• Important operating
and maintenance
instructions included.
WARNING: If the information in these
instructions is not followed exactly, a fi re
or explosion may result causing property
damage, personal injury, or death.
• DO NOT store or use gasoline or other fl am-
mable vapors and liquids in the vicinity of this
or any other appliance.
• What to do if you smell gas
- DO NOT try to light any appliance.
- DO NOT touch any electrical switch. DO
NOT use any phone in your building.
- Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call
the fi re department.
• Installation and service must be performed
by a qualifi ed installer, service agency , or the
gas supplier.
This appliance may be installed as an OEM installation in
manufactured home (USA only) or mobile home and must be
installed in accordance with the manufacturer’s instructions
and the manufactured home construction and safety standard,
Title 24 CFR, Part 3280 or Standard for Installation in Mobile
Homes, CAN/CSA Z240MH, in Canada.
This appliance is only for use with the type(s) of gas indicated
on the rating plate.
• Read, understand and follow
these instructions for safe
installation and operation.
DO NOT
DISCARD
• Leave this manual with
party responsible for use
and operation.
WARNING
HOT SURFACES!
Glass and other surfaces are hot during
operation AND cool down.
Hot glass will cause burns.
• DO NOT touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as
fi replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other fl ammable
materials.
• Keep clothing, furniture, draperies and other fl ammable
materials away.
This appliance has been supplied with an integral barrier
to prevent direct contact with the fi xed glass panel. DO
NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the
barrier is not present or help is needed to properly install one.
In the Commonwealth of Massachusetts installation must be
performed by a licensed plumber or gas fi tter.
See Table of Contents for location of additional Commonwealth
of Massachusetts requirements.
Installation and service of this appliance should be
performed by qualifi ed personnel. Hearth & Home
Technologies suggests NFI certifi ed or factory trained
professionals, or technicians supervised by an NFI
certifi ed professional.
Read this manual before installing or operating this appliance.
Please retain this owner’s manual for future reference.
A. Congratulations
Congratulations on selecting a Heat & Glo gas fi replace, an
elegant and clean alternative to wood burning fi replaces.
The Heat & Glo gas fi replace you have selected is designed
to provide the utmost in safety, reliability, and effi ciency.
As the owner of a new fi replace, you’ll want to read and
carefully follow all of the instructions contained in this
owner’s manual. Pay special attention to all cautions and
warnings.
Homeowner Reference Information
This owner’s manual should be retained for future
reference. We suggest that you keep it with your other
important documents and product manuals.
The information contained in this owner’s manual, unless
noted otherwise, applies to all models and gas control
systems.
Your new Heat & Glo gas fi replace will give you years of
durable use and trouble-free enjoyment. Welcome to the
Heat & Glo family of fi replace products!
We recommend that you record the following pertinent
information about your fi replace.
Model Name: ___________________________________________ Date purchased/installed: __________________
Serial Number: __________________________________________ Location on fi replace: _____________________
Dealership purchased from: _______________________________ Dealer Phone: __________________________
Notes: _______________________________________________________________________________________
_____________________________________________________________________________________________
Listing Label Information/Location
This product may be covered by one or more of the following patents: (Nos produits sont couverts par un ou plusieurs des brevets suivants): (United States)
4593510,4686807, 4766876, 4793322, 4811534, 5000162, 5016609, 5076254, 5113843, 5191877, 5218953, 5263471, 5328356,5341794, 5347983, 5429495,
5452708,5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485,5931661, 5941237, 594711 2,5996575, 6006743, 6019099, 6048195,
6053165, 6145502, 6170481, 6237588, 6296474, 6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2,
6729551, 6736133, 6748940, 6748942, D320652, D445174, D462436; (Canada)1297749, 2195264, 2225408; or other U.S. and foreign patents pending (ou
autresbrevetsamericainsetetrangersenattente).
Type of Gas
Not for use with solid fuel .
(Ne doit pas entre utilise avec un combustible solide).
Ty pe of Gas (Sorte De Gaz) :
NATURA L GAS
Gas and Electric
Information
Minimum Permissible Gas Supply for Purpos es of Input Adjustment .
Approved Minimum (De Gaz) Acceptabl e 0. 0 in w. c.(Po. Col. d’eau) Maximum Pressure (Pression) 0. 0 in w. c.(Po. Col. d’eau) Maximum Manifold Pressure (Pression) 0. 0 in w. c. (Po. Col. d’eau) Minimum Manifold Pressure (Pression) 0. 0 in w. c. (Po. Col. d’eau)
T o tal Electrical Requirements: 000V ac, 00Hz., less than 00 Ampere s
AL TI TUDE :0-0000 FT . 0000-0000FT .
MAX. INPU T BTUH: 00,000 00,000
MIN. INPU T BTUH: 00,000 00,000
ORIFICE SIZE: #XXXXX #XXXXX
The model information regarding your specifi c fi replace can be found on
the rating plate usually located in the control area of the fi replace.
He at & Gl o, a of Hearth & Ho me Te chnologies, Inc.
20802 Kensington Boulevard, Lakeville, MN 5504 4
This appliance must be installed in accordance with local codes, if any; if not, follow ANSI Z223.1
in the USA or CAN/CG A B149 installation codes. (Installer l’ appa re il selon les codes ou regl emen ts
lo caux ou , en l’absence de tels reglements, selon les codes d’in stallation CAN/CGA-B149.)
B. Limited Lifetime Warranty
Hearth & Home Technologies LIMITED WARRANTY
Hearth & Home Technologies (“HHT”) and its respective brands extends the following warranty for HHT gas, wood, pellet
and electric appliances purchased from an authorized HHT dealer and installed in the United States of America or Canada.
Warranty starts with date of purchase by the original owner (End User) except as noted for replacement parts.
Warranty PeriodHHT Manufactured Appliances and Venting
PartsLaborGasWoodPellet
1 YearXXXXXX
EPA
Wood
ElectricVenting
Components Covered
All Parts and Material Except as
covered by Conditions, Exclusion,
and Limitations listed
XX
2 years
3 yearsXFirepots
5 years3 yearsXXCastings & Baffl es
7 years3 yearsXXX
10 years1 yearXBurners, Logs & Refractory
Limited
Lifetime
1 yearXFirebox & Heat Exchanger
90 DaysXXXXXX All Replacement Parts
XXXXBlowers
XMolded Refractory Panels
Igniters, Electronic Components,
and Glass
Firebox, HHT Chimney,
Termination & Heat
Exchanger
See Conditions, Exclusions, and limitations. 9-01-08
CONDITIONS, EXCLUSIONS & LIMITATION OF LIABILITY
• This warranty applies to the original owner and is transferable up to two years from date of purchase to the new homeowner,
provided the purchase was made through an authorized dealer or distributor of HHT, and the appliance remains in its
original place of installation.
• The maximum amount recoverable under this warranty is limited to the purchase price of the product.
• In no event shall HHT be liable for any incidental or consequential damages caused by defects in the product.
• Adjustments, regular maintenance, cleaning and temporary repairs, or the failure to duplicate the problem in the home is
not covered under this warranty.
• This limited warranty does not extend to or include surface fi nish on the appliance or terminations, door gasketing, glass
gasketing, glass discoloration, fi rebrick, pellet logs, kaowool or other ceramic insulating materials. Rust and/or corrosion
on any of the metal surfaces, cast iron components, baffl es, fi repots, doors, or fi rebox area are not covered by this
warranty.
• Noise resulting from minor expansion, contraction, or movement of certain parts is normal and complaints related to this
noise are not covered by this warranty.
• HHT’s obligation under this warranty does not extend to damages resulting from: (1) installation, operation or maintenance
of the appliance not in accordance with the installation instructions; operating instructions and the listing agent identifi cation
label furnished with the appliance; (2) installation which does not comply with local building codes; (3) shipping, improper
handling, improper operation, abuse, misuse, accident or unworkmanlike repairs; (4) environmental conditions, inadequate
ventilation or drafting caused by tight sealing construction of the structure or handling devices such as exhaust fans or forced
air furnaces or other such causes; (5) use of fuels other than those specifi ed in the operating instructions; (6) installation
or use of components not supplied with the appliance or any other components not expressly authorized and approved
by HHT; and/or (7) modifi cation of the appliance not expressly authorized and approved by HHT in writing.
• This warranty does not apply to non-HHT venting components, hearth components or other accessories used in conjunction
with the installation of this product.
• This warranty is void if the appliance has been over-fi red or operated in atmospheres contaminated by chlorine, fl uorine,
or other damaging chemicals the appliance is subject to prolonged periods of dampness or condensation, or there is any
damage to the appliance or other components due to water or weather damage which is the result of, but not limited to,
improper chimney or venting installation.
• HHT’s liability under this warranty is limited to the replacement and repair of defective components or workmanship during
the applicable period. HHT may fully discharge all of its obligations under such warranties by repairing the defective
component(s) at HHT’s discretion. Shipping costs are not covered under this warranty.
• Some states do not allow exclusions or limitation of incidental or consequential damages, so those limitations may not
apply to you. This warranty gives you specifi c rights; you may also have other rights, which vary from state to state.
• EXCEPT TO THE EXTENT PROVIDED BY LAW, HHT MAKES NO EXPRESS WARRANTIES OTHER THAN THE
WARRANTY SPECIFIED HEREIN. THE DURATION OF ANY IMPLIED WARRANTY IS LIMITED TO DURATION OF
THE WARRANTY SPECIFIED ABOVE.
This Limited Warranty is effective on all HHT appliances sold after September 01, 2008 and supersedes any and all
warranties currently in existence.
If warranty service is needed, you should contact your installing dealer. If the installing dealer is unable to provide necessary
parts or components, contact the nearest authorized HHT dealer or supplier.
LABORATORY: Underwriters Laboratories, Inc. (UL)
TYPE: Direct Vent Gas Appliance Heater
STANDARD: ANSI Z21.88-2007 • CSA 2.33a-2007
This product is listed to ANSI standards for “Vented Gas
Appliance Heaters” and applicable sections of “Gas Burning Heating Appliances for Manufactured Homes and
Recreational Vehicles”, and “Gas Fired Appliances for
Use at High Altitudes”.
NOTICE: This installation must conform with local codes.
In the absence of local codes you must comply with the
National Fuel Gas Code, ANSI Z223.1-latest edition in
the U.S.A. and the CAN/CGA B149 Installation Codes in
Canada.
NOT INTENDED FOR USE AS A PRIMAR Y HEAT SOURCE.
This appliance is tested and approved as either supplemental room heat or as a decorative appliance. It should not be
factored as primary heat in residential heating calculations.
B. Tempered Glass Specifi cations
Hearth & Home Technologies appliances manufactured
with tempered glass may be installed in hazardous locations such as bathtub enclosures as defi ned by the Con-
sumer Product Safety Commission (CPSC). The tempered
glass has been tested and certifi ed to the requirements
of ANSI Z97.1 and CPSC 16 CFR 1202 (Safety Glazing
Certifi cation Council SGCC# 1595 and 1597. Architectur-
al Testing, Inc. Reports 02-31919.01 and 02-31917.01).
This statement is in compliance with CPSC 16 CFR Sec-tion 1201.5 “Certifi cation and labeling requirements”
which refers to 15 U.S. Code (USC) 2063 stating “…Such
certifi cate shall accompany the product or shall otherwise
be furnished to any distributor or retailer to whom the
product is delivered.”
Some local building codes require the use of tempered
glass with permanent marking in such locations. Glass
meeting this requirement is available from the factory.
Please contact your dealer or distributor to order.
NOTICE: If the heating value of the gas has been reduced,
these rules do not apply. Check with your local gas utility
or authorities having jurisdiction.
When installing above 2000 feet elevation:
• In the USA: Reduce input rate 4% for each 1000 feet
above 2000 feet.
• In CANADA: Reduce input rate 10% for elevations
between 2000 feet and 4500 feet. Above 4500 feet,
consult local gas utility.
Check with your local gas utility to determine proper orifi ce
size.
