Hearth and Home Technologies Cyclone-Cust User Manual

Page 1
Model: Cyclone-Cust
Owner’s Manual
Installation and Operation
CAUTION
DO NOT DISCARD THIS MANUAL
• Important operating and maintenance instructions included.
WARNING: If the information in these instructions is not followed exactly, a fi re or explosion may result causing property damage, personal injury, or death.
• Do not store or use gasoline or other fl am- mable vapors and liquids in the vicinity of this or any other appliance.
• What to do if you smell gas
- Do not touch any electrical switch. Do not
use any phone in your building.
- Immediately call your gas supplier from a
neighbor’s phone. Follow the gas suppli­er’s instructions.
- If you cannot reach your gas supplier, call
the fi re department.
• Installation and service must be performed by a qualifi ed installer, service agency , or the gas supplier.
This appliance may be installed as an OEM installation in manufactured home (USA only) or mobile home and must be installed in accordance with the manufacturer’s instructions and the manufactured home construction and safety standard, Title
24 CFR, Part 3280 or Standard for Installation in Mobile Homes, CAN/CSA Z240MH.
This appliance is only for use with the type(s) of gas indicated on the rating plate.
• Read, understand and follow these instructions for safe installation and operation.
DO NOT
DISCARD
• Leave this manual with party responsible for use and operation.
WARNING
HOT SURFACES!
Glass and other surfaces are hot during operation AND cool down.
Hot glass will cause burns.
• Do not touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other fl ammable materials.
• Keep clothing, furniture, draperies and other fl ammable materials away.
This appliance has been supplied with an integral barrier to prevent direct contact with the fi xed glass panel. DO NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one.
In the Commonwealth of Massachusetts:
• installation must be performed by a licensed plumber or gas fi tter;
See Table of Contents for location of additional Commonwealth of Massachusetts requirements.
Installation and service of this appliance should be performed by qualifi ed personnel. Hearth & Home Technologies suggests NFI certifi ed or factory trained professionals, or technicians supervised by an NFI certifi ed professional.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 1
Page 2
Read this manual before installing or operating this appliance.
Please retain this owner’s manual for future reference.
Congratulations
Congratulations on selecting a Heat & Glo gas appliance —an elegant and clean alternative to wood burning appliances. The Heat & Glo gas appliance you have selected is designed to provide the utmost in safety, reliability, and effi ciency.
As the owner of a new appliance, you’ll want to read and carefully follow all of the instructions contained in this Owner’s Manual. Pay special attention to all Cautions and Warnings.
Homeowner Reference Information
This Owner’s Manual should be retained for future reference. We suggest that you keep it with your other important documents and product manuals.
The information contained in this Owner’s Manual, unless noted otherwise, applies to all models and gas control systems.
Your new Heat & Glo gas appliance will give you years of durable use and trouble-free enjoyment. Welcome to the Heat & Glo family of appliance products!
We recommend that you record the following pertinent information about your appliance.
Model Name: ___________________________________________ Date purchased/installed: __________________ Serial Number: __________________________________________ Location on appliance: ____________________ Dealership purchased from: _______________________________ Dealer Phone: __________________________ Notes: _______________________________________________________________________________________ _____________________________________________________________________________________________
Listing Label Information/Location
This product may be coveredby one or more ofthe following patents: (Nos produitssont couverts par un ouplusieurs des brevets suivants): (United States) 4593510,4686807, 4766876, 4793322, 4811534, 5000162, 5016609, 5076254, 5113843, 5191877, 5218953, 5263471, 5328356,5341794, 5347983, 5429495, 5452708,5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485,5931661, 5941237, 594711 2,5996575, 6006743,6019099, 6048195, 6053165, 6145502, 6170481, 6237588, 6296474, 6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940, 6748942, D320652,D445174, D462436; (Canada)1297749, 2195264, 2225408;or other U.S. and foreignpatents pending (ou autresbrevetsamericainsetetrangersenattente).
Type of Gas
Not for use with solid fuel . (Ne doit pas entre utilise avec un combustible solide).
Ty pe of Gas (Sorte De Gaz) :
NATURA L GAS
Gas and Electric Information
Minimum Permissible Gas Supply for Purpos es of Input Adjustment . Approved Minimum (De Gaz) Acceptabl e 0. 0 in w. c. (Po. Col. d’eau) Maximum Pressure (Pression) 0. 0 in w. c. (Po. Col. d’eau) Maximum Manifold Pressure (Pression) 0. 0 in w. c. (Po. Col. d’eau) Minimum Manifold Pressure (Pression) 0. 0 in w. c. (Po. Col. d’eau) T o tal Electrical Requirements: 000V ac, 00Hz., less than 00 Ampere s
AL TI TUDE : 0-0000 FT . 0000-0000FT . MAX. INPU T BTUH: 00,000 00,000 MIN. INPU T BTUH: 00,000 00,000 ORIFICE SIZE: #XXXXX #XXXXX
The model information regarding your specifi c appliance can be found on the rating plate usually located in the control area of the appliance.
He at & Gl o, a of Hearth & Ho me Te chnologies, Inc. 20802 Kensington Boulevard, Lakeville, MN 5504 4
This appliance must be installed in accordance with local codes, if any; if not, follow ANSI Z223.1 in the USA or CAN/CG A B149 installation codes. (Installer l’ appa re il selon les codes ou regl emen ts
lo caux ou , en l’absence de tels reglements, selon les codes d’in stallation CAN/CGA-B149.)
bran d
ANSI Z21X X-XXXX · CS A 2.XX-MXX · UL307B
IN CANADA
Mode l:
(Modele):
Serial
(Serie):
XXXXXXXX
XXXXXXXX
MADE IN US A
Model Number
Serial Number
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/082
Page 3
Table of Contents
1 Listing and Code Approvals
A. Appliance Certifi cation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
B. Glass Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
C. BTU Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
D. High Altitude Installations . . . . . . . . . . . . . . . . . . . . . . . . . . 4
E. Non-Combustible Materials Specifi cation. . . . . . . . . . . . . . 4
F. Combustible Materials Specifi cation . . . . . . . . . . . . . . . . . 4
G. Electrical Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
H. Requirements for the Commonwealth of Massachusetts . . 5
2 Getting Started
A. Design and Installation Considerations . . . . . . . . . . . . . . . 6
B. Tools and Supplies Needed . . . . . . . . . . . . . . . . . . . . . . . . 6
C. Inspect Appliance and Components . . . . . . . . . . . . . . . . . . 6
3 Framing and Clearances
A. Selecting Appliance Location . . . . . . . . . . . . . . . . . . . . . . . 7
B. Constructing the Appliance Chase . . . . . . . . . . . . . . . . . . . 8
C. Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
D. Mantel Projections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4 Termination Locations
A. Vent Termination Minimum Clearances . . . . . . . . . . . . . . 10
5 Vent Information and Diagrams
A. Vent Table Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
B. Use of Elbows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
C. Measuring Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
D. Vent Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
9 Gas Information
A. Fuel Conversions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
B. Gas Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
C. Gas Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
10 Electrical Information
A. Recommendation for Wire . . . . . . . . . . . . . . . . . . . . . . . . 28
B. Connecting to the Appliance. . . . . . . . . . . . . . . . . . . . . . . 29
C. Hot Surface Ignition Wiring. . . . . . . . . . . . . . . . . . . . . . . . 29
11 Finishing
A. Mantel Projections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
B. Facing Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
12 Appliance Setup
A. Remove Shipping Materials . . . . . . . . . . . . . . . . . . . . . . . 31
B. Clean the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
C. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
D. Glass Assembly Installation . . . . . . . . . . . . . . . . . . . . . . . 31
13 Operating Instructions
A. Before Lighting Appliance. . . . . . . . . . . . . . . . . . . . . . . . . 32
B. Lighting Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
C. After Appliance is Lit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
D. Frequently Asked Questions . . . . . . . . . . . . . . . . . . . . . . 34
14 Maintaining and Servicing Appliance
A. Fan Motor Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
B. Maintenance Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6 Vent Clearances and Framing
A. Pipe Clearances to Combustibles . . . . . . . . . . . . . . . . . . 17
B. Wall Penetration Framing . . . . . . . . . . . . . . . . . . . . . . . . . 17
C. Vertical Penetration Framing . . . . . . . . . . . . . . . . . . . . . . 18
7 Appliance Preparation
A. Securing and Leveling the Appliance . . . . . . . . . . . . . . . . 19
8 Installing Vent Pipe
A. Assembly of Vent Sections . . . . . . . . . . . . . . . . . . . . . . . . 20
B. Disassembly of Vent Sections . . . . . . . . . . . . . . . . . . . . . 22
C. Installing Heat Shield and Horizontal Termination Cap . . 23 D. Installing Roof Flashing and Vertical Termination Cap . . . 24
= Contains updated information.
15 Reference Materials
A. Appliance Dimension Diagram . . . . . . . . . . . . . . . . . . . . . 38
B. Vent Components Diagrams . . . . . . . . . . . . . . . . . . . . . . 39
C. Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
D. Limited Lifetime Warranty . . . . . . . . . . . . . . . . . . . . . . . . . 44
E. Contact Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 3
Page 4
1
1
Listing and Code Approvals
A. Appliance Certifi cation
MODELS: Cyclone-Cust LABORATORY: Underwriters Laboratories, Inc. (UL) TYPE: Direct Vent Gas Fireplace STANDARD: ANSI Z21.50-2000 • CSA2.33-2000 • UL307B
This product is listed to ANSI standards for “Vented Gas Fireplaces” and applicable sections of “Gas Burning Heat­ing Appliances for Manufactured Homes and Recreational Vehicles”, and “Gas Fired Appliances for Use at High Altitudes”.
NOT INTENDED FOR USE AS A PRIMAR Y HEAT SOURCE.
This appliance is tested and approved as either supplemen­tal room heat or as a decorative appliance. It should not be factored as primary heat in residential heating calculations.
