can exhibit a very high pressure drop for the fan motor
and reduce air ow resulting in poor performance. It is
especially important to provide consistent washing of
these lters (in opposite direction of the normal air ow)
once per month using a high pressure wash similar to
that found at self-serve car washes.
Condensate Drain
In areas where airborne bacteria produce a slime in
the drain pan, it may be necessary to treat chemically
with an algaecide every three months or so to minimize
the problem. The condensate pan may also need to be
cleaned periodically to assure indoor air quality. The
condensate drain can pick up lint and dirt, especially with
dirty lters. Inspect the drain twice a year to avoid the
possibility of overow.
Cabinet
Do not allow water to stay in contact with the cabinet for
long periods of time to prevent corrosion of the cabinet
sheet metal. Generally vertical cabinets are set up from
the oor a few inches for prevention. The cabinet can be
cleaned using a mild detergent.
Refrigerant System
To maintain sealed circuit integrity, do not install service
gauges unless unit operation appears abnormal.
Reference the operating chart for pressure and
temperatures. Verify that air and water ow rates and
temperatures are at proper levels before servicing the
refrigerant circuit.
WARNING!
To avoid the release of refrigerant into the atmosphere,
the refrigerant circuit of this unit must be serviced only by
technicians who meet local, state, and federal prociency
requirements.
42
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
Functional Troubleshooting
FaultHtg Clg Possible CauseSolution
Main power ProblemsXX Green Status LED OffCheck Line Voltage circuit breaker and disconnect
HP Fault-Code 2X Reduced or no water flowCheck pump operation or valve operation/setting
High pressurein cooling
LP/LOC Fault-Code 3XX Insufficient chargeCheck for refrigerant leaks
Low Pressure/Loss of Charge X
FP1 Fault - Code 4XReduced or no water flowCheck pump operation or water valve operation/setting
Water Coil low
temperature limit
FP2 fault - Code 5X Reduced or no Air flowCheck for dirty air filter and clean or replace
Air Coil low
temperature limit
Condensate Fault-Code
Over/Under VoltageCode 7
(Auto resetting)Check power supply wire size
Unit Performance
Sentinel-Code 8
No Fault Code ShownXX No compressor operationSee "Only fan operates"
Unit Short CyclesXX Dirty Air FilterCheck and Clean air filter
Only Fan RunsXX Thermostat positionInsure thermostat set for heating or cooling operation
6
X
Water Temperature out of range in
cooling
XReduced or no Air flowCheck for dirty air filter and clean or replace
in heatingCheck fan motor operation and airflow restrictions
X
Air Temperature out of range in
heating
XX
Overcharged with refrigerant
XX
Bad HP SwitchCheck switch continuity and operation. Replace
Compressor pump down at startup
in heatingPlugged strainer or filter. Clean or replace.
XInadequate anti-freeze levelCheck antifreeze density with hydrometer
Improper temperature limit setting
X
(30°F vs 10°F [-1°C vs -12°C])
XWater Temperature out of range Bring water temp within design parameters
XX Bad thermistorCheck temp and impedance correlation per chart
in coolingCheck fan motor operation and airflow restrictions
X Air Temperature out of range
Improper temperature limit setting
X
(30°F vs 10°F [-1°C vs -12°C])
XX Bad thermistorCheck temp and impedance correlation per chart
XX Blocked DrainCheck for blockage and clean drain
XX Improper trapCheck trap dimensions and location ahead of vent
X Poor DrainageCheck for piping slope away from unit
X Moisture on sensorCheck for moisture shorting to air coil
XX Under Voltage
XX
Over Voltage
XHeating mode FP2>125°F [52°C] Check for poor air flow or overcharged unit.
Cooling Mode FP1>125°F [52°C]
X
OR FP2< 40ϒF [4ϒC]
XX Compressor OverloadCheck and Replace if necessary
XX Control boardReset power and check operation
XX Unit in "Test Mode"Reset power or wait 20 minutes for auto exit.
XX Unit selection
XX Compressor OverloadCheck and Replace if necessary
XX Unit locked outCheck for lockout codes. Reset power.
XX Compressor OverloadCheck compressor overload. Replace if necessary.
