Heat Controller BDE-123-A, BDE-103-A User Manual

Through-The-Wall
Air Conditioner
Service Manual
CAUTION
-Before servicing the unit, read the "safety precautions" in this manual.
-Only for authorized service personnel.
HEAT CONTROLLER, INC.
BDE-123-A
—2—
1. PREFACE
1.1 SAFETY PRECAUTIONS ...............................2
1.2 INSULATION RESISTANCE TEST.................2
1.3 FEATURES.....................................................4
1.4 CONTROL LOCATIONS.................................4
2.
DISASSEMBLY INSTRUCTIONS
2.1 MECHANICAL PARTS....................................6
2.1.1 FRONT GRILLE.....................................6
2.1.2 CABINET................................................6
2.1.3 CONTROL BOX.....................................6
2.2 AIR HANDLING PARTS..................................7
2.2.1
ORIFICE, HEATER ASSY AND TURBO FAN
.........7
2.2.2 FAN........................................................7
2.2.3 SHROUD................................................8
2.3 ELECTRICAL PARTS.....................................8
2.3.1 MOTOR..................................................8
2.3.2 COMPRESSOR.....................................8
2.3.3 CAPACITOR..........................................8
2.3.4 POWER CORD......................................9
2.3.5 THERMOSTAT ......................................9
2.3.6 ROTARY SWITCH.................................9
2.4 REFRIGERATION CYCLE............................10
2.4.1 CONDENSER......................................10
2.4.2 EVAPORATOR....................................10
2.4.3 CAPILLARY TUBE...............................10
3.
INSTALLATION
3.1 HOW TO INSTALL THE UNIT ......................13
3.2 INSTALLATION KITS CONTENTS...............14
3.3 SUGGESTED TOOL REQUIREMENTS.......15
3.3.1 PREPARATION OF SLEEVE ..............15
3.3.2 UNIT INSTALLATION..........................16
4.
TROUBLESHOOTING GUIDE
4.1 OUTSIDE DIMENSIONS...............................17
4.2 PIPING SYSTEM ..........................................17
4.3 TROUBLESHOOTING GUIDE......................18
5. SCHEMATIC DIAGRAM
5.1 CIRCUIT DIAGRAM......................................23
6. EXPLODED VIEW..................................24
7. REPLACEMENT PARTS LIST.......25
1. PREFACE
This
SERVICE MANUAL provides various service information, including the mechanical and electrical
parts etc. This room air conditioner was manufactured and assembled under a strict quality control system. The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.
1.1 SAFETY PRECAUTIONS
1. When servicing the unit, set the ROTARY SWITCH or POWER SWITCH to OFF(O) and unplug the power cord.
2. Observe the original lead dress. If a short circuit is found, replace all parts which have been overheated or damaged by the short circuit.
3. After servicing the unit, make an insulation resistance test to protect the customer from being exposed to shock hazards.
1.2
INSULATION RESISTANCE TEST
1. Unplug the power cord and connect a jumper between 2 pins (black and white).
2. The grounding conductor (green or green & yellow) is to be open.
3. Measure the resistance value with an ohm meter between the jumpered lead and each exposed metallic part on the equipment at all the positions (except OFF or O) of the ROTARY SWITCH.