E. Non-Combustible Materials Specifi cation
Material which will not ignite and burn. Such materials are
those consisting entirely of steel, iron, brick, tile, concrete,
slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a
Vertical Tube Furnace at 750 ºC and UL763 shall be
considered non-combustible materials.
F. Combustible Materials Specifi cation
Materials made of or surfaced with wood, compressed paper, plant fi bers, plastics, or other material that can ignite
and burn, whether fl ame proofed or not, or plastered or
unplastered shall be considered combustible materials.
G. Electrical Codes
NOTICE: This appliance must be electrically wired
and grounded in accordance with local codes or, in the
absence of local codes, with National Electric Code
ANSI/NFPA 70-latest edition or the Canadian Electric
Code CSA C22.1.
• A 110-120 VAC circuit for this product must be protected
with ground-fault circuit-interrupter protection, in
compliance with the applicable electrical codes, when it is
installed in locations such as in bathrooms or near sinks.
Note: The following requirements reference various
Massachuset ts and national codes not contained in this
document.
H. Requirements for the Commonwealth of
Massachusetts
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7)
feet above fi nished grade in the area of the venting, in-
cluding but not limited to decks and porches, the following
requirements shall be satisfi ed:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gas fi tter
shall observe that a hard wired carbon monoxide detector
with an alarm and battery back-up is installed on the fl oor
level where the gas equipment is to be installed. In addition, the installing plumber or gas fi tter shall observe that
a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of
the dwelling, building or structure served by the side wall
horizontal vented gas fueled equipment. It shall be the
responsibility of the property owner to secure the services
of qualifi ed licensed professionals for the installation of
hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic,
the hard wired carbon monoxide detector with alarm and
battery back-up may be installed on the next adjacent
fl oor level.
In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply
with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
Inspection
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed
in accordance with the provisions of 248 CMR 5.08(2)(a)1
through 4.
Exemptions
The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition
of NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fu-
eled equipment installed in a room or structure separate
from the dwelling, building or structure used in whole or
in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting
system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
• Detailed instructions for the installation of the venting
system design or the venting system components; and
• A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall
horizontally vented gas fueled equipment does not provide the parts for venting the fl ue gases, but identifi es
“special venting systems”, the following requirements
shall be satisfi ed by the manufacturer:
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA
720 and be ANSI/UL 2034 listed and IAS certifi ed.
Signage
A metal or plastic identifi cation plate shall be permanent-
ly mounted to the exterior of the building at a minimum
height of eight (8) feet above grade directly in line with the
exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read,
in print size no less than one-half (1/2) inch in size, “GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
• The referenced “special venting system” instructions
shall be included with the appliance or equipment installation instructions; and
• The “special venting systems” shall be Product Ap-
proved by the Board, and the instructions for that system shall include a parts list and detailed installation
instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting
instructions, and/or all venting design instructions shall
remain with the appliance or equipment at the completion
of the installation.
See Gas Connection section for additional Commonwealth of Massachusetts requirements.
Page 9
2
2
Operating Instructions
User Guide
A. Gas Fireplace Safety
WARNING
HOT SURFACES!
Glass and other surfaces are hot during
operation AND cool down.
Hot glass will cause burns.
• DO NOT touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as
fi replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other
fl ammable materials.
• Keep clothing, furniture, draperies and other fl ammable
materials away.
This appliance has been supplied with an integral barrier
to prevent direct contact with the fi xed glass panel. DO
NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the
barrier is not present or help is needed to properly install one.
If you expect that small children or vulnerable adults may
come into contact with this fi replace, the following precau-
tions are recommended:
• Install a physical barrier such as:
- A decorative fi rescreen.
- Adjustable safety gate.
• Install a switch lock or a wall/remote control with child
protection lockout feature.
• Keep remote controls out of reach of children.
• Never leave children alone near a hot fi replace, whether
operating or cooling down.
• Teach children to NEVER touch the fi replace.
• Consider not using the fi replace when children will be
present.
Contact your dealer for more information, or visit: www.
hpba.org/staysafe.
T o prevent unintended operation when not using your fi re-
place for an extended period of time (summer months,
vacations, trips, etc):
• Remove batteries from remote controls.
• Turn off wall controls.
• Unplug 3 volt adapter plug and remove batteries on IPI
models.
B. Your Fireplace
WARNING! DO NOT operate fi replace before read-
ing and understanding operating instructions. Failure
to operate fi replace according to operating instructions
could cause fi re or injury.
If desired, a fan kit may be added. Contact your dealer to
order the correct fan kit.
D. Clear Space
WARNING! DO NOT place combustible objects in front
of the fi replace or block louvers. High temperatures may
start a fi re. See Figure 2.2.
A void placing candles and other heat-sensitive objects on
mantel or hearth. Heat may damage these objects.
3 FT. IN FRONT OF FIREPLACE
CLE
AR S
PACE
Figure 2.2 Clear Space
F. Fixed Glass Assembly
See Section 14.G.
G. Remote Controls, Wall Controls and Wall
Switches
Follow the instructions supplied with the control installed
to operate your fi replace:
For safety:
• Install a switch lock or a wall/remote control with child
protection lockout feature.
• Keep remote controls out of reach of children.
See your dealer if you have questions.
H. Before Lighting Fireplace
Before operating this fi replace for the fi rst time, have a
qualifi ed service technician:
• Verify all shipping materials have been removed from
inside and/or underneath the fi rebox.
• Review proper placement of logs, ember material and/or
other decorative materials.
• Check the wiring.
• Check the air shutter adjustment.
• Ensure that there are no gas leaks.
• Ensure that the glass is sealed and in the proper position
and that the integral barrier is in place.
WARNING! Risk of Fire or Asphyxiation! DO NOT operate fi replace with fi xed glass assembly removed.
E. Decorative Doors and Fronts
WARNING! Risk of Fire! Install ONLY doors or fronts
approved by Hearth & Home Technologies. Unapproved
doors or fronts may cause fi replace to overheat.
This fireplace has been supplied with an integral
barrier to prevent direct contact with the fi xed glass
panel. DO NOT operate the fi replace with the barrier
removed.
Contact your dealer or Hearth & Home Technologies if
the barrier is not present or help is needed to properly
install one.
For more information refer to the instructions supplied with
your decorative door or front.
The IPI system may be operated with two D-cell batteries. When using batteries, unplug the transformer. To prolong battery
life, remove them when using the transformer.
FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fi re or explosion
may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an
intermittent pilot ignition (IPI) device
which automatically lights the burner. DO NOT try to light the burner by
hand.
B.BEFORE LIGHTING, smell all around
the appliance area for gas. Be sure to
smell next to the fl oor because some
gas is heavier than air and will settle
on the fl oor.
WHA T TO DO IF YOU SMELL GAS
• DO NOT try to light any appliance.
• DO NOT touch any electric switch; do
not use any phone in your building.
WARNING:
DO NOT CONNECT 110 VAC TO
THE CONTROL VALVE.
Improper installation, adjustment, alteration, service or maintenance can
cause injury or property damage. Refer to the owner’s information manual
provided with this appliance.
This appliance needs fresh air for
safe operation and must be installed
so there are provisions for adequate
combustion and ventilation air.
If not installed, operated, and maintained in accordance with the manufacturer’s instructions, this product
could expose you to substances in fuel
or fuel combustion which are known to
the State of California to cause cancer, birth defects, or other reproductive
harm.
Keep burner and control compartment
clean. See installation and operating
instructions accompanying appliance.
• Immediately call your gas supplier
from a neighbor’s phone. Follow the
gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re department.
C. DO NOT use this appliance if any
part has been under water. Immediately call a qualifi ed service tech-
nician to inspect the appliance and
to replace any part of the control
system and any gas control which
has been under water.
CAUTION:
Hot while in operation. DO NOT touch.
Keep children, clothing, furniture, gasoline and other liquids having fl ammable
vapors away.
DO NOT operate the appliance with
fi xed glass assembly removed, cracked
or broken. Replacement of the fi xed
glass assembly should be done by a
licensed or qualifi ed service person.
NOT FOR USE
WITH SOLID FUEL
For use with natural gas and propane.
A conversion kit, as supplied by the
manufacturer, shall be used to convert
this appliance to the alternate fuel.
Also Certifi ed for Installation in a
Bedroom or a Bedsitting Room.
For assistance or additional information, consult a qualifi ed installer, ser-
vice agency or the gas supplier.
LIGHTING
INSTRUCTIONS
(IPI)
1. Turn off all electric power to the appliance.
2. This appliance is equipped with an ignition
device which automatically lights the burner.
DO NOT try to light the burner by hand.
GAS
VALVE
3. Wait fi ve (5) minutes to clear out any gas.
Then smell for gas, including near the fl oor. If
you smell gas, STOP! Follow “B” in the Safety
Information located on the left side of this label. If you do not smell gas, go to next step.
4. Turn on all electric power to the appliance.
5. To light the burner, fl ip the ON/OFF switch to
the “ON” position. (The ON/OFF switch may
include a wall switch if so equipped).
6. If the appliance will not operate, follow the instructions “To Turn Off Gas to Appliance” and
call your service technician or gas supplier.
TO TURN OFF
GAS TO APPLIANCE
1. Turn wall control or ON/OFF switch to “OFF”.
2. Turn off all electric power to the appliance if
service is to be performed.
593-913F
Hearth & Home Technologies fi replace, please refer to www.fi replaces.com.
• The fireplace should be run three to four hours
continuously on high.
• Turn the fi replace off and allow it to completely cool.
• Remove fi xed glass assembly. See Section 14.G.
• Clean fi xed glass assembly. See Section 3.
• Replace the fi xed glass assembly and run continuously
on high an additional 12 hours.
This cures the materials used to manufacture the fi re-
place.
NOTICE! Open windows for air circulation during fi re-
place break-in.
• Some people may be sensitive to smoke and odors.
• Smoke detectors may activate.
K. Frequently Asked Questions
ISSUESOLUTIONS
Condensation on the glass
Blue fl ames
Odor from fi replace
Film on the glass
Metallic noise
This is a result of gas combustion and temperature variations. As the fi replace warms, this
condensation will disappear.
This is a result of normal operation and the fl ames will begin to yellow as the fi replace is al-
lowed to burn for 20 to 40 minutes.
When fi rst operated, this fi replace may release an odor for the fi rst several hours. This is
caused by the curing of materials from manufacturing. Odor may also be released from
fi nishing materials and adhesives used near the fi replace. These circumstances may require
additional curing related to the installation environment.
This is a normal result of the curing process of the paint and logs. Glass should be cleaned
within 3 to 4 hours of initial burning. A non-abrasive cleaner such as gas fi replace glass
cleaner may be necessary. See your dealer.
Noise is caused by metal expanding and contracting as it heats up and cools down, similar to
the sound produced by a furnace or heating duct. This noise does not affect the operation or
longevity of the fi replace.
Any safety screen or guard removed for servicing must be
replaced prior to operating the fi replace.
When properly maintained, your fi replace will give you
many years of trouble-free service. We recommend annual service by a qualifi ed service technician.
A. Maintenance Tasks-Homeowner
Installation and repair should be done by a qualifi ed service
technician only. The fi replace should be inspected before
use and at least annually by a professional service person.
The following tasks may be performed annually by the
homeowner. If you are uncomfortable performing any of
the listed tasks, please call your dealer for a service appointment.
More frequent cleaning may be required due to lint from
carpeting or other factors. Control compartment, burner
and circulating air passageway of the fi replace must be
kept clean.
CAUTION! Risk of Burns! The fi replace should be turned
off and cooled before servicing.
• Inspect venting and termination cap for blockage or
obstruction such plants, bird nests, leaves, snow, debris,
etc.
• Verify termination cap clearance to subsequent construction (building additions, decks, fences, or sheds). See
Section 6.
• Inspect for corrosion or separation.
• Verify weather stripping, sealing and fl ashing remains
intact.
• Inspect draft shield to verify it is not damaged or missing.
