Entering Water Temperature Range: 20 - 120°F (-6.7 - 48.9°C)
Horizontal Water Source Heat Pump
Sizes 015-060
006-060
Vertical Water Source Heat Pump
Sizes 015-060
006-060
HBH & HBV Model Structure
Basic Unit Description:
The basic unit price includes sealed heat pump refrigerant circuit and
air handler within cabinetry, lter, and a factory installed hanger kit on
horizontal units.
• Cabinetry - Compact design - galvanized steel construction -
- com pres sor access panels - FPT water con nec tions - high and low
high and low voltage knockouts - 1” (25mm), air lter and lter rack. All
voltage knock outs - 1” (25mm), air lter and lter rack. All vertical
vertical units have a left or right return air option, sizes 006-030 have a
units have a left or right return air option, sizes 015 - 030 have a front
front return option. All horizontal units have eld convertible discharge air
return option. All hor i zon tal units have eld convertible dis charge air
patterns with extra parts required.
patterns with no extra parts required.
• Standard Controls - CXM Controller, loss of charge switch, high
pressure switch, water coil low temperature cutout, lockout safety
circuit resetable at ther mo stat or dis con nect, LED fault indication,
ve minute anti-short cycle protection, random start, high and low
voltage pro tec tion, con den sate over ow pro tec tion, dry contact for
alarm.
• Compressor - High ef ciency hermetic scroll or rotary, overload
pro tect ed - internally sprung & externally isolated using dual vibration
dampening system for extra quiet operation. Mounting system
incorporates rubber grommet isolation under the compressor and
rubber grommet isolation between the compressor mounting tray and
unit base.
006
• Reversing Valve - 4-way, pilot operated, solenoid activated in the
copper tubing interconnecting all components - sealed & tested
non-ozone depleting, HFC-410A refrigerant circuit with high & low
side schraeder ports.
• Water to Refrigerant Coil - Tube-in-tube, convoluted copper inner
water tube.
• Refrigerant to Air Coil - Lanced aluminum ns on ri ed copper
tubes.
• Blower Motor - Three-speed PSC direct drive, permanently
lu bri cat ed (Two-speed on 575 volt applications).
• UltraQuiet Option - Compressor incorporates spring mounting
system, 015-060 include compressor discharge muf er, blower
housing is covered with high density noise suppression material.
• Application - Units can be applied in WLHP, GWHP, or GLHP
R-410A refrigerant circuit with high & low
applications.
IOM Instructions HBH/V COMPACT Heat Controller, Inc.
General Information
Safety
Warnings, cautions and notices appear throughout this manual.
Read these items carefully before attempting any installation,
service or troubleshooting of the equipment.
DANGER: Indicates an immediate hazardous situation, which
if not avoided will result in death or serious injury. DANGER
labels on unit access panels must be observed.
WARNING: Indicates a potentially hazardous situation, which if
not avoided could result in death or serious injury.
WARNING! All refrigerant discharged from this unit must be
recovered WITHOUT EXCEPTION. Technicians must follow
industry accepted guidelines and all local, state, and federal
statutes for the recovery and disposal of refrigerants. If a
compressor is removed from this unit, refrigerant circuit oil will
remain in the compressor. To avoid leakage of compressor oil,
refrigerant lines of the compressor must be sealed after it is
removed.
WARNING!
CAUTION: Indicates a potentially hazardous situation or an
unsafe practice, which if not avoided could result in minor or
moderate injury or product or property damage.
NOTICE: Notication of installation, operation or maintenance
information, which is important, but which is not hazard-related.
WARNING!
WARNING! The Refrigerant Application and Service Manual
should be read and understood before attempting to service
refrigerant circuits with HFC-410A.
R-410A.
WARNING!
WARNING! To avoid the release of refrigerant into the
atmosphere, the refrigerant circuit of this unit must be
serviced only by technicians who meet local, state, and
federal prociency requirements.
CAUTION!
CAUTION!
these units as a source of heating or cooling during the
construction process. The mechanical components and
lters will quickly become clogged with construction dirt and
debris, which may cause system damage.
To avoid equipment damage, DO NOT use
Inspection
Upon receipt of the equipment, carefully check the shipment
against the bill of lading. Make sure all units have been received.