B. Glass Specifi cations
Hearth & Home Technologies appliances manufactured with tempered glass may be installed in hazardous loca­tions such as bathtub enclosures as defi ned by the Con- sumer Product Safety Commission (CPSC)
This statement is in compliance with CPSC 16 CFR Sec- tion 1201.5 “Certifi cation and labeling requirements” which refers to 15 U.S. Code (USC) 2063 stating “…Such certifi cate shall accompany the product or shall otherwise be furnished to any distributor or retailer to whom the product is delivered.”
Some local building codes require the use of tempered glass with permanent marking in such locations. Glass meeting this requirement is available from the factory. Please contact your dealer or distributor to order.
Note: This installation must conform with local codes. In the absence of local c odes you must comply w ith the National Fuel Gas Code, ANSI Z223.1 -latest edition in the U.S.A. and the CAN/CGA B149 Installation Codes in Canada.
C. BTU Specifi cations
Models
(U.S. or Canada)
Cyclone-Cust
US
(0-2000 FT)
CANADA
(2000-4500 FT)
Maximum
Input
BTU/h
13,500 12,150
Minimum
Input
BTU/h
-
-
Orifi ce
Size
(DMS)
50 51
D. High Altitude Installations
U.L. Listed gas appliances are tested and approved with­out requiring changes for elevations from 0 to 2000 feet in the U.S.A. and Canada.
When installing this appliance at an elevation above 2000 feet, it may be necessary to decrease the input rating by changing the existing burner orifi ce to a smaller size. Input rate should be reduced by 4% for each 1000 feet above a 2000 foot elevation in the U.S.A., or 10% for el­evations between 2000 and 4500 feet in Canada. If the heating value of the gas has been reduced, these rules do not apply . To identify the proper orifi ce size, check with the local gas utility.
If installing this appliance at an elevation above 4500 feet (in Canada), check with local authorities.
WARNING
Do NOT use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
E. Non-Combustible Materials Specifi cation
Material which will not ignite and burn. Such materials are those consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750ºC, shall be considered
non-combustible materials.
F. Combustible Materials Specifi cation
Materials made of or surfaced with wood, compressed paper, plant fi bers, plastics, or other material that can ig- nite and burn, whether fl ame proofed or not, or whether plastered or unplastered shall be considered combustible materials.
G. Electrical Codes
NOTICE: This appliance must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with National Electric Code ANSI/NFPA
70-latest edition or the Canadian Electric Code CSA C22.1.
• A 110-120 VAC circuit for this product must be protected
with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/084
Page 5
Note: The following requirements reference various Massachuset ts and national codes not contained in this document.
H. Requirements for the Commonwealth of
Massachusetts
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above fi nished grade in the area of the venting, in- cluding but not limited to decks and porches, the following requirements shall be satisfi ed:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fi tter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the fl oor level where the gas equipment is to be installed. In addi­tion, the installing plumber or gas fi tter shall observe that a battery operated or hard wired carbon monoxide detec­tor with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualifi ed licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fu­eled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent oor level. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that dur­ing said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Inspection
The state or local gas inspector of the side wall horizon­tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector ob­serves carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equip-
ment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fu-
eled equipment installed in a room or structure sep­arate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
• Detailed instructions for the installation of the venting
system design or the venting system components; and
• A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not pro­vide the parts for venting the fl ue gases, but identifi es “special venting systems”, the following requirements shall be satisfi ed by the manufacturer:
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accor­dance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certifi ed.
Signage
A metal or plastic identifi cation plate shall be permanent- ly mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fu­eled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB­STRUCTIONS”.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 5
• The referenced “special venting system” instructions
shall be included with the appliance or equipment in­stallation instructions; and
• The “special venting systems” shall be Product Ap-
proved by the Board, and the instructions for that sys­tem shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Ap­proved side wall horizontally vented gas fueled equip­ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
See Gas Connection section for additional Common­wealth of Massachusetts requirements.
Page 6
2
2
Getting Started
A. Design and Installation Considerations
Heat & Glo direct vent gas appliances are designed to operate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the out­side. No additional outside air source is required.
CAUTION
Check building codes prior to installation.
• Installation MUST comply with local, regional, state and national codes and regulations.
• Consult local building, fi re offi cials or authorities having jurisdic- tion about restrictions, installation inspection, and permits.
When planning an appliance installation, it’s necessary to determine the following information before installing:
• Where the appliance is to be installed.
• The vent system confi guration to be used.
• Gas supply piping.
• Electrical wiring.
• Framing and fi nishing details.
• Whether optional accessories—devices such as a wall switch, or remote control—are desired.
WARNING
Keep appliance dry.
• Mold or rust may cause odors.
• Water may damage controls.
B. Tools and Supplies Needed
Before beginning the installation be sure that the following tools and building supplies are available.
C. Inspect Appliance and Components
WARNING
Inspect appliance and components for damage. Damaged parts may impair safe operation.
• Do NOT install damaged components.
• Do NOT install incomplete components.
• Do NOT install substitute components. Report damaged parts to dealer.
• Carefully remove the appliance and components from the packaging.
• The vent system components and trim doors are shipped in separate packages.
• Report to your dealer any parts damaged in shipment, particularly the condition of the glass.
• Read all of the instructions before starting the insta­llation. Follow these instructions carefully during the installation to ensure maximum safety and benefi t.
WARNING
Hearth & Home Technologies disclaims any responsibility for, and the warranty will be voided by, the following actions:
• Installation and use of any damaged appliance or vent system component.
• Modifi cation of the appliance or vent system.
• Installation other than as instructed by Hearth & Home Technologies.
• Improper positioning of the glass door.
• Installation and/or use of any component part not approved by Hearth & Home Technologies.
Any such action may cause a fi re hazard.
Reciprocating saw Framing material Pliers Hi temp caulking material Hammer Gloves Phillips screwdriver Framing square Flat blade screwdriver Electric drill and bits (1/4 in.) Plumb line Safety glasses Level 1/2 - 3/4 inch length, #6 or #8 Self-drilling screws Manometer Voltmeter Tape measure Noncorrosive leak check solution One 1/4 inch female connection (for optional fan).
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/086
Page 7
3
3
Framing and Clearances
Note:
Illustrations reflect typical installations and are FOR
DESIGN PURPOSES ONLY.
Illustrations/diagrams are not drawn to scale.
Actual installation may vary due to individual design
preference.
A. Selecting Appliance Location
When selecting a location for your appliance it is important to consider the required clearances to walls (see fi gure 3.1).
0
A
WARNING
Fire Risk Provide adequate clearance:
• Around air openings
• To combustibles
• For service access Locate appliance away from traffi c areas.
Note: For actual appliance dimensions refer to Sec­tion 16.
B
In addition to these framing dimensions, also reference the following sections:
• Clearances and Mantel Projections (Sections 3.C and 3.D)
• Vent Clearances and Framing (Section 6).
C
D
Model A B C D
Cyclone-Cust
Inches 17 17 17 17
Millimeters 432 432 432 432
Figure 3.1 Appliance Locations
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 7
Page 8
B. Constructing the Appliance Chase
A chase is a vertical boxlike structure built to enclose the gas appliance and/or its vent system. Vertical vents that run on the outside of a building may be, but are not re­quired to be, installed inside a chase.
Construction of the chase may vary with the type of build­ing. These instructions are not substitutes for the require­ments of local building codes. Local building codes MUST be checked.
Chases should be constructed in the manner of all out­side walls of the home to prevent cold air drafting prob­lems. The chase should not break the outside building envelope in any manner.
Walls, ceiling, base plate and cantilever fl oor of the chase should be insulated. Vapor and air infi ltration barriers should be installed in the chase as per regional codes for the rest of the home. Additionally, in regions where cold air infi ltration may be an issue, the inside surfaces may be sheetrocked and taped for maximum air tightness.
To further prevent drafts, the wall shield and ceiling restops should be caulked with high temperature caulk to seal gaps. Gas line holes and other openings should be caulked with high temp caulk or stuffed with unfaced insulation. If the appliance is being installed on a cement slab, a layer of plywood may be placed underneath to prevent conducting cold up into the room.
A
B
C
C. Clearances
Fire Risk. Odor Risk.
Install appliance on hard metal or wood surfaces extending full width and depth of appliance.
Do NOT install appliance directly on carpeting, vinyl, tile or any combustible material other than wood.
Fire Risk.
Construct chase to all clearance specifi cations in manual.
Locate and install appliance to all clearance specifi cations in manual.
WARNING
WARNING
E
F
MAX
Clearances to Combustibles
ABCD E F G
Inches 42-1/2 0 0 17-1/2 17-1/2 6-3/8 41-3/8*
mm 1080 0 0 445 445 162 1051
D
G
* This dimension must be held to +0 inch to -1/2 inch to assure the fi restop
conceals the connection of the glass tube to the slip section.
Figure 3.2 Clearances to Combustibles
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/088
Page 9
D. Mantel Projections
FRAMING
MEMBER
SLIP
SECTION
COMBUSTIBLE
MATERIAL
FIRESTOP
34-3/8 in.
TO CEILING
AND/OR MANTEL
TOP
OF UNIT
Figure 3.3 Clearances to mantels or other combustibles above appliance
GLASS
TUBE
41-3/8 in.
(+0 to -1/2 in.)
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 9
Page 10
4
4
Termination Locations
A. Vent Termination Minimum Clearances
WARNING
Fire Risk. Explosion Risk. Inspect external vent cap regularly.
• Ensure no debris blocks cap.
• Combustible materials blocking cap may ignite.
• Restricted air fl ow affects burner operation.
WARNING
Fire Risk. Explosion Risk. Maintain vent clearance to combustibles as
specifi ed.
• Do not pack air space with insulation or other materials.
Failure to keep insulation or other materials away from vent pipe may cause fi re.
Measure vertical clearances from this surface.
HORIZONTAL
OVERHANG
2 FT. MIN.
GAS DIRECT VENT TERMINATION CAP
Roof Pitch H (Min.) Ft.
Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0
20 INCHES MIN.
LOWEST
DISCHARGE
OPENING
H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING
X
12
ROOF PITCH
VERTICAL
WALL
IS X/ 12
* 3 foot minimum in snow regions
Figure 4.2 Minimum height from roof to lowest discharge opening
Figure 4.2 specifi es minimum vent heights for various pitched roofs.
Measure horizontal clearances from this surface.