B. Maintenance Tasks-Qualifi ed Service
Technician
The following tasks must be performed by a qualifi ed ser-
vice technician.
Gasket Seal and Glass Assembly Inspection
Frequency: Annually
By: Qualifi ed Service Technician
T ools needed: Protective gloves, drop cloth and a stable
work surface.
• Inspect gasket seal and its condition.
• Inspect fi xed glass assembly for scratches and nicks that
can lead to breakage when exposed to heat.
• Confi rm there is no damage to glass or glass frame.
Replace as necessary.
• Verify that fi xed glass assembly is properly retained and
attachment components are intact and not damaged.
Replace as necessary.
Logs
Frequency: Annually
By: Qualifi ed Service Technician
Tools needed: Protective gloves.
• Inspect for damaged or missing logs. Replace as necessary.
Refer to Section 14 for log placement instructions.
• Verify correct log placement and no fl ame impingement
causing sooting. Correct as necessary.
Firebox
Frequency: Annually
By: Qualifi ed Service Technician
Tools needed: Protective gloves, sandpaper, steel wool,
cloths, mineral spirits, primer and touch-up paint.
• Inspect for paint condition, warped surfaces, corrosion
or perforation. Sand and repaint as necessary.
• Replace fi replace if fi rebox has been perforated.
Control Compartment and Firebox Top
Frequency: Annually
By: Qualifi ed Service Technician
Tools needed: Protective gloves, vacuum cleaner, dust
cloths
• V acuum and wipe out dust, cobwebs, debris or pet hair.
Use caution when cleaning these areas. Screw tips that
have penetrated the sheet metal are sharp and should
be avoided.
NOTICE: Illustrations and photos refl ect typical installations and are for design purposes only . Illustrations/diagrams are not
drawn to scale. Actual product may vary from pictures in manual
Getting Started
Installer Guide
HORIZONTAL
TERMINATION CAP
(SECTION 10.G )
FRAMING/HEADER
(SECTION 5.B)
NON-COMBUSTIBLE ROOF FLASHING
MAINTAINS MINIMUM CLEARANCE
AROUND PIPE (SECTION 10.D)
Heat & Glo direct vent gas appliances are designed to
operate with all combustion air siphoned from outside of
the building and all exhaust gases expelled to the outside.
No additional outside air source is required.
Installation MUST comply with local, regional, state and
national codes and regulations. Consult insurance carrier,
local building inspector, fi re offi cials or authorities having
jurisdiction over restrictions, installation inspection and
permits.
Before installing, determine the following:
• Where the appliance is to be installed.
• The vent system confi guration to be used.
• Gas supply piping.
• Electrical wiring requirements.
• Framing and fi nishing details.
• Whether optional accessories—devices such as a fan,
wall switch, or remote control—are desired.
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. For
assistance or additional information, consult a qualifi ed
service technician, service agency or your dealer.
C. Tools and Supplies Needed
Before beginning the installation be sure that the following
tools and building supplies are available.
Tape measure Framing material
Pliers High temperature caulking material
Hammer Phillips screwdriver
Gloves Framing square
Voltmeter Electric drill and bits (1/4 in.)
Plumb line Safety glasses
Level Reciprocating saw
Manometer Flat blade screwdriver
Non-corrosive leak check solution
1/2 - 3/4 in. length, #6 or #8 Self-drilling screws
One 1/4 in. female connection (for optional fan).
D. Inspect Appliance and Components
• Carefully remove the appliance and components from
the packaging.
• The vent system components and decorative doors and
fronts may be shipped in separate packages.
• If packaged separately, the log set and appliance grate
must be installed.
• Report to your dealer any parts damaged in shipment,
particularly the condition of the glass.
• Read all of the instructions before starting the instal-
lation. Follow these instructions carefully during the
installation to ensure maximum safety and benefi t.
WARNING! Risk of Fire or Explosion! Damaged parts
could impair safe operation. DO NOT install damaged, incomplete or substitute components. Keep appliance dry.
Hearth & Home T echnologies disclaims any responsibility for ,
and the warranty will be voided by, the following actions:
• Installation and use of any damaged appliance or vent
system component.
• Modifi cation of the appliance or vent system.
• Installation other than as instructed by Hearth & Home
Technologies.
• Improper positioning of the gas logs or the glass door.
• Installation and/or use of any component part not approved
by Hearth & Home Technologies.
Any such action may cause a fi re hazard.
WARNING! Risk of Fire, Explosion or Electric Shock!
DO NOT use this appliance if any part has been under
water. Call a qualifi ed service technician to inspect the
appliance and to replace any part of the control system
and/or gas control which has been under water.
When selecting a location for the appliance it is important to
consider the required clearances to walls (see Figure 5.1).
WARNING! Risk of Fire or Burns! Provide adequate
clearance around air openings and for service access.
Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
36 in.
914 mm
PIER
36 in.
914 mm
NOTICE: Illustrations refl ect typical installations and are
FOR DESIGN PURPOSES ONLY. Illustrations/diagrams
are not drawn to scale. Actual installation may vary due to
individual design preference.
A chase is a vertical box-like structure built to enclose the
gas appliance and/or its vent system. In cooler climates
the vent should enclosed inside the chase.
NOTICE: Treatment of ceiling fi restops and wall shield
fi restops and construction of the chase may vary with the
type of building. These instructions are not substitutes
for the requirements of local building codes. Therefore,
you MUST check local building codes to determine the
requirements to these steps.
Chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems. The chase should not break the outside building
envelope in any manner.
Walls, ceiling, base plate and cantilever fl oor of the chase
should be insulated. Vapor and air infi ltration barriers
should be installed in the chase as per regional codes for
the rest of the home. Additionally, in regions where cold
air infi ltration may be an issue, the inside surfaces may be
sheetrocked and taped for maximum air tightness.
To further prevent drafts, the wall shield and ceiling fi re-
stops should be caulked with high temperature caulk to
seal gaps. Gas line holes and other openings should be
caulked with high temp caulk or stuffed with unfaced insulation. If the appliance is being installed on a cement
slab, a layer of plywood may be placed underneath to
prevent conducting cold up into the room.
C. Clearances
NOTICE: Install appliance on hard metal or wood surfaces
extending full width and depth. DO NOT install directly
on carpeting, vinyl, tile or any combustible material other
than wood.
WARNING! Risk of Fire! Maintain specifi ed air space
clearances to appliance and vent pipe:
• Insulation and other materials must be secured to prevent
accidental contact.
• The chase must be properly blocked to prevent blown
insulation or other combustibles from entering and
making contact with fi replace or chimney.
• Failure to maintain airspace may cause overheating and
a fi re.
C
D
ST-36TRB-IPI
Inches
Millimeters
A
B
ABCDEFGHI
DVP Pipe SLP Pipe
Rough
Opening
(Width)
25421996858410928030013914
Rough
Opening
(Width)
108-5/838-1/8234331-5/800 1/236
Rough
Opening
(Height)
DVP Pipe*
Rough
Opening
(Depth)
Rough
Opening
(Width)
E
F
Clearance
to Ceiling
I
G
Combustible
Floor
Combustible
Flooring
H
Ends of
Appliance
Sides of
Appliance
* Adjust framing dimensions for interior sheathing (such as sheetrock)
Figure 5.2 Clearances to Combustibles ST-36TRB-IPI
WARNING! Risk of Fire! Comply with all minimum clearances as specifi ed. Framing or fi nishing material closer than
the minimums listed must be constructed entirely of noncombustible materials (i.e., steel studs, concrete board, etc).
See-Through Combustible Mantel
18
16
18
17
TO CEILING
32
25
19
Note: All
measurements
in inches.
2-1/2
12
11
10
9
8
7
6
5
4
3
11
10
5
15
14
13
12
See-Through Non-Combustible Mantel
TO CEILING
Note: All
measurements
in inches.
Figure 5.7 Minimum Vertical and Maximum Horizontal
Dimensions of Non-Combustibles
MAX.
18
12
11
10
9
8
7
1
6
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
4
3
2
32
12
6
5
MIN.
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
Figure 5.5 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles
PIER/LCOR/RCOR Combustible Mantel
18
16
TO CEILING
18
17
19
Note: All
measurements
in inches.
12
11
10
9
8
7
6
5
4
3
1
11
10
5
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
15
14
13
12
25
32
PIER/LCOR/RCOR Non-Combustible Mantel
TO CEILING
MAX.
Note: All
measurements
in inches.
6
4
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
Figure 5.8 Minimum Vertical and Maximum Horizontal
Dimensions of Non-Combustibles
12
10
9
8
7
9
8
7
6
32
MIN.
12
10
Figure 5.6 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles
A = 12 inches.................clearances above grade, veranda,
(See Note 1)
porch, deck or balcony
B = 12 inches.................clearances to window or door
that may be opened, or to permanently closed window. (Glass)
C = 18 inches.................vertical clearance to unventilated
soffi t or to ventilated soffi t located
above the terminal
30 inches .................for vinyl clad soffi ts and below
electrical service
D = 9 inches..................clearance to outside corner
E = 6 inches...................clearance to inside corner
F = 3 ft. (Canada) ..........not to be installed above a gas
meter/regulator assembly within 3
feet (90 cm) horizontally from the
center-line of the regulator
G = 3 ft ...........................clearance to gas service regulator
vent outlet
H = 9 inches (U.S.A.)
12 inches (Canada) clearance to non-mechanical
(See Note 2)
air supply inlet to building or the
combustion air inlet to any other
appliance
i = 3 ft. (U.S.A.)
6 ft. (Canada) ...........clearance to a mechanical (pow-
(See Note 2)
** a vent shall not terminate directly above a sidewalk or paved driveway
which is located between two single family dwellings and serves both
dwellings.
*** only permitted if veranda, porch, deck or balcony is fully open on a
minimum of 2 sides beneath the fl oor, or meets Note 2.
Note 1: On private property where termination is less than 7 feet above a
sidewalk, driveway, deck, porch, veranda or balcony, use of a listed cap
shield is suggested. (See vents components page)
Note 2: Termination in a covered alcove space (spaces open only on one
side and with an overhang) are permitted with the dimensions specifi ed
for vinyl or non-vinyl siding and soffi ts. 1. There must be 3 feet minimum
between termination caps. 2. All mechanical air intakes within 10 feet
of a termination cap must be a minimum of 3 feet below the termination
cap. 3. All gravity air intakes within 3 feet of a termination cap must be a
minimum of 1 foot below the termination cap.
Figure 6.4 Minimum Clearances for Termination
ered) air supply inlet
= AREA WHERE TERMINAL IS NOT PERMITTED
J** = 7 ft. ......................... clearance above paved
(See Note 1)
sidewalk or a paved driveway
located on public property
K = 6 inches................. clearance from sides of electri-
(See Note 5)
cal service
L = 12 inches................ clearance above electrical
(See Note 5)
service
Covered Alcove Applications
M*** = 18 inches .............clearance under veranda, porch,
42 inches .........vinyl
N = 6 inches ........... non-vinyl sidewalls
12 inches ......... vinyl sidewalls
O = 18 inches ......... non-vinyl soffi t and overhang
42 inches ......... vinyl soffi t and overhang
P = 8 ft.
1 cap3 feet 2 x Q
2 caps6 feet 1 x Q
3 caps9 feet2/3 x Q
4 caps12 feet1/2 x Q
Q
= # termination caps x 3 R
MIN
Note 3: Local codes or regulations may require different
clearances.
Note 4: Termination caps may be hot. Consider their proximity to
doors or other traffi c areas.Note 5: Location of the vent termination must not interfere with
access to the electrical service.
In the U.S and Canada: Vent system termination is NOT permitted
in screened porches.
Vent system termination is permitted in porch areas with two or more
sides open. You must follow all side walls, overhang and ground
clearances as stated in the instructions.
Heat & Glo assumes no responsibility for the improper performance
of the appliance when the venting system does not meet these
requirements.
deck, balcony or overhang
Q
MIN
= (2 / # termination caps) x Q
MAX
R
MAX
ACTUAL
ACTUAL
ACTUAL
ACTUAL
ACTUAL
CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED.