4. The value should be over 1MΩ.
CONTENTS
—3—
1.3 SPECIFICATIONS
1.3.1 FOR BDE-103-A/BDE-123-A
REMARK
POWER SUPPLY
CAPACITY (Btu/h) INPUT (W) RUNNING CURRENT
(A) E.E.R. (Btu/W.h) CAPACITY (Btu/h) INPUT (W) RUNNING CURRENT
(A)
INDOOR (°C)
OUTDOOR (°C)
INDOOR (°C)
OUTDOOR (°C) REFRIGERANT (R-22) CHARGE(g) EVAPORATOR CONDENSER FAN, INDOOR FAN, OUTDOOR FAN SPEEDS (FAN/COOLING/HEATING) FAN MOTOR OPERATION CONTROL ROOM TEMP. CONTROL
CONSTRUCTION ELECTRIC HEATER
COMPRESSOR FAN MOTOR ELECTRIC HEATER
DRAIN SYSTEM NET WEIGHT (lbs/kg) DIMENSION (inch) (W x H x D) (mm) SLEEVE DIMESION (inch) (W x H x D) (mm) SLEEVE DEPTH (inch) WITH FRONT GRILLE (mm)
1Ø, 208/ 230V, 60Hz
9,800/10,000 11,400/11,700
1,040/1,060 1,210/1,250
5.2/4.7 6.2/5.8
9.4 9.4 9,200/11,200
2,900/3,500
14.0/15.3
26.7 (DB) 19.4 (WB) 35 (DB) 23.9 (WB)
21.1 (DB) 15.6 (WB)
8.3 (DB) 6.1 (WB)
440(15.5 OZ) 470(16.6 OZ)
2 ROW 12 STACKS 3 ROW 12 STACKS
2 ROW 17 STACKS, L-BENDED TYPE
TURBO FAN
PROPELLER TYPE FAN WITH SLINGER-RING
1/ 2/ 2
6 POLES
ROTARY SWITCH
THERMOSTAT
VERTICAL LOUVER (RIGHT & LEFT)
HORIZONTAL LOUVER (UP & DOWN)
TOP-DOWN
3.5KW, 230V
EXTERNAL OVERLOAD PROTECTOR
INTERANL THERMAL PROTECTOR
FUSE LINK, BIMETAL THERMOSTAT
1.6m (3 WIRE WITH GROUDING)
ATTACHMENT PLUG (CORD-CONNECTED TYPE)
SPLASHED BY FAN SLINGER
80/36 81/37
24
21
/32 x 1413/32 x 1921/32
626 x 366 x 499
257/8 x 15
17
/32 x 16
23
/32
656 x 394 x 425
20
510
MODELS
ITEMS
OPERATING TEMPERA­TURE
AIR DIRECTION CONTROL
POWER CORD
PROTECTOR
HEATING
COOLING
COOLING
HEATING
LOUVERED­FIN TYPE
BDE-103-A BDE-123-A
OPTIONAL PART
1.4 FEATURES
• Designed for cooling only.
• Powerful and quiet cooling.
• Top-down chassis for the simple installation and service.
1.5 CONTROL LOCATIONS
1.5.1 COOLING ONLY MODEL
• OPERATION
• VENTILATION
The ventilation lever is located in the right of the air discharge. The ventilation lever must be in the CLOSE position in order to maintain the best cooling conditions. When fresh air is necessary in the room, set the ventilation lever to the OPEN position. The damper is opened and room air is exhausted outside.
• ENERGY SAVER (optional)
On : Both the fan and the compressor turn on and turn off
together while operation knob is set to the Cool position. You can get the more economical operation.
Off : The fan runs constantly while operation knob is set to
the Cool position.
You can access the Energy Saver switch when you open the inlet grille.
• Side air-intake, side cooled-air discharge.
• Built in adjustable THERMOSTAT.
• Washable one-touch filter.
• Compact size.
—4—
PULL OPEN / PUSH CLOSE
Off On
Energy Saver
Med
Fan
Off
Low
Fan
High
Cool
Med Cool
Low Cool
Operation
6
7
8
9
5
1
2
3
4
Thermostat
C
o
o
l
e
r
Off - Turns air conditioner off. Med Fan - Med speed fan operation without cooling. Low Fan - Low speed fan operation without cooling. High Cool - Cooling with high speed fan operation. Med Cool - Cooling with med speed fan operation. Low Cool - Cooling with low speed fan operation.
This automatically controls the temperature of the indoor air. Turn the knob so that arrow points to the larger marks for greater cooling. Point the arrow to the smaller marks for more moderate cooling. (i.e. the higher number, the greater cooling)
1.5.2 COOLING AND HEATING MODEL
OPERATION
5
A slight heat odor may come from the unit when first switching to HEAT after the cooling season is over. This odor, caused by fine dust particles on the heater, will disappear quickly.
Turn the Temperature Knob to the desired setting. The central position is a normal setting for average conditions. You can change this setting, if necessary, in accordance with your temperature preference.
The thermostat automatically controls cooling or heating, but the fan runs continuously whenever the air conditioner is in operation. If the room is too warm, turn the thermostat control clockwise. If the room is too cool, turn the thermostat control counterclockwise.
OFF - Turns the air conditioner off. FAN ONLY - The low fan speed operation without cooling/heating. LOW COOL - Cooling with the low speed fan operation. HIGH COOL - Cooling with the high speed fan operation. LOW HEAT - Heating with the low speed fan operation. HIGH HEAT - Heating with the high speed fan operation.
When the air conditioner has been performed its cooling or heating operation and is turned off or set to the fan position, wait at least 3 minutes before resetting to the cooling operation again.
