Heat Controller HBH-V User Manual

ENGINEERING
DESIGN GUIDE
Commercial Horizontal & Vertical
Packaged Water-Source Heat Pumps:
HBH/V Compact
Heat Controller, Inc. • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.com
Engineering Design Guide HBH/V SERIES Heat Controller, Inc.
Table of Contents
Selection Procedure .......................................................................................................................... 3-4
Performance Data - HB H/V 012 ........................................................................................................ 10
Performance Data - HB H/V 015 .........................................................................................................11
Performance Data - HB H/V 018 ........................................................................................................ 12
Performance Data - HB H/V 024 ........................................................................................................ 13
Performance Data - HB H/V 030 ........................................................................................................ 14
Performance Data - HB H/V 036 ........................................................................................................ 15
Performance Data - HB H/V 042 ........................................................................................................ 16
Performance Data - HB H/V 048 ........................................................................................................ 17
Performance Data - HB H/V 060 ........................................................................................................ 18
Air Flow Correction Tables ................................................................................................................. 19
Antifreeze Correction Table ................................................................................................................ 20
Blower Performance Data ............................................................................................................. 21-22
Physical Data ..................................................................................................................................... 23
HB - Horizontal Dimensional Data................................................................................................. 24-25
HB - Vertical Upow Dimensional Data ......................................................................................... 26-27
Corner Weights for HB Series Units ................................................................................................... 28
Electrical Data .................................................................................................................................... 29
Electrical Data - (High Static Table) .................................................................................................... 30
Typical Wiring Diagram Single Phase HB Units With CXM Controller ............................................... 31
Typical Wiring Diagram Three Phase 208/230V HB Units With CXM Controller ............................... 32
Typical Wiring Diagram Three Phase 460/575V HB Units with CXM Controller ................................ 33
1
Heat Controller, Inc. HBH/V SERIES Engineering Design Guide
HB Series
The HBH/V Series exceeds ASHRAE 90.1 efciencies, and uses R-410A zero ozone depletion refrigerant,
making it an extremely environmentally-friendly option. HBH/V is eligible for additional LEED™ (Leadership in Energy and Environmental Design) points because of the “green” technology design. With one of the smallest
cabinets in the industry, the HBH/V will easily t into
tight spaces. Designed to be backward compatible with thousands of older water-source heat pumps.
Available in sizes from 1/2 ton (1.76 kW) through 5 tons
(17.6 kW) with multiple cabinet options (vertical upow
and horizontal) the HBH/V offers a wide range of units for most any installation. The HBH/V has an extended range
refrigerant circuit, capable of geothermal ground loop
applications (with optional extended range insulation) as well as boiler-tower water loop applications. Standard features include: Copeland scroll compressors (rotary for
size 018 and below), microprocessor controls, galvanized steel cabinet, galvanized steel with epoxy powder painted
drain pan and sound absorbing air handler insulation.
Heat Controller’s exclusive double isolation compressor mounting system makes the HBH/V the quietest unit on the market. Compressors are mounted via rubber
vibration isolators to a heavy gauge mounting plate,
which is further isolated from the cabinet base with rubber grommets for maximized vibration/sound attenuation. The easy access control box and large access panels make installing and maintaining the unit easier than other water-source heat pumps currently
in production, proving that a small unit can be easy to
service.
The HBH/V Series is full of options, such as an
e-coated air coil. Optional high static fan motor expands the operating range and helps overcome some of
the challenges associated with ductwork for retrot
installations. A Cupro-Nickel water-coil and sound absorbing mute package are options that make a great unit even better.
The HBH/V Series Water-Source Heat Pumps are designed to meet the challenges of today’s HVAC demands with one of the most innovative products available on the market.
Unit Features
• Sizes 006 (1/2 ton, 1.76 kW) through 060 (5 tons, 17.6 kW)
• R-410A refrigerant
• Exceeds ASHRAE 90.1 efciencies
• Galvanized steel construction
• Epoxy powder painted galvanized steel drain pan
• Sound absorbing glass ber insulation
• Unique double isolation compressor mounting via
vibration isolating rubber grommets for quiet operation
• Insulated divider and separate compressor/air handler
compartments
• Copeland scroll compressors (rotary for size 018 and
below)
• TXV metering device
• Microprocessor controls standard
• Field convertible discharge air arrangement for
horizontal units
• PSC three-speed fan motor
• Internally trapped condensate drain line (vertical units
only)
• Unit Performance Sentinel performance monitoring
system
• Eight Safeties Standard
• Extended range (20 to 120°F, -6.7 to 48.9°C) capable
• High static blowers available
• Cupro-Nickel water-coil available
• Sound absorbing UltraQuiet package available
2
Engineering Design Guide HBH/V SERIES Heat Controller, Inc.
To convert Inch-Pound (English) to SI (Metric)
LWT = EWT -
HE
GPM x 500
LAT = EAT +
HC
CFM x1.08
LWT = EWT +
HR
GPM x 500
LAT (DB) = EAT (DB) -
SC
CFM x1.08
LC = TC - SC
S/T =
SC
TC
Heating
Cooling
Selection Procedure
Reference Calculations
Legend and Glossary of Abbreviations
BTUH = BTU( British Thermal Unit) per hour
CFM = airow, cubic feet/minute COP = coefcient of performance = BTUH output/BTUH input DB = dry bulb temperature (°F) EAT = entering air temperature, Fahrenheit (dry bulb/wet bulb) EER = energy efciency ratio = BTUH output/Watt input
EPT = external pipe thread ESP = external static pressure (inches w.g.) EWT = entering water temperature
GPM = water ow in U.S. gallons/minute HE = total heat of extraction, BTUH HC = air heating capacity, BTUH HR = total heat of rejection, BTUH
HWC = hot water generator (desuperheater) capacity, Mbtuh
IPT = internal pipe thread
KW = total power unit input, kilowatts LAT = leaving air temperature, °F LC = latent cooling capacity, BTUH LWT = leaving water temperature, °F
MBTUH = 1000 BTU per hour S/T = sensible to total cooling ratio
SC = sensible cooling capacity, BTUH TC = total cooling capacity, BTUH
WB = wet bulb temperature (°F) WPD = waterside pressure drop (psi & ft. of hd.)