Inspect the packaging of each unit, and inspect each unit for
damage. Insure that the carrier makes proper notation of any
shortages or damage on all copies of the freight bill and completes
a common carrier inspection report. Concealed damage not
discovered during unloading must be reported to the carrier within
15 days of receipt of shipment. If not led within 15 days, the
freight company can deny the claim without recourse. Note: It is
the responsibility of the purchaser to le all necessary claims with
the carrier. Notify your equipment supplier of all damage within
fteen (15) days of shipment.
Storage
Equipment should be stored in its original packaging in a clean,
dry area. Store units in an upright position at all times. Stack
units a maximum of 3 units high.
Unit Protection
Cover units on the job site with either the original packaging or an
equivalent protective covering. Cap the open ends of pipes stored
on the job site. In areas where painting, plastering, and/or spraying
has not been completed, all due precautions must be taken to
avoid physical damage to the units and contamination by foreign
material. Physical damage and contamination may prevent proper
start-up and may result in costly equipment clean-up.
Examine all pipes, ttings, and valves before installing any of
the system components. Remove any dirt or debris found in or
on these components.
Pre-Installation
Installation, Operation, and Maintenance instructions are
provided with each unit. Horizontal equipment is designed for
installation above false ceiling or in a ceiling plenum. Other
unit congurations are typically installed in a mechanical room.
The installation site chosen should include adequate service
clearance around the unit. Before unit start-up, read all manuals
and become familiar with the unit and its operation. Thoroughly
check the system before operation.
Heat Controller, Inc. HBH/V COMPACT IOM Instructions
General Information
Prepare units for installation as follows:
1. Compare the electrical data on the unit nameplate with
ordering and shipping information to verify that the correct
unit has been shipped.
2. Keep the cabinet covered with the original packaging until
installation is complete and all plastering, painting, etc. is
nished.
3. Verify refrigerant tubing is free of kinks or dents and that it
does not touch other unit components.
4. Inspect all electrical connections. Connections must be
clean and tight at the terminals.
5. Remove any blower support packaging (water-to-air units
only).
6. Loosen compressor bolts on units equipped with
compressor spring vibration isolation until the compressor
rides freely on the springs. Remove shipping restraints.
7. Some airow patterns are eld convertible (horizontal units
only). Locate the airow conversion section of this IOM.
8. Locate and verify any hot water generator (HWG), hanger,
or other accessory kit located in the compressor section or
blower section.
CAUTION!
CAUTION!
direction of rotation veried at start-up. Verication is achieved by
checking compressor Amp draw. Amp draw will be substantially
lower compared to nameplate values. Additionally, reverse rotation
results in an elevated sound level compared to correct rotation.
Reverse rotation will result in compressor internal overload trip
within several minutes. Verify compressor type before proceeding.
All three phase scroll compressors must have
CAUTION!
CAUTION! DO NOT store or install units in corrosive
environments or in locations subject to temperature or
humidity extremes (e.g., attics, garages, rooftops, etc.).
Corrosive conditions and high temperature or humidity can
signicantly reduce performance, reliability, and service life.
Always move and store units in an upright position. Tilting
units on their sides may cause equipment damage.
CAUTION!
CAUTION! CUT HAZARD - Failure to follow this caution
may result in personal injury. Sheet metal parts may have
sharp edges or burrs. Use care and wear appropriate
protective clothing, safety glasses and gloves when
handling parts and servicing heat pumps.
NOTICE! Failure to remove shipping brackets from springmounted compressors will cause excessive noise, and
could cause component failure due to added vibration.
IOM Instructions HBH/V COMPACT Heat Controller, Inc.
Unit Physical Data
HBH/V Series
HB Series
Compressor (1 Each)RotaryScroll
Factory Charge R410A (oz)1718.5233243434750707482
PSC Fan Motor & Blower
Fan Motor Type/SpeedsPSC/3PSC/3PSC-3PSC/3PSC/3PSC/3PSC/3PSC/3PSC/3PSC/3PSC/3
Fan Motor (hp)1/251/101/10 1/6 1/6 1/4 3/4 1/2 3/4 3/4 1
Blower Wheel Size (Dia x w) 5x55x56x58x78x79x79x79x89x810x1011x10
Water Connection Size
IPT1/2”1/2”1/2”1/2"1/2"3/4"3/4"3/4"3/4"1"1"
Vertical
Air Coil Dimensions (H x W)10x1510x1510x1520x17.2520x17.2520x17.2520x17.2524x21.7524x21.7624x28.2524x28.25
Filter Standard - 1" Throwaway10x1810x1810x1820x2020x2020x2020x2024x2424x241-14x24, 1-18x24 1-14x24, 1-18x24
Models 006-012 have spring compressor mounts, all others have grommets,TXV expansion device, and 1/2” & 3/4” electrical knockouts.