(See Figure 4.4 for specifi c clearances)
Figure 4.1
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0810
GAS, WOOD OR FUEL
OIL TERMINATION
GAS
TERMINATION
C
A
Gas
Termination
A 6 in. 20 in. min. Horizontal distance between terminations B 20 in. 24 in. min. Distance to perpendicular wall C 18 in. 18 in. Vertical distance between terminations
Figure 4.3 Multiple Vertical Termination
Wood & Fuel Oil
Termination
B
Comments
Page 11
V
R
M
N
P
Q
(See Note 2)
T
S
Electrical
V
Service
V
S
V
D*
= VENT TERMINAL
V
A = 12 inches.................clearances above grade, veranda,
(See Note 1)
X
= AIR SUPPLY INLET
porch, deck or balcony
B = 12 inches.................clearances to window or door
that may be opened, or to perma­nently closed window. (Glass)
D* = 18 inches.................vertical clearance to unventilated
soffi t or to ventilated soffi t located above the terminal
*30 inches ................for vinyl clad soffi ts and below
electrical service
F = 9 inches..................clearance to outside corner
G = 6 inches...................clearance to inside corner
H = 3 ft. (Canada) ..........not to be installed above a gas
meter/regulator assembly within 3
feet (90 cm) horizontally from the
center-line of the regulator
I = 3 ft ...........................clearance to gas service regulator
vent outlet J = 9 inches (U.S.A.)
12 inches (Canada) clearance to non-mechanical
air supply inlet to building or the
combustion air inlet to any other
appliance K = 3 ft. (U.S.A.)
6 ft. (Canada) ...........clearance to a mechanical (pow-
ered) air supply inlet
= AREA WHERE TERMINAL IS NOT PERMITTED
L** = 7 ft. ......................... clearance above paved
(See Note 1)
sidewalk or a paved driveway located on public property
M*** = 18 inches................ cl earance under veranda, porch,
deck, balcony or overhang
42 inches ............... vinyl
S = 6 inches................. clearance from sides of electri-
(See Note 5)
cal service
T = 12 inches................ clearance above electrical
(See Note 5)
service
Alcove Applications
N = 6 inches ..................non-vinyl sidewalls
12 inches ................vinyl sidewalls
P = 8 ft.
Q
MIN
1 cap 3 feet 2 x Q 2 caps 6 feet 1 x Q 3 caps 9 feet 2/3 x Q 4 caps 12 feet 1/2 x Q
Q
= # termination caps x 3 R
MIN
= (2 / # termination caps) x Q
MAX
R
MAX
ACTUAL
ACTUAL
ACTUAL
ACTUAL
ACTUAL
** a vent shall not terminate directly above a sidewalk or paved driveway
which is located between two single family dwellings and serves both dwellings.
*** only permitted if veranda, porch, deck or balcony is fully open on a
minimum of 2 sides beneath the fl oor, or meets Note 2.
Note 1: On private property where termination is less than 7 feet above a sidewalk, driveway, deck, porch, veranda or balcony, use of a listed cap shield is suggested. (See vents components page)
Note 2: Termination in an alcove space (spaces open only on one side and with an overhang) are permitted with the dimensions specifi ed for vinyl or non-vinyl siding and soffi ts. 1. There must be 3 feet minimum between termination caps. 2. All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below the termination cap. 3. All gravity air intakes within 3 feet of a termination cap must be a minimum of 1 foot below the termination cap.
Note 3: Local codes or regulations may require different clearances.
Note 4: Termination caps may be hot. Consider their proximity to doors or other traffi c areas.
Note 5: Location of the vent termination must not interfere with access to the electrical service.
WARNING: In the U.S: V ent system termination is NOT permitted in screened porches. Y ou must follow side wall, overhang and ground clearances as stated in the instructions.
In Canada: Vent system termination is NOT permitted in screened porches. Vent system termination is permitted in porch areas with two or more sides open. You must follow all side walls, overhang and ground clearances as stated in the instructions.
Heat & Glo assumes no responsibility for the improper performance of the appliance when the venting system does not meet these
Figure 4.4 Minimum Clearances for Termination
requirements.
CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 11
Page 12
5
5
Vent Information and Diagrams
A. Vent Table Key
The abbreviations listed in this vent table key are used in the vent diagrams.
Symbol Description
First section (closest to appliance) of vertical length
V
1
Second section of vertical length
V
2
First section (closest to appliance) of horizontal length
H
1
Second section of horizontal length
H
2
Vertical
12 in.
8-1/2 in.
8-1/2 in.
WARNING
Fire Hazard. Explosion Risk. Asphyxiation Risk. Do NOT connect this gas appliance to a chimney
ue serving a separate solid-fuel or gas burning appliance.
• Vent this appliance directly outside.
• Use separate vent system for this appliance. May impair safe operation of this appliance or
other appliances connected to the fl ue.
B. Use of Elbows
CAUTION
ALL vent confi guration specifi cations MUST be followed.
• This product is tested and listed to these specifi cations.
• Appliance performance will suffer if specifi cations are not followed.
Diagonal runs have both vertical and horizontal vent as­pects when calculating the effects. Use the rise for the vertical aspect and the run for the horizontal aspect (see Figure 5.1).
Two 45º elbows may be used in place of one 90º elbow . On 45º runs, one foot of diagonal is equal to 8.5 inches hori­zontal run and 8.5 inches vertical run. A length of straight pipe is allowed between two 45º elbows (see Figure 5.1).
Horizontal
Figure 5.1
C. Measuring Standards
Vertical and horizontal measurements listed in the vent diagrams were made using the following standards.
1. Pipe measurements are shown using the effective length of pipe (see Figure 5.2).
2. Measurements are made from the appliance outer wrap, not from the standoffs.
3. Horizontal terminations are measured to the outside mounting surface (fl ange of termination cap) (see Figure 4.1).
4. V ertical terminations are measured to bottom of termi­nation cap.
5. Horizontal pipe installed level with no rise.
Effective Length
Inches Millimeters
Effective
Height/Length
Pipe
DVP4 4 102
DVP6 6 152 DVP12 12 305 DVP24 24 610 DVP36 36 914 DVP48 48 1219 DVP6A 3 to 6 76 to 152
DVP12A 3 to 12 76 to 305 DVP12MI 3 to 12 76 to 305 DVP24MI 3 to 24 76 to 610
Figure 5.2 DVP Pipe Effective Length
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0812
Page 13
D. Vent Diagrams
Fire Risk. Explosion Risk. Do NOT pack insulation or other combustibles between ceiling fi restops.
• ALWAYS maintain specifi ed clearances around venting and fi restop systems.
• Install wall shield and ceiling fi restops as specifi ed. Failure to keep insulation or other material away from vent pipe may cause fi re.
1. Top Vent - Horizontal Termination
WARNING
One Elbow
NOTE: A minimum of 2 feet before
the fi rst 90º elbow can be achieved by using a 12 inch section of DVP and the (cyclone-12slip) slip section.
Figure 5.3
Two Elbows
VT Min. HT Max.
2 ft. 2 ft. 3 ft. 6 ft. 4 ft. 10 ft. 5 ft. 15 ft.
+ HT = 40 ft. Max
V
T
V
T
H
T
H
1
H
2
VT Min. HT Max.
* * 2 ft. 2 ft. * * 3 ft. 6 ft. * * 4 ft. 10 ft. * * 5 ft. 15 ft.
V
+ HT = 40 ft. Max.
T
H
T
*No specifi c restrictions on this value
EXCEPT VT + HT cannot exceed 40 ft. Max.
Figure 5.4
V
T
H
2
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 13
H
1
Page 14
1. Top Vent - Horizontal Termination - (continued)
Three Elbows
H
V
1
****2 ft.2 ft. ****3 ft.6 ft. ****4 ft.10 ft. ****5 ft.15 ft.
T
H
1
*No specifi c restrictions on this value EXCEPT
VT + HT cannot exceed 40 ft. Max.
V
2
V
+ HT = 40 ft. Max.
T
H
VT Min. HT Max.
2
H
V
V
2
2
H
1
V
1
T
Figure 5.5
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0814
Page 15
2. Top Vent - Vertical Termination
No Elbow
CAP
VT MAX.
40 ft.
SLIP
SECTION
Flue Restrictor
FLUE
RESTRICTOR
Part No.
Inside
Diameter
Max. Vertical
)
(V
T
2061-204 2-3/4 in. 15-30 ft.
V
T
2061-203 2-1/2 in. 30 ft. or more
GLASS
CYLINDER
ASSEMBLY
Figure 5.6
Two Elbows
Drop the fl ue restrictor into the slip section as shown.
V
1
* * 2 ft. 2 ft. * * 3 ft. 6 ft. * * 4 ft. 10 ft. * * 5 ft. 15 ft.
*No specifi c restrictions on this value EXCEPT
VT + HT cannot exceed 40 ft. Max.
V
T
V
2
H
T
V
1
V
2
V
+ HT = 40 ft. Max.
T
VT Min. HT Max.
Figure 5.7
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 15
Page 16
2. Top Vent - Vertical Termination - (continued)
Three Elbows
V
1
H
1
H
2
V
VT Min. HT Max.
2
****2 ft.2 ft. ****3 ft.6 ft. ****4 ft.10 ft. ****5 ft.15 ft.
V
+ HT = 40 ft. Max.
T
*No specifi c restrictions on this value EXCEPT
VT + HT cannot exceed 40 ft. Max.
V
T
V
2
H
T
H
2
H
1
V
1
Figure 5.8
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0816
Page 17
6
6
Vent Clearances and Framing
A. Pipe Clearances to Combustibles
WARNING
Fire Risk. Explosion Risk. Maintain vent clearance to combustibles as
specifi ed.
• Do not pack air space with insulation or other materials.
Failure to keep insulation or other materials away from vent pipe may cause fi re.
Note: Slope not required.