Conversion Table - to convert inch-pound (English) to SI (Metric)
Air Flow Water Flow Ext Static Pressure Water Pressure Drop
Airflow (L/s) = CFM x 0.472 Water Flow (L/s) = gpm x 0.0631 ESP (Pa) = ESP (in of wg) x 249 PD (kPa) = PD (ft of hd) x 2.99
3
Heat Controller, Inc. HBH/V SERIES Engineering Design Guide
Selection Procedure
Step 1 Determine the actual heating and cooling loads at the
desired dry bulb and wet bulb conditions.
Step 2
Step 3 Select a unit based on total and sensible cooling
Step 4 Enter tables at the design water ow and water
Step 5 Read the heating capacity. If it exceeds the design
Obtain the following design parameters: Entering water
temperature, water ow rate in GPM, air ow in CFM, water ow pressure drop and design wet and dry bulb temperatures. Air ow CFM should be between 300 and
450 CFM per ton. Unit water pressure drop should be kept as close as possible to each other to make water
balancing easier. Go to the appropriate tables and nd the proper indicated water ow and water temperature.
conditions. Select a unit which is closest to, but no larger than, the actual cooling load.
temperature. Read the total and sensible cooling
capacities (Note: interpolation is permissible,
extrapolation is not).
criteria it is acceptable. It is quite normal for Water­Source Heat Pumps to be selected on cooling capacity only since the heating output is usually greater than the cooling capacity.
Example Equipment Selection For Cooling
Step 1 Load Determination: Assume we have determined that the appropriate cooling load
at the desired dry bulb 80°F and wet bulb 65°F conditions is
as follows:
Total Cooling ......................................23,700 BTUH
Sensible Cooling ................................. 16,500 BTUH
Entering Air Temp .... 80°F Dry Bulb / 65°F Wet Bulb
Step 2 Design Conditions:
Similarly, we have also obtained the following design parameters:
Entering Water Temp ....................................... 90°F
Water Flow (Based upon 10°F rise in temp.) 6.0 GPM
Air Flow .................................................... 800 CFM
Step 3, 4 & 5 HP Selection: After making our preliminary selection (TC024), we enter the tables at design water ow and water temperature and read Total Cooling, Sens. Cooling and Heat of Rej. capacities:
Total Cooling .......................................23,400 BTUH
Sensible Cooling ................................. 17,500 BTUH
Heat of Rejection ................................30,200 BTUH
Step 6 Determine the correction factors associated with the
variable factors of dry bulb, wet bulb and air ow.
Corrected Total Cooling =
tabulated total cooling x wet bulb correction x air ow
correction Corrected Sensible Cooling = tabulated sensible cooling x dry bulb correction x air
ow correction
Step 7 Compare the corrected capacities to the load
requirements. Normally if the capacities are within 10%
of the loads, the equipment is acceptable. It is better
to undersize than oversize, as undersizing improves
humidity control, reduces sound levels and extends the
life of the equipment.
Step 8 When completed, calculate water temperature rise
and assess the selection. If the units selected are not
within 10% of the load calculations, then review what
effect changing the GPM, water temperature and/or air
ow and air temperature would have on the corrected
capacities. If the desired capacity cannot be achieved,
select the next larger or smaller unit and repeat the
procedure. Remember, when in doubt, undersize
slightly for best performance.
Step 6 & 7 Entering Air and Airow Corrections: Next, we determine our correction factors.
Table Ent Air Air Flow Corrected
Corrected Total Cooling = 23,400 x 0.9681 x 1.0050 = 22,767 Corrected Sens Cooling = 17,500 x 1.1213 x 0.9820 = 19,270 Corrected Heat of Reject = 30,200 x 0.9747 x 1.0434 = 30,713
Step 8 Water Temperature Rise Calculation & Assessment:
Actual Temperature Rise 10.2°F
When we compare the Corrected Total Cooling and Corrected
Sensible Cooling gures with our load requirements stated in Step 1, we discover that our selection is within +/- 10% of our sensible load requirement. Furthermore, we see that our Corrected Total Cooling gure is within 1,000 Btuh the actual
indicated load.
4
Engineering Design Guide HBH/V SERIES Heat Controller, Inc.
HEAT CONTROLLER OEM PRICE LIST
HBH & HBV COMPACT Horizontal & Vertical HFC-410a Units
H B H A0 3 6 C3 3 0 A L B
1 2 3 4 5 6 7
8
9 10 11 12 13 14
HB = HEAT CONTROLLER COMPACT 410A
MODEL TYPE
H = HORIZONTAL (NON PAINTED)
CONFIGURATION
V = VERTICAL (PAINTED POLAR ICE)
UNIT SIZE
018 - 1,8 024 - 1,3,4,8 030 - 1,3,4,8 036 - 1,3,4,8 042 - 1,3,4,5 048 - 1,3,4,5 060 - 1,3,4,5
REVISION LEVEL
A = CURRENT REVISION FOR SIZES 006 - 060
VOLTAGE
C = CXM
CONTROLS
3 = STANDARD RANGE
CABINET INSULATION
0 = NONE
FUTURE USE
A = Copper Water Coil w/E-Coated Air Coil
HEAT EXCHANGER OPTIONS
C = Copper Water Coil w/Non-Coated Air Coil
L = LEFT RETURN
RETURN AIR OPTIONS
R = RIGHT RETURN F = FRONT RETURN, VERTICAL 009-030
B = BACK DISCHARGE, HORIZONTAL ONLY
SUPPLY AIR OPTIONS
Y = BACK DISCHARGE, HIGH STATIC
HORIZONTAL 018 - 060
T = TOP DISCHARGE, VERTICAL ONLY V = TOP DISCHARGE, HIGH STATIC
VERTICAL 018 - 060
S = STRAIGHT DISCHARGE, HORIZONTAL ONLY Z = STRAIGHT DISCHARGE, HIGH STATIC
HORIZONTAL 018 - 060
J = Cupro-Nickel Water Coil w/E-Coated Air Coil N = Cupro-Nickel Water Coil w/Non-Coated Air Coil
4 = STANDARD RANGE, WITH ULTRA QUIET
015 - 1,8
1 = 208-230/60/1 8 = 265/60/1 3 = 208-230/60/3 4 = 460/60/3 5 = 575/60/3
C = STANDARD RANGE, COOLING ONLY, VERTICAL UNITS
3 = DISCHARGE PRESSURE WATER REGULATING VALVE (COOLING ONLY) NOT AVAILABLE ON UNIT SIZES 006, 009 AND 012
V = LEFT RETURN, S.S DRAIN PAN W = RIGHT RETURN, S.S DRAIN PAN Z = FRONT RETURN, S.S. DRAIN PAN 009-030
}
Voltage Code
Entering Water Temperature Range: 20 - 120°F (-6.7 - 48.9°C)
Horizontal Water Source Heat Pump Sizes 015-060
006-060
Vertical Water Source Heat Pump Sizes 015-060
006-060
HBH & HBV Model Structure
Basic Unit Description:
The basic unit price includes sealed heat pump refrigerant circuit and air handler within cabinetry,  lter, and a factory installed hanger kit on horizontal units.
