Hearth and Home Technologies CR36D, CL36D User Manual

Page 1
CL36D and CR36D
WOODBURNING FIREPLACE
INSTALLATION & OPERATING
INSTRUCTIONS
WARNING!
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a qualified installer, service agency or the gas supplier.
02-02 1 12538 Rev D
Page 2
CL36D AND CR36D INSTALLATION INSTRUCTIONS
Table of Contents
Design and Installation Considerations ........................................................................................... 3
A. Listings and Code Approvals .......................................................................................................... 4
B. Description of the Fireplace System .............................................................................................. 4
C. Fireplace System Components ...................................................................................................... 5
D. Pre-Installation Preparation .......................................................................................................... 10
E. Chimney Requirements................................................................................................................ 12
F. Installation of Fireplace ................................................................................................................ 15
G. Constructing a Chase .................................................................................................................. 22
H. Operating Instructions .................................................................................................................. 25
I. Maintenance Instructions ............................................................................................................. 29
Index ........................................................................................................................................... 31
Warranty ...................................................................................................................................... 32
CAUTION:
Do not expose the fireplace to the elements (i.e. rain, etc.) and keep the fireplace dry at all times. Wet insulation will produce an odor when the fireplace is used.
SAFETY PRECAUTIONS
1. Please read these installation instructions completely
before beginning installation procedures. Failure to follow them could cause a fireplace malfunction resulting in serious injury and/or property damage.
2. Always check your local building codes prior to
installation. The fireplace installation must comply with all local, regional, state and national codes and regulations.
3. An adequate supply of replacement combustion air
from outside the house must be available to the fire for the fireplace to operate properly. To achieve this, the use of the optional outside air kit is highly recommended.
In the event the home is unusually tightly sealed, the optional combustion air kit may not provide all the air required to support combustion. Hearth Technologies Inc. is not responsible for any smoking or related problems that may result from the lack of adequate combustion air. It is the responsibility of the builder/ contractor to ensure that adequate combustion air has been provided for the fireplace.
4. This fireplace must be installed with the Hearth
Technologies Inc. (HTI) SL Series Chimney System.
The chimney system must always terminate outside the building. Be sure to follow all chimney specifications given in these installation instructions.
5. NEVER leave children unattended when there is a fire
burning in the fireplace.
6. This woodburning fireplace is built for solid fuel only. NEVER use gasoline, gasoline type lantern fuel,
kerosene, charcoal lighter fluid, or similar liquids in this fireplace. Keep any flammable liquids a safe distance from the fireplace.
7. DO NOT use chimney cleaners or flame colorants in your fireplace.
8. The flue damper must be open at all times when the fireplace is in use.
9. While servicing this fireplace, always shut off any electricity or gas to the fireplace. This will prevent possible electric shock or burns. Also, make sure the fireplace is completely cooled before servicing.
10. To ensure a safe fireplace system and to prevent the build up of soot and creosote, inspect and clean the fireplace and chimney prior to use and periodically during the burning season. See page 29 for cleaning instructions.
Page 3
CL36D AND CR36D INSTALLATION INSTRUCTIONS
DESIGN AND INSTALLATION CONSIDERATIONS
When selecting a location for your woodburning fireplace, it is important to evaluate a number of considerations. Modern construction techniques can create conditions that may not allow your chimney to draft properly. This may result in smoke spillage from your fireplace, as well as cause other combustion appliances to operate incorrectly.
Tightly sealed construction is important for energy efficiency. Unfortunately, a great deal of effort has been directed to tightening up sidewall construction, while considerably less attention has been paid to tightening upper portions of the warm air envelope (insulated ceilings). This has increased the Stack Effect, a condition that increases the negative pressure generated by the structure. This negative pressure will directly affect the drafting performance of a fireplace chimney. To minimize the negative pressure generated by stack effect, make certain that all ductwork installed in the attic spaces is sealed airtight. Minimize the number of recessed light fixtures installed in the insulated ceiling, and use sealed recessed light fixtures. Finally, make certain the whole house fans and attic access panels are tightly sealed. These are important design considerations that must be observed during the design and construction stage of the home.
If you desire to put a fireplace in your basement, we recommend that you consider a direct vent gas fireplace. Basements always have a significant negative air pressure that causes the fireplace system to be more susceptible to smoke spillage and cold flue backdrafting. Since direct vent gas fireplaces are sealed, they are not affected by the negative pressure that exists in basements.
Finally, woodburning fireplaces perform best when their chimney (roof termination) is located on the upper half of the roof, especially when cathedral ceilings are present. Chimneys that are located on the lower half of the roof realize what is known as lazy flue and will not draft as well as a chimney that is located in the upper portion of the roof. The reason for this is that the stack effect generated by the overall height of the living spaces inside the house will exceed the draft generated by the chimney system. If you desire to place a woodburning fireplace in a location where the termination cap would be located on the lower half of a roof, such as on an outside wall at the base of a cathedral ceiling, we recommend that you consider using a direct vent gas fireplace. This will assure the homeowner a fireplace that operates correctly.
These properties do not affect just your woodburning factory built fireplace. They can cause any woodburning fireplace as well as any conventionally vented (B-vent) gas appliance to operate improperly. Careful planning at this stage of your project will ensure satisfaction with the operation of your fireplace once it is completed.
02-02 3 12538 Rev D
Page 4
CL36D AND CR36D INSTALLATION INSTRUCTIONS
A. LISTINGS AND CODE APPROVALS
This fireplace system has been tested and listed in accordance with UL 127 standards, and has been listed by Underwriters Laboratories Inc. for installation and operation in the United States and Canada.
This fireplace has been tested and listed for use with the optional components listed on page 5. These optional components may be purchased separately and installed at a later date. However, installation of an outside air kit will require significant reconstruction, and should be installed at the time of the initial fireplace installation.
Check with your local building code agency prior to installing this fireplace to ensure compliance with local codes, including the need for permits and follow-up inspections. If you need assistance during installation, please contact your local dealer or the Heatilator Technical Services Department, Hearth Technologies Inc., 1915 W. Saunders St., Mt. Pleasant, Iowa 52641 (1-800-843-2848).
Heatilator® is a registered trademark of Hearth Technologies Inc., Division, HON INDUSTRIES.
WARNING!
This fireplace and its components are designed to be installed and operated as a system. Any alteration to or substitution for items in this system, unless allowed by these installation instructions, will void the Underwrit­ers Laboratories listing and may void the product warranty. It may also create a hazardous installation. Read through these instructions thoroughly before starting your installation and follow them carefully throughout your project.
B. DESCRIPTION OF THE FIREPLACE SYSTEM
1. The Heatilator fireplace system consists of the following: a. Fireplace/Integral Grate/Outside Combustion Air System b. Refractory c. Chimney Termination Cap d. Chimney System e. Hearth Extension
2. Optional Components Include: a. Glass Doors b. Chimney Air Kit
Note: Illustrations used throughout these instructions
reflect typical installations and are for design purposes only. Actual installation may vary slightly due to indi­vidual design preferences. However, minimum and maxi­mum clearances must be maintained at all times.