1 in. CLEARANCE
AROUND VERTICAL
SECTIONS
3 in. TOP
CLEARANCE
1 in. SIDE AND
BOTTOM CLEARANCE
B. Wall Penetration Framing
Combustible Wall Penetration
Frame a hole in a combustible wall for an interior wall shield fi restop, (Figure 6.2) whenever a wall is penetrated. Use same size framing materials as those used in the wall construction. The wall shield fi restop maintains minimum clearances and prevents cold air infi ltration.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncombus­tible materials such as concrete, a hole with diameter one inch greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall shield fi restop is only required on one side and no heat shield is necessary.
If your local inspector requires the wall shield fi restop on both sides, then both wall shield fi restops must have a heat shield attached to them.
Figure 6.1 Pipe Clearances
FINISHING MATERIAL
DECORATIVE
FIRESTOP
Figure 6.2 Exterior Wall Hole
10 in. X 10 in.
FRAMED
OPENING
41-3/8 in.
(+0 to -1/2 in.)
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 17
Page 18
C. Vertical Penetration Framing
WARNING
Fire Hazard Keep loose materials or blown
insulation from touching the vent pipe.
• National building codes recommend using attic shield to keep loose materials/ blown insulation from contacting vent.
• Hearth & Home Technologies requires the use of an attic shield.
Installing the Ceiling Firestop
• Frame an opening 10 inches by 10 inches whenever the vent system penetrates a ceiling/fl oor (see Figure 6.3).
• Frame the area with the same sized lumber as used in ceiling/fl oor joist.
• When installing a top vent vertical termination appliance the hole should be directly above the appliance, unless the ue is offset.
• Do not pack insulation around the vent. Insulation must be kept away from the pipe.
ATTIC ABOVE
10 IN. (254 MM)
10 IN.
(254 MM)
HOLE SHOULD MEASURE
10 IN. X 10 IN.
(254 MM X 254 MM)
INSIDE TO INSIDE
Installing Attic Shield Note: An additional ceiling restop is not
required if attic shield is used.
• Frame opening for attic shield.
• Attic shield may be installed above or below ceiling (see Figure 6.4).
• Secure with three fasteners on each side.
• Fold tabs at top of attic shield in toward vent pipe. Tabs must keep vent pipe centered within shield.
• Field construct additional shield height if insulation is deeper than height of attic shield.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0818
Figure 6.3
BEND TABS IN
AROUND PIPE
3 FASTENERS
ATTIC SHIELD INSTALLED
BELOW CEILING
Figure 6.4 Installing the Attic Shield
PER SIDE
ATTIC SHIELD INSTALLED
ABOVE CEILING
Page 19
7
7
Appliance Preparation
A. Securing and Leveling the Appliance
WARNING
Fire Risk.
Prevent contact with sagging, loose insulation.
Do NOT install against combustible materials
such as exposed insulation, plastic and insulation backer.
The diagram shows how to properly position, level, and secure the appliance (see Figure 7.1). Holes are provided to secure the appliance to the framing members with screws.
• Horizontal venting - refer to Vent Clearances and Framing (Section 6) for hole location.
• Place the appliance into position.
• Level the appliance from side to side and front to back.
• Shim the appliance as necessary . It is acceptable to use wood shims.
• Secure the appliance to the framing by using nails or screws through the holes in the base plate of the appliance.
SCREW HOLES PROVIDED FOR SECURING
Figure 7.1 Proper positioning, leveling and securing of an appliance
WARNING
Fire Risk.
• ALWAYS maintain specifi ed clearances around the appliance.
• Do NOT notch into the framing around the appliance spacers. Failure to keep insulation, framing or other material away from
the appliance may cause fi re.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 19
Page 20
8
8
FIRST
SECTION
OF PIPE
This first section
must be adequately
secured to the
framing to
support the
remaining pipe sections.
1-1/2 in. Min.
6 in. Max.
(PIPE OVERLAP)
SLIP
SECTION
(CYCLONE -12 SLIP)
GLASS CYLINDER ASSEMBLY
NOTE: Do not secure CYCLONE-12SLIP section to DVP pipe or glass with sealant or screws .
Installing Vent Pipe
A. Assembly of Vent Sections
DVP Series Venting Only
Attach the fi rst vent components to the starting collar. At- tach the slip section (cyclone-12 slip) onto the glass cylin­der (see Figure 8.1).
The next section of pipe slips into the slip section and must have an overlap of 1-1/2 inch but no more than 6 inches, to allow the slip section room to slide up for glass removal.
The fi rst section of pipe must be secured to the framing to make it rigid and allow it to support the remaining pipe sections.
Figure 8.1
Note: It is critical that the relationship of the DVP pipe, Cy-
clone-12SLIP and glass asembly is installed per specifi cation shown in Figure 8.1. The Cyclone-12SLIP section MUST be able to be manipulated up and down to ensure routine main­tenance to the fi replace can be performed.
WARNING
Do not mix pipe, fi ttings or joining methods from different manufacturers.
WARNING
Fire Risk Exhaust Fumes Risk Impaired Performance of Appliance
• Overlap pipe slip sections at least 1-1/2 inches.
• Use pilot holes for screws.
• Screws must not exceed one inch long.
• Pipe may separate if not properly joined.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0820
Commercial, Multi-family (Multi-level exceeding two stories), & High-Rise Applications
For Installation into Commercial, multi-family (multi-level ex­ceeding two stories) or high-rise applications: All pipe joints must be sealed with high temperature silicone, including the slip section that connects directly to the horizontal termina­tion cap, but not including the CYCLONE-12SLIP.
• Apply a bead of silicone sealant inside the female outer pipe joint prior to joining sections. See Figure 8.2
• Only outer pipes are sealed. Do not seal the inner fl ue. All unit collar, pipe, slip section, elbow and cap outer fl ues shall be sealed in this manner, unless otherwise stated.
Note: The end of the pipe sections with the lances/tabs on it will face toward the appliance.
WARNING
Fire Risk Explosion Risk If slip section seals are broken during the
removal of the termination cap, gas will leak and a fi re or explosion may occur.
Do not break silicone seals on slip sections.
Assembling Pipe Sections
Insert the inner fl ue of section A into the fl ared inner fl ue of section B.
Start the outer fl ue of section A over the outer fl ue of section B (see Figure 8.3). Note: The end of the pipe sections with the lances/tabs on it will face towards the appliance.
Once both inner and outer fl ues are started, press section A onto section B fi rmly until all lances have snapped into place. Check to make sure they have snapped together (see Figure 8.4) and the seams are not aligned (see Fig­ure 8.5). Tug slightly on section A to confi rm it has com- pletely locked into place.
For 90º and 45º elbows that are changing the vent direction from horizontal to vertical, one screw minimum should be put in the outer fl ue at the horizontal elbow joint to prevent the elbow from rotating.
High Temperature Silicone Sealant
Commercial, Multi-family (multi-level exceeding two
stories), or High-rise Applications only
Figure 8.2 Lances
Page 21
Cut from this end
A
B
Figure 8.3
Note: Make sure that the seams are not aligned to prevent
unintentional disconnection.
CORRECT
Figure 8.4
(outer)
Cut from this end
(inner)
Figure 8.6
Assembling DVP-12A Slip Sections
The outer ue of the slip section should slide over the outer ue of the pipe section and into (inner fl ue) the last pipe
section (see Figure 8.7) . Slide together to the desired length, making sure that a 1-
1/2 inch outer fl ue overlap is maintained between the pipe section and slip section.
The pipe and slip section need to be secured by driving two screws through the overlapping portions of the outer ues using the pilot holes (see Figure 8.8).
This will secure the slip section to the desired length and prevent it from separating. The slip section can then be attached to the next pipe section.
If the slip section is too long, the inner and outer fl ues of the slip section can be cut to the desired length.
INCORRECT
Figure 8.5 Seams
Assembling Minimum Installations (MI) Sections
MI sections are non-unitized so that they can be cut to a certain length. Cut these sections to length from the non­expanded end (see Figure 8.6). For installations into com­mercial, multi-family (multilevel exceeding two stories) or high-rise applications, it is required to seal MI (non-unitized) pipe with a bead of silicone sealant. Apply to the overlap of outer pipe sections only.
They can then be attached by fi rst connecting the expanded end of the MI inner fl ue with the inner pipe from the adjacent pipe section and securing with three screws. The expanded portion of the MI inner fl ue must overlap completely with the unexpanded end of the adjacent pipe section.
The outer fl ue can then be inserted into the adjacent outer ue expanded end and attached to the next pipe section with three screws. The other end of the MI pipe section can then be attached by fi tting another pipe section to it and snapping it together, as normal.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 21
Pilot hole
Figure 8.7 Slip Section Pilot Holes
Figure 8.8 Screws into Slip Section
Page 22
Securing the Vent Sections Vertical Sections
Vertical sections of pipe must be supported every 8 feet above the fi replace base. For the Cyclone, there must be an additional vent support (wall bracket) placed around the rst section of pipe (see Figure 8.9). The vent support or plumber’s strap (spaced 120º apart) may be used.
Horizontal Sections
Horizontal sections of vent must be supported every 5 feet with a vent support or plumber’s strap.
WALL
BRACKET
WALL STUD
8 FT.
(2.4mm)
B. Disassembly of Vent Sections
T o disassemble any two pieces of pipe, rotate either section (see Figure 8.1 1), so that the seams on both pipe sections are aligned (see Figure 8.12). They can then be carefully pulled apart.
WARNING
Fire Risk. Explosion Risk. Combustion Fume Risk.
Use vent run supports per installation instructions.
Connect vent sections per installation instructions.
• Maintain all clearances to combustibles.
• Do NOT allow vent to sag below connection point to appliance.
Improper support may allow vent to sag or separate.
3 in. Min.
DO NOT SEAL OR SCREW
1 IN.
MINIMUM
*Note: This fi rst section of pipe must be secured to the framing to make it
rigid and allow it to support the remaining pipe sections.
Figure 8.9 Installing Support Brackets
*WALL
BRACKET
SLIP SECTION
(CYCLONE-12 SLIP)
GLASS TUBE
FIREPLACE
BASE
Figure 8.11 Rotate Seams for Disassembly
Figure 8.10 Securing Horizontal Pipe Sections
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0822
Figure 8.12 Align and Disassemble Vent Sections
Page 23
C. Installing Heat Shield and Horizontal Termination Cap
When installing a horizontal termination cap, follow the cap
WARNING
Fire Hazard Impaired performance of appliance
• Telescoping flue section of termination cap MUST be used when connecting pipe section to termination cap.