WARNING! Risk of Fire! Installation of this appliance
may require the use of heat shield 385-920 above the
fi rst 900 elbow in the venting system.
CORRECT INCORRECT
COMBUSTIBLE SURFACE
DIRECTION
UP
To Install the Heat Shield:
1. The heat shield is required above the fi rst elbow if the
clearance to combustible surface above is between three
(3) and four (4) inches. A shield is not required for clearances greater than four inches. See Figure 6.5.
COMBUSTIBLE
SURFACE
(Required for clearances
between 3 and 4 inches.)
HEAT
SHIELD
3 in. MIN
(76 mm)
HEAT SHIELD
90º ELBOW
Figure 6.6
• If the combustible materials are not in place at the
time of install the elbow heat shield may be screwed
to the exhaust pipe (see Figure 6.7). Cut the tabs as
shown and bend down. Secure the heat shield to the
pipe maintaining 3 inch to 4 inch between the pipe and
shield.
SCREW
3 in.
(76 mm)
Figure 6.5
2. Fasten the shield in place using the four pilot holes
provided in the part. The shield should be oriented such
that the 13-1/8 inch dimension (longest dimension) is
running in the same direction the elbow is pointing. The
shield should be centered directly above the elbow, and
positioned so that it creates a 1/2 inch airspace between
the shield and the combustible surface. See Figure 6.6.
Figure 6.7
Refer to Cinch Pipe and Termination Cap installation instructions.
• Continue adding vent components, locking each succeeding component into place.
• Ensure that each succeeding vent component is securely
fi tted and locked into the preceding component in the
vent system.
• 90º elbows may be installed and rotated to any point
around the preceding component’s vertical axis. If an
elbow does not end up in a locked position with the
preceding component, attach with a minimum of two (2)
sheet metal screws.
C. Install Support Brackets
Refer to cinch pipe and termination cap installation instructions.
This appliance is approved for use with Hearth & Home
Technologies a DVP venting system. Refer to Section
16B for vent component information.
DO NOT mix pipe, fi ttings or joining methods from differ-
ent manufacturers.
The pipe is tested to be run inside an enclosed wall.
There is no requirement for inspection openings at each
joint within the wall.
WARNING! Risk of Fire or Asphyxiation. This appliance requires a separate vent. DO NOT vent to a pipe
serving a separate solid fuel burning appliance.
Vertical
12 in.
8-1/2 in.
8-1/2 in.
B. Vent Table Key
The abbreviations listed in this vent table key are used in
the vent diagrams.
SymbolDescription
First section (closest to appliance) of vertical length
V
1
Second section of vertical length
V
2
First section (closest to appliance) of horizontal length
H
1
Subsequent sections of horizontal length
H
2
C. Use of Elbows
Diagonal runs have both vertical and horizontal vent aspects when calculating the effects. Use the rise for the
vertical aspect and the run for the horizontal aspect (see
Figure 7.1).
Two 45º elbows may be used in place of one 90º elbow.
On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216
mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A
length of straight pipe is allowed between two 45º elbows
(see Figure 7.1).
Horizontal
Figure 7.1
D. Measuring Standards
Vertical and horizontal measurements listed in the vent
diagrams were made using the following standards.
• Pipe measurements are shown using the effective length
of pipe (see Figure 7.2).
• Horizontal terminations are measured to the outside
mounting surface (fl ange of termination cap) (see Figure
6.1).
• Vertical terminations are measured to bottom of
termination cap.
• Horizontal pipe installed level with no rise.
Effective Length
InchesMillimeters
Effective
Height/Length
Pipe
DVP44102
DVP66152
DVP1212305
DVP2424610
DVP3636914
DVP48481219
DVP6A3 to 676 to 152
DVP12A 3 to 12 76 to 305
DVP12MI 3 to 12 76 to 305
DVP24MI 3 to 24 76 to 610
To replace the fi rst starter elbow with two 45° elbows,
refer to Figure 7.3. All other 90° elbows can be replaced
with two 45° elbows.
General Rules:
• A maximum of three 90° elbows (or six 45° elbows) may
be used in any vent confi guration. Some elbows may be
installed horizontally. See Figure 7.6.
• Elbows may be placed back to back anywhere in the
system as long as the fi rst 90° elbow is a starter elbow
except as shown in Figure 7.3.
• When penetrating a combustible wall, a wall shield
fi restop must be installed.
• When penetrating a combustible ceiling, a ceiling fi restop
must be installed.
• Horizontal runs of vent do not require vertical rise;
horizontal runs may be level.
Note: The Multi-Sided series fi replaces can adapt
to SLP series vent pipe, if desired.
When venting off the top of the unit, attach a DVP-2SL adapter to
the appliance starting collar, immediately followed by a minimum
48 inch vertical section of SLP series vent pipe.
After the 48 inch vertical section, the venting table rules
must be followed. The fi rst 48 inch vertical section is NOT
counted as part of the vertical components in the table. It is
still counted as part of the overall maximum run. All venting
table rules for the vent run must still be followed.
Example:
SLP pipe 7 ft. min. vertical = 11 ft. max. horizontal
DVP pipe 3 ft. min. vertical = 11 ft. max. horizontal
Top Vent—Horizontal Termination—Two 45° Elbows
Installation requirements to replace the fi rst 90° elbow with two 45° elbows:
4 ft min.
(1.22 m)
16 ft max.
(4.87 m)
Note: Reference Figure 7.14 for
special instructions for use of 45º
elbow on rear vent appliances.
Figure 7.3 Minimum Installation Requirements for Two 45° Elbows-Top Vent-Horizontal Termination
termination off the top of the appliance, the optional vertical termination baffl e should be used.
V
1
Exhaust restrictor Instructions
1. Remove refractory panel and exhaust baffl e from pilot
side of appliance. Use a 1/4 inch nut driver and remove
the two screws that secure it in place. To remove the
exhaust baffl e, remove the three screws securing the
refractory panel in place. See Figure 7.8.
Refractory Panel
To access the
exhaust opening,
remove the refractory
panel and exhaust baffle.
To remove refractory
panel, remove the two
screws on top. To remove
the exhaust baffle, remove
the three screws securing it.
Figure 7.7
Exhaust restrictors are recommended for these vertically terminated products which have excessive draft.
Exhaust restrictors will compensate for high draft, and
restore visual fl ame height. If the vent confi guration has
a total vertical of 15-60 feet, an exhaust restrictor may
be needed. The exhaust restrictor can be located in the
appliance manual bag.
Top Vent Application
Exhaust restrictor
Note:Besuretoreinstall the exhaust
baffle and refractory
panel after exhaust
restrictor installation.
Rear Vent Application
Exhaust restrictor
Note: Be sure to reinstall the e x h a u s t
baffle and refractory
panel after exhaust
restrictor installation.
2. Break the exhaust restrictor into two pieces. Do this
by bending the part back and forth until it breaks (see
Figure 7.9).
BREAK
HERE
4. Center the exhaust restrictor in the open end of the exhaust outlet and secure through the slots on the exhaust
restrictor with the 2-1/4 in. self tapping screws provided
in the appliance manual bag.
5. Reinstall the refractory panel.
1 2 3 4 5
SETTINGS
Figure 7.9 Exhaust Restrictor
3. Match the amount of vertical you have in the system
with the chart to fi nd the appropriate position to set the
exhaust restrictor (see Figure 7.10).
Vertical
4 ft.1-1
8 ft.2-21-21-1
15 ft.3-33-22-21-2
20 ft.3-43-33-32-3
25 ft.3-43-33-32-3
30 ft.4-43-43-43-3
35 ft.4-43-43-43-3
40 ft.5-44-44-43-4
TOP VENTREAR VENT
NGLPNGLP
No
RestrictorNoRestrictorNoRestrictor
No
Restrictor
1 2 3 4 5
Figure 7.10
45 ft.5-44-44-43-4
50 ft.5-55-45-44-4
55 ft.5-55-45-44-4
Note: If the DVP-2SL adapter and SLP pipe is used, you
MUST subtract one number from the table above.
Example: Top vent 40 ft vertical with DVP pipe = 5-4
WARNING! Risk of Fire! Maintain air space clearance to
vent. DO NOT pack insulation or other combustibles:
• Between ceiling fi restops
• Between wall shield fi restops
• Around vent system
Failure to keep insulation or other material away from
vent pipe may cause over heating and fi re.
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).
• DVP heat shield - designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184
mm) thick.
• If wall thickness is less than 4 in. the existing heat shields must be field trimmed. If
wall thickness is greater than 7-1/4 in. a DVP-HSM-B will be required.
• SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8 in. (111 mm to
194 mm thick).
• If wall thickness is less than 4-3/8 the existing heat shields must be field trimmed.
If wall thickness is greater than 7-5/8 in. a DVP-HSM-B will be required.
(DVP-SLP Pipe Shown)
3 in. (76 mm)
top clearance
1 in. (25 mm)
clearance around
vertical sections
Heat
Shield
Wall
Shield
Firestop
3 in. (76 mm)
top clearance *
Heat
Shield
1 in. (25 mm)
clearance
bottom & sides
B. Wall Penetration Framing
Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must
frame a hole for the wall shield fi restop(s). The wall shield fi restop maintains minimum clearances and prevents cold
air infi ltration.
• The opening must be framed on all four sides using the
same size framing materials as those used in the wall
construction.
• SLP pipe - A wall shield fi restop must be placed on each
side of an interior wall. A minimum 1-1/2 in. (38 mm)
overlap of attached heat shields must be maintained.
• DVP pipe - A wall shield fi restop is required on one side
only on interior walls. If your local inspector requires a
wall shield fi restop on both sides, then both wall shield fi restops must have a heat shield (refer to Section 16.B.)
attached to them.
• See Section 8.M. for information for regarding the installation of a horizontal termination cap.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncombustible materials such as concrete, a hole with diameter
one in. greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall
shield fi restop is only required on one side and no heat
shield is necessary.
WALL
WALL
3 in. (76 mm)
top clearance *
Heat
Shield
1 in. (25 mm)
clearance
bottom & sides
Heat
Shield
Wall
Shield
Firestop
* When using SLP pipe, minimum clearances from the vent pipe to combustible materi-
als at wall shield firestops are: T op: 2-1/2 in. (64 mm)
Bottom: 1/2 in. (13 mm)
Sides: 1 in. (25 mm)
Figure 8.1 Horizontal Venting Clearances To Combustible
Materials
10 in.
10 in.
A*
B*
A* B*CD
43-3/4 in. 28 in.42-3/4 in.27 in.
* Shows center of vent framing hole for top or rear venting. The center of the
hole is one (1) inch (25.4 mm) above the center of the horizontal vent pipe.
Figure 8.2 Wall Penetration
12 in.
12 in.
D
C
Note: When venting off the top of the unit using SLP pipe, a
10 in. x 10 in. framing hole is required.
A ceiling fi restop MUST be used between
fl oors and attics.
• DVP pipe only - Frame an opening 10 in.
by 10 in. (254 mm by 254 mm) whenever
the vent penetrates a ceiling/fl oor (see
Figure 8.3).
• SLP pipe only - Frame opening 9 in. x 9
in. (229 mm x 229 mm) whenever the vent
penetrates a ceiling/fl oor (see Figure 8.3).
• Frame the area with the same sized lumber
as used in ceiling/fl oor joist.
• The ceiling fi restop may be installed above or
below the ceiling joists when installed with a
attic insulation shield. It must be under joists
between fl oors that are not insulated. Refer
to Figure 8.4.
• Secure with three fasteners on each side.
WARNING! Risk of Fire! DO NOT pack insu-
lation around the vent. Insulation must be kept
back from the pipe to prevent overheating.
WARNING! Fire Risk. DO NOT allow loose materials or
insulation to touch vent. Hearth & Home Technologies
Inc. requires the use of an attic shield.