The illustrations and diagrams used throughout these installation instructions are not drawn to scale.
Figure 1 - Typical Fireplace System
Page 5
CL36D AND CR36D INSTALLATION INSTRUCTIONS
C. SYSTEM COMPONENTS
1. Fireplace Components
#golataC:noitpircseD
D63RC/D63LCspirtSnoitcetorPhtraeHdnaetarGlargetnIhtiw,ecalperiF
6341MDkcalB-weiV-raelC,dlof-iB-srooDssalG
B6341MDssarBdehsiloP-weiV-raelC,dlof-iB-srooDssalG S6341MDleetSsselniatS-weiV-raelC,dlof-iB-srooDssalG
6341PDkcalB-detniT-srooDssalG
B6341PDssarBdehsiloP-detniT-srooDssalG S6341PDleetSsselniatS-detniT-srooDssalG 6341EPDlenaPdnE-srooDssalG
B6341EPDssarBdehsiloP-lenaPdnE-srooDssalG S6341EPDleetSsselniatS-lenaPdnE-srooDssalG
3XHnoisnetxEhtraeH
R3RG/L3RG)ecalperiFhtiwdedulcni(etarGlargetnI
41KA)ecalperiFhtiwdedulcni(tiKriAedistuO
Bi-Fold Glass Doors
DM1436 DM1436B DM1436S
GR3L/GR3R Integral
Grate
02-02 5 12538 Rev D
Perception Glass Doors
DP1436 DP1436B DP1436S
Perception Glass Door
End Panel
DPE1436 DPE1436B DPE1436S
HX3 - Hearth Extension
Page 6
CL36D AND CR36D INSTALLATION INSTRUCTIONS
Fireplace Dimensions
AK14 - Outside Air Kit
Page 7
CL36D AND CR36D INSTALLATION INSTRUCTIONS
2. Chimney Components
The following pictures show only those chimney components which may be safely used with this fireplace.
#golataC:noitpircseD
A4KACtiKriAyenmihC
4DIriAedistuO/tcuDdetalusnI
4DUriAedistuO/tcuDdetalusninU
603LSgnol"6-noitceSyenmihC 213LSgnol"21-noitceSyenmihC 813LSgnol"81-noitceSyenmihC 423LSgnol"42-noitceSyenmihC 633LSgnol"63-noitceSyenmihC 843LSgnol"84-noitceSyenmihC
3LSrezilibatSyenmihC
513L51-nruteR/tesffOyenmihC 033L03-nruteR/tesffOyenmihC 833SF 933S51-potseriF 043S03-potseriF
8SAdleihSnoitalusnIcittAthgiartS
778BJdnaBtnioJyenmihC
678BCtekcarByenmihC
073FRhctiP21/6ottalF-gnihsalFfooR
173FRhctiP21/21ot21/6-gnihsalFfooR 443RTpaCnoitanimreTdnuoR 243RTpaCnoitanimreTgnipocseleTdnuoR 573TSpaCnoitanimreTerauqS 543STpaCnoitanimreTerauqS
P543STdetniaP-paCnoitanimreTerauqS
53TCpoTesahC
33SDL'3x'3-duorhSevitaroceD
64SDL'6x'4-duorhSevitaroceD
thgiartS-potseriF
02-02 7 12538 Rev D
Page 8
Chimney Sections
#golataCAB
603LS"6"¾4 213LS"21"¾01 813LS"81"¾61 423LS"42"¾22 633LS"63"¾43 843LS"84"¾64
=AhtgnellautcA =Bfohtgnel(htgnelevitceffE
CL36D AND CR36D INSTALLATION INSTRUCTIONS
SL3 - Chimney Stabilizer
sahtiretfatrapyenmihc
)rehtonaotdeppansneeb
Offset/Return
#golataCA
513L51
033L03
Firestop Spacer
#golataCAB
833S0"½41 933S5181 043S03"32
CB876
Chimney Bracket
RF370 - Roof Flashing
Flat to 6/12 Pitch
3
/8"
JB877
Joint Band
RF371 - Roof Flashing
6/12 to 12/12 Pitch
AS8
Straight Attic
Insulation Shield
Page 9
CL36D AND CR36D INSTALLATION INSTRUCTIONS
LDS33 (3 x 3) LDS46 (4 x 6)
Decorative Shroud
ST375
Square
Termination Cap
TR344 Round
Termination Cap
TS345/TS345P
Square
Termination Cap
TR342
Round Telescoping
Termination Cap
CT35
Chase Top
02-02 9 12538 Rev D
CAK4A
Chimney Air Kit
Page 10
CL36D AND CR36D INSTALLATION INSTRUCTIONS
WARNING!
To prevent contact with sagging or loose insulation, the fireplace must not be installed against vapor barriers or exposed insulation. Localized overheating could occur and a fire could result.
D. PRE-INSTALLATION PREPARATION
1. Fireplace Locations and Space Requirements
Several options are available to you when choosing a location for your fireplace. This fireplace may be used as a room divider, installed along a wall, across a corner or used in an exterior chase. See Figure 2.
Locating the fireplace in a basement, near frequently opened doors, central heat outlets or returns, or other locations of considerable air movement can affect the performance and cause intermittent smoke spillage from the front of the fireplace. Consideration should be given to these factors before deciding on a location.
CLEARANCES!
A minimum ½ air clearance must be maintained at the back and side of the fireplace assembly.
Chimney sections at any level require a 2 minimum air space clearance between the framing and chimney section.
Figure 2 - Fireplace Locations
Figure 3 shows a typical installations assuming an outside air kit is being used. Therefore, an allowance must be made for 90° bends. Less space is required when ducting goes directly outside without forming elbows.
These are rough framing
dimensions only.
htiW
riAedistuO
"44=A63=A
Figure 3
Installation Along a Wall or an Exterior Chase
tuohtiW
riAedistuO
5
/8"
WARNING!
Do not draw outside air from garage spaces. Exhaust products of gasoline engines are hazardous. Do not install outside air ducts such that the air may be drawn from attic spaces, basements or above the
roofing where other heating appliances or fans and chimneys exhaust or utilize air. These precautions will reduce the possibility of fireplace smoking or air flow reversal.
Page 11
CL36D AND CR36D INSTALLATION INSTRUCTIONS
2. Framing the Fireplace
The CL36D/CR36D fireplace will fit a framed opening of 44 or 365/8 wide (depending on where the outside air is located) x 42½ tall. The finished cavity depth must be no less than 22½.