• Cabinetry - Compact design - galvanized steel construction -
Cabinetry – Compact design - galvanized steel construction -
powder coat nish on front access panels - controls access panel
controls access panel - compressor access panels - FPT water
- com pres sor access panels - FPT water con nec tions - high and low
connections - high and low voltage knockouts - 1” (25mm), air lter
voltage knock outs - 1” (25mm), air lter and lter rack. All vertical
and lter rack. All vertical units have a left or right return air option,
units have a left or right return air option, sizes 015 - 030 have a front
sizes 006-030 have a front return option. All horizontal units have eld
return option. All hor i zon tal units have eld convertible dis charge air
convertible discharge air patterns with extra parts required.
patterns with no extra parts required.
• Standard Controls - CXM Controller, loss of charge switch, high
pressure switch, water coil low temperature cutout, lockout safety circuit resetable at ther mo stat or dis con nect, LED fault indication, ve minute anti-short cycle protection, random start, high and low voltage pro tec tion, con den sate over ow pro tec tion, dry contact for alarm.
• Compressor - High ef ciency hermetic scroll or rotary, overload
pro tect ed - internally sprung & externally isolated using dual vibration dampening system for extra quiet operation. Mounting system incorporates rubber grommet isolation under the compressor and rubber grommet isolation between the compressor mounting tray and unit base.
006
5
• Reversing Valve - 4-way, pilot operated, solenoid activated in the
cool mode.
• Refrigerant Circuit - Utilizes expansion valve metering device -
copper tubing interconnecting all components - sealed & tested non-ozone depleting, HFC-410A refrigerant circuit with high & low side schraeder ports.
• Water to Refrigerant Coil - Tube-in-tube, convoluted copper inner
water tube.
• Refrigerant to Air Coil - Lanced aluminum  ns on ri ed copper
tubes.
• Blower Motor - Three-speed PSC direct drive, permanently
lu bri cat ed (Two-speed on 575 volt applications).
• UltraQuiet Option - Compressor incorporates spring mounting
system, 015-060 include compressor discharge muf er, blower housing is covered with high density noise suppression material.
• Application - Units can be applied in WLHP, GWHP, or GLHP
R-410A refrigerant circuit with high & low
applications.
Heat Controller, Inc. HBH/V SERIES Engineering Design Guide
Performance Data ARI/ASHRAE/ISO 13256-1
ASHRAE/ARI/ISO 13256-1. English (IP) Units
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Model
HB-006
HB-009
HB-012
HB-015
HB-018
HB-024
HB-030
HB-036
HB-042
HB-048
HB-060
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Heating capacities based upon 68°F DB, 59°F WB entering air temperature
All ratings based upon operation at lower voltage of dual voltage rated models
Cooling 86°F Heating 68°F Cooling 59°F Heating 50°F Cooling 77°F Heating 32°F
Capacity
Btuh
5,800 13.2 7,500 4.7 6,900 21.1 6,200 4.0 6,200 15.4 4,900 3.4
8,800 13.4 11,600 4.2 10,100 21.0 9,800 3.9 9,300 15.7 7,900 3.4
11,700 13.5 15,200 4.3 13,700 20.8 12,500 3.8 12,000 14.9 9,900 3.2
14,500 15.4 17,300 5.0 16,800 24.5 14,400 4.4 15,000 17.2 11,100 3.6
17,300 14.3 21,500 5.0 20,600 24.2 17,200 4.4 18,400 16.3 13,900 3.4
23,700 13.4 28,500 4.7 26,700 20.9 24,000 4.1 24,900 15.4 18,500 3.3
28,100 13.4 35,100 4.6 31,700 20.1 29,600 4.1 28,900 15.1 23,400 3.4
34,500 13.5 45,200 4.4 38,700 20.7 37,500 4.0 35,300 14.9 29,600 3.3
40,100 13.1 52,700 4.3 45,900 19.6 44,000 3.8 40,500 14.4 34,300 3.2
47,700 13.3 55,900 4.7 54,300 20.5 46,500 4.1 49,000 14.7 36,400 3.4
59,400 13.4 77,000 4.3 66,600 19.9 64,000 3.8 60,100 14.8 50,500 3.1
EER
Btuh/W
Capacity
Btuh
COP
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
Capacity
Btuh6
EER
Btuh/W
Capacity
Btuh
COP
ASHRAE/ARI/ISO 13256-1. Metric (SI) Units
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Model
HB-006
HB-009
HB-012
HB-015
HB-018
HB-024
HB-030
HB-036
HB-042
HB-048
HB-060
Cooling capacities based upon 27°C DB, 19°C WB entering air temperature Heating capacities based upon 20°C DB, 15°C WB entering air temperature
All ratings based upon operation at lower voltage of dual voltage rated models
Cooling 30°C Heating 20°C Cooling 15°C Heating 10°C Cooling 25°C Heating 0°C
Capacity
Watts
10.11 4.0 13.24 4.4 11.34 6.1 10.99 4.0 10.34 4.4 8.67 3.3
11.75 3.8 15.44 4.3 13.45 5.7 12.89 3.8 11.87 4.2 10.05 3.2
13.98 3.9 16.38 4.7 15.91 6.0 13.62 4.1 14.36 4.3 10.67 3.4
17.40 3.9 22.56 4.3 19.51 5.8 18.75 3.8 17.61 4.3 14.80 3.1
Cooling
COP W/W
1.70 3.9 2.20 4.7 2.02 6.2 1.82 4.0 1.82 4.5 1.44 3.4
2.58 3.9 3.40 4.2 2.96 6.2 2.87 3.9 2.72 4.6 2.31 3.4
3.43 4.0 4.45 4.3 4.01 6.1 3.66 3.8 3.52 4.4 2.90 3.2
4.25 4.5 5.07 5.0 4.92 7.2 4.22 4.4 4.39 5.0 3.25 3.6
5.07 4.2 6.30 5.0 6.04 7.1 5.04 4.4 5.39 4.8 4.07 3.4
6.94 3.9 8.35 4.7 7.82 6.1 7.03 4.1 7.30 4.5 5.42 3.3
8.23 3.9 10.28 4.6 9.29 5.9 8.67 4.1 8.47 4.4 6.86 3.4
Capacity
Watts
COP
Capacity
Watts
Cooling
COP W/W
Capacity
Watts
COP
Capacity
Watts
Cooling
COP W/W
Capacity
Watts
COP
6
kW HR EER
Airow
CFM
HC kW HE LAT COP
Engineering Design Guide HBH/V SERIES Heat Controller, Inc.