The National Fuel Gas Code ANSI Z223.1 and NFPA 54
requires an attic shield constructed of 26 gauge minimum
metal that extends at least 2 in. (51 mm) above insulation.
Attic shields must meet specifi ed clearance and be se-
cured in place.
Flat Ceiling Installation
• Remove one shield from box.
NOTICE: Cut previously installed batt insulation to make
room for the attic insulation shield.
• Wrap shield around pipe if pipe is already installed in
area to be insulated.
• Match the three holes in each side and fasten with three
screws to form a tube.
• Bend three tabs on the bottom of the shield outward to
allow attachment to the ceiling fi restop.
• Bend the remaining bottom tabs inward 90° to maintain
the air space between the pipe and the shield. Set the
shield on the ceiling fi restop and attach to the fi restop.
• Bend all tabs inward 90° around the top of the shield.
These tabs must be used to prevent blown insulation
from getting between the shield and vent pipe, and to
maintain air space clearance.
BEND ALL TABS INWARD 90°
TO MAINTAIN CLEARANCE
AND PREVENT INSULATION
FROM FALLING INSIDE
INSERT 3
SCREWS
Figure 8.5 Attic Insulation Shield
LASER-ETCHED
CUT LINES
BEND 3 TABS
OUTWARD TO
FASTEN TO CEILING
FIRESTOP-BEND
REMAINING TABS
INWARD 90 DEGREES
TO MAINTAIN
CLEARANCE
Vaulted Ceiling Installation
• The attic insulation shield has been laser-etched with cut
lines and ceiling pitches to make fi eld trimming easier.
• Remove one shield from box.
NOTICE: Cut previously installed batt insulation to make
room for the attic insulation shield.
• Cut the attic insulation shield (if application is for vaulted
ceiling) using a laser-etched cut line, to fi t your ceiling
pitch. Snip cut edge to recreate 1 in. bend tabs all the
way around the bottom.
• Wrap shield around pipe if pipe is already installed in
area to be insulated.
• Match the three holes in each side and fasten with three
screws to form a tube.
• Bend three tabs on the bottom of the shield outward to
allow attachment to the ceiling fi restop.
• Bend the remaining bottom tabs inward 90° to maintain
the air space between the pipe and the shield. Set the
shield on the ceiling fi restop and attach to the fi restop.
• Bend all tabs inward 90° around the top of the shield.
These tabs must be used to prevent blown insulation
from getting between the shield and vent pipe, and to
maintain air space clearance.
CAUTION! Risk of Cuts, Abrasions or Flying Debris.
Wear protective gloves and safety glasses during installation. Sheet metal edges are sharp.
NOTICE: Once appliance is set up for top or rear venting,
it CANNOT be changed at a later time.
Figure 9.1 Remove the elbow heat shield by removing
the four screws holding it to the top of the appliance. Refer to Section 6B to determine if the elbow heat shield is
required.
NOTICE: Once the vent cap has been removed it CANNOT
be reattached.
Figure 9.3 Fold the center parts of the retaining band up
and use to remove the vent cap.
Figure 9.2 Cut the metal retaining band and fold the sides
out.
Figure 9.4 Remove and discard the seal cap, insulation
donut, insulation plug, and the insulation basket. Attach the
fi rst vent section (it will snap into place). Slide the vent
gasket onto the vent section and then, up against the appliance. Secure the vent gasket to the appliance with two
self-tapping screws found in the manual bag. Note: The
vent gasket can found in the manual bag.
Proceed to Section 9. C.
Page 41
B. Rear Vent
NOTICE: Once appliance is set up for top or rear venting,
it CANNOT be changed at a later time.
Figure 9.5 Cut the metal retaining band.
NOTICE: Once the vent cap has been removed it CANNOT
be reattached.
Figure 9.7 Discard the seal cap, insulation plug and the
insulation basket.
Figure 9.8 Attach the fi rst vent section (it will snap into
place). Slide the vent gasket onto the vent section and then,
up against the appliance. Secure the vent gasket to the
appliance with two self-tapping screws found in the manual
bag. Note: The vent gasket can found in the manual bag.
Page 42
C. Securing and Leveling the Appliance
WARNING! Risk of Fire! Prevent contact with:
• Sagging or loose insulation
• Insulation backing or plastic
• Framing and other combustible materials
Block openings into the chase to prevent entry of blown-
in insulation. Make sure insulation and other materials
are secured.
DO NOT notch the framing around the appliance
standoffs.
Failure to maintain air space clearance may cause
overheating and fi re.
NOTICE: Failure to ensure that the fi replace opening
is square may result in the decorative front not fi tting
properly.
6. Bend out nailing tabs on each side making sure to keep
the nailing tabs fl ush with the framing.
7. Using a framing square, make sure that the sides of
the appliance are square to the bottom as shown in
Figure 9.10.
The diagram shows how to properly position, level, and
secure the appliance (see Figure 9.9). Nailing tabs are provided to secure the appliance to the framing members.
1. Venting - refer to V ent Clearances and Framing (Section
8) for hole location.
2. When installing a LCOR or RCORfi replace remove
the nailing tab located on the side of the unit and
reattach it to the front corner of the unit as shown in
Figure 9.8 (R-COR).
90º
SID
E TO SIDE
FRONT TO BACK
Figure 9.9 Proper Positioning and Leveling of an Appliance
8. Secure the appliance to the framing by using nails
or screws through the nailing tabs. It is acceptable to
use plumber strap to secure the unit to the framing if
necessary. See Figure 9.10. Be sure to maintain all
clearances to combustible material.
Figure 9.8 Attach Nailing Tab to Front Corner of Unit
3. Place the appliance into position, making sure to
maintain proper clearance to combustibles.
4. Level the appliance from side to side and front to back. It
is acceptable to use wood shims under the appliance.
5. Fasten the appliance to the fl oor using the pilot holes
located at the bottom of the appliance.
Note: Once appliance is setup for top or rear venting, it
CANNOT be changed at a later time.
Page 43
10
10
Lances
Installing Vent Pipe (DVP and SLP Pipe)
A. Assemble Vent Sections (DVP Pipe Only)
Attach Vent to the Firebox Assembly
Note: The end of the pipe sections with the lanced tabs will face
toward the appliance.
Attach the fi rst pipe section to the starting collar:
• Lanced pipe end to the starting collar
• Inner pipe over inner collar
• Push the pipe section until all lanced tabs snap in place
• Lightly tug on pipe to confi rm it has locked.
Commercial, Multi-family (Multi-level exceeding two stories), or High-Rise Applications
All outer pipe joints must be sealed with high temperature
silicone, including the slip section that connects directly to
the horizontal termination cap.
• Apply a bead of silicone sealant inside the female outer
pipe joint prior to joining sections. See Figure 10.1
• Only outer pipes need to be sealed. All unit collar, pipe,
slip section, elbow and cap outer fl ues shall be sealed
in this manner, unless otherwise stated.
Figure 10.1 High Temperature Silicone Sealant
A
Lances
WARNING! Risk of Fire or Explosion! DO NOT break
silicone seals on slip sections. Use care when removing termination cap from slip pipe. If slip section seals
are broken during removal of the termination cap, vent
may leak.
Assemble Pipe Sections (DVP Pipe Only)
Per Figure 10.2:
• Start the inner pipe on the lanced end of section A into
the fl ared end of section B.
• Start the outer pipe of section A over the outer pipe of
section B.
• Once both vents sections are started, push fi rmly until
all lanced tabs lock into place.
• Lightly tug on the pipe to confi rm the tabs have locked.
It is acceptable to use screws no longer than 1/2 in. (13
mm) to hold outer pipe sections together. If predrilling holes,
DO NOT penetrate inner pipe.
For 90° and 45° elbows that are changing the vent direction
from horizontal to vertical, one screw minimum should be
put in the outer fl ue at the horizontal elbow joint to prevent
the elbow from rotating. Use screws no longer than 1/2
in. (13 mm). If predrilling screw holes, DO NOT penetrate
inner pipe.
B
Figure 10.2
Note: Make sure that the seams are not aligned to prevent
To attach the fi rst vent component to the starting collars
of the appliance:
• Attach an SLP-DVP24 adapter to the starting collar of
the appliance.
• Lock the vent components into place by sliding the pipe
section onto the collar.
• Align the seam of the pipe and seam of collar to allow
engagement. Rotate the vent component to lock into
place. Use this procedure for all vent components. See
Figure 10.5.
• Slide the gasket over the fi rst vent section and place it
fl ush to the appliance. This will prevent cold air infi ltration.
High temperature caulk may be used to hold the part in
place.
• Continue adding vent components, locking each
succeeding component into place.
• Ensure that each succeeding vent component is securely
fi tted and locked into the preceding component.
Commercial, Multi-family (Multi-level exceeding two stories), or High-Rise Applications
For Installation into a commercial, multi-family (multi-level
exceeding two stories) or high-rise applications: All outer
pipe joints must be sealed with high temperature silicone,
including the slip section that connects directly to the horizontal termination cap.
• Apply a bead of silicone sealant inside the female outer
pipe joint prior to joining sections. See Figure 10.1.
• Only outer pipes need to be sealed. All unit collar, pipe,
slip section, elbow and cap outer fl ues shall be sealed
in this manner, unless otherwise stated.
C. Assemble Slip Sections
• Slide the inner fl ue of the slip section into the inner fl ue of
the pipe section and the outer fl ue of the slip section over
the outer fl ue of the pipe section. See Figure 10.6.
• Slide together to the desired length.
Pilot hole
Figure 10.6 Slip Section Pilot Holes
• Maintain a 1-1/2 in. (38 mm) overlap between the slip
section and the pipe section.
• Secure the pipe and slip section with two screws no
longer than 1/2 in. (13 mm), using the pilot holes in the
slip section. See Figure 10.7.
WARNING! Risk of Fire or Explosion! DO NOT break
silicone seals on slip sections. Use care when removing termination cap from slip pipe. If slip section seals
are broken during removal of the termination cap, vent
may leak.
Note: Align seams to engage pipe,
then rotate counterclockwise to lock
Figure 10.5 Adding Venting Components
Figure 10.7 Screws into Slip Section
• Continue adding pipe as necessary following instructions
in “Assembling Pipe Sections.”
NOTICE: If slip section is too long, the inner and outer fl ues
of the slip section can be cut to the desired length.
NOTICE: When installing a vent system with an HRC
termination cap, all pipe system joints shall be sealed using
a high temperature silicone sealant.
• Apply a bead of silicone sealant inside the female outer
pipe joint prior to joining sections.
• Only outer pipes are sealed, sealing the inner fl ue is not
required.
• All unit collar, pipe, slip section, elbow and cap outer
fl ues shall be sealed.
• Vertical runs of DVP pipe must be supported every 8 ft.
(2.44 m) after the 25 ft. (7.62 m) maximum unsupported
rise.
• Vertical runs of SLP pipe must be supported every 8 ft.
(2.44 m).
• Horizontal sections must be supported every 5 feet
(1.52 m).
• Vent supports or plumbers strap (spaced 120º apart)
may be used to support. See Figures 10.8 and 10.9.
• Wall shield fi restops may be used to provide horizontal
support.
• SLP ceiling fi restops have tabs that may be used to
provide vertical support.
WARNING! Risk of Fire, Explosion or Asphyxiation!
Improper support may allow vent to sag and separate.
Use vent run supports and connect vent sections per installation instructions. DO NOT allow vent to sag below
connection point to appliance.
E. Disassemble Vent Sections
• Rotate either section (see Figure 10.10) so the seams
on both pipe sections are aligned as shown in Figure
A decorative ceiling thimble can be installed on a fl at ceil-
ing through which the vent passes. The decorative ceiling
thimble is used to cover the fi restop.
• Seal the gap between the vent pipe and fi restop using
high temperature silicone to prevent cold air infi ltration.
• Install the decorative ceiling thimble by sliding it up to
the ceiling and attaching it using the provided screws.
A decorative cathedral ceiling support box can be installed
on a cathedral ceiling through which the vent passes.