006009012015018024030036042048060
285
18x2520x28 or 2-20x1420x28 or 2-20x14
1-20x24, 1-20x14
1-20x24, 1-20x14
Unit Maximum Water Working Pressure
Options
Base Unit
Discharge Pressure
Water Regulating Valve
Use the lowest maximum pressure rating when multiple options are combined.
Max Pressure PSIG [kPa]
500 [3,445]
140 [965]
Heat Controller, Inc. HBH/V COMPACT IOM Instructions
Horizontal Installation
Horizontal Unit Location
Units are not designed for outdoor installation. Locate
the unit in an INDOOR area that allows enough space
for service personnel to perform typical maintenance or
repairs without removing unit from the ceiling. Horizontal
units are typically installed above a false ceiling or in a
ceiling plenum. Never install units in areas subject to
freezing or where humidity levels could cause cabinet
condensation (such as unconditioned spaces subject
to 100% outside air). Consideration should be given to
access for easy removal of the lter and access panels.
Provide sufcient room to make water, electrical, and
duct connection(s).
If the unit is located in a conned space, such as a closet,
provisions must be made for return air to freely enter the
space by means of a louvered door, etc. Any access panel
screws that would be difcult to remove after the unit is
installed should be removed prior to setting the unit. Refer
to Figure 3 for an illustration of a typical installation. Refer
to unit engineering design guide for dimensional data.
Mounting Horizontal Units
Horizontal units have hanger kits pre-installed from the factory
as shown in Figure 1. Figure 3 shows a typical horizontal unit
installation.
Horizontal heat pumps are typically suspended above a ceiling
or within a soft using eld supplied, threaded rods sized to
support the weight of the unit.
Use four (4) eld supplied threaded rods and factory provided
vibration isolators to suspend the unit. Hang the unit clear of the
oor slab above and support the unit by the mounting bracket
assemblies only. DO NOT attach the unit ush with the oor
slab above.
Pitch the unit toward the drain as shown in Figure 2 to improve
the condensate drainage. On small units (less than 2.5
tons/8.8kW) ensure that unit pitch does not cause condensate
leaks inside the cabinet.
In limited side access installations, pre-removal of the
control box side mounting screws will allow control box
removal for future servicing (HB units only).
Conform to the following guidelines when selecting
unit location:
1. Provide a hinged access door in concealed-spline
or plaster ceilings. Provide removable ceiling
tiles in T-bar or lay-in ceilings. Refer to horizontal
unit dimensions for specic series and model in
unit submittal data. Size the access opening to
accommodate the service technician during the
removal or replacement of the compressor and the
removal or installation of the unit itself.
2.
Provide access to hanger brackets, water valves
and ttings. Provide screwdriver clearance to access
panels, discharge collars and all electrical connections.
3. DO NOT obstruct the space beneath the unit with
piping, electrical cables and other items that prohibit
future removal of components or the unit itself.
4. Use a manual portable jack/lift to lift and support the
weight of the unit during installation and servicing.
The installation of water source heat pump units and all
associated components, parts and accessories which
make up the installation shall be in accordance with
the regulations of ALL authorities having jurisdiction
and MUST conform to all applicable codes. It is the
responsibility of the installing contractor to determine and
comply with ALL applicable codes and regulations.
Figure 1: Hanger Bracket
3/8" [10mm] Threaded
Rod (by others)
Vibration Isolator
(factory supplied)
Washer
(by others)
Double Hex Nuts
(by others)
Figure 2: Horizontal Unit Pitch
1/4" [6.4mm] pitch
for drainage
Drain
Connection
IOM Instructions HBH/V COMPACT Heat Controller, Inc.
HORIZONTAL INSTALLATION
Figure 3: Typical Horizontal Unit Installation
Horizontal Installation
Figure 3: Typical Horizontal Unit Installation
3/8" [10mm] threaded rods
(by others)
Return Air
Power Wiring
Supply Air
Unit Power
Insulated supply duct with
at least one 90 deg elbow
to reduce air noise
Flexible Duct
Connector
Unit Power
Disconnect
(by others)
Unit Hanger
Air Coil
To obtain maximum performance, the air coil should be cleaned
before start-up. A 10% solution of dishwasher detergent and
water is recommended for both sides of the coil. A thorough
water rinse should follow. UV based anti-bacterial systems
may damage e-coated air coils.