Figure 4 shows a typical framing (using 2 x 4 lumber) of the fireplace, assuming combustible materials are used. All required clearances to combustibles around the fireplace must be adhered to. Any framing across the top of the fireplace must be above the level of the top standoffs. Chimney sections at any level require a 2 minimum air
space clearance between the framing and chimney section.
Figure 4 - Framing the Fireplace
CLEARANCES!
A minimum ½ air clearance must be maintained at the back and side of the fireplace assembly.
Chimney sections at any level require a 2 minimum air space clearance between the framing and chimney section.
WARNING!
Do not apply combustible finishing materials over any part of the black face of this fireplace or a structure fire may result. The black metal fireplace front may only be covered with noncombustible materials such as ce­ramic tile, brick or stone. Do not cover or block any cooling air slots. Do not cover any portion of the opening to the fireplace that would prevent the installation of an authorized glass door.
02-02 11 12538 Rev D
Page 12
CL36D AND CR36D INSTALLATION INSTRUCTIONS
3. Sidewalls/Surrounds
Adjacent combustible side walls must be located a minimum of 18 from the fireplace opening. See Figure below. If you are using a decorative surround constructed of combustible material, it must be located within the shaded area defined below. Short stub walls are also acceptable if they are contained within the shaded area.
E. CHIMNEY REQUIREMENTS
When planning your fireplace location, the chimney construction and necessary clearances must be considered. The fireplace system and chimney components have been tested to provide flexibility in construction. The following figures are the minimum distances from the base of the fireplace.
1. Minimum overall straight height 14 ft.
2. Minimum height with offset/return 14.5 ft.
3. Maximum height 50 ft.
4. Maximum chimney length between an offset and return 20 ft.
5. Maximum distance between chimney stabilizers 35 ft.
6. Double offset/return minimum height 20 ft.
7. Maximum unsupported chimney length between the offset and return 6 ft.
8. Maximum straight unsupported chimney height above the fireplace 35 ft.
Page 13
CL36D AND CR36D INSTALLATION INSTRUCTIONS
1. Using Offsets and Returns
a. To bypass any overhead obstructions, the chimney may be offset using a 15° (SL315) or a 30° (SL330) offset/
return. Perform the following steps to determine the correct chimney component combination for your particular installation.
b. An offset and return may be attached together or a chimney section(s) may be used between an offset and
return.
1) Measure how far the chimney needs to be shifted to enable it to avoid the overhead obstacle. See Figure 5,
dimension A to determine chimney sections required to achieve the needed shift.
2) After determining the offset dimension, refer to Table 1 and find the A dimension closest to but not less than the distance of shift needed for your installation.
3) The B dimension that coincides with the A dimension represents the required vertical clearance that is
needed to complete the offset and return.
4) Read across the chart and find the number of chimney sections required and the model number of those particular chimney parts.
5) Whenever the chimney penetrates a floor/ceiling, a firestop spacer must be installed.
6) The effective height of the fireplace assembly is 38½ and is measured from the base of fireplace to top
of starter collar.
WARNING!
Do not combine offsets to create an offset greater than 30° from vertical. This may create a fire hazard since the natural draft may be restricted.
Table 1 Offset Chart*
°503
5
/8"313/8"37/8"411/2"------
1
7
/8"713/4"61/4"815/8"1 - - - - -
2
--8
1
4
/2"325/8"91/4"323/4"- 1 - - - -
--11
3
"692
1
7
/4""43415/8""33-2----
/8"211/4""92--1---
--51
--71
--02
5
/8"643/4"121/4"445/8"----1-
01
7
/8"153/8"325/8"843/8"1 - - - 1 -
11
--62
3
/4"853/8"721/4"553/4"-----1
31
"51"3692
1
61
/2"863/4"235/8"461/4"- 1 - - - 1
"8147
5
/8"535/8"961/2"--1--1
--83
-- "1487
3
/4"197/8"445/8""58----11
22
"4269
7
/8"3011/2"055/8"591/2"-----2
52
1
/2""74981/8"1 - - - 1 1
5
/8""¾222-----
5
/8"727/8"11-- --
1
/4"431/8"---1--
5
/8"831/4"1 - - 1 - -
5
/8"341/2"- - 2 - - -
5
/8"357/8"---2--
5
/8""951----1
5
/8"475/8"---1-1
3
/4"1 - - 1 - 1
* Proper assembly of air cooled chimney parts result in an overlap at chimney
joints of 1¼. Effective length is built into this chart.
603LS213LS813LS423LS633LS843LSABAB
Figure 5 - Chimney Offset/
Return
Example: Your A
dimension from Figure 7 is 14½. Using Table 1 the dimension closest to, but not less than 14½ is 14
5
/8 using a 30° offset/return. It is then determined from the table that you would need 33 (Dimension B) between the offset and return. The chimney components that best fit your application are two SL312s.
02-02 13 12538 Rev D
Page 14
CL36D AND CR36D INSTALLATION INSTRUCTIONS
2. Chimney Height Requirements (above roof line)
a. Major building codes specify a minimum chimney
height above the roof top. These specifications are summarized in what is known as the Ten Foot Rule. This rule states:
If the horizontal distance from the side of the chimney to the peak of the roof is ten feet or less, the top of the chimney must be at least two feet above the peak of the roof, but never less than three feet in overall height above the highest point where it passes through the roof.
If the horizontal distance from the side of the chimney to the peak of the roof is more than ten feet, a chimney height reference point is established on the surface of the roof a distance of ten feet from the side of the chimney in a horizontal plane. The top of the chimney must be at least two feet above this reference point, but never less than three feet in height above the highest point where it passes through the roof. See Figure 6.
b. These chimney heights are necessary in the
interest of safety but do not ensure smoke-free operation. Trees, buildings, adjoining roof lines, adverse wind conditions, etc. may create a need for a taller chimney should smoking occur.
3. Number of Sections Required
To determine the chimney components needed to complete your particular installation, follow the steps below:
a. Determine the total vertical height of the fireplace
installation. This dimension is measured from the base of the fireplace assembly to the point where the smoke exits the termination cap.
b. Subtract the effective height of the fireplace
assembly (38½) from the overall height of the fireplace installation (measured from the base of the fireplace to the bottom of the termination cap).
c. Refer to Table 2 to determine what components
must be selected to complete the fireplace installation.
d. Determine the number of firestop spacers,
stabilizers, roof flashing, etc. required to complete the fireplace installation.
Figure 6 - Chimney Height
Table 2
STNENOPMOCYENMIHCFOTHGIEH
rezilibatSyenmihC
3
3LS4
srecapSpotseriF
833SF"0 933SF"0 043SF"0
snruteR/stesffO
513LS31 033LS
gnihsalFfooR
073FR0 173FR0
*snoitceSyenmihC
603LS4 213LS01 813LS61 423LS"¾22 633LS43 843LS64
*Dimensions reflect effective height.