• Use a plumb-bob to mark the center line of the venting
system on the ceiling and drill a small hole through the
ceiling and roof at this point. Locate the hole and mark
the outline of the cathedral ceiling support box on the
outside roof.
• Remove shingles or other roof covering as necessary
to cut the rectangular hole for the support box. Cut the
hole 1/8 in. (3 mm) larger than the support box outline.
• Lower the support box through the hole in the roof until its
bottom is at least 2 in. (51 mm) below the ceiling (Figure
10.12).
• Level the support box both vertically and horizontally and
temporarily tack it in place through the inside walls into
the roof sheathing.
• Use tin snips to cut the support box from the top corners
down to the roof line and fold the resulting fl aps to the
roof. See Figure 10.13.
• Nail the fl aps to the roof AFTER running a bead of non
hardening sealant between the fl aps and the roof.
WARNING! Risk of Fire! Clean out ALL materials from
inside the support box and complete the vertical vent run
and termination.
LEVEL
CATHEDRAL CEILING
SUPPORT BOX
2 in. (51 mm) MIN. BELOW
FINISHED CEILING
CUT HOLE 1/8 in. (3 mm)
GREATER IN SIZE THAN
PATTERN OF SUPPORT
BOX AS IT IS PROJECTED
ONTO ROOF LINE
Figure 10.17 Assembling the Storm Collar Around the Pipe
Figure 10.15
Note: Skip this section if using the RF4-8.
• See minimum vent heights for various pitched roofs
(Figure 10.14) to determine the length of pipe to extend
through the roof.
• Slide the roof fl ashing over the pipe sections extending
through the roof as shown in Figure 10.15.
HORIZONTAL
OVERHANG
CAULK
2 FT.
MIN.
GAS DIRECT VENT
TERMINATION CAP
Roof Pitch H (Min.) Ft.
Flat to 6/12........................................1.0*
Over 6/12 to 7/12 ............................1.25*
Over 7/12 to 8/12 ..............................1.5*
Over 8/12 to 9/12 ..............................2.0*
Over 9/12 to 10/12 ............................. 2.5
Over 10/12 to 11/12 ......................... 3.25
Over 11/12 to 12/12 ........................... 4.0
Over 12/12 to 14/12 ........................... 5.0
Over 14/12 to 16/12 ........................... 6.0
Over 16/12 to 18/12 ........................... 7.0
Over 18/12 to 20/12 ........................... 7.5
Over 20/12 to 21/12 ........................... 8.0
20 INCHES MIN.
LOWEST
DISCHARGE
OPENING
X
12
ROOF PITCH
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
* 3 foot minimum in snow regions
VERTICAL
WALL
IS X/ 12
Figure 10.15
H. Assemble and Install Storm Collar
CAUTION! Risk of Cuts, Abrasions or Flying Debris.
Wear protective gloves and safety glasses during installation. Sheet metal edges are sharp.
• Connect both halves of the storm collar with two screws
(see Figure 10.16).
• Wrap the storm collar around the exposed pipe section
closest to the roof and align brackets. Insert a bolt
(provided) through the brackets and tighten the nut to
complete the storm collar assembly . Make sure the collar
is tight against the pipe section.
• Slide the assembled storm collar down the pipe section
until it rests on the roof fl ashing (see Figure 10.17).
• Caulk around the top of the storm collar (see Figure 10.23).
Figure 10.14 Minimum Height From Roof To Lowest Discharge
Opening
NOTICE: Failure to properly caulk the roof fl ashing could
cause water entry.
• Caulk the gap between the roof fl ashing and the outside
diameter of the pipe.
• Caulk the perimeter of the fl ashing where it contacts the
roof surface. See Figure 10.15.
Figure 10.17 Assembling the Storm Collar Around the Pipe
Page 48
I. Install RF4-8
The RF4-8 may be used in place of the roof fl ashing and
storm collar (Sections 10.G. and 10.H.)
Pipe must be supported within 12 inches of the roofline
using plumbers strapping or an SLP-FS when using
the RF4-8 Flashing. Refer to Section 8.D. Secure Vent
Sections.
SECURE WITH 4
SCREWS NO LONGER
THAN 1 IN. (25 MM)
SLP-FS
Figure 10.18 Secure Pipe with SLP-FS
Figure 10.20 Apply Sealant
• Trim the rubber boot (using scissors or a utility knife),
cutting along the marked measurement lines. See Figure
10.19. Use the 150 mm line for SLP, 210 mm for DVP.
• Lubricate pipe or fl ue with water and slide the fl ashing
down. It may be necessary to trim the top shingles around
the base of the rubber boot to ensure a good fi t.
• Draw around fl ashing, remove.
• Apply silicone sealant to roof inside the lines (Figure 10.20)
• Lubricate pipe or fl ue with water and slide fl ashing down.
Seat fi rmly in sealant. Nail roof fl ashing to the roof.
• Apply silicone sealant on the top outside of the base plate
on the sides and on top edge. See Figure 10.21. Install
shingles, Apply sealant at the top edge of the rubber
boot. See Figure 10.22.
• We recommend that you top coat with conventional
acrylic house paint to improve the appearance of your
galvanized base fl ashing.
• Attach the vertical termination cap by sliding the inner
collar of the cap into the inner fl ue of the pipe section
while placing the outer collar of the cap over the outer
fl ue of the pipe section.
• Secure the cap by driving three self-tapping screws
(supplied) through the pilot holes in the outer collar of the
cap into the outer fl ue of the pipe (see Figure 10.23).
TERMINATION CAP
(1 of 3)
STORM
COLLAR
SCREWS
CAULK
Figure 10.23
K. Install Decorative Wall Components (SLP
only)
A decorative wall thimble can be installed on wall through
which the vent passes. The decorative wall thimble is used
to cover the wall shield fi restop.
• Slide the decorative wall thimble over the last section of
horizontal pipe before connecting the termination cap to
the pipe.
• Once the pipe section and the termination cap have been
connected, slide the wall thimble up to the interior wall
surface and attach with screws provided. See Figure
10.24.
L. Heat Shield Requirements for Horizontal
Termination
WARNING! Risk of Fire! To prevent overheating and fi re,
heat shields must extend through the entire wall thickness.
• DO NOT remove the heat shields attached to the
wall shield fi restop and the horizontal termination cap
(shown in Figure 10.25).
• Heat shields must overlap 1-1/2 in. (38 mm) minimum.
There are two sections of the heat shield. One section
is factory-attached to the wall shield fi restop. The other
section is factory-attached to the cap. See Figure 10.25.
If the wall thickness does not allow the required 1-1/2 in.
(38 mm) heat shield overlap when installed, an extended
heat shield must be used.
• If the wall thickness is less than 4 in./102 mm (DVP)
or 4-3/8 in./ 111 mm (SLP), the heat shields on the cap
and wall shield fi restop must to be trimmed. A minimum
1-1/2 in. (38 mm) overlap MUST be maintained.
• Use an extended heat shield if the fi nished wall thickness
is greater than 7-1/4 in. (184 mm).
• The extended heat shield may need to be cut to length
maintaining suffi cient length for a 1-1/2 in. (38 mm)
overlap between heat shields.
• Attach the extended heat shield to either of the existing
heat shields using the screws supplied with the extended
heat shield. Refer to vent components diagrams in the
back of this manual.
• Rest the small leg on the extended heat shield on top
of the pipe section to properly space it from the pipe
section.
Important Notice: Heat shields may not be fi eld constructed.
WARNING! Risk of Fire! The telescoping fl ue section of
the termination cap MUST be used when connecting vent.
• 1-1/2 (38 mm) minimum overlap of fl ue telescoping
section is required.
Failure to maintain overlap may cause overheating and
fi re.
• Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
• Flash and seal as appropriate for siding material at
outside edges of cap.
• When installing a horizontal termination cap, follow
the cap location guidelines as prescribed by current
ANSI Z223.1 and CAN/CGA-B149 installation codes
and refer to Section 6 of this manual.
CAUTION! Risk of Burns! Local codes may require installation of a cap shield to prevent anything or anyone
from touching the hot cap.
NOTICE: For certain exposures which require superior
resistance to wind-driven rain penetration, a fl ashing kit and
HRC caps are available. When penetrating a brick wall, a
brick extension kit is available for framing the brick.
Note: When using termination caps with factory-supplied
heat shield attached, no additional wall shield fi restop is
required on the exterior side of a combustible wall.
HEAT SHIELD OR
EXTENDED
WALL SHIELD
FIRESTOP
INNER VENT
OUTER VENT
VENT DEPTH FROM BACK OF APPLIANCE TO
OUTSIDE SURFACE OF EXTERIOR WALL
(SEE CHART BELOW)
Figure 10.25 Venting through the wall
HEAT SHIELD
SLIP SECTION
CAN BE EXTENDED
INTERIOR
Cap Specifi cation Chart
(depth without using additional pipe sections)
DVP-TRAPK1
Top Vent
Depth
2-7/8 in to
36 inch
Multisided
Series
DVP-TRAP1 can adjust 1-1/2 in. (3-1/8 to 4-5/8 in.)
DVP-TRAP2 can adjust 4 in. (5-3/8 to 9-3/8)
DVP-HPC1 can adjust 2-1/8 in. (4-1/4 to 6-3/8)
DVP-HPC2 can adjust 4-1/8 in. (6-3/8 to 10-1/2)
• Gas line sizing requirements will be determined in ANSI
Z223.1 National Fuel Gas Code in the USA and CAN/
CGA B149 in Canada.
• Pressure requirements are:
Gas PressureNatural GasPropane
Minimum inlet pressure5.0 in. w.c.11.0 in. w.c.
Maximum inlet pressure14.0 in. w.c.14.0 in. w.c.
Manifold pressure3.5 in. w.c.10.0 in. w.c.
WARNING! Risk of Fire/Explosion! High pressure will
damage valve. Low pressure may cause explosion.
• Verify inlet pressures. Verify minimum pressures when
other household gas appliances are operating.
• Install regulator upstream of valve if line pressure is
greater than 1/2 psig.
WARNING
Fire Risk.
Explosion Hazard.
High pressure will damage valve.
• Disconnect gas supply piping BEFORE
pressure testing gas line at test pressures
above 1/2 psig.
• Close the manual shutoff valve BEFORE
pressure testing gas line at test pressures
equal to or less than 1/2 psig.
Note: Have the gas supply line installed in accordance with
local codes, if any. If not, follow ANSI 223.1. Installation
should be done by a qualifi ed installer approved and/or
licensed as required by the locality. (In the Commonwealth
of Massachusetts installation must be performed by a
licensed plumber or gas fi tter).
Note: A listed (and Commonwealth of Massachusetts approved) 1/2 in. (13 mm) T-handle manual shut-off valve
and fl exible gas connector are connected to the 1/2 inch
(13 mm) control valve inlet.
• If substituting for these components, please consult
local codes for compliance.
C. Gas Connection
• Refer to Reference Section 16 for location of gas line
access in appliance.
• Gas line may be run through knockout(s) provided.
• The gap between supply piping and gas ac cess hole
may be caulked with high temperature caulk or stuf fe d
with non-combustible, unfaced insulation to prev ent cold
air infi ltration.
• Ensure that gas line does not come in contact with outer
wrap of the appliance. Follow local codes.
• Pipe incoming gas line into valve compartment.
• Connect incoming gas line to the 1/2 in. (13 mm)
connection on manual shutoff valve.
WARNING! Risk of Fire or Explosion! Support control
when attaching pipe to prevent bending gas line.
• A small amount of air will be in the gas supply lines.
WARNING! Risk of Fire or Explosion! Gas build-up dur ing line purge could ignite.
• Purge should be performed by qualified service
technician.
• Ensure adequate ventilation.
• Ensure there are no ignition sources such as sparks
or open fl ames.
Light the appliance. It will take a short time for air to purge
from lines. When purging is complete the appliance will
light and operate normally.
WARNING! Risk of Fire, Explosion or Asphyxiation!