CAUTION
HEAT PUMP MODELS
When the outdoor temperature is lower than
-4°C (24°F), the electric heater will turn on instead of the heat pump.
6
2.1 MECHANICAL PARTS
2.1.1 FRONT GRILLE
1. Open the inlet grille upward or downward.
2. Remove the screw which fastens the front grille.
3. Pull the front grille from the right side.
4. Remove the front grille. (See Fig. 1)
5. Re-install the component by referring to the removal procedure.
2.1.2 CABINET
1. After disassembling the FRONT GRILLE, remove the 9 screws which fasten the cabinet at the both sides and the top. (See Fig. 2) Keep these for later use.
2.1.3 CONTROL BOX
1. Remove the front grille. (Refer to section 2.1.1)
2. Remove the screw which fasten the control box. (See Fig. 3)
3. Pull the control box from the barrier.(See Fig.3)
4. Discharge the capacitor by placing a 20,000 ohm resistor across the capacitor terminals.
5. Disconnect two wire housings in the control box.
6. Pull the control box forward completely.
7. Re-install the components by referring to the removal procedure. (See Fig. 3) (Refer to the circuit diagram found on pages 26~27 in this manual and on the control box.)
2. DISASSEMBLY INSTRUCTIONS
Before the following disassembly, POWER SWITCH is set to OFF and disconnected the power cord.
Figure 1
Figure 2
Figure 3
Figure 7
7
2.2 AIR HANDLING PARTS
2.2.1 ORIFICE, HEATER ASSY AND TURBO FAN
1. Remove the front grille. (Refer to section 2.1.1)
2. Remove the cabinet. (Refer to section 2.1.2)
3. Remove the 2 screws which fasten the evaporator at the left side and the right side. (See Fig. 4)
4. Move the evaporator sideward carefully.
5. Remove the 2 terminals carefully (See Fig. 5, at Electric Heater Model only)
6. Remove the 4 screws which fasten the orifice. (See Fig. 5)
7. Remove the orifice. (See Fig. 5)
8. Remove the clamp which secures the turbo fan with plier. (See Fig. 6)
9. Remove the turbo fan with plier or your hand without touching blades. (See Fig. 7)
10. Re-install the components by referring to the removal procedure, above.
2.2.2 FAN
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the brace and shroud cover.
(Refer to section 2.2.1)
3. Remove the 6 screws which fasten the condenser.
4. Move the condenser sideways carefully.
5. Remove the clamp which secures the fan.
6. Remove the fan. (See Fig. 8)
7. Re-install the components by referring to the
removal procedure, above.
Figure 4
Figure 5
Figure 6
Figure 8
8
2.2.3 SHROUD
1. Remove the fan. (Refer to section 2.2.2)
2. Remove the screw which fasten the shroud.
3. Remove the shroud. (See Fig. 9)
4. Re-install the component by referring to the
removal procedure, above.
2.3 ELECTRICAL PARTS
2.3.1 MOTOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the clamp cord and disconnect a wire
housing in control box. (Refer to section 2.1.3)
3. Remove the turbo fan. (Refer to section 2.2.2)
4. Remove the fan. (Refer to section 2.2.2)
5. Remove the 4 or 2 screws which fasten the motor.
(See Fig. 10)
6. Remove the motor.
7. Re-install the components by referring to the
removal procedure, above.
2.3.2 COMPRESSOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Discharge the refrigerant system using Freon
TM
Recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the Freon
TM
. Leave the valve in place after
servicing the system.
3. Disconnect the 3 leads from the compressor.
4. After purging the unit completely, unbraze the
suction and discharge tubes at the compressor connections.
5. Remove the 3 nuts and the 3 washers which
fasten the compressor. (See Fig. 11)
6. Remove the compressor.
7. Re-instill the components by referring to the
removal procedure, above.
2.3.3 CAPACITOR
1. Remove the control box. (Refer to section 2.1.3)
2. Remove knobs and the tips which fasten the
display panel.
3. Disconnect the 2 leads from the rocker switch and
remove the panel (Energy saver model only).
4. Remove 2 screws and unfold the control box.
(See Fig. 12)
5. Remove the Rotary Switch.
6. Remove the screw and the clamp which fastens
the capacitor. (See Fig. 12)
7. Disconnect all the leads of capacitor terminals.
8. Re-install the components by referring to the
removal procedure, above.