/4"
3
/8"
41
½
"
3
/4"
3
/4"
3
/4"
3
/4"
3
/4"
Page 15
CL36D AND CR36D INSTALLATION INSTRUCTIONS
F. INSTALLATION OF FIREPLACE
WARNING!
Before starting, do the following:
1. Wear gloves and safety glasses for protection.
2. Keep hand tools in good condition. Sharpen cutting edges and make sure tool handles are secure.
3. Always maintain the minimum air space required to the enclosure to prevent fire.
1. Positioning the Fireplace
This fireplace may be placed on either a combustible or noncombustible continuous flat surface. Follow the instructions for framing on pages 10-12. Slide the fireplace into position. Be sure to provide the
minimum ½ air clearance at the sides and back of the fireplace assembly.
2. Placing the Protective Metal Hearth Strips
Included with your fireplace you will find three metal hearth strips measuring approximately 28 x 4. These strips are used to provide added protection where the fireplace and the hearth extension meet.
Slide each metal strip 2 under the front edge of the fireplace. The individual pieces must overlap each other by 1 minimum in the middle of the fireplace to provide continuous coverage of the floor. See Figure7. These metal strips should extend from the front and sides of the fireplace opening by 2.
3. Leveling the Fireplace
Level the fireplace side-to-side and front-to-back. Shim with noncombustible material, such as sheet metal, as necessary. Secure the fireplace (using the nailing flanges located on either side of the fireplace) to the vertical framing.
Important: To ensure proper fit of the glass doors, check the fireplace opening for square. Measure diagonal distances of the opening to make sure they are equal. If they are not equal, continue to shim the fireplace until those diagonals are equal.
02-02 15 12538 Rev D
Figure 7 - Positioning the Metal Strips
Page 16
4. Assembling Chimney Sections
Attach either a straight chimney section or an offset to the top of the fireplace (depending on your installation requirement). Chimney sections are locked together by pushing downward until the top section meets the stop bead on the lower section.
The inner flue is placed to the inside of the flue section below it. The outer casing is placed outside the outer casing of the chimney section below it. See Figure8.
WARNING!
Carefully follow the instructions for assembly of the pipe and other parts needed to install this fireplace system. Failure to do so may result in a fire, especially if combustibles are too close to the fireplace or chimney and air spaces are blocked, preventing the free movement of cooling air.
CL36D AND CR36D INSTALLATION INSTRUCTIONS
Figure 8
Assembling Chimney
Sections
5. Installing Firestop Spacers
Mark and cut out an opening in the ceiling for the firestop spacer being utilized (14½ x 14½ for an FS338, 14½ x 183/8 for an FS339 and 14½ x 23 for an FS340). Frame the opening with the same dimension lumber used in the ceiling joists. Install the firestop spacer. These firestop spacers are designed to provide the minimum 2 air space required around the chimney. In all situations, the firestop spacers are to be nailed to the ceiling joists from the bottom or fireplace side, EXCEPT when the space above is an insulated ceiling or attic space. In this situation, the firestop spacer must be nailed from the top side to prevent loose insulation from falling into the required 2 air space around the chimney. See Figure 9.
CAUTION:
Firestop spacers must be used whenever the chimney penetrates a ceiling/floor area.
Figure 9
Installing the Firestop Spacer
Page 17
CL36D AND CR36D INSTALLATION INSTRUCTIONS
6. Attic Insulation Shield
An insulation shield should be installed when there is a possibility of insulation coming into contact with the factory built chimney system. The insulation shield is installed by positioning it over the vertical chimney section where it penetrates a firestop spacer. The firestop spacer will support the insulation shield. See Figure 10.
Figure 10 - Installing an Attic Insulation Shield
8. Securing the Chimney System
When offsets and returns are joined to straight pipe sections, they must be locked into position with the screws provided (outer only), using the predrilled holes. To prevent gravity from pulling the chimney sections apart, the returns and the chimney stabilizers have straps for securing these parts to joists or rafters. See Figure 11.
Note: You must provide support for the pipe dur-
ing construction and check to be sure inadvertent loading has not dislodged the chimney section from the fireplace or at any chimney joint.
7. Double-checking the Chimney Assembly
Continue assembling the chimney sections up through the firestop spacers as needed. While doing so, be aware of the height and unsupported chimney length limitations that are given on page 12 under Chimney Requirements.
Check each section by pulling up slightly from the top to ensure proper engagement before installing the succeeding sections. If they have been connected correctly, they will not disengage when tested.
CAUTION:
Inner flue and outer liner sections cannot be dis­assembled once locked together. Plan ahead to ensure the proper installation height is achieved with the selected chimney components.
WARNING!
Maintain a minimum of 2 air clearance to all parts of the chimney system at all times! Fail-
ure to maintain this 2 air clearance will cause a structure fire.
Figure 11 - Offset/Return with Stabilizer
WARNING!
When chimney sections exceeding six feet in length are installed between an offset and re­turn, structural support must be provided to re­duce off-center loading and prevent chimney sections from separating at the chimney joints.
02-02 17 12538 Rev D
Page 18
CL36D AND CR36D INSTALLATION INSTRUCTIONS
9. Marking the Exit Point of the Roof
Locate the point where the chimney will exit the roof by plumbing down to the center of the chimney. Drive a nail up through the roof to mark the center. See Figure12.
10.Cutting out the Hole in the Roof
Measure to either side of the nail and mark the 14½x14½ opening required. This is measured on the horizontal; actual length may be larger depending on the pitch of the roof. Cut out and frame the opening. See Chapter 25 of the Uniform Building Code for
Roof Framing Details.
Be sure to maintain a 2 minimum air space between the chimney section and the roof.
11.Assembling the Chimney Sections Through the Roof
Continue to add chimney sections through the roof opening, maintaining at least a 2 air space.
12.Installing the Roof Flashing
If a roof flashing is to be used, install the roof flashing appropriate to the roof pitch and install a round termination cap following the instructions shipped with the cap.
For chase installations you can use a round termination cap (TR344), a round telescoping termination cap (TR342) or a square termination cap (ST375/TS345/TS345P). A chase installation must use a chase top. Chase tops are available from your Heatilator distributor. See page 22 for building a chase.
Figure 12 - Ceiling/Attic Construction
13.Installing the Outside Air Kit
The outside air kit is supplied as a standard feature with this fireplace and its use is highly recommended to minimize the effects of negative pressure within the structure. It is recommended to utilize the shortest duct run to optimize the performance of the outside air kit. The outside air kit inlet thimble should be positioned at least four feet above the ground level, in a manner that will not allow snow, leaves, etc. to block the inlet.
The outside air kit is installed on the left hand side of the fireplace. Remove the cover plate from the side of the fireplace assembly where the air kit is to be installed. See Figure 13 for handle location/operation.
Figure 13 - Air Kit Handle Location
14.Installing the Chimney Air Kit
When installing the chimney air kit, follow the instructions provided with this accessory.