Check all fi ttings and connections with a non-corrosive
commercially available leak-check solution. DO NOT use
open fl ame. Fittings and connections could have loos-
ened during shipping and handling.
WARNING! Risk of Fire! DO NOT change valve settings.
This valve has been preset at the factory.
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced,
these rules do not apply. Check with your local gas utility
or authorities having jurisdiction.
When installing above 2000 feet elevation:
• In the USA: Reduce burner orifi ce 4% for each 1000 feet
above 2000 feet.
• In the CANADA: Reduce burner orifi ce 10% for elevations
between 2000 feet and 4500 feet. Above 4500 feet,
consult local gas utility.
NOTICE: This appliance must be electrically wired
and grounded in accordance with local codes or, in the
absence of local codes, with National Electric Code
ANSI/NFPA 70-latest edition or the Canadian Electric
Code CSA C22.1.
• Wire the appliance junction box to 110-120 VAC. This is
required for use of optional accessories (standing pilot
ignition) or proper operation of the appliance (Intellifi re
ignition).
• A 110-120 VAC circuit for this product must be protected
with ground-fault circuit-interrupter protection, in
compliance with the applicable electrical codes, when it is
installed in locations such as in bathrooms or near sinks.
• Low voltage and 110 VAC voltage cannot be shared
within the same wall box.
WARNING! Risk of Shock or Explosion! DO NOT wire
1 10V to the valve or to the appliance wall switch. Incorrect
wiring will damage controls.
C. Optional Accessories Requirements
• This appliance may be used with a wall switch, wall
mounted thermostat and/or a remote control.
Wiring for optional Hearth & Home T echnologies approved
accessories should be done now to avoid reconstruction.
Follow instructions that come with those accessories.
D. Electrical Service and Repair
WARNING! Risk of Shock! Label all wires prior to disconnection when servicing controls. Wiring errors can
cause improper and dangerous operation. Verify proper
operation after servicing.
WARNING! Risk of Shock! Replace damaged wire with
type 105° C rated wire. Wire must have high temperature
insulation.
B. Intellifi re Ignition System Wiring
• Wire the appliance junction box to 110 VAC for proper
operation of the appliance.
WARNING! Risk of Shock or Explosion! DO NOT wire
IPI controlled appliance junction box to a switched circuit.
Incorrect wiring will override IPI safety lockout.
• Refer to Figure 12.2, Intellifi re Pilot Ignition (IPI) Wiring
Diagram.
• This appliance is equipped with an Intellifi re control valve
which operates on a 3 volt system.
• Plug the 3-volt AC transformer into the appliance junction
box to supply power to the unit OR install two D cell
batteries (not included) into the battery pack before use.
NOTICE: Batteries should not be placed in the battery
pack while using the transformer. Remove batteries before
using the transformer, and unplug the transformer before
installing the batteries. Battery polarity must be correct or
module damage will occur.
The junction box must be wired from the INSIDE of the
appliance:
• Determine which side of the appliance the junction box
is located on.
• Pull the electrical wires from outside the appliance through
the knockout making sure to use a Romex connector to
fasten the electrical wires to the unit.
• Pull enough wire into the valve compartment to easily reach
the junction box location.
• Remove the screw attaching the junction box to the junction
box bracket and set it aside.
• Route the wire through the knockout in the junction box
bracket.
• Wire the junction box and reattach it to the bracket by
inserting the tab in the slot and attaching with screw
previously removed. Ensure that a Romex connector is
used to attach the electrical wires to the junction box.
ROMEX CONNECTORS
Figure 12.4 Junction Box Detail
NOTICE: DO NOT wire
110 VAC to wall switch.
F. Wall Switch Installation for Fan (Optional)
If the box is being wired to a wall mounted switch for use
with a fan (See Figure 12.5):
• The power supply for the appliance must be brought into
a switch box.
• The power can then be supplied from the switch box to
the appliance using a minimum of 14-3 with ground wire.
• At the switch box connect the black (hot) wire and red
(switch leg) wire to the wall switch as shown.
• At the appliance connect the black (hot), white (neutral)
and green (ground) wires to the junction box as shown.
• Add a 1/4 in. insulated female connector to the red (switch
leg) wire, route it through the knockout in the face of the
junction box, and connect to the top fan switch connector
(1/4 in. male) as shown.
The splatter guard is a piece of corrugated material used
to protect the appliance during the installation process before fi nishing work on the whole hearth is complete.
Splatter guards must be removed before appliance is
fi red.
WARNING
Risk of Fire
• Splatter guard must be removed before lighting
appliance.
• Before splatter guard is installed:
Close ball valve to prevent accidental lighting.
Step 1. Turn off gas to valve. Red gas shutoff knob is
located on ball valve. Disconnect the 3 volt transformer
from the junction box. See Figure 13.1.
Figure 13.1 Preparation to Install Splatter Guard
To install the Splatter Guard:
Step 2. Crease fl ap on top side of splatter guard using the
scored line as the guide. See Figure 13.2.
Figure 13.3 Folding of Right and Left Sides of Splatter Guard
Step 4. Center the splatter guard in front of the unit as
shown in Figure 13.3. Place the splatter guard in the unit
by guiding the top fl ap into proper position and then con-
tinuing to guide the tabs on the side fl aps into the top slot
on the left and right sides of the appliance. The top slot
is indicated in Figure 13.5 Take care not to bend or break
off the tabs.
Figure 13.4 Installation of Splatter Guard
Figure 13.2 Folding Top Flap
Step 3. Crease fl aps on left and right sides of splatter guard
using the scored line as the guide. See Figure 13.2.
Step 5. Fold bottom fl ap along score line as indicated in
Figure 13.6 and tuck into valve access area of appliance.
Splatter guard should fi t securely on front of unit.
Figure 13.6 Folding Bottom Flap
Figure 13.9 Securing Tabs Inside Front of Splatter Guard
Once plumbing and wiring are complete on the fi replace,
the lower access panel may be closed until the time that the
splatter guard must be removed for fi ring the appliance.
Figure 13.7 Prepare to Open Lower Access Panel
Step 6. To open lower access panel of splatter guard,
place one hand above score line and place two fi ngers
from other hand in the round holes on the front of the
splatter guard. See Figure 13.7. Pull out and fold up the
panel as shown in Figure 13.8. Disengage the tabs on
left and right bottom of splatter guard and fi t them into
the square holes. The tabs are now inside the front of
the splatter guard; carefully bend them down. See Figure
13.8.
Figure 13.10 Splatter Guard with Lower Access Panel Open
To Close the Lower Access Panel:
Carefully disengage the tabs from the square holes and
bend the access panel to its original position. Bend the
center bottom fl ap and insert it into the bottom of the ap-
pliance.
Figure 13.11 Splatter Guard with Lower Access Panel Closed
To Remove the Splatter Guard:
Carefully grab splatter guard on or near the vertical center
on the left and right sides. Pull outward gently, but fi rmly,
taking care not to tear or remove the inserted tabs.
Page 57
B. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clearances as specifi ed. Framing closer than the minimums list-
ed must be constructed entirely of noncombustible materials (i.e., steel studs, concrete board, etc.) Failure to comply
could cause fi re.
See-Through Mantel Projection
16
18
17
TO CEILING
25
19
18
32
Note: All
measurements
in inches.
2-1/2
12
11
10
9
8
7
6
5
4
3
11
10
5
15
14
13
12
See-Through Mantel Projection
TO CEILING
Note: All
measurements
in inches.
Figure 13.14 Minimum Vertical and Maximum Horizontal
Dimensions of Non-Combustibles
MAX.
18
12
11
10
9
8
7
1
6
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
4
3
2
6
5
32
MIN.
12
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
Figure 13.12 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles
PIER/LCOR/RCOR Mantel Projection
16
18
17
TO CEILING
18
Note: All
measurements
in inches.
12
11
10
9
8
7
6
5
4
3
1
11
10
5
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
15
14
13
12
19
25
32
PIER/LCOR/RCOR Mantel Projection
TO CEILING
MAX.
Note: All
measurements
in inches.
6
4
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
Figure 13.15 Minimum Vertical and Maximum Horizontal
Dimensions of Non-Combustibles
12
10
9
8
7
7
6
12
10
9
8
32
MIN.
Figure 13.13 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles
Note: Clearance from opening to perpendicular wall.
1/2 in.
Figure 13.16 Combustible Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
C. Facing Material
• Metal front faces may be covered with non-combustible
materials only.
• Facing and/or fi nishing materials must not interfere with
air fl ow through louvers, operation of louvers or doors,
or access for service.
• Facing and/or fi nishing materials must never overhang
into the glass opening.
• Observe all clearances when applying combustible
materials.
• Seal joints between the fi nished wall and appliance top
and sides using a 300 °F minimum sealant. Refer to
Figure 13.17.
WARNING! Risk of Fire! DO NOT apply combustible
materials beyond the minimum clearances. Comply with
all minimum clearances to combustibles as specifi ed in
this manual. Overlapping materials could ignite and will
interfere with proper operation of doors and louvers.
D. Finishing Material
Only doors certifi ed for use with this appliance model may
be used. Contact your dealer for a list of doors that may
be used. Once you have determined what kind of door
and fi nishing material is going to be used on the fi replace,
you may use the table below which shows the door models and the fi nishing material thickness allowed. For an
inside fi t there is an available template to assist with siz-
ing the fi nishing material.
ST-36TRB-IPI
DOORFIT
AeroInsideAny13.18
FolioInsideAny13.18
Arcadia
Halston
Chateau
Valencia
Galleria
Overlap1 inch13.19
InsideAny13.20
Overlap1 inch13.19
Inside1 inch - 2 inch13.21
Overlap1 inch13.19
InsideAny13.20
Overlap1 inch13.19
InsideAny13.20
Overlap1 inch13.19
Inside1 inch - 2 inch13.21
PIER-36TRB-IPI
DOORFIT
AeroInsideAny13.22
ChateauInsideAny13.22
ArcadiaInsideAny13.22
FINISH MATERIAL
MAXIMUM
THICKNESS
FINISH MATERIAL
MAXIMUM
THICKNESS
SEE FIGURE
SEE FIGURE
Finish wall material may be
combustible - Top and Sides
Use the table below to identify the hearth system that will be used. The table will also help identify effects on the various
dimensions. Some hearth systems will elevate the appliance off the fl oor at a given dimension. For example, if appliance
will be used with a Kenwood Cabinet with Base, the appliance will be elevated 9-1/4 inches. The 9-1/4 inch elevation
will also have to be added to the following: Extension Wall Hole referenced in Figure 8.2 (Exterior Wall Hole) and Rough
Opening Height (header height) referenced in Figure 5.2. Note: Finished fl oor thickness should also be considered when
determining installation dimensions.
MODELDESCRIPTIONPART #
KENWOOD CABINET KDC48DBP032-7/8 in.
KENWOOD CABINET W/ BASE KDC48DBP W/ HTKDC48DBP9-1/4 in.32-7/8 in.
KENWOOD CORNER CABINETKDA48SBP032-7/8 in.
KENWOOD CORNER CABINET W/ BASE KDA48SBP W/ HTKDA48SBP9-1/4 in.32-7/8 in.
KENWOOD MANTEL AFKDMPB0 (See Note 3)27-3/8 in.
KENWOOD MANTEL W/ BASE AFKDMPB W/ HTKDMPB9-1/4 in.29-3/8 in.
LAURENT SURROUND LAURENT-361-1/2 in.N/A
CAMDEN SURROUNDCAM36PG0 N/A
CAMDEN SURROUND W/HEARTHCAM36PGH1-3/4 in.N/A
CAMDEN SURROUND W/MANTELCAMM36PG0 N/A
HEARTH
MONROE SURROUND MON36PG0 N/A
MONROE SURROUND W/HEARTH MON36PGH1-3/4 in.N/A
MONROE SURROUND W/MANTELMONM36PG0 N/A
MONROE SURROUND W/MANTEL &
HEARTH
CAMM36PGH1-3/4 in.N/A
ESSEXM36PGH1-3/4 in.N/A
MONM36PGH1-3/4 in.N/A
ELEVATED APPLIANCE
DIMENSION
See Note 1
MARBLE LEG CUT
LENGTH
See Note 2
Note 1. Add dimensions to Exterior Wall Hole (Figure 8.2) and Rough Opening Height (Figure 5.2).