Figure 9
Figure 10
Figure 11
Figure 12
9
2.3.4 POWER CORD
1. Remove the control box. (Refer to section 2.1.3)
2. Unfold the control box. (Refer to section 2.3.3)
3. Disconnect the grounding screw from the control
box.
4. Disconnect 2 receptacles.
5. Remove a screw which fastens the clip cord.
6. Pull the power cord. (See Fig. 13)
7. Re-install the component by referring to the
removal procedure, above. (Use only one ground-marked hole for ground connection.)
8. If the supply cord of this appliance is damaged, it
must be replaced by the special cord. (The special cord means the cord which has the same specification marked on the supply cord fitted to the unit.)
2.3.5 THERMOSTAT
1. Remove the control box. (Refer to section 2.1.3)
2. Unfold the control box. (Refer to section 2.3.3)
3. Remove the 2 screws which fasten the thermostat.
4. Disconnect all the leads of thermostat terminals.
5. Remove the thermostat. (See Fig. 14)
6. Re-install the components by referring to the
removal procedure, above.
2.3.6 ROTARY SWITCH
1. Remove the control box. (Refer to section 2.1.3)
2. Unfold the control box. (Refer to section 2.3.3)
3. Remove 2 screws which fasten the rotary switch.
4. Disconnect all the leads of the rotary switch
terminals.
5. Remove the rotary switch. (See Fig. 15)
6. Re-install the components by referring to the
above removal procedure, above.
Figure 13
Figure 14
Figure 15
10
2.4 REFRIGERATION CYCLE
2.4.1 CONDENSER
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the brace and the shroud cover.
(Refer to section 2.2.1)
3. Remove the 5 screws which fasten the condenser.
4. After discharging the refrigerant completely,
unbraze the interconnecting tube at the condenser connections.
5. Remove the condenser.
6. Re-install the components by referring to notes.
(See Fig. 16)
2.4.2 EVAPORATOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Discharge the refrigerant completely.
3. Remove the 2 screws which fasten the evaporator
at the left side and the right side.
4. Move the evaporator sideward carefully and then
unbraze the interconnecting tube at the evaporator connectors.
5. Remove the evaporator.
6. Re-install the components by referring to notes.
(See Fig. 17)
2.4.3 CAPILLARY TUBE
1. Remove the cabinet. (Refer to section 2.1.2)
2. After discharging the refrigerant completely,
unbraze the interconnecting tube at the capillary tube.
3. Remove the capillary tube.
4. Re-install the components by referring to notes.
Figure 16
Figure 17
Discharge the refrigerant system using Freon
TM
Recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the Freon
TM
. Leave the valve in place
after servicing the system.
CAUTION
11
Replacement of the refrigeration cycle.
1. When replacing the refrigeration cycle, be sure to
discharge the refrigerant system using a Freon
TM
recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.
2. After discharging the unit completely, remove the
desired component, and unbrace the pinch-off tubes.
3. Solder service valves into the pinch-off tube ports,
leaving the valves open.
4. Solder the pinch-off tubes with Service valves.
5. Evacuate as follows.
1) Connect the vacuum pump, as illustrated Fig. 18A.
2) Start the vacuum pump, slowly open manifold valves A and B with two full turns counterclockwise and leave the valves closed. The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold
and entire system.
3) Operate the vacuum pump for 20 to 30 minutes, until 600 microns of vacuum is obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop
the vacuum pump.
4) Remove the hose from the vacuum pump and place it on the charging cylinder. See Fig. 18B. Open valve C. Discharge the line at the manifold connection.
5) The system is now ready for final charging.
6. Recharge as follows :
1) Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.
2)
Connect the charging cylinder as shown in Fig. 18B. With valve C open, discharge the hose at the manifold connection.
3) Open valve A and allow the proper charge to enter the system. Valve B is still closed.
4) If more charge is required, the high-side will not take it. Close valve A.
5) With the unit running, open valve B and add the balance of the charge.
a. Do not add the liquid refrigerant to the Low-
side.
b. Watch the Low-side gauge; allow pressure to
rise to 30 lbs. c. Turn off valve B and allow pressure to drop. d. Repeat steps B and C until the balance of the
charge is in the system.
6) When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.
NOTES
If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.
CAUTION
12
Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pinch-off tool capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.