Thermostat
Wiring
Stainless steel braided hoses with
Stainless steel braid hose
threaded connections
with integral "J" swivel
and one swivel end
Optional Balancing Valve
Optional Low Pressure Drop Water
Ball Valve with optional
integral P/T plug
Control Valve
(can be internally mounted
on some models)
Water Out
Water In
Building
Loop
NOTICE! Installation Note - Ducted Return: Many horizontal
WSHPs are installed in a return air ceiling plenum application
(above ceiling). Vertical WSHPs are commonly installed in a
mechanical room with free return (e.g. louvered door). Therefore,
lter rails are the industry standard and are included on Heat
Controller, Inc., commercial heat pumps for the purposes of
holding the lter only. For ducted return applications, the lter rail
must be removed and replaced with a duct ange or lter rack.
Canvas or exible connectors should also be used to minimize
vibration between the unit and ductwork.
Heat Controller, Inc. HBH/V COMPACT IOM Instructions
Water
Connection End
Return Air
Remove Screws
Water
Connection End
Return Air
Rotate
Move to Side
Side Discharge
Return Air
Water
Connection End
Discharge Air
Drain
Back Discharge
Replace Screws
Field Conversion of Air Discharge
Overview
Horizontal units can be eld converted between side (straight)
and back (end) discharge using the instructions below.
Note: It is not possible to eld convert return air between
left or right return models due to the necessity of
refrigeration copper piping changes.
Preparation
It is best to eld convert the unit on the ground before hanging.
If the unit is already hung it should be taken down for the eld
conversion.
Side to Back Discharge Conversion
1.
Place unit in well lit area. Remove the screws as shown in
Figure 4 to free top panel and discharge panel.
2. Lift out the access panel and set aside. Lift and rotate
the discharge panel to the other position as shown, being
careful with the blower wiring.
3.
Check blower wire routing and connections for tension or
contact with sheet metal edges. Reroute if necessary.
4. Check refrigerant tubing for contact with
other components.
5. Reinstall top panel and screws noting that the location for
some screws will have changed.
6. Manually spin the fan wheel to insure that the wheel is not
rubbing or obstructed.
7. Replace access panels.
Figure 4: Left Return Side to Back
Back to Side Discharge Conversion
If the discharge is changed from back to side, use above
instruction noting that illustrations will be reversed.
Left vs. Right Return
It is not possible to eld convert return air between left or right
return models due to the necessity of refrigeration copper
piping changes. However, the conversion process of side to
back or back to side discharge for either right or left return
conguration is the same. In some cases, it may be possible
to rotate the entire unit 180 degrees if the return air connection
needs to be on the opposite side. Note that rotating the unit will
move the piping to the other end of the unit.
Figure 5: Right Return Side to Back
Water
Connection End
Water
Connection End
Return Air
Drain
Discharge Air
Return Air
Supply Duct
Side Discharge
Back Discharge
IOM Instructions HBH/V COMPACT Heat Controller, Inc.
*3/4" IPT
Trap Depth
1.5" [38mm]
Min 1.5"
[38mm]
1/4" per foot
(21mm per m)
drain slope
3/4" PVC or
Copper by others
Rev.: 6/26/09S
Vent
* Some units include a painted drain
connection. Using a threaded pipe or
similar device to clear any excess paint
accumulated inside this fitting may
ease final drain line installation.
Horizontal Installation
Condensate Piping – Horizontal Units
Pitch the unit toward the drain as shown in Figure 2 to
improve the condensate drainage. On small units (less
than 2.5 tons/8.8 kW), insure that unit pitch does not
cause condensate leaks inside the cabinet.
Install condensate trap at each unit with the top of the trap
positioned below the unit condensate drain connection as
shown in Figure 6.
Each unit must be installed with its own individual trap
and connection to the condensate line (main) or riser.
Provide a means to ush or blow out the condensate line.
DO NOT install units with a common trap and/or vent.
Always vent the condensate line when dirt or air can
collect in the line or a long horizontal drain line is
required. Also vent when large units are working against
higher external static pressure than other units connected
to the same condensate main since this may cause
poor drainage for all units on the line. WHEN A VENT
IS INSTALLED IN THE DRAIN LINE, IT MUST BE
LOCATED AFTER THE TRAP IN THE DIRECTION OF
THE CONDENSATE FLOW.