• Maintain a 1-1/2 inch minimum overlap on telescoping fl ue section of termination cap.
location guidelines as prescribed by current ANSI Z223.1 and CAN/CGA-B149 installation codes.
WARNING
Burn Risk
• Local codes may require installation of a cap shield to prevent anything or anyone from touching the hot cap.
WARNING
Fire Risk Exhaust Fumes Risk Impaired Performance of Appliance
• Overlap pipe slip sections at least 1-1/2 inches.
• Use pilot holes for screws.
• Screws must not exceed 1 inch long.
• Pipe may separate if not properly joined.
Heat Shield Requirements for Horizontal Termination
For all horizontally vented appliances, a heat shield MUST be placed one inch above the top of the vent between the wall shield fi restop and the base of the termination cap.
There are two sections of the heat shield. One section is factory-attached to the wall shield fi restop. The other section is factory-attached to the cap. See Figure 8.12.
If the wall thickness does not allow the required 1-1/2 inch (38 mm) heat shield overlap when installed, an extended heat shield (DVP-HSM-B) must be used.
Important Notice: Heat shields may not be eld constructed.
NOTE: Where required, an exterior wall ashing is available.
When penetrating a brick wall, a brick extension kit is available for framing the brick.
HEAT SHIELD OR
EXTENDED
WALL SHIELD
FIRESTOP
INNER VENT
OUTER VENT
VENT DEPTH FROM BACK OF APPLIANCE TO
OUTSIDE SURFACE OF EXTERIOR WALL
(SEE CHART BELOW)
Figure 8.13 Venting through the Wall
HEAT SHIELD
SLIP SECTION
CAN BE EXTENDED
INTERIOR
HEAT SHIELD
1-1/2 IN. (38 MM) MIN.
OVERLAP
SHEATHING
EXTERIOR
The extended heat shield (DVP-HSM-B) may need to be cut to length. You will attach the cut heat shield to the existing cap heat shield or wall shield fi restop heat shield (refer to Figure 8.12) using the supplied screws. You MUST maintain a 1-1/2 in. (38 mm) overlap of the extended heat shield and the existing shields (both ends of the heat shield). The small leg on the extended heat shield should rest on the top of the vent (pipe section) to properly space it from the pipe section.
Installing the Horizontal Termination Cap
Vent termination must not be recessed in the wall. Siding may be brought to the edge of the cap base.
Flash and seal as appropriate for siding material at outside edges of cap.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 23
Cap Specifi cation Chart
(depth without using additional pipe sections)
DVP-TRAPK1
Top Vent
Depth
3-1/2 in. to
Cyclone-
Cust
DVP-TRAP1 can adjust 1-1/2 in. (3-1/8 to 4-5/8) DVP-TRAP2 can adjust 4 in. (6-9/16 to 10-9/16) DVP-HPC1 can adjust 2-1/8 in. (4-1/4 to 6-3/8) DVP-HPC2 can adjust 4-1/8 in. (6-3/8 to 10-1/2)
5-3/8 in.
DVP-HPC1
Top Vent
Depth
6-1/4 in. to
8-3/8 in.
DVP-TRAP1
Rear Vent
Depth
N/A
DVP-HPC1
Rear Vent
Depth
N/A
DVP-TRAPK2
Top Vent
Depth
6 in. to
10 in.
DVP-HPC2
Top Vent
Depth
8-3/8 in. to
12-1/2 in.
DVP-TRAP2
Rear Vent
Depth
N/A
DVP-HPC2
Rear Vent
Depth
N/A
Page 24
D. Installing Roof Flashing and Vertical Ter-
mination Cap
To install roof fl ashing see Figure 8.14. For installation of vertical termination cap see minimum
vent heights for various pitched roofs (see Figure 8.14).
HORIZONTAL
OVERHANG
2 FT. MIN.
GAS DIRECT VENT TERMINATION CAP
20 INCHES MIN.
LOWEST
DISCHARGE
OPENING
H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING
X
12
ROOF PITCH
VERTICAL
WALL
IS X/ 12
Caulk the gap between the roof fl ashing and the outside diameter of the pipe. Also caulk the perimeter of fl ashing that contacts roof surface as shown in Figure 8.16.
To attach the vertical termination cap, slide the inner col­lar of the cap into the inner fl ue of the pipe section and place the outer collar of the cap over the outer fl ue of the pipe section.
Secure with three screws into the outer fl ue. Secure the cap by driving the three self-tapping screws (supplied) through the pilot holes in the outer collar of the cap into the outer ue of the pipe (see Figure 8.15).
TERMINATION CAP
Roof Pitch H (Min.) Ft.
Flat to 6/12........................................1.0*
Over 6/12 to 7/12 ............................1.25*
Over 7/12 to 8/12 ..............................1.5*
Over 8/12 to 9/12 ..............................2.0*
Over 9/12 to 10/12 ............................. 2.5
Over 10/12 to 11/12 .........................3.25
Over 11/12 to 12/12 ...........................4.0
Over 12/12 to 14/12 ........................... 5.0
Over 14/12 to 16/12 ........................... 6.0
Over 16/12 to 18/12 ........................... 7.0
Over 18/12 to 20/12 ........................... 7.5
Over 20/12 to 21/12 ........................... 8.0
* 3 foot minimum in snow regions
Figure 8.14 Minimum height from roof to lowest discharge opening
WARNING
Fire Risk. Explosion Risk. Inspect external vent cap regularly.
• Ensure no debris blocks cap.
• Combustible materials blocking cap may ignite.
• Restricted air fl ow affects burner operation.
(1 of 3)
STORM COLLAR
SCREWS
CAULK
Figure 8.14
CAULK
Figure 8.15
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0824
Page 25
Assembling and Installing Storm Collar
CAUTION
Sharp Edges
• Wear protective gloves and safety glasses during installation.
Connect both halves of the storm collar with two screws (see Figure 8.17).
Wrap the storm collar around the exposed pipe section and align brackets. Insert a bolt (provided) through the brackets and tighten nut to complete storm collar assem­bly (see Figure 8.18).
Slide the assembled storm collar down the pipe section until it rests on the roof fl ashing.
Caulk around the top of the storm collar (see Figure 8.15).
Figure 8.18 Assembling the Storm Collar Around the Pipe
Figure 8.17 Assembling the Storm Collar
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 25
Page 26
9
9
Gas Information
A. Fuel Conversions
No fuel conversions allowed.
B. Gas Pressures
Proper input pressures are required for optimum appli­ance performance. Gas line sizing requirements need to be made following NFPA54.
WARNING
Fire Risk. Explosion Hazard. High pressure will damage valve.
• Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.
• Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.
WARNING
Verify inlet pressures.
• High pressure may cause overfi re condition.
• Low pressure may cause explosion.
• Verify minimum pressures when other household gas appliances are operating.
Install regulator upstream of valve if line pressure is greater than 1/2 psig.
Pressure requirements for appliance are shown in the table below. Minimum pressures must be met when other household gas appliances are operating.
C. Gas Connection
Note: Have the gas supply line installed in accordance
with local building codes, if any. If not, follow ANSI
223.1. Installation should be done by a qualifi ed installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fi tter ).
Note: A listed (and Commonwealth of Massachusetts ap­proved) 1/2 inch (13 mm) T-handle manual shut-of f valve and exible gas connector are connected to the 1/2 inch (13 mm) control valve inlet.
• If substituting for these components, please consult local codes for compliance.
Refer to Reference Section 16 for location of gas line access in appliance.
Note: Gas line may be run from either side of the appliance provided the hole in the outer wrap does NOT exceed 2-1/2 inches in diameter and does not penetrate the fi rebox.
WARNING
Gas Leak Risk
• Support control when attaching pipe to prevent bending gas line.
Note: The gap between supply piping and gas access hole may be caulked with high temperature c aulk o r stu ffed with non-combustible, unfaced insulation to prevent cold air infi ltration.
Pressure Natural Gas
Minimum inlet pressure 5.0 inches w.c. Maximum inlet gas pressure 14.0 inches w.c. Manifold pressure 3.5 inches w.c.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0826
Page 27
• Ensure that gas line does not come in contact with outer wrap of appliance. Follow local codes.
• Incoming gas line should be piped into the valve compartment and connected to the 1/2 inch connection on the manual shutoff valve.
WARNING
Fire or Explosion Hazard
• Gas buildup during line purge may ignite.
• Purge should be performed by qualifi ed technician.
• Ensure adequate ventilation.
• Ensure there are no ignition sources such as sparks or open fl ames.
• A small amount of air will be in the gas supply lines. When fi rst lighting appliance it will take a short time for air to purge from lines. When purging is complete the appliance will light and operate normally.
WARNING
CHECK FOR GAS LEAKS Explosion Risk Fire Risk Asphyxiation Risk
• Check all fi ttings and connections.
• Do not use open fl ame.
• After the gas line installation is complete, all connections must be tightened and checked for leaks with a commercially-available, non-corrosive leak check solution. Be sure to rinse off all leak check solution following testing.
Fittings and connections may have loosened during shipping and handling.
HIGH AL TITUDE INST ALLATIONS
U.L. Listed gas appliances are tested and approved without requiring changes for elevations from 0 to 2000 feet in the U.S.A. and Canada.
When installing this appliance at an elevation above 2000 feet, it may be necessary to decrease the input rating by changing the existing burner orifi ce to a smaller size. Input rate should be reduced by 4% for each 1000 feet above a 2000 foot elevation in the U.S.A., or 10% for elevations between 2000 and 4500 feet in Canada. If the heating value of the gas has been reduced, these rules do not apply . T o identify the proper orifi ce size, check with the local gas utility.
If installing this appliance at an elevation above 4500 feet (in Canada), check with local authorities.
WARNING
Fire hazard. Do NOT change the valve settings.
• This valve has been preset at the factory.
• Changing valve settings may result in fi re hazard or bodily injury.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 27
Page 28
10
10
Transformer bracket
Connectors
*Front of fi replace has been removed to show the electrical panel position within appliance.