XX Thermostat wiring
Check for line voltage between L1 and L2 on the contactor
Check for 24VAC between R and C on CXM/DXM
Check primary/secondary voltage on transformer
Check water flow adjust to proper flow rate
Bring water temp within design parameters
Dirty Air Coil- construction dust etc.
Too high of external static. Check static vs blower table
Bring return air temp within design parameters
Check superheat/subcooling vs typical operating condition
table
Check charge and start-up water flow
Check water flow adjust to proper flow rate
Clip JW3 jumper for antifreeze (10°F [-12°C]) use
Too high of external static. Check static vs blower table
Too much cold vent air? Bring entering air temp within
design parameters
Normal airside applications will require 30°F [-1°C] only
Check slope of unit toward outlet
Poor venting. Check vent location
Check power supply and 24VAC voltage before and during
operation.
Check compressor starting. Need hard start kit?
Check 24VAC and unit transformer tap for correct power
supply voltage
Check power supply voltage and 24VAC before and during
operation.
Check 24VAC and unit transformer tap for correct power
supply voltage
Check for poor water flow, or air flow
Unit may be oversized for space. Check sizing for actual
load of space.
Check thermostat wiring at heat pump. Jumper Y and R
for compressor operation in test mode.
43
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
Only Compressor RunsXXThermostat wiring
Check G wiring at heat pump. Jumper G and R for fanoperation.
XXFan motor relay
Jumper G and R for fan operation. Check for Line voltageacross BR contacts.
Check fan power enable relay operation (if present)
XXFan motorCheck for line voltage at motor. Check capacitor
XXThermostat wiring
Check thermostat wiring at heat pump. JumperY and R forcompressor operation in test mode.
Unit Doesn't Operate inCooling
XReversing Valve
Set for cooling demand and check 24VAC on RV coil and atCXM/DXM board.
If RV is stuck, run high pressure up by reducing water flowand while operating engage and disengage RV coil voltageto push valve.
XThermostat setupCheck for 'O' RV setup not 'B'
XThermostat wiring
Check O wiring at heat pump. Jumper O and R for RV coil'Click'.
X
Thermostat wiring
Put thermostat in cooling mode. Check for 24VAC on O(check between C and O); check for 24VAC on W (checkbetween W and C). There should be voltage on O, but noton W. If voltage is present on W, thermostat may be bador wired incorrectly.
Functional Troubleshooting
Only Compressor RunsXX Thermostat wiring
XX Fan motor relay
XX Fan motorCheck for line voltage at motor. Check capacitor
XX Thermostat wiring
Unit Doesn't Operate in
Cooling
Performance
Troubleshooting
Insufficient capacity/XX Dirty FilterReplace or clean
Not cooling or heatingXReduced or no Air flowCheck for dirty air filter and clean or replace
properlyin heatingCheck fan motor operation and airflow restrictions
X Reversing Valve
X Thermostat setupCheck for 'O' RV setup not 'B'
X Thermostat wiring
Thermostat wiring
X
Htg Clg Possible CauseSolution
X Reduced or no Air flowCheck for dirty air filter and clean or replace
in coolingCheck fan motor operation and airflow restrictions
XX Leaky duct work
XX Low refrigerant chargeCheck superheat and subcooling per chart
XX Restricted metering deviceCheck superheat and subcooling per chart. Replace.
X Defective Reversing ValvePerform RV touch test
XX Thermostat improperly locatedCheck location and for air drafts behind stat
XX Unit undersized
XX Scaling in water heat exchanger Perform Scaling check and clean if necessary
Check G wiring at heat pump. Jumper G and R for fan
operation.
Jumper G and R for fan operation. Check for Line voltage
across BR contacts.
Check fan power enable relay operation (if present)
Check thermostat wiring at heat pump. Jumper Y and R for
compressor operation in test mode.
Set for cooling demand and check 24VAC on RV coil and at
CXM/DXM board.
If RV is stuck, run high pressure up by reducing water flow
and while operating engage and disengage RV coil voltage
to push valve.
Check O wiring at heat pump. Jumper O and R for RV coil
'Click'.