Figure 6: Horizontal Condensate Connection
CAUTION!
CAUTION! Ensure condensate line is pitched toward drain
1/4” per foot [21mm per m] of run.
Duct System Installation
Proper duct sizing and design is critical to the
performance of the unit. The duct system should be
designed to allow adequate and even airow through
the unit during operation. Air ow through the unit MUST
be at or above the minimum stated airow for the unit
to avoid equipment damage. Duct systems should
be designed for quiet operation. Refer to Figure 3 for
horizontal duct system details or gure 8 for vertical duct
system details. A exible connector is recommended
for both discharge and return air duct connections on
metal duct systems to eliminate the transfer of vibration
to the duct system. To maximize sound attenuation of
the unit blower, the supply and return plenums should
include internal berglass duct liner or be constructed
from ductboard for the rst few feet. Application of the
unit to uninsulated ductwork in an unconditioned space
DUCT SYSTEM INSTALLATION
is not recommended, as the unit’s performance will be
adversely affected.
At least one 90° elbow should be included in the supply
duct to reduce air noise. If air noise or excessive air ow
is a problem, the blower speed can be changed. For
airow charts, consult submittal data for the series and
model of the specic unit.
If the unit is connected to existing ductwork, a previous
check should have been made to insure that the
ductwork has the capacity to handle the airow required
for the unit. If ducting is too small, as in the replacement
of a heating only system, larger ductwork should be
installed. All existing ductwork should be checked for
leaks and repaired as necessary.
Heat Controller, Inc. HBH/V COMPACT IOM Instructions
noise
Flexible canvas ductconnector to reducenoise and vibration
Use turning vanes insupply transition
Internally insulate supplyduct for first 4’ [1.2m] each way to reduce noise
Internally insulate returntransition duct to reducenoise
Rounded returntransition
Rev.: 6/2/09S
Vertical Installation
Vertical Unit Location
Units are not designed for outdoor installation. Locate
the unit in an INDOOR area that allows enough space
for service personnel to perform typical maintenance
or repairs without removing unit from the mechanical
room/closet. Vertical units are typically installed in a
mechanical room or closet. Never install units in areas
subject to freezing or where humidity levels could cause
cabinet condensation (such as unconditioned spaces
subject to 100% outside air). Consideration should be
given to access for easy removal of the lter and access
panels. Provide sufcient room to make water, electrical,
and duct connection(s).
If the unit is located in a conned space, such as a closet,
provisions must be made for return air to freely enter
the space by means of a louvered door, etc. Any access
panel screws that would be difcult to remove after the
unit is installed should be removed prior to setting the
unit. Refer to Figures 7 and 8 for typical installation
illustrations. Refer to unit submittal data or engineering
design guide for dimensional data.
1. Install the unit on a piece of rubber, neoprene or
other mounting pad material for sound isolation. The
pad should be at least 3/8” [10mm] to 1/2” [13mm] in
thickness. Extend the pad beyond all four edges of
the unit.
2. Provide adequate clearance for lter replacement
and drain pan cleaning. Do not block lter access
with piping, conduit or other materials. Refer to
unit submittal data or engineering design guide for
dimensional data.
3. Provide access for fan and fan motor maintenance
and for servicing the compressor and coils without
removing the unit.
4. Provide an unobstructed path to the unit within the
closet or mechanical room. Space should be sufcient
to allow removal of the unit, if necessary.
5.
In limited side access installations, pre-removal of the
control box side mounting screws will allow control box
removal for future servicing (TC units only).
6. Provide access to water valves and ttings and
screwdriver access to the unit side panels, discharge
collar and all electrical connections.
HB
Figure 7: Vertical Unit Mounting
Air Pad or Extruded
polystyrene insulation board
Figure 8: Typical Vertical Unit Installation Using
Ducted Return Air
Internally insulate supply
duct for first 4’ [1.2 m] each way
to reduce noise
Use turning vanes in
supply transition
Flexible canvas duct
connector to reduce
noise and vibration
Rounded return
transition
Internally insulate return
transition duct to reduce
Rev.: 6/2/09S
IOM Instructions HBH/V COMPACT Heat Controller, Inc.