Performance Data
Selection Notes
For operation in the shaded area when water is used
in lieu of an anti-freeze solution, the LWT (Leaving
Water Temperature) must be calculated. Flow must be maintained to a level such that the LWT is maintained
above 40°F [4.4*C] when the JW3 jumper is not clipped
(see example below). This is due to the potential of the
refrigerant temperature being as low as 32°F [0°C] with 40°F [4.4°C] LWT, which may lead to a nuisance cutout
due to the activation of the Low Temperature Protection. JW3 should never be clipped for standard range equipment or systems without antifreeze.
Example:
At 50°F EWT (Entering Water Temperature) and 2.25 gpm/ton, a 3 ton unit has a HE of 27,300 Btuh. To calculate LWT, rearrange the formula for HE as follows:
HE = TD x GPM x 500, where HE = Heat of Extraction
(Btuh); TD = temperature difference (EWT - LWT) and
GPM = U.S. Gallons per Minute.
TD = HE / (GPM x 500)
TD = 27,300 / (6.75 x 500)
TD = 8°F
LWT = EWT - TD
LWT = 50 - 8 = 42°F
In this example, as long as the EWT does not fall below 50°F, the system will operate as designed. For EWTs below 50°F, higher ow rates will be required (open loop systems, for example, require at least 2 gpm/ton when EWT is below 50°F).
7
Heat Controller, Inc. HBH/V SERIES Engineering Design Guide
Performance Data HBH/V 006
Performance capacities shown in thousands of Btuh220 CFM Nominal (Rated) Airow
EWT
GPM
°F
1.5 1.7 4.0 395 170 4.3 0.49 2.7 93.3 2.6
20 Operation not recommended
1.5 1.7 4.0 525 225 4.4 0.44 2.9 88.0 2.9
0.8 0.5 1.2 170 7.4 4.2 0.57 0.28 8.4 26.4 170 4.6 0.50 3.0 95.2 2.7
0.8 0.5 1.2 225 7.7 4.8 0.62 0.29 8.7 26.4 225 4.7 0.45 3.2 89.5 3.1
1.1 0.8 1.8 170 7.4 4.1 0.55 0.26 8.3 28.5 170 4.8 0.51 3.2 96.2 2.8
30
1.1 0.8 1.8 225 7.7 4.6 0.60 0.27 8.6 28.5 225 4.9 0.46 3.4 90.3 3.2
1.5 1.3 2.9 170 7.3 4.0 0.54 0.25 8.2 29.2 170 4.9 0.51 3.2 96.8 2.8
1.5 1.3 2.9 225 7.6 4.5 0.59 0.26 8.5 29.2 225 5.0 0.46 3.5 90.7 3.2
0.8 0.4 0.9 170 7.3 4.3 0.59 0.31 8.3 23.2 170 5.3 0.52 3.6 98.8 3.0
0.8 0.4 0.9 225 7.6 4.8 0.64 0.33 8.7 23.2 225 5.4 0.47 3.8 92.3 3.4
1.1 0.6 1.4 170 7.4 4.2 0.57 0.29 8.4 25.8 170 5.5 0.53 3.8 100.2 3.1
40
1.1 0.6 1.4 225 7.7 4.8 0.62 0.30 8.7 25.8 225 5.7 0.47 4.1 93.3 3.5
1.5 1.0 2.4 170 7.4 4.2 0.56 0.28 8.4 26.9 170 5.7 0.53 3.9 100.9 3.1
1.5 1.0 2.4 225 7.7 4.7 0.61 0.29 8.7 26.9 225 5.8 0.48 4.2 93.9 3.6
0.8 0.3 0.8 170 6.9 4.2 0.61 0.35 8.1 19.9 170 6.0 0.54 4.2 102.7 3.3
0.8 0.3 0.8 225 7.2 4.8 0.66 0.36 8.5 19.9 225 6.1 0.48 4.5 95.3 3.7
1.1 0.5 1.2 170 7.2 4.3 0.59 0.32 8.3 22.5 170 6.3 0.55 4.5 104.4 3.4
50
1.1 0.5 1.2 225 7.5 4.8 0.64 0.33 8.6 22.5 225 6.5 0.49 4.8 96.6 3.9
1.5 0.9 2.0 170 7.3 4.3 0.58 0.31 8.3 23.8 170 6.5 0.55 4.6 105.4 3.4
1.5 0.9 2.0 225 7.6 4.8 0.63 0.32 8.7 23.8 225 6.7 0.50 5.0 97.4 3.9
0.8 0.3 0.6 170 6.5 4.1 0.63 0.39 7.9 16.8 170 6.7 0.56 4.9 106.7 3.5
0.8 0.3 0.6 225 6.8 4.7 0.69 0.40 8.2 16.8 225 6.9 0.50 5.2 98.4 4.0
1.1 0.5 1.0 170 6.9 4.2 0.61 0.36 8.1 19.1 170 7.1 0.57 5.2 108.6 3.7
60
1.1 0.5 1.0 225 7.1 4.8 0.67 0.37 8.4 19.1 225 7.3 0.51 5.5 99.9 4.2
1.5 0.8 1.8 170 7.0 4.2 0.61 0.34 8.2 20.4 170 7.3 0.57 5.3 109.7 3.7