Page 19
CL36D AND CR36D INSTALLATION INSTRUCTIONS
15.Completion of the Enclosure
Complete the fireplace enclosure, allowing space for outside air ducts and gas piping if desired. Electrical wiring should not come in contact with the fireplace.
A minimum clearance of ½ must be maintained between the fireplace sides and the enclosure as well as the fireplace back and the enclosure. See
pages 10-12 for framing details.
Note: Use only a noncombustible material to finish the face of the fireplace below the level of the front standoffs. A noncombustible material such as USG MICORE CV230 Mineral Fiber Board, or USG DUROCK Cement Board is recommended for this purpose.
CAUTION:
When using a gas log set, the fireplace damper must be set in the fully open position. This en­sures proper venting of combustion products.
16.Gas Log/Lighter Provisions
Knockouts are provided on both sides of the fireplace to allow for connection of a certified gas log lighter or a decorative gas appliance with a maximum input of 100,000 BTU/hour, incorporating an automatic gas shut-off device and complying with the Standard for
Decorative Gas Appliances for Installation in Vented Fireplaces, ANSI Z21.60. The decorative gas
appliance should be installed in accordance with the National Fuel Gas Code, ANSI Z223.1-1980. The side refractories are designed to allow ½ iron pipe to pass through. Use a noncombustible sealant to seal any opening between the gas pipe and refractory on the inside. Repack the insulation removed to seal around the gas pipe where it exits the side of the fireplace. A minimum 1½ air clearance must be provided around the ½ iron pipe for a minimum of 4 inches beyond the fireplace. See Figure 14.
WARNING!
This fireplace was not tested by the fireplace manufacturer for use with an unvented gas log heater. To reduce risk of injury, do not install an unvented gas log heater in this fireplace unless it has been specifically tested and listed by Underwriters Laboratories Inc. for use in this specific model fireplace. Unless the unvented gas log heater is tested and listed for use in this factory built fireplace, a fire hazard may be created that can result in a structure fire.
Figure 14 - Air Clearance Around Gas Line
CLEARANCES!
A minimum ½ air clearance must be maintained at the back and side of the fireplace assembly.
Chimney sections at any level require a 2 minimum air space clearance between the framing and chimney section.
02-02 19 12538 Rev D
Page 20
CL36D AND CR36D INSTALLATION INSTRUCTIONS
17.Hearth Extension
A hearth extension must be installed with all fireplaces to protect the combustible floor in front of the fireplace from both radiant heat and sparks.
The construction of, and materials used for a hearth extension are shown in Figures 15 and 16. A hearth extension of this construction may be covered with any noncombustible decorative material and may have a maximum thickness as per the illustration. Seal gaps between the hearth extension and the front of the fireplace with a bead of noncombustible sealant.
Figure 15 - Factory Built Hearth Extension
Field constructed hearth extensions should be constructed in accordance with the instructions in Figure 16. In all cases, the hearth extension must extend a minimum of 16 to the front and 8 on either side of the fireplace opening. The field constructed hearth extension must be constructed from ½ MICORE CV230, or a material with an equivalent insulation value.
Figure 16 - Field Constructed Hearth Extension
WARNING!
Hearth extensions are to be installed only as illustrated to prevent high temperatures from occurring on concealed combustible materials. Hearth sealing strips prevent burning or hot particles from inad­vertently falling directly on combustible surfaces in the event the building should settle and disturb the original construction.
Page 21
CL36D AND CR36D INSTALLATION INSTRUCTIONS
18.Position the Hearth Extension
Position and secure the hearth extension over the protective metal strips that have been placed partially under the fireplace front. These strips should be protruding approximately 2 from under the fireplace front and 2 on both sides of the fireplace opening.
Seal the crack between the hearth extension and fireplace with a bead of noncombustible sealant.
See Figure 17. Apply a noncombustible finishing material of your choice to the hearth extension.
c. Noncombustible Sealant Material
Sealants which will not ignite and burn; General Electric RTV103 Black (or equivalent), Rutland, Inc. Fireplace Mortar #63 (or equivalent).
After completing the framing and applying the facing material (dry wall) over the framing, a ½ wide (maximum) bead of noncombustible sealant must be used to close off any gaps at the top and sides between the fireplace and facing to prevent cold air leaks.
Only noncombustible materials may be used to cover the black metal fireplace front.
20.Mantel
A combustible mantel may be positioned no lower than 41 above the platform or floor the fireplace is set on. The combustible mantel may have a maximum depth of 10. See Figure 18. Combustible trim pieces that project no more than 1½ from the face of the fireplace can be placed no closer than 6 from the top and side of the fireplace opening. Combustible trim must not cover the black metal surfaces of the fireplace. This mantel clearance is in accordance with
Section 7-3.3.3 of ANSI/NFPA211.
Figure 17 - Position the Hearth Extension
19.Finishing Material
Do not install combustible materials over the black face of the fireplace! This poses a safety hazard and may start a fire. You may only use noncombustible
material over the black face of the fireplace.
a. Combustible Material
Material which is made of or surfaced with wood, compressed paper, plant fibers, plastics, or any material capable of igniting and burning, whether flame proofed or not, plastered or unplastered.
b. Noncombustible Material
Material which will not ignite and burn. Such materials are those consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination thereof.
Figure 18 - Mantel Position
21.Glass Doors
This fireplace has been tested and listed for use with doors as specified in Section C, Fireplace System Components. Please refer to the manual packed with each set of doors for installation instructions.
02-02 21 12538 Rev D
Page 22
CL36D AND CR36D INSTALLATION INSTRUCTIONS
G. CONSTRUCTING A CHASE
A chase is a vertical boxlike enclosure built around the chimney and fireplace. A chase may be constructed for the fireplace and chimney or for the chimney only. It is most commonly constructed on an outside wall.
In cold climates, it is recommended that the chase floor be insulated using batt type insulation between the floor joists.
Three examples of chase applications are shown in Figure 19.
1. Fireplace and chimney enclosed in an exterior
chase.
2. Chimney offset through exterior wall and
enclosed in chase.
3. Chase constructed on roof.
1. Materials
a. The chase is constructed using framing
materials much the same as the walls in your home. A variety of materials may be used including brick, stone, veneer brick, or standard siding materials.
b. In constructing the chase, several factors must
be considered:
1) Maintain a ½ air space around the fireplace.
2) Maintain a 2 air space around the chimney.
3) The chase top must be constructed of
noncombustible material.
4) In cold climates, a firestop spacer should be
installed in an insulated false ceiling at the 8 level above the fireplace assembly. This reduces heat loss through the chase.
5) In cold climates, the walls of the chase
should be insulated to the level of the false ceiling as shown in Figure 20. This will help reduce heat loss from the home around the fireplace.
Figure 19 - Chase Constructions
Figure 20 - Chase Assembly
Page 23
CL36D AND CR36D INSTALLATION INSTRUCTIONS
2. Chase Top
Construct a chase of desired materials maintaining a minimum 2 air space around the chimney.