Vertical Installation
Sound Attenuation for Vertical Units
Sound attenuation is achieved by enclosing the unit within a
small mechanical room or a closet. Additional measures for
sound control include the following:
1. Mount the unit so that the return air inlet is 90° to the
return air grille. Refer to Figure 9. Install a sound bafe as
illustrated to reduce line-of sight sound transmitted through
return air grilles.
2.
Mount the unit on a rubber or neoprene isolation pad to minimize vibration transmission to the building structure.
Figure 9: Vertical Sound Attenuation
Condensate Piping – Vertical Units
Vertical units utilize a condensate hose inside the cabinet as
a trapping loop; therefore an external trap is not necessary.
Figure 10a shows typical condensate connections. Figure 10b
illustrates the internal trap for a typical vertical heat pump.
Each unit must be installed with its own individual vent (where
necessary) and a means to ush or blow out the condensate
drain line. Do not install units with a common trap and/or vent.
Figure 10a: Vertical Condensate Drain
*3/4" IPT
Vent
3/4" PVC
(21mm per m)
Water
Connections
Alternate
Condensate
Location
NOTICE! Units with clear plastic drain lines should have
regular maintenance (as required) to avoid buildup of debris,
especially in new construction.
* Some units include a painted drain connection. Using a
threaded pipe or similar device to clear any excess paint
accumulated inside this fitting may ease final drain line installation.
Figure 10b: Vertical Internal Condensate Trap
Heat Controller, Inc. HBH/V COMPACT IOM Instructions
Swivel
EPT
Piping Installation
Installation of Supply and Return Piping
Follow these piping guidelines.
1. Install a drain valve at the base of each supply and
return riser to facilitate system ushing.
2. Install shut-off / balancing valves and unions at each
unit to permit unit removal for servicing.
3. Place strainers at the inlet of each system
circulating pump.
4. Select the proper hose length to allow slack between
connection points. Hoses may vary in length by +2%
to -4% under pressure.
5. Refer to Table 1. Do not exceed the minimum bend
radius for the hose selected. Exceeding the minimum
bend radius may cause the hose to collapse, which
reduces water ow rate. Install an angle adapter to
avoid sharp bends in the hose when the radius falls
below the required minimum.
Insulation is not required on loop water piping except
where the piping runs through unheated areas, outside
the building or when the loop water temperature is
below the minimum expected dew point of the pipe
ambient conditions. Insulation is required if loop water
temperature drops below the dew point (insulation is
required for ground loop applications in most climates).
A backup wrench is required when tightening water
connections on HB series to prevent water line damage.
CAUTION!
CAUTION! Corrosive system water requires corrosion resis-
tant ttings and hoses, and may require water treatment.
CAUTION!
CAUTION! Do not bend or kink supply lines or hoses.
CAUTION!
CAUTION! Piping must comply with all applicable codes.
Table 1: Metal Hose Minimum Bend Radii
Hose DiameterMinimum Bend Radii
1/2" [12.7mm]2-1/2" [6.4cm]
3/4" [19.1mm]4" [10.2cm]
1" [25.4mm]5-1/2" [14cm]
1-1/4" [31.8mm]6-3/4" [17.1cm]
Pipe joint compound is not necessary when Teon®
thread tape is pre-applied to hose assemblies or when
ared-end connections are used. If pipe joint compound
is preferred, use compound only in small amounts on
the external pipe threads of the tting adapters. Prevent
sealant from reaching the ared surfaces of the joint.
Note: When anti-freeze is used in the loop, insure that it
is compatible with the Teon tape or pipe joint compound
that is applied.
Maximum allowable torque for brass ttings is 30 ft-lbs
[41 N-m]. If a torque wrench is not available, tighten
nger-tight plus one quarter turn. Tighten steel ttings
as necessary.
Optional pressure-rated hose assemblies designed
specically for use with Heat Controller units are available.
Similar hoses can be obtained from alternate suppliers.
Supply and return hoses are tted with swivel-joint ttings
at one end to prevent kinking during installation.
Refer to Figure 11 for an illustration of a typical supply/
return hose kit. Adapters secure hose assemblies to the
unit and risers. Install hose assemblies properly and
check regularly to avoid system failure and reduced
service life.
NOTICE! Do not allow hoses to rest against structural
building components. Compressor vibration may be
transmitted through the hoses to the structure, causing
unnecessary noise complaints.
Figure 11: Supply/Return Hose Kit
Rib Crimped
Length
(2 ft [0.6m] Length Standard)
Brass
Fitting
Brass
Fitting
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.