Plastic grommet
Electrical Information
A. Recommendation for Wire
This appliance requires 110-120 VAC be wired directly to the transformer. See Figure 10.1.
1. Ensure that the electrical service being installed to the appliance is turned “OFF” by verifying with a volt meter.
WARNING
Shock hazard. Wire 110V to transformer. Do NOT wire 110V to valve. Do NOT wire 110V to wall switch.
• Incorrect wiring will damage millivolt valves.
• Incorrect wiring will override HSI safety lockout and may cause explosion.
2. Bring the electrical service wire through the wire re­straint located on the right side of the appliance. Leave about 10 inches of electric service wire inside the ap­pliance to permit for future service maintenance.
3. Locate the (2) female insulated connectors installed on the transformer and the (1) ground connector screwed to the right side of the transformer bracket.
Note: The factory installed yellow female insulated connectors (2) and yellow ground connector (1) are designed for use with 10/12 AWG wire. If another gauge wire is being used, these connectors should be replaced with the appropriate gauge insulated connectors to ensure a proper connection. See Figure 10.2.
4. Route electrical service wires through plastic grom­met as show in Figure 10.1. This plastic grommet is located on the right side of the Transformer bracket.
5. Connect the L1 (Black) service wire to the supplied yellow female insulated connector located on trans­former terminal (23) using a wire crimping tool. See Figure 10.2.
6. Connect the neutral (White) service wire to the yellow female insulated connector located on transformer ter­minal (1) using a wire crimping tool. See Figure 10.2.
7. Connect the ground (Green) wire to the 1/4 in. ground screw located on the front right of the transformer bracket. See Figure 10.2.
Connectors
Transformer bracket
Figure 10.2
Note: The system is polarity sensitive. Polarit y must be
correct for this fi replace to operate correctly.
Note: This appliance must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with National Electric Code ANSI/NFPA 70-latest edition or the Canadian Electric Code, CSA C221.1.
• A 110-120 V AC circuit for this product must be protected
with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks.
Plastic grommet
*Front of fi replace has been removed to show the electrical panel position within appliance.
Figure 10.1 Electrical Panel position inside Appliance with Front removed.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0828
Page 29
B. Connecting to the Appliance
WARNING
Wire 110V to terminal block. Do NOT wire 110V to valve. Do NOT wire 110V to wall switch.
• Incorrect wiring will damage this valve.
• Incorrect wiring will override HSI safety lockout and may cause explosion.
• This appliance comes factory wired with a remote control for operation. The remote can be removed and the appliance can be wired to run off of a standard wall switch. Refer to the wiring diagram for more information.
• Keep wire lengths short as possible by removing any excess wire length.
• Low voltage and 110 VAC voltage cannot be shared within the same wall box.
C. Hot Surface Ignition Wiring
This appliance requires a 110 VAC supply to the appli­ance terminal block for operation. A wiring diagram is shown in Figure 10.9. This appliance is equipped with a 24V valve.
Optional Accessories Requirements
Wiring for optional accessories should be done now to avoid reconstruction.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
WARNING
Shock hazard.
• Replace damaged wire with type 105º C rated wire.
• Wire must have high temperature insulation.
REMOTE
7
2
6
HOT SURFACE IGNITOR (HSI)
GROUND
(L1) 120-BLACK (N) NEUTRAL-WHITE
8
24 VOLT TRANS
1
CONTROL MODULE
1
3
5
9
4
3
FAN MOTOR
2
SENSOR
Figure 10.9 Wiring diagram
ITEM PART DESCRIPTION COLOR(S)
1 (M)L1 - (M)F1 - (T) 23 - -120V Black 2 (FT) BTM-IGN-(T)1- +120V Black/White 3 (V)1 & (V)3 - GND & (T)4 Blue/Green 4 (V)2 & (V)4 - (M)MV1 Red 5 (M) F2 - (FT) TOP White 6 (M)S1-IGN White 7 FEMALE RECEPTACLE PLUG Black/White/Green 8 REMOTE WITH PIGTAIL - (M)W OPTIONAL Red 9 (M)R - (M)W - (M)P.SW - REM/WS Red
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 29
Page 30
11
11
Finishing
A. Mantel Projections
This appliance is approved to be installed with a clearance to the ceiling and/or other projections of 34-3/8 inch minimum from the top of the fi replace (see Figure 11.1).
SLIP
SECTION
FRAMING
MEMBER
COMBUSTIBLE
MATERIAL
NON-COMBUSTIBLE
FIRESTOP
34-3/8 in.
TO CEILING
AND/OR MANTEL
TOP
OF UNIT
Figure 11.1 Clearances to mantels or other combustibles above appliance
GLASS
TUBE
(+0 to -1/2 in.)
41-3/8 in.
B. Facing Material
WARNING
Fire Risk. Do NOT obstruct air inlet or outlet grilles. Do NOT modify grilles.
• Modifying or covering grilles could cause temperature rise and fi re hazard.
Finishing materials must not interfere with:
• Air fl ow through grilles or louvers.
• Operation of louvers or doors.
• Access for service.
COMBUSTIBLE
ON SIDES
0 IN.
SEALANT MATERIAL
Figure 11.2 Facing Diagram
0 IN.
Sheetrock or other fi nishing materials can be brought to within 0 inches on the sides and bottom.
Finishing materials for the top of the fi replace base must be noncombustible and removable for access to controls. All clearances must be maintained (see Figure 11.3).
Ø 9-1/8 in. MIN.
OPENING
MATERIAL MUST BE NON-COMBUSTIBLE
AND REMOVABLE
TOP MUST
MAINTAIN 1/2 in.
CLEARANCE
1/2 in.
WARNING
Fire Risk. Finish all edges and fronts to clearances and
specifi cations listed in manual.
• Install combustible materials only up to specified clearances on top, front and side.
• Seal joints between the fi nished wall and appliance top and sides using only a 300º F minimum sealant.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0830
Figure 11.3
Page 31
12
12
Appliance Setup
A. Remove Shipping Materials
Remove shipping materials from inside or underneath the rebox.
B. Clean the Appliance
Clean/vacuum any sawdust that may have accumulated inside the fi rebox or underneath in the control cavity.
C. Accessories
Install approved accessories per instructions included with accessories. See Service Parts List for appropriate accessories. Refer to Section 15.
WARNING
Shock or fi re risk. Use ONLY optional accessories approved for
this appliance.
• Using non-listed accessories voids warranty.
• Using non-listed accessories may result in a safety hazard.
• Only Hearth & Home Technologies approved accessories may be used safely.
Figure 12.2 Position the bottom of the glass assembly by centering it on the platform as shown.
D. Glass Assembly Installation
LOCKING
HOOKS
Figure 12.1
Figure 12.3 Once the glass cylinder is centered, while
pushing down, twist the glass cylinder clockwise to en­gage the locking hooks. Turn the glass cylinder counter­clockwise while pushing down to remove.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 31
Page 32
13
13
Operating Instructions
A. Before Lighting Appliance
Before operating this appliance have a qualifi ed tech- nician:
• Remove all shipping materials from inside and/or underneath the fi rebox.
• Check the wiring.
• Ensure that there are no gas leaks.
• Ensure that the glass is sealed and in the proper position.
• Ensure that the fl ow of combustion and ventilation air is not obstructed (front grilles and vent caps).
WARNING
Glass cylinder must be in place when appliance is operating.
Risk of:
• Combustion Fumes
• Fire Do NOT operate appliance with glass cylinder
removed.
• Remove glass cylinder for servicing only.
• Glass replacement should be done by qualifi ed technician. qualifi ed technician.
WARNING
HOT SURFACES!
Glass and other surfaces are hot during operation AND cool down.
Hot glass will cause burns.
• Do not touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other ammable materials.
• Keep clothing, furniture, draperies and other fl ammable materials away.
This appliance has been supplied with an integral barrier to prevent direct contact with the fi xed glass panel. Do NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to the owner’s information manual provided with this appliance. For assistance or additional information consult a qualifi ed installer, service agency or the gas supplier.
WARNING
Do NOT use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0832
Page 33
B. Lighting Appliance HSI Ignition
FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: If you do not follow these instructions
exact ly, a fi re or explosion may result causing proper t y damage, personal injury or loss of life.
A. This appliance is equipped with an
hot surface ignition device which automatically lights the burner. Do not try to light the burner by hand.
B. BEFORE LIGHTING, smell all
around the appliance area for gas. Be sure to smell next to the fl oor because some gas is heavier than air and will settle on the fl oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier
WARNING:
DO NOT CONNECT 110 VAC TO THE CONTROL VALVE.
Improper installation, adjustment, al­teration, service or maintenance can cause injury or property damage. Re­fer to the owner’s information manual provided with this appliance.
This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air.
If not installed, operated, and main­tained in accordance with the man­ufacturer’s instructions, this product could expose you to substances in fuel or fuel combustion which are known to the State of California to cause can­cer, birth defects, or other reproduc­tive harm.
Keep burner and control compartment clean. See installation and operating instructions accompanying appliance.
from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas su­pplier, call the fi re department.
C. Do not use this appliance if any
part has been under water. Imme­diately call a qualifi ed service tech- nician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
CAUTION:
Hot while in operation. Do not touch. Keep children, clothing, furniture, gaso­line and other liquids having fl ammable vapors away.
Do not operate the appliance with panel(s) removed, cracked or broken. Replacement of the panel(s) should be done by a licensed or qualifi ed service person.
NOT FOR USE
WITH SOLID FUEL
This appliance is only for use with the type(s) of gas indicated on the rating plate. This appliance is not convert­ible to other gases.
Also Certifi ed for Installation in a Bedroom or a Bedsitting Room.
For assistance or additional informa­tion, consult a qualifi ed installer, ser- vice agency or the gas supplier.
LIGHTING
INSTRUCTIONS
(HSI)
1. Turn off all electric power to the appliance.
2. This appliance is equipped with an ignition
device which automatically lights the burner. Do not try to light the burner by hand.
3. Wait fi ve (5) minutes to clear out any gas. Then smell for gas, including near the fl oor. If you smell gas, STOP! Follow “B” in the Safety Information located on the left side of this la­bel. If you don’t smell gas, go to next step.