1.5 0.8 1.8 225 7.3 4.8 0.66 0.36 8.5 20.4 225 7.5 0.51 5.7 100.7 4.3
0.8 0.2 0.5 170 6.0 4.0 0.66 0.43 7.5 14.0 170 7.4 0.58 5.5 110.5 3.8
0.8 0.2 0.5 225 6.3 4.5 0.72 0.45 7.8 14.0 225 7.6 0.52 5.9 101.4 4.3
1.1 0.4 0.9 170 6.4 4.1 0.64 0.40 7.8 16.0 170 7.8 0.58 5.8 112.4 3.9
70
1.1 0.4 0.9 225 6.7 4.6 0.70 0.42 8.1 16.0 225 8.0 0.53 6.2 102.8 4.5
1.5 0.7 1.6 170 6.6 4.1 0.63 0.38 7.9 17.1 170 8.0 0.59 5.9 113.4 4.0
1.5 0.7 1.6 225 6.8 4.7 0.69 0.40 8.2 17.1 225 8.2 0.53 6.4 103.6 4.5
0.8 0.2 0.5 170 5.6 3.8 0.68 0.47 7.2 12.0 170 7.9 0.59 5.9 113.2 4.0
0.8 0.2 0.5 225 5.8 4.3 0.74 0.49 7.5 12.0 225 8.1 0.53 6.3 103.5 4.5
1.1 0.4 0.8 170 5.9 3.9 0.67 0.45 7.4 13.2 170 8.3 0.60 6.3 115.4 4.1
80
1.1 0.4 0.8 225 6.1 4.4 0.73 0.46 7.7 13.2 225 8.5 0.54 6.7 105.1 4.6
1.5 0.6 1.5 170 6.2 4.0 0.65 0.42 7.6 14.7 170 8.4 0.60 6.3 115.7 4.1
1.5 0.6 1.5 225 6.4 4.6 0.71 0.44 7.9 14.7 225 8.6 0.54 6.7 105.3 4.6
0.8 0.2 0.5 170 5.3 3.7 0.70 0.5 7.0 10.7 170 8.2 0.60 6.2 114.7 4.0
0.8 0.2 0.5 225 5.5 4.2 0.76 0.52 7.3 10.7 225 8.4 0.5 6.6 104.6 4.6
1.1 0.3 0.8 170 5.6 3.8 0.68 0.47 7.2 11.9 170 8.5 0.6 6.4 116.2 4.1
85
1.1 0.3 0.8 225 5.8 4.3 0.74 0.49 7.5 11.9 225 8.7 0.5 6.8 105.8 4.7
1.5 0.6 1.4 170 5.8 3.9 0.67 0.45 7.4 13.1 170 8.5 0.6 6.4 116.4 4.1
1.5 0.6 1.4 225 6.1 4.4 0.73 0.47 7.7 13.1 225 8.7 0.5 6.8 105.9 4.7
0.8 0.2 0.4 170 5.0 3.6 0.72 0.53 6.7 9.4 170 8.5 0.61 6.4 116.3 4.1
0.8 0.2 0.4 225 5.2 4.1 0.79 0.55 7.0 9.4 225 8.7 0.55 6.8 105.8 4.7
1.1 0.3 0.7 170 5.3 3.7 0.70 0.49 7.0 10.7 170 8.6 0.62 6.5 117.0 4.1
90
1.1 0.3 0.7 225 5.5 4.2 0.76 0.52 7.3 10.7 225 8.8 0.55 7.0 106.4 4.7
1.5 0.6 1.3 170 5.5 3.8 0.69 0.48 7.1 11.5 170 8.7 0.62 6.5 117.1 4.1
1.5 0.6 1.3 225 5.7 4.3 0.75 0.50 7.4 11.5 225 8.9 0.56 7.0 106.5 4.7
0.8 0.2 0.4 170 4.4 3.4 0.76 0.58 6.4 7.6 395
0.8 0.2 0.4 225 4.6 3.8 0.83 0.60 6.6 7.6 525
1.1 0.3 0.7 170 4.7 3.5 0.74 0.55 6.6 8.7 395
100
1.1 0.3 0.7 225 4.9 4.0 0.80 0.57 6.9 8.7 525
1.5 0.5 1.2 170 4.9 3.6 0.73 0.53 6.7 9.3 395
1.5 0.5 1.2 225 5.1 4.0 0.79 0.55 7.0 9.3 525
0.8 0.2 0.3 170 3.9 3.1 0.81 0.63 6.0 6.2 395
0.8 0.2 0.3 225 4.1 3.6 0.87 0.66 6.3 6.2 525
1.1 0.3 0.6 170 4.2 3.3 0.78 0.60 6.2 7.0 395
110
1.1 0.3 0.6 225 4.4 3.7 0.85 0.62 6.5 7.0 525
1.5 0.5 1.2 170 4.3 3.3 0.77 0.58 6.3 7.4 395
1.5 0.5 1.2 225 4.5 3.8 0.83 0.61 6.6 7.4 525
0.8 0.1 0.3 170 3.5 3.0 0.85 0.68 5.8 5.0 395
0.8 0.1 0.3 225 3.6 3.3 0.93 0.71 6.0 5.0 525
1.1 0.3 0.6 170 3.7 3.0 0.83 0.65 5.9 5.6 395
120
1.1 0.3 0.6 225 3.8 3.4 0.90 0.68 6.2 5.6 525
1.5 0.5 1.1 170 3.8 3.1 0.81 0.64 6.0 6.0 395
1.5 0.5 1.1 225 4.0 3.5 0.88 0.67 6.2 6.0 525
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not reect fan or pump power corrections for ARI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.
Operation below 40°F EWT is based upon a 15% antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above. See Performance Data Selection Notes for operation in the shaded areas.
WPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT
Airow
CFM
TC SC
Sens/Tot
Ratio
kW HR EER
Airow
CFM
HC kW HE LAT COP
Operation not recommended
8
Engineering Design Guide HBH/V SERIES Heat Controller, Inc.