3. Termination Cap
a. Install the chimney sections up through the chase
enclosure. When using a TR344 round termination cap, the uppermost top section of pipe must extend 6 above the top of the chase collar to allow installation of the storm collar and termination cap. See Figure 21.
b. For installations utilizing a TR342 telescoping
round termination cap, the uppermost chimney section must be below the top of the chase top, but not more than 14½ below the top of the chase top flashing collar. See Figure 22.
Figure 21 - Installing a TR344 Round Termination Cap
Figure 22 - Installing a TR342 Round
Telescoping Termination Cap
02-02 23 12538 Rev D
Page 24
CL36D AND CR36D INSTALLATION INSTRUCTIONS
WARNING!
Detailed instructions for installation of the chase top, storm collar and termination cap are packaged with these parts. To avoid danger of fire, all instructions must be strictly followed, including the provision of air space clearance between chimney system and enclosure. To protect against the effects of corrosion on those parts exposed to the weather, we recommend that the chase top and termination cap be painted with a rust-resistant paint.
c. For installations utilizing an ST375 square
termination cap the last chimney section must not be more than 4½ below the chase top. See Figure 24.
d. For installation utilizing a TS345/TS345P Square
Termination Cap, the uppermost chimney section must not be more than 3 below the chase top. See Figure 25.
e. Attach the chase top (CT35) to the top of the
chase.
f. Install the termination cap, following the
instructions provided with it.
Figure 24 - Installing an ST375 Square
Termination Cap
Figure 25 - Installing a TS345/TS345P
Square Termination Cap
WARNING!
Never install a single wall slip section or smoke-pipe in a chase structure. The higher temperature of this single wall pipe may radiate sufficient heat to combustible chase materials to cause a fire.
Page 25
CL36D AND CR36D INSTALLATION INSTRUCTIONS
H. OPERATING INSTRUCTIONS
Note: Save and pass this instruction manual to subsequent home owners. The informa-
tion provided is intended to notify and warn them about making unsafe future modifications such as the addition of shelves or the use of unauthorized parts and repairs.
1. General Information
This fireplace is intended to operate as a supplemental heat source for a single room. It is not designed to function as a primary heat source for a structure.
Fireplaces, as well as other woodburning appliances, have been used safely for many years. It has been our experience that most problems are caused by improper installation and operation of the fireplace. Make certain that installation and operation of the fireplace system is in accordance with these instructions.
It is extremely important that the fire be supervised whenever the fireplace is in use. It is also recommended that an annual inspection be performed on the fireplace system to determine if the flue system needs to be cleaned, or as in the case of any appliance, if minor repairs are required to maintain the system in top operating condition.
This factory built fireplace is intended for use with either solid fuel (firewood) or a decorative gas appliance that has been tested and listed to the Standard for
Decorative Gas Appliances for Installation in Vented Fireplaces, ANSI Z21.60. When operating
your fireplace, the flue damper must be in the open position.
This fireplace was not tested and listed for use with an unvented gas log heater. Do not install an unvented gas log heater in this fireplace and operate it with the flue damper in the closed position unless the unvented gas log heater has been specifically tested and listed for use in this fireplace by Underwriters Laboratories Inc.
Use of an unvented gas log heater in this factory built fireplace may create a fire hazard that can result in a structure fire.
WARNING!
DO NOT operate this fireplace with the flue damper in the closed position. Combustion products must vent up the chimney system to prevent carbon monoxide poisoning, and to prevent hot combustion gases from contacting and overheating combustible surfaces. Failure to operate this fireplace with the damper in the open position may result in asphyxiation or a structure fire.
2. Outside Air
A source of air (oxygen) is required in order for combustion to take place. Whatever air is consumed by the fire must be replaced through cracks around windows, under doors, etc. Most newly constructed houses or existing homes fitted with tightly sealed doors and windows are relatively air tight. In this case, an outside air source must be made available to feed combustion air from outside the home.
A damper control handle allows the individual control of the outside air inlet if your fireplace is equipped with this option. Use of outside air for combustion is highly recommended to conserve heated air within the structure and to provide make up air to keep the fireplace venting properly.
This fireplace will operate correctly only if adequate ventilation is provided to allow proper draft to the fireplace system. Hearth Technologies Inc. assumes no responsibility for the improper performance of the fireplace system caused by inadequate draft due to environmental conditions, down drafts, tight sealing construction of the structure, or mechanical exhausting devices which create a negative air pressure within the structure where the fireplace is located.
CAUTION:
Fireplace operation does require air. Do not take air from other fuel burning appliances which can result in improper venting (smoking) or air dilu­tion. Always provide adequate makeup air.
3. Flue Damper
The flue damper must be in a full open position, and is operated by moving the handle up toward the top of the fireplace. Before lighting the fire, verify this by looking up from the inside of the fireplace. Always operate this fireplace with the damper fully open. Please note: down drafts, obstructions, damaged or poor (wet) fuels can cause smoke spillage.
02-02 25 12538 Rev D
Page 26
CL36D AND CR36D INSTALLATION INSTRUCTIONS
WARNING!
Do not store fuel within the clearances to com­bustibles, or in the space required for refueling and ash removal. See maintenance instructions, Clear Space Near the Fireplace.
4. Glass Doors
Most efficient fireplace operation using glass doors is with the doors open. When the doors are open, the screen must be closed. Only Hearth Technologies Inc. glass doors may be used. See Figure 26 for proper glass door operation.
Figure 26
Proper Operating Positions of Bi-Fold Doors
5. Grate
The factory installed integral grate must be used to hold the logs from falling out of an open fireplace and to allow air to pass between the burning logs. It is important to keep the fire off the hearth and to allow the ashes to collect beneath the fire, thereby forming a layer of additional heat protection.
6. Firescreen
A firescreen is always provided to control sparks. It must be closed whenever the fireplace is in use. Glass doors or firescreens must not be used to hold burning material inside the fireplace. Only those glass door units specifically tested and listed for use with the specific fireplace model should be used. Screens should be closed when the glass doors are closed.
CAUTION:
When left closed while burning your fireplace, firescreens and glass doors will be HOT.
Handle with care!
7. Wood Fuel
FIREWOOD: Your fireplace performance depends on the quality of the firewood you use. All seasoned wood, regardless of species, contains about 8,000 BTUs per pound, and hardwoods have a greater density than soft woods. A piece of hardwood will contain about 60% more BTUs than an equal size piece of soft wood. Firewood is commonly sold by the cord (128 cu. ft.). A cord of seasoned oak (hardwood) would contain about 60% more potential energy than a cord of seasoned pine (soft wood).
Soft woods are generally considered coniferous. These are trees with needle-like leaves that stay green all year and carry their seeds exposed in a cone. Examples of soft wood trees are Douglas fir, pine, spruce, and cedar. Soft woods require less time to dry, burn faster and are easier to ignite than hardwoods.