A
COMPOUND GAUGE
EVAPORATOR (LOW PRESSURE SIDE)
COMPRESSOR
CAPILLARY TUBE
CONDENSER (HIGH PRESSURE SIDE)
SEE INSETS
BELOW
MANIFOLD
GAUGE
B
Figure 18A-Pulling Vacuum
Figure 18B-Charging
A
B
EXTERNAL VACUUM PUMP
LOW
B
HI
A
CHARGING CYLINDER
C
13
3. INSTALLATION
3.1 HOW TO INSTALL THE UNIT
For existing sleeve, you should measure the wall sleeve
dimensions. You can install the new air conditioner according to these installation instructions to achieve the best performence. All wall sleeves used to mount the new air conditioner must be in good structural condition and have the rear grille that securely attaches to the sleeve or the flange of the sleeve to secure the new air conditioner.
To avoid vibration and noise, make sure the unit is installed securely and firmly.
A. BEFORE ATTACHING THE FRONT
GRILLE TO THE CABINET, IF YOU WANT TO PULL OUT THE FILTER UPWARD;
1. There should be no obstacle, like a fence, within 20" which
might restrict heat radiation from the condenser.
2. To prevent reducing performance, install the unit so that
louvers of the cabinet are not blocked.
B. IF YOU WANT TO PULL OUT THE FILTER
DOWNWARD;
The grille is already designed for that way.
1. Install the unit a little obliquely outward not to leak the
condensed water into the room (about 1/2" or 1/4" bubble with level).
2. Install the unit with its bottom portion 30~60" above the floor
level.
3. The power cord must be connected to an independent
circuit. The green wire must be grounded.
14-13/32" (366 mm)
24-21/32"
(626 mm)
18"(458 mm)
19-21/32"
(499 mm)
15- 17/32"
(394 mm)
25-
7
/8"
(656 mm)
16-
23
/32"
(425 mm)
Over 20"
HEAT
RADIATION
WALL
WALL
INSULATION SLEEVE
INTAKE
AIR
COOLED
AIR
Level
1/4" Bubble
1/4" Bubble
of the level
There are sharp edges that can cause serious cuts.
When lifting the air conditioner, it is HEAVY.
Use 2 peoples to lift.
CAUTION
Dimension of air conditioner
Dimension of sleeve assembly (optional)
14
3.2 INSTALLATION KITS CONTENTS
Air Conditioner
1
2
Sleeve Assembly
(optional, including expanded
aluminum metal grille)
1 Insulation Front (1 ea)
3 Insulation Vertical (4 ea)
(Adhesive backed)
4 Support Block (4 ea)
(Adhesive backed)
5 Baffle (2 ea)
(Plastic sheet)
2 Insulation Horizontal (2 ea)
(Adhesive backed)
Louvered Grille
(optional)
Trim (2 ea)
4
5
3
14"
(355 mm)
82-11/16"
(2,100 mm)
26-
3
/8"
(670 mm)
15
3.3.1 PREPARATION OF SLEEVE
1. Remove the old air conditioner from the wall sleeve and prepare the wall sleeve. Clean the interior of the sleeve (do not disturb the insulation or seals). The wall sleeve must be fastened in the wall securely before installing the new air conditioner.
2. Prepare the wall sleeve for installation of the new unit according to the following installation procedures. Before you prepare the wall sleeve, you should check the wall sleeve dimensions.
3. Redirect the louvers at the back of the wall sleeves as following A and B lengths in the below table.
4. Sleeve (up to 18 inches deep) When the depth of your existing sleeve is deeper than 18", please skip to step 5. Remove the backing from horizontal insulation and attach them to the inside of the wall sleeve as shown below.
Remove the backing from insulation vertical and attach them to the inside of the wall sleeve, as shown below.
5. Sleeve (18~22 inches deep) When the depth of your existing sleeve is not deeper than 18", please skip to step 6. Cut the baffles and the support blocks as following C length in the below table.