Performance Data HBH/V 009
Performance capacities shown in thousands of Btuh325 CFM Nominal (Rated) Airow
EWT
GPM
°F
2.3 4.5 10.5 395 250 6.5 0.73 4.2 94.2 2.6
20 Operation not recommended
2.3 4.5 10.5 525 330 6.7 0.66 4.4 88.8 3.0
1.1 1.3 3.0 250 10.2 6.0 0.59 0.39 11.6 26.6 250 7.1 0.74 4.7 96.3 2.8
1.1 1.3 3.0 330 10.7 6.8 0.64 0.40 12.0 26.6 330 7.3 0.67 5.0 90.4 3.2
1.7 1.9 4.4 250 10.5 6.0 0.57 0.36 11.7 29.5 250 7.4 0.75 4.9 97.4 2.9
30
1.7 1.9 4.4 330 10.9 6.8 0.62 0.37 12.2 29.5 330 7.6 0.67 5.3 91.2 3.3
2.3 3.5 8.1 250 10.6 6.0 0.56 0.34 11.8 31.1 250 7.5 0.75 5.1 97.9 2.9
2.3 3.5 8.1 330 11.0 6.8 0.61 0.36 12.3 31.1 330 7.7 0.68 5.4 91.7 3.4
1.1 0.9 2.0 250 9.9 6.0 0.61 0.43 11.3 22.8 250 8.0 0.76 5.5 99.8 3.1
1.1 0.9 2.0 330 10.3 6.8 0.66 0.45 11.8 22.8 330 8.2 0.69 5.9 93.1 3.5
1.7 1.5 3.5 250 10.1 6.0 0.59 0.40 11.5 25.4 250 8.4 0.77 5.8 101.1 3.2
40
1.7 1.5 3.5 330 10.5 6.8 0.64 0.41 12.0 25.4 330 8.6 0.69 6.2 94.1 3.6
2.3 3.0 6.8 250 10.3 6.0 0.59 0.38 11.6 26.8 250 8.6 0.78 6.0 101.8 3.2
2.3 3.0 6.8 330 10.7 6.8 0.64 0.40 12.0 26.9 330 8.8 0.70 6.4 94.7 3.7
1.1 0.6 1.5 250 9.4 6.0 0.63 0.48 11.1 19.5 250 9.0 0.79 6.4 103.3 3.4
1.1 0.6 1.5 330 9.8 6.7 0.69 0.50 11.6 19.5 330 9.2 0.71 6.8 95.8 3.8
1.7 1.3 2.9 250 9.7 6.0 0.62 0.45 11.3 21.7 250 9.4 0.80 6.7 104.8 3.5
50
1.7 1.3 2.9 330 10.1 6.8 0.67 0.47 11.7 21.7 330 9.6 0.72 7.2 97.0 3.9
2.3 2.6 6.0 250 9.9 6.0 0.61 0.43 11.3 23.0 250 9.6 0.80 6.9 105.6 3.5
2.3 2.6 6.0 330 10.3 6.8 0.66 0.45 11.8 23.0 330 9.8 0.72 7.4 97.6 4.0
1.1 0.5 1.2 250 9.0 5.9 0.65 0.54 10.8 16.5 250 9.9 0.81 7.2 106.8 3.6
1.1 0.5 1.2 330 9.4 6.7 0.71 0.57 11.3 16.5 330 10.2 0.73 7.7 98.5 4.1
1.7 1.1 2.5 250 9.3 5.9 0.64 0.50 11.0 18.5 250 10.4 0.82 7.6 108.4 3.7
60
1.7 1.1 2.5 330 9.7 6.7 0.69 0.52 11.5 18.5 330 10.6 0.74 8.1 99.8 4.2
2.3 2.3 5.4 250 9.5 6.0 0.63 0.48 11.1 19.6 250 10.6 0.83 7.8 109.3 3.7
2.3 2.3 5.4 330 9.8 6.7 0.69 0.50 11.6 19.6 330 10.9 0.75 8.3 100.5 4.3
1.1 0.4 0.9 250 8.5 5.8 0.68 0.61 10.6 14.0 250 10.8 0.84 8.0 110.1 3.8
1.1 0.4 0.9 330 8.8 6.5 0.74 0.63 11.0 14.0 330 11.1 0.75 8.5 101.1 4.3
1.7 1.0 2.3 250 8.8 5.8 0.66 0.56 10.7 15.6 250 11.3 0.85 8.4 111.9 3.9
70
1.7 1.0 2.3 330 9.2 6.6 0.72 0.59 11.2 15.6 330 11.6 0.77 9.0 102.5 4.4
2.3 2.1 4.9 250 9.1 5.9 0.65 0.53 10.9 17.1 250 11.4 0.85 8.5 112.1 3.9
2.3 2.1 4.9 330 9.5 6.7 0.71 0.55 11.3 17.1 330 11.6 0.77 9.0 102.7 4.4
1.1 0.3 0.8 250 8.0 5.6 0.70 0.67 10.3 11.8 250 11.7 0.87 8.7 113.3 4.0
1.1 0.3 0.8 330 8.3 6.3 0.77 0.70 10.7 11.8 330 12.0 0.78 9.3 103.6 4.5
1.7 0.9 2.1 250 8.3 5.7 0.69 0.63 10.5 13.2 250 12.2 0.88 9.1 115.1 4.0
80
1.7 0.9 2.1 330 8.6 6.5 0.75 0.66 10.9 13.2 330 12.5 0.79 9.8 105.0 4.6
2.3 2.0 4.6 250 8.6 5.8 0.67 0.59 10.6 14.4 250 12.2 0.88 9.2 115.4 4.1
2.3 2.0 4.6 330 8.9 6.5 0.73 0.62 11.1 14.4 330 12.5 0.79 9.8 105.2 4.6
1.1 0.3 0.7 250 7.7 5.5 0.71 0.7 10.1 11.0 250 12.0 0.88 9.0 114.5 4.0
1.1 0.3 0.7 330 8.0 6.2 0.78 0.73 10.5 11.0 330 12.3 0.8 9.6 104.6 4.6
1.7 0.9 2.0 250 8.0 5.6 0.70 0.67 10.3 12.1 250 12.6 0.9 9.5 116.5 4.1
85
1.7 0.9 2.0 330 8.4 6.4 0.76 0.69 10.7 12.1 330 12.9 0.8 10.1 106.1 4.7
2.3 1.9 4.4 250 8.3 5.7 0.69 0.63 10.5 13.3 250 12.6 0.9 9.5 116.8 4.1
2.3 1.9 4.4 330 8.7 6.5 0.75 0.65 10.9 13.3 330 12.9 0.8 10.2 106.3 4.7
1.1 0.3 0.6 250 7.5 5.4 0.72 0.73 10.0 10.2 250 12.3 0.89 9.3 115.7 4.1
1.1 0.3 0.6 330 7.8 6.2 0.79 0.76 10.4 10.2 330 12.6 0.80 9.9 105.5 4.6