Hardwoods are generally considered deciduous. Deciduous trees are broadleaf trees that lose their leaves in the fall. Their seeds are usually found within a protective pod or enclosure. Some examples are oak, maple, apple, and birch. It should be noted that there are some deciduous trees that are not considered hardwoods, such as poplar, aspen, and alder. Hardwoods require more time to season, burn slower and are usually harder to ignite than soft woods.
The best wood fuel is a combination of soft wood and hardwood. Start the fire with soft wood; the fire will give off quick heat to bring the appliance up to operating temperature, and then the hardwood can be added for slow, even heat and longer burn time.
MOISTURE: Regardless of which species of wood you burn, the single most important factor that effects the way your fireplace operates is the amount of moisture in the wood. The majority of the problems fireplace owners experience are caused by trying to burn wet, unseasoned wood.
Freshly cut wood can be as much water as it is wood, having a moisture content of around 50%. Imagine a wooden bucket that weighs about eight pounds. Fill it with a gallon of water, put it in the fireplace and try to burn it. This sounds ridiculous but that is exactly what you are doing if you burn unseasoned wood.
WARNING!
Burning wet, unseasoned wood can cause ex­cessive creosote accumulation. When ignited it can cause a chimney fire that may result in a serious house fire.
Page 27
CL36D AND CR36D INSTALLATION INSTRUCTIONS
SEASONING: Seasoned firewood is nothing more than wood that is cut to size, split and air dried to a moisture content of around 20%. The time it takes to season wood varies from around nine months for soft woods to as long as eighteen months for hardwoods. The key to seasoning wood is to be sure it has been split, exposing the wet interior and increasing the surface area of each piece. A tree that was cut down a year ago and not split is likely to have almost as high a moisture content now as it did when it was cut.
The following guideline will ensure properly seasoned wood:
a. Stack the wood to allow air to circulate freely
around and through the woodpile.
b. Elevate the woodpile off the ground to allow air
circulation underneath.
c. The smaller the pieces, the faster the drying
process. Any piece over six inches in diameter should be split.
d. Cover the top of the woodpile for protection from
rain and snow. Avoid covering the sides and ends completely. Doing so may trap moisture from the ground and impede air circulation.
The problems with burning wet, unseasoned wood are twofold: First, you will receive less heat output from wet wood because it requires energy in the form of heat to evaporate the water trapped inside. This is wasted energy that should be used for heating your home. Secondly, this moisture evaporates in the form of steam which has a cooling effect in your fireplace and chimney system. When combined with tar and other organic vapors from burning wood it will form creosote which condenses in the relatively cool fireplace and chimney.
8. Starting a Fire
Check the flue damper to be certain it is in the full open position. Place crumpled or twisted paper under the fireplace grate. Loosely arrange kindling or small pieces of wood to form a layer above the paper.
The fires must be built on the fireplace grate, without danger of the burning fuel falling out of the fireplace opening.
Light the paper and add small pieces of wood until a hot bed of embers has been established.
After establishing the fire bed, and the small firewood is burning briskly, add a minimum of three average sized pieces of split firewood, place the wood in such a manner to allow combustion air and flames between them.
Note: The first three or four fires should be of mod-
erate size to allow the oils and binders to be burned from the fireplace and the refractory and paint to cure. You may notice an industrial odor the first few fires. This is considered normal.
As you use the fireplace, expansion and contraction will cause minor cracking of the refractory. This is normal, unavoidable, and will not affect the perfor­mance of the fireplace. If the cracks become large enough that the metal behind the refractory is ex­posed or large pieces fall out, the panels should be replaced.
CAUTION:
Never use gasoline, gasoline-type lantern fuel, kerosene, charcoal lighter fluid, or similar liq­uids to start or freshen up a fire in this fire­place. Keep all such liquids well away from the fireplace.
WARNING!
Fireplaces equipped with doors should be oper­ated only with the doors fully open or fully closed. If doors are left partially open, gas and flame may be drawn out of the fireplace opening, creating the risk of both fire and smoke.
9. Draft Problems
Note: When first lighting your fireplace, it may be necessary to pre-warm the flue to establish a draft. This is done by holding a rolled up piece of burning newspaper under the flue damper for a few moments. This will help reduce smoke spillage during start­up.
This fireplace will operate correctly only if adequate ventilation is provided to allow proper draft to the fireplace system. Hearth Technologies Inc. assumes no responsibility for the improper performance of the fireplace system caused by inadequate draft due to environmental conditions, down drafts, tight sealing construction of the structure, or mechanical exhausting devices which will create a negative air pressure within the structure where the fireplace is located.
02-02 27 12538 Rev D
Page 28
CL36D AND CR36D INSTALLATION INSTRUCTIONS
Flue draft is measured as negative pressure in the chimney. The amount of negative pressure determines how strong the draft is. The draft is important because it draws the combustion air into the fireplace and pulls the smoke out of the chimney. There are three basic criteria essential in establishing and maintaining flue draft:
· Availability of combustion air.
· Heat generated from the fire.
· Diameter and height of the flue system.
These three factors work together as a system to create the flue draft. Increasing or decreasing any one of them will affect the other two and thus change the amount of draft in the entire system. See Figure 27.
Figure 27 - Flue Draft
If the fire is hard to start and smoke spills out of the fireplace, or you find it difficult to establish and maintain a moderately high burn rate, then the flue draft is too low and corrective measures must be taken.
Be sure you have air available for combustion and that your firewood is dry and well seasoned. Build your fires properly and according to the instructions given in operating instructions, Starting a Fire. Be sure your flue system is installed correctly and that it is the proper diameter and height. Check for the following:
· All chimney sections are properly installed and the joints are tightly sealed.
· The chimney is clean and free of creosote buildup.
· Make sure overhanging trees and branches are cut back within ten feet of the top of the chimney.
· Ensure the chimney cap is clean and free of any buildup of soot or creosote.
If you still suspect you have a low draft problem it may be necessary to increase the volume of air in your flue system. Since the diameter of your flue system is matched with the size of the flue collar and should not be changed, then the height of the system must be increased. Add chimney sections a little at a time until the draft improves.
In some cases, regardless of what you do, it can still be difficult to establish the proper flue draft. This is especially evident when using an exterior factory built chimney or exterior masonry chimney. Try placing several sheets of crumpled paper on top of your kindling as close to the flue outlet of the fireplace as possible. Light this paper first then the paper under the kindling. The heat generated from the rapidly burning paper on top of the kindling should help get the draft established.
Still other factors can affect how well your flue system performs. Neighboring structures, high winds, tall trees, even hillsides can affect air currents around the chimney. Well designed chimney caps are available that can help. Your fireplace dealer is the local expert in your area. He can usually make suggestions or discover problems that can be easily corrected allowing your fireplace to operate correctly as it has been designed, providing safe and economical heat for your home.