SCREWDRIVER(+, -), RULER, KNIFE, HAMMER, PENCIL, LEVEL
3.3 SUGGESTED TOOL REQUIREMENTS
Width of the existing
wall sleeve
25-1/2"(648 mm)
3
/4"(654 mm)
25­26" (660 mm)
3
/4"(680 mm)
26­27" (686 mm)
1
/2"
AB
(12 mm)
45~60° 45~60°
A
3
2-
/4" (70 mm)
3
/4" (70 mm)
2­3" (75 mm)
1
/4" (80 mm)
3-
1
3-
/2" (90 mm)
1-1/4"
(32 mm)
45~60°
B
3
4-
/4"(120 mm) 5" (130 mm) 5" (130 mm)
1
/2"(140 mm)
5-
1
5-
/2"(140 mm)
Top view of the wall sleeveWall Wall
Insulation
Horizontal
(2 ea)
Wall
Wall Sleeve
Front
Wall
Wall Sleeve
Front
Depth of the existing
wall sleeve
5
/8" (473 mm)3/4" (20 mm)
18-
C
19-3/4" (502 mm) 1-3/4" (45 mm) 22" (559 mm) 4"
(100 mm)
A
B
C
Support Block
Baffle
C
16
Remove the backing from vertical and horizontal insulation and attach them to the inside of the wall sleeve as shown below. Remove the backing from the support blocks and attach them to the inside of the wall sleeve as shown below. Slide the baffles in the slots of the support blocks.
3.3.2 UNIT INSTALLATION
1. Remove the backing from vertical insulation and attach them to the back of the unit as shown below.
2. Install the new unit into the wall sleeve.
3. Insert front insulation between the wall sleeve and the unit. A flat-bladed screwdriver or putty knife is recommended.
4. To assemble trim, insert the snaps into the slots of others. To install trim to the sleeve, slide the trim through the unit until it is flush with the wall sleeve.
Wall
Trim (2 ea)
Wall
Wall Sleeve
Vertical Insulation
Front
A
B
Wall
Wall
Sleeve
Insulation Horizontal
A+1/4"
(6 mm)
B+
1
/4"
(6 mm)
Insulation Vertical
Front
17
4. TROUBLESHOOTING GUIDE
4.1 OUTSIDE DIMENSIONS
19-21/32"
(499mm)
24-
21
/32"
(626mm)
14-
13
/32"
(366mm)
CONDENSER COILS
EVAPORATOR COILS
FAN
MOTOR
: REFRIGERANT FLOW
TURBO FAN
CAPILLARY TUBE
COMPRESSOR
4.2 PIPING SYSTEM
Following is a brief description of the important components and their functions in the refrigeration system. Refer to Fig. 19 to follow the refrigeration cycle and the flow of the refrigerant in the cooling cycle.
MOTOR
COMPRESSOR
OIL
(LIQUID REFRIGERANT)
CAPILLARY TUBE
OUTSIDE COOLING AIR FOR REFRIGERANT PASS THROUGH
SUCTION LIME COOL LOW PRESSURE VAPOR
COOLED AIR
COMPLETE LIQUID BOIL OFF POINT
LIQUID PRESSURE DROP
ROOM AIR HEAT LOAD
VAPOR INLET
HOT DISCHARGED AIR
LIQUID OUTLET
HIGH PRESSURE VAPOR LIQUID PEFRIGERANT LOW PRESSURE VAPOR
ROOM AIR CONDITIONER
EVAPORATOR COILS CONDENSER COILS
CYCLE OF REFRIGERATION
Figure 19
18
4.3 TROUBLESHOOTING GUIDE
In general, possible trouble is classified in two causes. The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit is running but cooling is ineffective
Ineffective Cooling
Check of outdoor coil (heat exchanger) & the fan operation.
Check gas leakage.
Repair gas leak.
Replacement of unit if the unit is beyond repair.
Satisfactory operation with temperature difference of inlet & outlet air ; 44.6~50˚F
Check heat load increase.
Unexpected residue
Overloaded Circuit
Check of inside gas pressure.
Adjusting of refrigerant charge
Malfunction of compressor
Replacement of compressor
Check of cold air circulation for smooth flow.
Dirty indoor coil (Heat exchanger)
Malfunction of fan
Clogged of air filter
Obstruction at air outlet
Correct above trouble
Stop of auto air-swing
Check clogging in refrigeration circuit.
Repair clogging in refrigeration circuit.
19
Fails to Start
Check of circuit breaker and fuse.
Gas leakage of feeler bulb of thermostat
Check of control switch.
Only fan fails to start.
Improper wiring.
Defect of fan motor capacitor.
Irregular motor resistance ( ). Irregular motor insulation ( ).
Replacement of fan motor
Regular but fails to start
Replacement of compressor (locking of rotor, metal)
Improper thermostat setting
Loose terminal connection.
Improper wiring
Irregular motor resistance ( )
Irregular motor insulation ( )
Replacement of compressor (Motor damaged)
Drop of power voltage.
Check capacitor.
Replacement.
Only compressor fails to start.
Defect of compressor capacitor.
Check of power source.
Check of control switch setting.