1.7 0.8 1.9 250 7.7 5.5 0.71 0.70 10.1 11.1 250 12.9 0.91 9.8 117.9 4.2
90
1.7 0.8 1.9 330 8.1 6.3 0.78 0.73 10.6 11.1 330 13.3 0.82 10.5 107.2 4.8
2.3 1.8 4.3 250 8.0 5.6 0.70 0.66 10.3 12.1 250 13.0 0.91 9.9 118.2 4.2
2.3 1.8 4.3 330 8.4 6.4 0.76 0.69 10.7 12.1 330 13.3 0.82 10.5 107.4 4.8
1.1 0.2 0.6 250 6.8 5.1 0.76 0.82 9.6 8.2 395
1.1 0.2 0.6 330 7.0 5.8 0.82 0.86 10.0 8.2 525
1.7 0.8 1.7 250 7.1 5.3 0.74 0.78 9.8 9.2 395
100
1.7 0.8 1.7 330 7.4 6.0 0.81 0.81 10.2 9.2 525
2.3 1.7 4.0 250 7.3 5.4 0.73 0.75 9.9 9.7 395
2.3 1.7 4.0 330 7.6 6.1 0.80 0.78 10.3 9.7 525
1.1 0.2 0.5 250 6.1 4.8 0.79 0.90 9.2 6.8 395
1.1 0.2 0.5 330 6.3 5.4 0.85 0.94 9.5 6.8 525
1.7 0.7 1.6 250 6.5 5.0 0.77 0.86 9.4 7.6 395
110
1.7 0.7 1.6 330 6.8 5.6 0.84 0.89 9.8 7.6 525
2.3 1.6 3.8 250 6.7 5.1 0.76 0.83 9.5 8.0 395
2.3 1.6 3.8 330 7.0 5.8 0.83 0.87 9.9 8.0 525
1.1 0.2 0.4 250 5.4 4.4 0.82 0.98 8.7 5.5 395
1.1 0.2 0.4 330 5.6 5.0 0.89 1.02 9.1 5.5 525
1.7 0.7 1.6 250 5.8 4.6 0.80 0.94 9.0 6.2 395
120
1.7 0.7 1.6 330 6.0 5.2 0.87 0.98 9.4 6.2 525
2.3 1.6 3.6 250 6.0 4.7 0.79 0.91 9.1 6.5 395
2.3 1.6 3.6 330 6.2 5.4 0.86 0.95 9.5 6.5 525
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not reect fan or pump power corrections for ARI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.
Operation below 40°F EWT is based upon a 15% antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above. See Performance Data Selection Notes for operation in the shaded areas.
WPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT
Airow
CFM
TC SC
Sens/Tot
Ratio
kW HR EER
Airow
CFM
HC kW HE LAT COP
Operation not recommended
9
Heat Controller, Inc. HBH/V SERIES Engineering Design Guide
Performance Data HBH/V 012
Performance capacities shown in thousands of Btuh400 CFM Nominal (Rated) Airow
EWT
GPM
°F
3.0 8.5 19.6 300 300 8.5 0.98 5.3 96.2 2.5
20 Operation not recommended
3.0 8.5 19.6 400 400 8.7 0.88 5.7 90.2 2.9
1.5 1.9 4.3 300 14.2 8.2 0.58 0.55 16.1 25.8 300 9.3 1.00 6.0 98.6 2.7
1.5 1.9 4.3 400 14.8 9.3 0.63 0.57 16.8 25.8 400 9.5 0.90 6.4 91.9 3.1
2.3 3.6 8.4 300 14.3 8.2 0.58 0.51 16.1 27.9 300 9.6 1.01 6.3 99.7 2.8
30
2.3 3.6 8.4 400 14.9 9.3 0.63 0.53 16.7 27.9 400 9.9 0.91 6.8 92.8 3.2
3.0 6.7 15.5 300 14.3 8.2 0.58 0.50 16.0 28.8 300 9.8 1.02 6.5 100.4 2.8
3.0 6.7 15.5 400 14.9 9.3 0.63 0.52 16.6 28.8 400 10.1 0.92 7.0 93.3 3.2
1.5 1.4 3.2 300 14.0 8.1 0.58 0.61 16.0 22.9 300 10.6 1.04 7.1 102.6 3.0
1.5 1.4 3.2 400 14.5 9.2 0.63 0.63 16.7 22.9 400 10.8 0.93 7.6 95.0 3.4
2.3 3.0 6.9 300 14.2 8.2 0.58 0.57 16.1 25.1 300 11.0 1.05 7.6 104.1 3.1
40
2.3 3.0 6.9 400 14.8 9.3 0.63 0.59 16.8 25.1 400 11.3 0.94 8.1 96.2 3.5
3.0 5.7 13.1 300 14.3 8.2 0.58 0.54 16.1 26.2 300 11.3 1.06 7.8 104.9 3.1
3.0 5.7 13.1 400 14.8 9.3 0.63 0.57 16.8 26.2 400 11.6 0.95 8.3 96.8 3.6
1.5 1.1 2.5 300 13.5 7.9 0.58 0.67 15.8 20.1 300 11.9 1.08 8.3 106.8 3.2
1.5 1.1 2.5 400 14.1 8.9 0.63 0.70 16.5 20.1 400 12.2 0.97 8.9 98.2 3.7
2.3 2.6 6.0 300 13.9 8.0 0.58 0.62 16.0 22.2 300 12.5 1.09 8.9 108.6 3.4
50
2.3 2.6 6.0 400 14.4 9.1 0.63 0.65 16.7 22.2 400 12.8 0.98 9.5 99.6 3.8
3.0 5.0 11.5 300 14.0 8.1 0.58 0.60 16.1 23.3 300 12.8 1.10 9.1 109.6 3.4
3.0 5.0 11.5 400 14.6 9.2 0.63 0.63 16.7 23.3 400 13.1 0.99 9.8 100.4 3.9
1.5 0.9 2.1 300 12.9 7.6 0.59 0.74 15.5 17.4 300 13.3 1.11 9.6 111.1 3.5
1.5 0.9 2.1 400 13.5 8.6 0.64 0.77 16.1 17.4 400 13.6 1.00 10.2 101.5 4.0
2.3 2.3 5.3 300 13.4 7.8 0.58 0.69 15.7 19.3 300 14.0 1.13 10.2 113.1 3.6