4. Turn on all electric power to the appliance.
5. To light the burner, ip the ON/OFF switch to
the “ON” position. (The ON/OFF switch may include a wall switch if so equipped).
6. It will take 15 to 30 seconds for the hot surface ignitor to warm-up before an ignition attempt is made.
7. If the appliance will not operate, follow the in­structions “To Turn Off Gas to Appliance” and call your service technician or gas supplier.
TO TURN OFF
GAS TO APPLIANCE
1. Turn off all electric power to the appliance if
service is to be performed.
2. Flip ON/OFF switch to the “OFF” position.
3. Turn gas off to this unit.
Hearth & Home Technologies fi replace, please refer to www.fi replaces.com.
For additional information on operating your
Final inspection by
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 33
2073-913C
Page 34
C. After Appliance is Lit
Initial Break-in Procedure
When you light the appliance, you may notice that it pro­duces heat which does have an associated odor or smell. If you feel this odor is excessive it may require the initial three to four hour continuous burn on high followed by a second burn up to 12 hours to fully drive off any odor from paint and lubricants used in the manufacturing process. Condensation of the glass is normal.
CAUTION
• Prevent accidental appliance operation when not attended.
• Unplug or remove batteries from remote control if absent or if appliance will not be used for an extended period of time.
• Property damage possible from elevated temperatures.
Note: The appliance should be run three to four hours on the initial start-up. Turn it off and let it cool completely. Remove and clean the glass. Replace the glass and run the appliance for an additional 12 hours. This will help to cure the products used in the paint and logs.
During this break-in period it is recommended that some windows in the house be opened for air circulation. This will help avoid setting off smoke detectors, and help eliminate any odors associated with the appliance’s initial burning.
WARNING
Fire Risk. High Temperatures. Keep combustible household items away from
appliance. Do NOT obstruct combustion and ventilation air.
• Do NOT place combustible items on top of or in front of appliance.
• Keep furniture, draperies away from appliance.
CAUTION
Smoke and odors released during initial operation.
• Open windows for air circulation.
• Leave room during initial operation.
• Smoke may set off smoke detectors.
Smoke and odors may be irritating to sensitive individuals.
WARNING
Fire Hazard. Keep combustible materials, gasoline and
other fl ammable vapors and liquids clear of appliance.
• Do NOT store fl ammable materials in the appliance’s vicinity.
• Do NOT use gasoline, lantern fuel, kerosene, charcoal lighter fl uid or similar liquids in this appliance.
• Combustible materials may ignite.
D. Frequently Asked Questions
ISSUE SOLUTIONS
Condensation on the glass
Blue fl ames
Odor from appliance
Film on the glass The glass cylinder can be cleaned with standard household glass cleaner. See glass assem-
Metallic noise
This is a result of gas combustion and temperature variations. As the appliance warms, this condensation will disappear.
This is a result of normal operation and the fl ames will begin to yellow as the appliance is al- lowed to burn for 8 to 5 minutes.
When fi rst operated, this appliance may release an odor for the fi rst several hours. This is caused by the curing of the paint and the burning off of any oils remaining from manufactur­ing. Odor may also be released from fi nishing materials and adhesives used around the appliance.
bly installation section for removal information. Noise is caused by metal expanding and contracting as it heats up and cools down, similar to
the sound produced by a furnace or heating duct. This noise does not affect the operation or longevity of the fi replace.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0834
Page 35
14
14
Although the frequency of appliance servicing and maintenance will depend on use and the type of installation, a qualifi ed service technician should perform an appliance checkup at the beginning of each heating season.
Maintaining and Servicing Appliance
WARNING
Risk of injury or property damage.
Before servicing:
• Turn off gas.
• Turn off electricity to appliance.
• Disable remote control, if one is present.
• Ensure appliance is completely cooled.
After servicing:
• Replace any screen or barrier that was removed.
• Reseal and reinstall any venting removed for servicing.
WARNING
Annual inspection by qualifi ed technician recommended.
Check:
• Condition of doors, surrounds and fronts.
• Condition of glass, glass assembly and glass seal.
• Obstructions of combustion and ventilation air.
• Condition of fi rebox.
• Burner ignition and operation.
• Gas connections and fi ttings.
• Obstructions of termination cap.
Clean:
• Glass
• Air passageways, grilles, control compartment
• Burner, burner ports
Risk of:
• Fire
• Delayed ignition or explosion
• Exposure to combustion fumes
• Odors
CAUTION
Handle glass assembly with care.
Note: Clean glass after initial 3-4 hours operation. Longer operation without cleaning glass may cause a permanent white fi lm on glass.
When cleaning glass assembly:
• Avoid striking, scratching or slamming glass.
• Do NOT use abrasive cleaners.
• Use a hard water deposit glass cleaner on white fi lm.
• Do NOT clean glass when hot.
• Turn off appliance after 3-4 hours of operation and ALLOW TO COOL.
• Remove and clean glass assembly.
• Replace glass assembly and operate appliance for additional 12 hours.
Refer to maintenance instructions.
A. Fan Motor Service
To service the fan motor , remove the glass assembly (see Glass Assembly Removal Instructions) and remove all screws from the top.
SCREWS
WARNING
Inspect external vent cap regularly.
• Ensure no debris blocks cap.
• Combustible materials blocking cap may ignite.
• Restricted air fl ow affects burner operation.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 35
Figure 14.1
Page 36
Figure 14.2 The glass platform plate can now be removed
by removing the 13 screws on the outer edge of this plat­form. Lift the platform. The HSI (Hot Surface Ignitor) and the sensor wire can be unplugged. Set platform aside.
Figure 14.4 The fan plate can now be accessed. Remove the four screws. Lift the fan plate, being careful to not cut or scar wiring while disconnecting them from the fan motor.
Figure 14.3 Remove the tube burner. It is held in place with one screw. Pull the burner tube away from orifi ce holder, rotating burner tube slightly, and remove it from the orifi ce.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0836
Page 37
B. Maintenance Tasks
Inspect Maintenance Tasks
1. Inspect for scratches, dents or other damage and repair as necessary.
Doors, Surrounds and Fronts
Gasket Seal, Glass Assembly and Glass
Valve Compartment and Firebox Top
2. Verify no obstructions to air ow through the louvers.
3. Verify maintenance of proper clearance to combustible household objects.
1. Inspect gasket seal and its condition.
2. Inspect glass cylinder for scratches and nicks that can lead to breakage when exposed to heat.
3. Con rm there is no damage to glass or glass frame. Replace as necessary.
4. Clean glass. Replace glass assembly if severely coated with silicate deposits that cannot be removed.
1. Vacuum and wipe out dust, cobwebs, debris or pet hair. Use caution when cleaning these areas. Screw tips that have penetrated the sheet metal are sharp and should be avoided.
2. Remove any foreign objects.
3. Verify unobstructed air circulation.
1. Verify burner is properly secured and aligned with pilot or igniter.
2. Clean off burner top, inspect for plugged ports, corrosion or deterioration. Replace burner if necessary.
3. Check for smooth lighting and ignition carryover to all ports. Verify there is no ignition delay.
Burner Ignition and Operation
Venting
Remote controls 1. Verify operation of remote.
4. Inspect for lifting or other ame problems.
5. Verify air shutter is clear of dust and debris.
6. Inspect ori ce for soot, dirt or corrosion.
7. Verify manifold and inlet pressures. Adjust regulator as required.
1. Inspect venting for blockage or obstruction such as bird nests, leaves, etc.
2. Con rm that termination cap remains clear and unobstructed by plants, etc.
3. Verify that termination cap clearance to subsequent construction (building additions, decks, fences or
sheds) has been maintained.
4. Inspect for corrosion or separation.
5. Verify weather stripping, sealing and ashing remains intact.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 37
Page 38
15
15
Reference Materials
A. Appliance Dimension Diagram
Dimensions are actual appliance dimensions. Use for reference only. For framing dimensions and clearances refer to Section 3.
A
I
ELECTRICAL
ACCESS
B
C
D
GAS LINE
ACCESS
ELECTRICAL
O
E
ACCESS
FIRESTOP
F
GAS LINE
ACCESS
G
H
SLIP
SECTION
P
Q
N
J
L
K
Location Inches Millimeter Location Inches Millimeter Location Inches Millimeter
A 8/12 215 G 2-1/4 58 M 2 51 B 17 430 H 1-1/4 33 N 2-1/2 64 C 8-1/2 215 I 7-7/8 200 O 42-1/8 1069 D 17 430 J 6-7/8 174 P 32-3/4 831 E 2 51 K 1-1/2 39 Q 41-3/8 1050
F 2-3/4 71 L 2-1/4 57
Figure 15.1 Appliance Dimensions
M
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0838
Page 39
B. Vent Components Diagrams
DVP Pipe (see chart)
10 in.
(254 mm)
24 in.
(610 mm)
Effective
Height/Length
Pipe
DVP4 4 102 DVP6 6 152 DVP12 12 305 DVP24 24 610 DVP36 36 914 DVP48 48 1219 DVP6A 3 to 6 76 to 152 DVP12A 3 to 12 76 to 305 DVP12MI 3 to 12 76 to 305 DVP24MI 3 to 24 76 to 610
Effective Length
Inches Millimeters
10 in.
(254 mm)
1 in.
(25 mm)
10-1/2 in. (267 mm)
4-7/8 in.
( 276 mm)
9-1/4 in.
(235 mm)
13-1/4 in. (337 mm)
10-7/8 in. (276 mm)
DVP45 (45 Elbow)
°
11-3/8 in. (289 mm)
7-3/8 in.
(187 mm)
1-1/4 in. (32 mm)
1/2 in.
TYP
(13 mm)
45
°
DVP-AS (Attic Shield)
10 in.
(254 mm)
UP
DVP-HVS (Vent Support)
5 in.
(127 mm)
DVP-FS (Ceiling Firestop)
1- 1/2 in.
(38 mm)
12 in.
(305 mm)
14 in.
(356 mm)
DVP90ST (90° Elbow)
12 in.
(305 mm)
6 in.