Put thermostat in cooling mode. Check for 24VAC on O
(check between C and O); check for 24VAC on W (check
between W and C). There should be voltage on O, but not
on W. If voltage is present on W, thermostat may be bad
or wired incorrectly.
Performance Troubleshooting
Too high of external static. Check static vs blower table
Too high of external static. Check static vs blower table
Check supply and return air temperatures at the unit and at
distant duct registers if significantly different, duct leaks
are present
XX Inlet Water too Hot or ColdCheck load, loop sizing, loop backfill, ground moisture.
High Head PressureXReduced or no Air flowCheck for dirty air filter and clean or replace
Low Suction PressureXReduced water flowCheck pump operation or water valve operation/setting
Low discharge air
temperature in heating
High humidityX Too high of air flowCheck fan motor speed selection and airflow chart
in heatingCheck fan motor operation and airflow restrictions
Too high of external static. Check static vs blower table
X Reduced or no water flowCheck pump operation or valve operation/setting
in coolingCheck water flow adjust to proper flow rate
X Inlet Water too HotCheck load, loop sizing, loop backfill, ground moisture.
X
Air Temperature out of range in
heating
X Scaling in water heat exchanger Perform Scaling check and clean if necessary
XX Unit OverchargedCheck superheat and subcooling. Reweigh in charge
XX Non-condensables insystemVacuum system and reweigh in charge
XX Restricted metering deviceCheck superheat and subcooling per chart. Replace.
in heatingPlugged strainer or filter. Clean or replace.
XWater Temperature out of range Bring water temp within design parameters
X Reduced Air flowCheck for dirty air filter and clean or replace
in coolingCheck fan motor operation and airflow restrictions
X Air Temperature out of range
XX Insufficient chargeCheck for refrigerant leaks
XToo high of air flowCheck fan motor speed selection and airflow chart
XPoor PerformanceSee 'Insufficient Capacity'
X Unit oversized
Bring return air temp within design parameters
Check water flow adjust to proper flow rate
Too high of external static. Check static vs blower table
Too much cold vent air? Bring entering air temp within
design parameters
*Filter drier not on some units with R22 refrigerant.
°F
FP2: HEATING
LIQUID LINE
FLASH
GAS LINE
°F
FP1
SENSOR
°F
°F°F
PSIPSI
WATER INWATER OUT
Look up pressure drop in
I.O.M. or spec. catalog to
determine flow rate.
COOLING CYCLE ANALYSIS -
AIR
COIL
°F°F
PSI
°F
PSI
PSI
°F
SAT
SUCTION
COMPRESSOR
DISCHARGE
°F
SAT
SAT
SUCTION
COMPRESSOR
°F
FILTER
DRIER*
FP1: CLG
LIQ LINE
COAX
°F
°F°F
PSIPSI
WATER INWATER OUT
DISCHARGE
HWG
°F
PSI
Look up pressure drop in
SAT
FP2: FLASH
GAS LINE
EXPANSION
VALVE
°F
OTHER SIDE
OF FILTR DR
I.O.M. or spec. catalog to
determine flow rate.
Heat of Extraction (Absorption) or Heat of Rejection =
________ flow rate (diff. (factor = _____________
Superheat
Subcooling
=
=
gpm) x ________ temp.deg. F) x ________ fluid
Suction temperature - suction saturation temp.
Discharge saturation temp. - liquid line temp.
=
=
(Btu/hr)
(deg F)
(deg F)
Note: Never connect refrigerant gauges during startup procedures. Conduct water-side analysis
using P/T ports to determine water ow and temperature difference. If water-side analysis shows
poor performance, refrigerant troubleshooting may be required. Connect refrigerant gauges as a
last resort.
45
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
Follow All Warnings and Cautions in
This Manual Before Attempting Conversion.
Field Conversion Options
Top Discharge to Straight Discharge Convertible
Follow all warnings and cautions in this manual
No More Ordering New Panels From the Vendor
before attempting conversion.
No More Buying a Different Size Belt
No More Heavy Lifting (Blower/Motor ASM)
What may have taken a day can now be a 15-minute job
Blower Access
Panel
C-Box/
Motor Access
Panel
Compressor
Access Panel
Step 1: Remove the three panels, as shown.
46
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
Step 2: Remove Blockoff Air Handler as shown.