60
2.3 2.3 5.3 400 13.9 8.8 0.63 0.72 16.4 19.3 400 14.3 1.02 10.8 103.1 4.1
3.0 4.5 10.3 300 13.6 7.9 0.58 0.67 15.8 20.4 300 14.3 1.14 10.5 114.2 3.7
3.0 4.5 10.3 400 14.1 8.9 0.63 0.69 16.5 20.4 400 14.7 1.03 11.2 104.0 4.2
1.5 0.8 1.8 300 12.2 7.3 0.60 0.82 15.0 14.9 300 14.7 1.15 10.8 115.3 3.7
1.5 0.8 1.8 400 12.7 8.3 0.65 0.85 15.6 14.9 400 15.0 1.04 11.5 104.8 4.2
2.3 2.1 4.8 300 12.5 7.4 0.59 0.77 15.2 16.3 300 15.4 1.18 11.4 117.6 3.8
70
2.3 2.1 4.8 400 13.1 8.4 0.64 0.80 15.8 16.3 400 15.8 1.06 12.2 106.5 4.4
3.0 4.1 9.5 300 12.7 7.5 0.59 0.75 15.3 17.0 300 15.8 1.19 11.7 118.8 3.9
3.0 4.1 9.5 400 13.3 8.5 0.64 0.78 15.9 17.0 400 16.2 1.07 12.5 107.5 4.4
1.5 0.7 1.5 300 11.4 7.0 0.61 0.90 14.5 12.7 300 16.0 1.20 11.9 119.4 3.9
1.5 0.7 1.5 400 11.9 7.9 0.67 0.94 15.1 12.7 400 16.4 1.08 12.7 108.0 4.5
2.3 1.9 4.4 300 11.8 7.1 0.60 0.85 14.7 13.9 300 16.8 1.22 12.6 121.7 4.0
80
2.3 1.9 4.4 400 12.3 8.0 0.65 0.88 15.3 13.9 400 17.2 1.10 13.4 109.8 4.6
3.0 3.8 8.8 300 12.0 7.2 0.60 0.83 14.8 14.5 300 17.2 1.24 12.9 123.0 4.1
3.0 3.8 8.8 400 12.5 8.1 0.65 0.86 15.4 14.5 400 17.6 1.11 13.8 110.7 4.6
1.5 0.6 1.5 300 10.9 6.8 0.62 0.9 14.2 11.7 300 16.6 1.22 12.5 121.3 4.0
1.5 0.6 1.5 400 11.4 7.7 0.68 0.98 14.7 11.7 400 17.0 1.1 13.3 109.4 4.6
2.3 1.8 4.2 300 11.4 6.9 0.61 0.89 14.4 12.8 300 17.4 1.3 13.1 123.6 4.1
85
2.3 1.8 4.2 400 11.9 7.9 0.66 0.93 15.0 12.8 400 17.8 1.1 14.0 111.2 4.6
3.0 3.7 8.5 300 11.6 7.0 0.60 0.87 14.5 13.4 300 17.7 1.3 13.4 124.8 4.1
3.0 3.7 8.5 400 12.1 7.9 0.66 0.90 15.1 13.4 400 18.2 1.1 14.3 112.1 4.7
1.5 0.6 1.4 300 10.5 6.7 0.63 0.99 13.9 10.7 300 17.3 1.24 13.0 123.3 4.1
1.5 0.6 1.4 400 10.9 7.5 0.69 1.03 14.4 10.7 400 17.7 1.12 13.9 110.9 4.6
2.3 1.8 4.1 300 11.0 6.8 0.62 0.93 14.1 11.7 300 18.0 1.28 13.6 125.5 4.1
90
2.3 1.8 4.1 400 11.4 7.7 0.67 0.97 14.7 11.7 400 18.4 1.15 14.5 112.6 4.7
3.0 3.6 8.2 300 11.2 6.8 0.61 0.91 14.3 12.3 300 18.3 1.29 13.9 126.6 4.2
3.0 3.6 8.2 400 11.6 7.7 0.67 0.95 14.8 12.3 400 18.8 1.16 14.8 113.5 4.7
1.5 0.5 1.2 300 9.5 6.4 0.67 1.07 13.2 8.9 300
1.5 0.5 1.2 400 9.9 7.2 0.72 1.12 13.8 8.9 400
2.3 1.7 3.8 300 10.1 6.5 0.65 1.02 13.5 9.8 300
100
2.3 1.7 3.8 400 10.5 7.3 0.70 1.06 14.1 9.8 400
3.0 3.3 7.7 300 10.4 6.6 0.64 1.00 13.8 10.4 300
3.0 3.3 7.7 400 10.8 7.5 0.69 1.04 14.3 10.4 400
1.5 0.5 1.1 300 8.5 6.0 0.71 1.17 12.5 7.3 300
1.5 0.5 1.1 400 8.9 6.8 0.77 1.22 13.1 7.3 400
2.3 1.6 3.6 300 9.1 6.2 0.68 1.12 12.9 8.1 300
110
2.3 1.6 3.6 400 9.4 7.0 0.74 1.16 13.4 8.1 400
3.0 3.2 7.3 300 9.4 6.3 0.67 1.09 13.1 8.6 300
3.0 3.2 7.3 400 9.8 7.1 0.73 1.14 13.7 8.6 400
1.5 0.4 1.0 300 7.5 5.7 0.76 1.27 11.8 5.9 300
1.5 0.4 1.0 400 7.8 6.4 0.82 1.32 12.3 5.9 400
2.3 1.5 3.4 300 8.0 5.8 0.73 1.22 12.2 6.6 300
120
2.3 1.5 3.4 400 8.3 6.6 0.79 1.27 12.7 6.6 400
3.0 3.0 7.0 300 8.3 5.9 0.71 1.19 12.4 7.0 300
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not reect fan or pump power corrections for ARI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.
Operation below 40°F EWT is based upon a 15% antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above. See Performance Data Selection Notes for operation in the shaded areas.
3.0 3.0 7.0 400 8.7 6.7 0.77 1.24 12.9 7.0 400
WPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT
Airow
CFM
TC SC
Sens/Tot
Ratio
kW HR EER
Airow
CFM
HC kW HE LAT COP
Operation not recommended
10
Loading...
+ 24 hidden pages