2020
COMPLAINT CAUSE REMEDY
Check voltage at outlet. Correct if none. Check voltage to rotary switch. If none, check
power supply cord. Replace cord if circuit is open. Check switch continuity. Refer to wiring diagram
for terminal identification. Replace switch if defective.
Connect wire. Refer to wiring diagram for terminal identification. Repair or replace loose terminal.
Test capacitor. Replace if not within ±10% of manufacturer's rating. Replace if shorted, open, or damaged.
Fan blade hitting shroud or blower wheel hitting scroll. Realign assembly.
Units using slinger ring condenser fans must have 1/4to 5/16inch clearance to the base. If it is hitting the base, shim up the bottom of the fan motor with mounting screw(s).
Check fan motor bearings; if motor shaft will not rotate, replace the motor.
Check voltage. See limits on this page. If not within limits, call an electrician.
Test capacitor. Check bearings. Does the fan blade rotate freely? If not, replace fan motor.
Pay attention to any change from high speed to low speed. If the speed does not change, replace the motor.
Check grommets; if worn or missing, replace them. If cracked, out of balance, or partially missing,
replace it. If cracked, out of balance, or partially missing,
replace it. Tighten it. If knocking sounds continue when running or
loose, replace the motor. If the motor hums or noise appears to be internal while running, replace motor.
No power Power supply cord
Rotary switch
Wire disconnected or connection loose
Capacitor (Discharge capacitor before testing.)
Will not rotate
Revolves on overload.
Grommets Fan
Turbo fan
Loose set screw Worn bearings
Fan motor will not run.
Fan motor runs intermittently
Fan motor noise.
21
NAME PLATE RATING MINIMUM MAXIMUM
115V 103.5V 126.5V
208/230V 187V 253V
COMPLAINT CAUSE REMEDY
Check voltage. See the limits on the preceding. page. If not within limits, call an electrician.
Check the wire connections, if loose, repair or replace the terminal. If wires are off, refer to wiring diagram for identification, and replace. Check wire locations. If not per wiring diagram, correct.
Check for continuity, refer to the wiring diagram for terminal identification. Replace the switch if circuit is open.
Check the position of knob If not at the coldest setting, advance the knob to this setting and restart unit. Check continuity of the thermostat. Replace thermostat if circuit is open.
Check the capacitor. Replace if not within ±10% of manufacturers rating. Replace if shorted, open, or damaged.
Check the compressor for open circuit or ground. If open or grounded, replace the compressor.
Check the compressor overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool it, and retest.)
Voltage
Wiring
Rotary
Thermostat
Capacitor (Discharge capacitor before servicing.)
Compressor
Overload
Compressor will not run, but fan motor runs.
ROOM AIR CONDITIONER VOLTAGE LIMITS
22
COMPLAINT CAUSE
REMEDY
Check the voltage. See the limits on the preced­ing page. If not within limits, call an electrician.
Check overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.)
If not running, determine the cause. Replace if required.
Remove the cabinet. inspect the interior surface of the condenser; if restricted, clean carefully with a vacuum cleaner (do not damage fins) or brush. Clean the interior base before reassembling.
If condenser fins are closed over a large area on the coil surface, head pressures will increase, causing the compressor to cycle. Straighten the fins or replace the coil. Test capacitor. Check the terminals. If loose, repair or replace. Check the system for a restriction. If restricted, clean of replace. Close if open. Determine if the unit is properly sized for the area to be cooled. Check the set screw or clamp. If loose or missing, correct. If the blower or fan is hitting air guide, rearrange the air handling parts. Remove the cabinet and carefully rearrange tubing not to contact cabinet, compressor, shroud, and barrier.
Voltage
Overload
Fan motor
Condenser air flow restriction
Condenser fins (damaged)
Capacitor Wiring Refrigerating system Air filter Exhaust damper door Unit undersized
Blower or fan
Copper tubing
Compressor cycles on overload.
Insufficient cooling or heating
Excessive noise.