(152 mm)
DVP-WS (Wall Shield Firestop)
1 in. (25 mm)
8 in.
(203 mm)
Figure 15.2 DVP vent components
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 39
Page 40
B. Vent Components Diagrams (continued)
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm) the
existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B will be required.
8 in.
15-1/8 in.
Max
Effective
Length
Wall Shield Firestop
Wall Shield Firestop
DVP90ST
14 in.
Heat Shield
DVP-TRAP1
Horizontal Termination Cap Kit
Heat Shield
DVP-TRAP SERIES
Horizontal Termination Cap
DVP-TRAP1
DVP-TRAP1
Term Cap
Trap1
Trap2
Wall Shield Firestop
Horizontal Termination Cap Kit
(Shown with optional extended heat shield)
Wall Shield Firestop
DVP90ST
Minimum
Effective Length
3-1/8 in. 4-5/8 in.
79 mm 117 mm 5-3/8 in. 9-3/8 in. 137 mm 238 mm
HSM
Heat Shield
DVP-TRAP2
HSM
Heat Shield
Maximum
Effective Length
DVP-TRAP2
DVP-TRAP2
Horizontal Termination Cap Kit
DVP-TRAPK1
Figure 15.3 DVP vent components
Horizontal Termination Cap Kit
DVP-TRAPK2
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0840
Page 41
B. Vent Components Diagrams (continued)
DVP-HSM-B Extended Heat Shield
13-1/4 in.
(367 mm)
31 in.
(787 mm)
24-5/8 in.
(625 mm)
24-5/8 in.
(625 mm)
Roof Flashing Multi-pak
13-3/4 in. (349 mm)
13-3/4 in. (349 mm)
BEK
Trap Cap Brick Extension
Figure 15.4 DVP vent components
RF6M
27-1/2 in.
(127 mm)
13-1/4 in.
(367 mm)
RF12M
Roof Flashing Multi-pak
5 in.
(127 mm)
7-1/4 in.
(184 mm)
12-1/2 in. (318 mm)
5-1/4 in.
(133 mm)
DVP-TVHW
VerticalTermination Cap (Highwind)
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 41
Page 42
C. Service Parts
CYCLONE-CUST
Service Parts Diagram
2
1
Beginning Manufacturing Date: May 2004
Ending Manufacturing Date: ______
3
4
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement parts for your appliance please provide model number and serial number. All parts listed in this manual may be ordered from an authorized dealer.
ITEM DESCRIPTION COMMENTS PART NUMBER
1 Top Cover Assembly 2061-005 2 Tube Assembly 2061-015
3 Ignitor 4 Flame Sensor 2061-142 Y
Fan Blade 2061-108 Flue Restrictor 2.5” Hole 2061-203 Flue Restrictor 2.75” Hole 2061-204
Additional service part numbers appear on following page.
Pre Aug 2007 Post Aug 2007
SRV2061-165 Y 2061-165 Y
Stocked at Depot
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0842
Page 43
Service Parts
CYCLONE-CUST
V alve Assembly
Valve Assembly Parts List
5
6
10
9
7
1
2
11
Beginning Manufacturing Date: May 2004
Ending Manufacturing Date: ______
4
3
8
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement parts for your appliance please provide model number and serial number. All parts listed in this manual may be ordered from an authorized dealer.
ITEM DESCRIPTION COMMENTS PART NUMBER
1 Burner Tube 2073-025 Y 2 Transformer 060-599 Y
3 Control Module
4 Relay Solder / Plug In
5 Terminal Block
Pre Feb 2005 2061-138 Y Post Feb 2005 SRV2061-592 Y Pre Feb 2005 2073-158 Y Post Feb 2005 N/A Pre Aug 2007 2073-157 Y Post Aug 2007 N/A
6 Fan Motor, 120 V, 60H2, 71A 2061-308 Y 7 Electric Valve
Pre Nov 2005 31828 Y
Post Nov 2005 2061-023 Y 8 Flex Tube 2005-009 Y 9 Flex Ball Valve Assembly 302-320A Y
10 Heat Shield
Pre Feb 2006 2061-180
Post Feb 2006 2061-209
11 Heat Shield 2061-177
Orifi ce (#50C) 582-850 Y Wire Bundle Assembly
Pre Aug 2007 2073-009 Y
Post Aug 2007 2073-050 Y
Stocked at Depot
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 43
Page 44
D. Limited Lifetime Warranty Hearth & Home Technologies LIMITED WARRANTY
Hearth & Home Technologies (“HHT”) and its respective brands extends the following warranty for HHT gas, wood, pellet and electric appliances purchased from an authorized HHT dealer and installed in the United States of America or Canada. Warranty starts with date of purchase by the original owner (End User) except as noted for replacement parts.
Warranty Period HHT Manufactured Appliances and Venting Parts Labor Gas Wood Pellet
1 Year XXXXXX
EPA
Wood
Electric Venting
Components Covered
All Parts and Material Except as
covered by Conditions, Exclusion,
and Limitations listed
XX
2 years
3 years X Firepots
5 years 3 years X X Castings & Baffl es
7 years 3 years X X X
10 years 1 year X Burners, Logs & Refractory
Limited
Lifetime
1 year X Firebox & Heat Exchanger
90 Days XXXXXX All Replacement Parts
XXXX Blowers
X Molded Refractory Panels
Igniters, Electronic Components,
and Glass
Firebox, HHT Chimney,
Termination & Heat
Exchanger
See Conditions, Exclusions, and limitations. 9-01-08
CONDITIONS, EXCLUSIONS & LIMITATION OF LIABILITY
This warranty applies to the original owner and is transferable up to two years from date of purchase to the new homeowner, provided the purchase was made through an authorized dealer or distributor of HHT, and the appliance remains in its original place of installation.
The maximum amount recoverable under this warranty is limited to the purchase price of the product.
In no event shall HHT be liable for any incidental or consequential damages caused by defects in the product.
Adjustments, regular maintenance, cleaning and temporary repairs, or the failure to duplicate the problem in the home is not covered under this warranty.
Page 1 of 2 4021-645A 09-01-08
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0844
Page 45
D. Limited Lifetime Warranty (continued)
• This limited warranty does not extend to or include surface fi nish on the appliance or terminations, door gasketing, glass gasketing, glass discoloration, fi rebrick, pellet logs, kaowool or other ceramic insulating materials. Rust and/or corrosion on any of the metal surfaces, cast iron components, baffl es, fi repots, doors, or fi rebox area are not covered by this warranty.
• Noise resulting from minor expansion, contraction, or movement of certain parts is normal and complaints related to this noise are not covered by this warranty.
• HHT’s obligation under this warranty does not extend to damages resulting from: (1) installation, operation or maintenance of the appliance not in accordance with the installation instructions; operating instructions and the listing agent identifi cation label furnished with the appliance; (2) installation which does not comply with local building codes; (3) shipping, improper handling, improper operation, abuse, misuse, accident or unworkmanlike repairs; (4) environmental conditions, inadequate ventilation or drafting caused by tight sealing construction of the structure or handling devices such as exhaust fans or forced air furnaces or other such causes; (5) use of fuels other than those specifi ed in the operating instructions; (6) installation or use of components not supplied with the appliance or any other components not expressly authorized and approved by HHT; and/or (7) modifi cation of the appliance not expressly authorized and approved by HHT in writing.
• This warranty does not apply to non-HHT venting components, hearth components or other accessories used in conjunction with the installation of this product.
• This warranty is void if the appliance has been over-fi red or operated in atmospheres contaminated by chlorine, fl uorine, or other damaging chemicals the appliance is subject to prolonged periods of dampness or condensation, or there is any damage to the appliance or other components due to water or weather damage which is the result of, but not limited to, improper chimney or venting installation.
• HHT’s liability under this warranty is limited to the replacement and repair of defective components or workmanship during the applicable period. HHT may fully discharge all of its obligations under such warranties by repairing the defective component(s) at HHT’s discretion. Shipping costs are not covered under this warranty.
• Some states do not allow exclusions or limitation of incidental or consequential damages, so those limitations may not apply to you. This warranty gives you specifi c rights; you may also have other rights, which vary from state to state.
• EXCEPT TO THE EXTENT PROVIDED BY LAW, HHT MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY SPECIFIED HEREIN. THE DURATION OF ANY IMPLIED WARRANTY IS LIMITED TO DURATION OF THE WARRANTY SPECIFIED ABOVE.
This Limited Warranty is effective on all HHT appliances sold after September 01, 2008 and supersedes any and all warranties currently in existence.
If warranty service is needed, you should contact your installing dealer. If the installing dealer is unable to provide necessary parts or components, contact the nearest authorized HHT dealer or supplier.
Page 2 of 2 4021-645A 09-01-08
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/08 45
Page 46
E. Contact Information
Heat & Glo, a brand of Hearth & Home Technologies Inc.
20802 Kensington Boulevard, Lakeville, MN 55044
www.heatnglo.com
Please contact your Heat & Glo dealer with any questions or concerns.
For the location of your nearest Heat & Glo dealer,
please visit www.heatnglo.com.
- NOTES -
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
CAUTION
DO NOT DISCARD THIS MANUAL
• Important operating and maintenance instructions included.
• Read, understand and follow these instructions for safe installation and operation.
• Leave this manual with party responsible for use and operation.
This product may be covered by one or more of the following patents: (United States) 4593510, 4686807, 4766876, 4793322, 4811534, 5000162, 5016609, 5076254, 51 13843, 5191877, 5218953, 5263471, 5328356, 5341794, 5347983, 5429495, 5452708, 5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237, 5947112, 5996575, 6006743, 6019099, 6048195, 6053165, 6145502, 6170481, 6237588, 6296474, 6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940, 6748942, 6769426, 6774802, 6796302, 6840261, 6848441, 6863064, 6866205, 6869278, 6875012, 6880275, 6908039, 6919884, D320652, D445174, D462436; (Canada) 1297749, 2195264, 2225408, 2313972; (Australia) 780250, 780403, 1418504 or other U.S. and foreign patents pending.
Heat & Glo • Cyclone-Cust • 2061-900 Rev. L • 10/0846
Printed in U.S.A. - Copyright 2008