Note 2. Verify Marble Cut Lengths on site prior to cutting.
Note 3. Dimensions assume use of a 3/4 in. Hearth Pad.
Remove shipping materials from inside or underneath the
fi rebox.
C. Clean the Appliance
Clean/vacuum any sawdust that may have accumulated
inside the fi rebox or underneath in the control cavity.
D. Accessories
Install approved accessories per instructions included
with accessories. Contact your dealer for a list of approved accessories.
WARNING! Risk of Fire and Electric Shock! Use ONLY
Hearth & Home Technologies-approved optional accessories with this appliance. Using non-listed accessories
could result in a safety hazard and will void the warranty.
E. Lava Rock and Glowing Ember Placement
WARNING! Risk of Explosion! Follow ember placement
instructions in manual. DO NOT place embers directly over
burner ports. Replace ember material annually . Improperly
placed embers interfere with proper burner operation.
Placing the Ember Material
Ember material is shipped with this gas appliance. T o place
the ember material:
• Embers CANNOT be placed directly over ports. Care
should be taken not to cover the lighting trail of ports
(from back to front).
• When placing Glowing Embers® onto the burner care
should be taken so that the ports are not covered. Place
the dime-size ember pieces just in front of the port trail,
but not on or in between the ports (see Figure 14.1).
Failure to follow this procedure will likely cause lighting
and sooting problems.
DO NOT PLACE EMBERS
IN THE CIRCLED AREAS
PILOT LOCATED HERE
Figure 14.1 Placement of Embers
• Place Glowing Embers on top of the log attachment
tabs to conceal their location. Ensure that the Glowing
Embers do not obstruct the port trail.
• Place Lava Rock on areas of base pan away from the
burner. Use this material to give the appliance a realistic
ash bed.
• Save the remaining ember materials for use during
appliance servicing. The embers provided should be
enough for 3 to 5 applications.
CAUTION: DO NOT reposition logs that have been
factory installed! Follow these instructions to position
the logs that were packaged separately.
Log Set Assembly: LOGS-2128
Models: ST-36TRB-IPI, PIER-36TRB-IPI
2
3
1
PILOT
B
C
D
igure 1. Log Assembly Location
STEP 1. CAUTION! Logs are fragile! Carefully remove the logs and cardboard tray from the inside of the fi replace.
See Figure 1. Remove the microfoam and inspect the logs for damage. Inspect the four factory installed logs for damage.
Locate the pilot in order to verify your position in relation to the appliance. See Figure 2.
NOTCH
1
Figure 2. Factory Installed Logs
1
C
HUMP
A
A
igure 3. Placement of Log #1
STEP 2. Log #1 (SRV2128-704): Mate the notch on the end of log # 1 with the hump on top of log A. Set the other
end of Log #1 onto the smooth area on top of Log C.
STEP 3. Log #2 (SRV2128-705): The Y-shaped end of log #2 should rest on log B and log C. The other end should
come in contact with the second grate tine from the left. Mate the bottom of log # 2 with the notches on top of log B and the
smooth area on top of the end of log C.
3
INDENTATIONS
Figure 6. Placement of Log #2
GRATE TINES
B
D
3
D
B
2
2
C
2
igure 7. Placement of Log #3
STEP 4. Log #3 (SRV2128-707): The bottom end of log #3 should come in contact with the far left grate tine. Mate
the bottom of log # 3 with the indentations on Log D and the top of Log #2.
WARNING! Risk of Asphyxiation! Handle fi xed glass
assembly with care. Inspect the gasket to ensure it is
undamaged and inspect the glass for cracks, chips or
scratches.
• DO NOTstrike, slam or scratch glass.
• DO NOToperate fi replace with glass removed, cracked, broken or scratched.
• Replace as a complete assembly.
Removing Fixed Glass Assembly
• Pull the four glass latches out of the grooves on the glass
frame top and bottom.
• Remove the glass door from the appliance.
• Multiple sides may be able to be removed based upon
model.
Replacing Fixed Glass Assembly
• Replace the glass door on the appliance.
• Pull out the four glass latches and place in the grooves
on the glass frame top and bottom.
• Make sure all sides are replaced properly.
H. Install Trim Kits and Surrounds
• Install optional trim kits and/or surrounds using the
instructions included with the accessory.
• Use non-combustible materials to cover the gap between
the sheet rock and the appliance (if desired).
I. Air Shutter Setting
This appliance has an adjustable air shutter (which controls the primary air) factory set for the minimum vertical
vent run (see Figure 12.15). If your installation has more
than the minimum required vertical vent length, adjustment of the air shutter may be necessary to obtain optimal fl ame appearance. This should be adjusted by a
qualifi ed installer at the time of installation.
By pushing the air shutter handle towards the pilot, you will
be closing the air shutter. To adjust loosen the wing nut.
Care should be taken when adjusting the air shutter so as
not to cause the appliance to soot. If sooting occurs the air
shutter will need to be opened by pushing the handle away
from the pilot. When fi nished tighten wing nut.
NOTICE: If sooting occurs, provide more air by opening
the air shutter.
With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service. If you
do experience a problem, this troubleshooting guide will assist a qualifi ed technician in the diagnosis of a problem and the
corrective action to be taken. This troubleshooting guide can only be used by a qualifi ed technician. Contact your dealer to
arrange a service call by a qualifi ed technician.
A. Intellifi re Ignition System
SymptomPossible CauseCorrective Action
1. Pilot won’t light.
The ignitor/module
makes noise, but no
spark.
2. Pilot won’t light,
there is no noise or
spark.
a. Incorrect wiring.Verify “S” wire (white) for sensor and “I” wire (orange) for ignitor
are connected to correct terminals on module and pilot assembly.
b. Loose connections or electrical
shorts in the wiring.
c. Ignitor gap is too large.Verify gap of igniter to right side of pilot hood. The gap should be
d. Module.Turn ON/OFF rocker switch or wall switch to OFF position. Remove
a. No power or transformer installed
incorrectly.
b. A shorted or loose connection in wir-
ing confi guration or wiring harness.
Verify no loose connections or electrical shorts in wiring from
module to pilot assembly. Verify connections underneath pilot assembly are tight; also verify connections are not grounding out to
metal chassis, pilot burner, pilot enclosure, mesh screen if present,
or any other metal object.
approximately .17 in. or 1/8 in. (3 mm).
ignitor wire “I” from module. Place a grounded wire about 3/16 in. (5
mm) away from “I” terminal on module. Place ON/OFF rocker switch
or wall switch in ON position. If there is no spark at “I” terminal
module must be replaced. If there is a spark at “I” terminal, module
is fi ne. Inspect pilot assembly for shorted sparker wire or cracked
insulator around electrode. Replace pilot if necessary .
Verify that transformer is installed and plugged into module. Check
voltage of transformer under load at spade connection on module
with ON/OFF switch in ON position. Acceptable readings of a good
transformer are between 3.2 and 2.8 volts AC.
Remove and reinstall the wiring harness that plugs into module.
Verify there is a tight fi t. Verify pilot assembly wiring to module. Re-
move and verify continuity of each wire in wiring harness. Replace
any damaged components.
c. Improper wall switch wiring.Verify that 110/VAC power is “ON” to junction box.
d. Module not grounded.Verify black ground wire from module wire harness is grounded to
metal chassis of appliance.
e. Module.Turn ON/OFF rocker switch or wall switch to OFF position. Re-
move ignitor wire “I” from module. Place ON/OFF rocker switch
or wall switch in ON position. If there is no spark at “I” terminal
module must be replaced. If there is a spark at “I” terminal, module
is fi ne. Inspect pilot assembly for shorted sparker wire or cracked
insulator around electrode.
a. Gas supply.Verify that incoming gas line ball valve is “open”. Verify that inlet
pressure reading is within acceptable limits, inlet pressure must
not exceed 14 in. W.C.
b. Ignitor gap is incorrect.Verify that spark gap from ignitor to pilot hood is .17 in. or 1/8 in (3 mm).
c. Module is not grounded.Verify module is securely grounded to metal chassis of appliance.
d. Module voltage output / Valve/Pilot
solenoid ohms readings.
Verify battery voltage is at least 2.7 volts. Replace batteries if volt-
age is below 2.7.
Page 66
Intellifi re Ignition System - (continued)
SymptomPossible CauseCorrective Action
4. Pilot lights but continues to spark, and main
burner will not ignite.
(If the pilot continues
to spark after the
pilot fl ame has been lit, fl ame rectifi cation has
not occurred.)
a. A shorted or loose connection in fl ame
sensing rod.
b. Poor fl ame rectifi cation or contaminated
fl ame sensing rod.
c. Module is not grounded.Verify module is securely grounded to metal chassis of
d. Damaged pilot assembly or contami-
nated fl ame sensing rod.
e. Module.Turn ON/OFF rocker switch or wall switch to OFF position.
Verify all connections to wiring diagram in manual. Verify
connections underneath pilot assembly are tight. Verify
connections are not grounding out to metal chassis, pilot
burner, pilot enclosure or screen if present, or any other
metal object.
With fi xed glass assembly in place, verify that fl ame is en-
gulfi ng fl ame sensing rod on left side of pilot hood. Flame
sensing rod
rect pilot orifi ce is installed and gas inlet is set to pressure
specifi cations. Clean fl ame sensing rod with emery cloth to
remove any contaminants that may have accumulated on
fl ame sensing rod.
appliance. Verify that wire harness is fi rmly connected to
the module.
Verify that ceramic insulator around the fl ame sensing
rod is not cracked, damaged, or loose. Verify connection
from fl ame sensing rod to white sensor wire. Clean fl ame
sensing rod with emery cloth to remove any contaminants
that may have accumulated on fl ame sensing rod. Verify
continuity with a multimeter with ohms set at lowest range.
Replace pilot if any damage is detected.
Remove ignitor wire “I” from module. Place ON/OFF rocker
switch or wall switch in ON position. If there is no spark at
“I” terminal module must be replaced. If there is a spark at
“I” terminal, module is fi ne.
DVP44102
DVP66152
DVP1212305
DVP2424610
DVP3636914
DVP48481219
DVP6A3 to 676 to 152
DVP12A 3 to 12 76 to 305
DVP12MI 3 to 12 76 to 305
DVP24MI 3 to 24 76 to 610
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be
used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm) the
existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B
will be required.
IMPORTANT: THIS IS DATED INFORMA TION. When requesting service or replacement
parts for your appliance please provide model number and serial number. All parts listed
in this manual may be ordered from an authorized dealer.
IMPORTANT: THIS IS DATED INFORMA TION. When requesting service or replacement
parts for your appliance please provide model number and serial number. All parts listed
in this manual may be ordered from an authorized dealer.
IMPORTANT: THIS IS DATED INFORMA TION. When requesting service or replacement
parts for your appliance please provide model number and serial number. All parts listed
in this manual may be ordered from an authorized dealer.
IMPORTANT: THIS IS DATED INFORMA TION. When requesting service or replacement
parts for your appliance please provide model number and serial number. All parts listed
in this manual may be ordered from an authorized dealer.
IMPORTANT: THIS IS DATED INFORMA TION. When requesting service or replacement
parts for your appliance please provide model number and serial number. All parts listed
in this manual may be ordered from an authorized dealer.
ITEMDESCRIPTIONCOMMENTSPART NUMBER
1Shutter Bracket Assembly
2
Pilot Assembly NG
Pilot Assembly LP
2118-121Y
2090-012Y
2090-013Y
3Flexible Gas Connector 530-302AY
4Flex Ball Valve Assembly 302-320AY
5
6
Orifi ce NG (#32C)
Orifi ce LP (#50C)
Valve NG 750-500Y
Valve LP750-501Y