23
5. SCHEMATIC DIAGRAM
5.1 CIRCUIT DIAGRAM
MODEL : BDE-103-A/BDE-123-A
6411A20048L
2H00598F
4681A20044E 4681A20041M
6120AR2359E
2H01127D
6750U-L028A 6750U-L039A
2520UKCK2BA 2520UKHK2AA
5300A20003A
3854AR3563D
WIRING DIAGRAM
COMP
MOTOR
CAPACITOR
ROTARY SWITCH
POWER INPUT
7
1
8 6
4 2
F
C
C
H
RD
BL BK
BL
BK
L H
OR(BR)
OR(BR)
THERMOSTAT
WH
BK
YL
BL
RD
RD
YL
C
L
H
R
S
C
BR(YL)
O.L.P
BK RD
RD RD
FUSE LINK
BI-METAL
THERMOSTAT
HEATER
BL
BK RD
BL
BK(BR)
(Plain)
WH(BL)
(Ribbed)
GN/YL
1
3
4 5
6 8
2
7
NO.
1 2 3 4 5 6 7 8
Q'TY
PER SET
1 1 1 1 1 1 1 1
RE-
MARKS
DESCRIPTION
POWER CORD ROTARY SWITCH FAN MOTOR CAPACITOR THERMOSTAT OVERLOAD PROTECTOR COMPRESSOR ELECTRIC HEATER
PART NO.
BDE-103-A BDE-123-A
24
6. EXPLODED VIEW
MODEL: BDE-103-A/BDE-123-A
354210
753010
753011
349480
554030
W48602
559011
346811
349600
567502
349001
130410
35211335211A
352115
352115-1
W48602
249950
137215
149410
W0CZZ
264110
130900
435301
135312
147581
147582-2
147582-1
352390
148000
554160
550140
149980
359012
266003
269310
552111
152302
135313
E
D
F
A
C
B
749180
25
7. REPLACEMENT PARTS LIST
MODEL: BDE-103-A/BDE-123-A
R: Service Parts N: Non Service parts
A 249950 CONTROL BOX ASSY, SINGLE 4995A20408E R
264110 POWER CORD ASSY 6411A20048L R 266003 SWITCH, ROTARY 2H00598F R 269310 THERMOSTAT ASSY 2H01127D R W0CZZ CAPACITOR, DRAWING 6120AR2359E R 149410 KNOB ASSY 4941A30005B R 137215 PANEL ASSY, CONTROL 3721A20049H R
B 554160 COMPRESSOR 2520UKCK2BA 2520UKHK2AA R
550140 ISOLATOR, COMP 4H00982E R 567502 O.L.P 6750U-L028A 6750U-L039A R
C 352113
TUBE ASSY, DISCHARGE SINGLE
5211A30588B 5211A21421C R
352115
TUBE ASSY, EVAPORATOR IN
5211A20289C 5211A29024E R
35211A
TUBE ASSY, SUCTION SINGLE
5211A20498B 5211A25028A R
552111 TUBE ASSY, CAPILLARY 5211A20214L 5210A22592L/M R
D 352390 AIR GUIDE ASSY 5239A10002F R
349001 DAMPER,VENTILATION 4900A20001A R
E 135312 GRILLE ASSY, FRONT 3531A20055G R
135313 GRILLE, INLET 3530A20020A R
147581 LOUVER, HORIZONTAL 4758A20008B R 147582-1 LOUVER, VERTICAL 4758A20009A R 147582-2 LOUVER, VERTICAL 4758A20009B R
152302 FILTER(MESH), A/C 5230A20007A R
F 753010 HEATER ASSY 5301A20011A R
753011 HEATER ASSY, ELECTRIC 5300A20003A R
349480 ORIFICE 4948A10006A R
149980 SHROUD 4998A10007B R
346811 MOTOR ASSY, SINGLE 4681A20044E 4681A20041M R
349600 MOUNT, MOTOR 4960A20005A 4960A20008A R
148000 BRACE 4800A30002A R
435301 GRILLE, REAR 3530A30002A R
354210 EVAPORATOR ASSY, FIRST 5421A20071E 5421A20071J R
359012 FAN, TURBO 5900A20009B R
554030 CONDENSER ASSY, BENT 5403A20040M 5403A20040D R
559011 FAN ASSY, AXIAL 5900AR1173A R
W48602 CLAMP, SPRING 3H02932B R
130410 BASE ASSY, SINGLE 3041A10038D 3041A10038F R
130900 CABINET 3090A20003B R
749180 TRIM 4918A20001A R
PART NO.
DESCRIPTION
REMARK
LOCATION
NO
.
BDE-103-A BDE-123-A
Specifications and performance data subject to change without notice.
HEAT CONTROLLER, INC.
1900 WELLWORTH AVENUE • JACKSON, MICHIGAN 49203
THE QUALITY LEADER IN CONDITIONING AIR
P/No.: 3828A20040F
Loading...