Loosen belt and remove.
Blockoff
Air Handler
Step 3
Step 3: Remove bolts (4x) off blower panel.
Remove bolts (4x) (2x ea. side) from blower sides.
Step 3
47
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
Step 4: Remove bolts (4x) and take blower glides out.
Blower Glides
(2x)
Step 5: Attach Blower Glides to Blower BTM Load Brackets as shown.
Use bottom set of holes (.203 Dia.) on Blower BTM Load Brackets.
Blower Shaft should be sitting right on top of the Blower Glides.
48
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
Step 6: Stand in front and pull Blower ASM on to the ridge of the Blower Glides.
Step 7: Rotate Blower ASM using Blower Glides as a guiding track.
Step 8: When the Blower ASM is parallel to the floor, push the Blower ASM
back so that the Blower Panel is flush with the unit.
49
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
Step 9: Attach Blower ASM with bolts (4x) as shown.
Step 10: Remove Bower Glides (2x) and re-attach back in compressor section.
Step 10
50
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
Important!
Step 11: Re-bolt Blower ASM to Blower BTM load brackets
4 ¼-20 UNC bolts, (2x) each side
Re-attach belt and tighten.
51
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
Step 12: Re-attach Blockoff Air Handler as shown.
Blockoff Air Handler
Blower Filler
Panel
C-Box/Motor Access
Panel
Compressor
Panel Access
Step 13: Put (3x) panels back on.
Reverse steps to change a Straight Discharge to a Top Discharge.
52
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
Front Control Box/ Motor Access to Back Access Convertible
Control Box Cover
• No More Dumping Charge/ Adding Charge
• No More Unbrazing/ Brazing Copper
• No More Heavy Lifting (Blower/ Motor ASM)
• No More Flipping Coil Over
What may have taken a day can now be a 15-minute job
Front C-Box/
Motor Access
Panel
Compressor
Access Panel
Step 1: Remove the three panels as shown.
Return Air
Control Box
Back Compressor/
C-Box/ Motor Access
Panel
Motor
Cover
Step 2: Remove Motor Cover and Control Box Cover as shown.
53
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
Step 3: Remove screws from Control Box (Qty 4x) and
A) flip down, B) slide across and C) flip up as shown using the
guide rails inside as a guide. Re-attach control box with screws.
Screws
Step 4: Loosen Belt tension and take Belt off.
Step 5: Remove Bolt-Belt Adjustment ASM as shown.
Step 5
A
B
Right Side View
C
Bolt-Belt Adjustment ASM
Step 4
54
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
Step 6: Move Bolt-Belt Adjustment ASM to opposite side and re-attach.
Step 6
Control Box Cover
Step 7: Put Belt back on and tighten.
Put Control Box Cover and
Motor Cover on return side.
Step 8: Place panels back on unit.
Reverse steps to go from
a front return to a back return.
Control Box
Motor Cover
Front Return Top Discharge
55
Heat Controller, Inc. HKV LArge CommerCiAL IOM Instructions
• Water In-Out Available on Either Side
• Hi-Low Voltage Access on Any Side
• Full Filter Frame - Bottom Access - 1”, 2”, or 4”
*
Water Out
2
Water In
2
1
Water In
• Filters - 1” or 2” Fiberglass and 4” Merv 8
1
Water Out
Control Box
1
1
Front Return Top Discharge
1. Water inlet and outlet connections are available on either side (left or right) of the unit.
MPT Plugs (Qty 2x) are shipped loose in plastic bag tied to water leg in front of the
unit. Installer must plug up water inlet/outlet side that is not being connected.
2. Electrical access is available on either side (left or right) of unit and is also available
(left or right) in the front of the unit.
3. 1” Filter rack can be field converted to 2”.
* Consult factory for availability and part numbers
*
56
IOM Instructions HKV LArge CommerCiALHeat Controller, Inc.
Condensate Drain Can Connect to Either Side of Unit
TLV Units come with flex hose and 1” FPT
HKV
condensate connection tied inside (shown above)
Installer will untie flex hose and make an internal trap
on either the left side (shown above) or on the right side.
Internally attach mounting plate with FPT fitting.
57
11/2010
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.