Page 29
CL36D AND CR36D INSTALLATION INSTRUCTIONS
I. MAINTENANCE INSTRUCTIONS
1. Disposal of Ashes
Ashes should be placed in a metal container with a tight-fitting lid. The closed container of ashes should be placed on a noncombustible floor or on the ground, well away from all combustible materials, pending final disposal. If the ashes are disposed of by burial in soil or otherwise locally dispersed, they should be retained in the closed container until all embers have thoroughly cooled.
A chimney fire can permanently damage your chimney system. This damage can only be re­paired by replacing the damaged component parts. Chimney fires are not covered by the Lim­ited Warranty and Buyer Protection Plan.
WARNING!
2. Creosote and Soot
Inspect the chimney internally for obstructions and construction damage. Flue pipe joints and seams must be continuous and mechanical tight. In a used chimney, additional inspection is needed for creosote buildup, which is the formation of a flammable sediment.
When wood is burned slowly, it produces tar and other organic vapors, which combine with expelled moisture to form creosote. The creosote vapors condense in the relatively cool chimney flue of a slow­burning fire. As a result, creosote residue accumulates on the flue lining. When ignited, this creosote makes an extremely hot fire.
The chimney should be inspected at least twice a year during the heating season to determine if creosote buildup has occurred.
If creosote has accumulated, it should be removed to reduce the risk of a chimney fire.
3. Chimney Cleaning
If you do detect a buildup of creosote, contact a qualified chimney sweep or clean it yourself. To do this, perform the following steps:
a. Open the damper. b. Hang a damp sheet across the fireplace opening
to stop dirt and soot from entering the room.
c. Remove the termination cap or housing top. d. Clean with a stiff nylon brush attached to a pole
OR tie a small burlap bag filled with straw and several small stones or sand. Work up and down the flue until the flue is clean.
e. Replace the termination cap or housing top.
4. Clear Space Near the Fireplace
Combustible materials must not be stored on the hearth extension. Room furnishings such as drapes, curtains, chairs, or other combustibles must be at least four feet from the open front of the fireplace.
Figure 28
Chimney & Termination Cap Cleaning
02-02 29 12538 Rev D
Page 30
CL36D AND CR36D INSTALLATION INSTRUCTIONS
HOMEOWNERS NOTES
Page 31
CL36D AND CR36D INSTALLATION INSTRUCTIONS
Index
A
Air Clearance 17, 19 Air Kit Handle Location 18 Ashes, Disposal of 29 Attic Insulation Shield 17
B
Building Codes 2, 4
C
Chase 22 Chase Top 9, 23 Chimney
Assembling Sections Through the
Roof 18 Checking the Assembly 17 Cleaning 29 Creosote 29 Exit Point Through the Roof 18 Height Requirements 14 Inspection 2 Requirements 12 Securing the System 17
Chimney Air Kit 9, 18 Chimney Bracket 8 Chimney Requirements 12 Chimney Sections
Assembling 16 Number Required 14
Chimney Stabilizer 8 Combustible
Material 20
Combustible Material 21 Combustion Air 2 Components 5 Construction 20, 23 Creosote 29
D
Damper 2 Description of the Fireplace System 4 Design and Installation Considerations
3
Dimensions 6 Draft 27
E
Exhaust Products 10
F
Fireplace
Enclosure 19
Locations 10 Firescreen 26 Firestop Spacer 8
Installation 16 Firewood 25, 26 Flue 25 Framing 11 Fuel 2, 25, 26
G
Gas Knockout Location 6 Gas Log/Lighter Provisions 19 General Information 25 Glass Doors 5, 21 Grate 26
H
Hearth Extension 20
Positioning 21
I
Installation
Fireplace 15 Installation Along a Wall 10 Insulation Shield 8, 17
J
Joint Band 8
L
Leveling the Fireplace 15 Locations 10
M
Maintenance 29 Mantel 21 Metal Hearth Strips 15 Moisture Content of Wood 25, 26
N
Negative Air Pressure 27 Noncombustible Material 21 Noncombustible Sealant Material 21
O
Offsets/Returns 13 Outside Air 25 Outside Air Kit 6, 18 Overhead Obstructions 13
P
Positioning 15 Pre-Installation Preparation 10
R
Roof Flashing 8, 18
S
Safety 15 Sealant Material 21 Seasoning the Wood 27 Shroud 9 Sidewalls/Surrounds 12 Smoke 10 Soot 29 Space Requirements 10 Standard for Decorative Gas Appli-
ances 19, 25
Starting a Fire 27
T
Ten Foot Rule 14 Termination Cap 9, 23 Typical Fireplace System 4
U
UL 127 Standards 4 Uniform Building Code for Roof
Framing Details 18
Unvented Gas Log Heater 19, 25
V
Ventilation 27
W
Wet Insulation 2 Wood
Moisture of 25, 26 Seasoning of 27
Wood Fuel 25, 26
02-02 31 12538 Rev D
Page 32
HEATILATOR WOODBURNING FIREPLACE
LIMITED WARRANTY
As part of its
20-YEAR BUYER PROTECTION PROGRAM
AS PART OF ITS 20 YEAR BUYER PROTECTION PROGRAM (PROGRAM, HEARTH TECHNOLOGIES INC. (HTI) is
pleased to offer a Limited Warranty and a Replacement Parts Advantage covering specific components of your Heatilator wood­burning fireplace system ( the Fireplace), installed in the United States of America or Canada. Dealers and employees of HTI
have no authority to make any warranty or authorize any remedies in addition to or inconsistent with the terms of this Program.
Limited Warranty.
HTI warrants the following components of your Heatilator woodburning fireplace to be free from original defects in material and workmanship during the applicable periods described: five years for the firebox assembly, chimney system and roof termination; two years for refractory firebox liners; and one year for the grate, wire mesh screens, fan system, outside air system, and glass doors. All limited warranty periods run from the date of initial installation of your Fireplace (the Installation Date). The Limited Warranty is subject to the conditions, exclusions and limitations of liability listed below.
Replacement Parts Advantage.
Under HTIs Replacement Parts Advantage, for a period of twenty years from your Installation Date of your Fireplace, if available, HTI will provide you with repair or replacement parts for defective components which are no longer under their applicable Limited Warranty, at 50% of the then current retail list price for such components. HTI shall have no responsibility for freight and labor charges related to such parts.
Conditions, Exclusions, & Limitations of Liability A. Both the Limited Warranty and Replacement Parts Advantage supplied by HTI apply only while the Fireplace is in its location
of original installation. HTIs obligation under this warranty does not extend to damages resulting from (1) installation, operation or maintenance of the Fireplace not in accordance with the Installation Instructions, Operating Instructions, and the Listing Agent Identification Label furnished with the Appliance; (2) installation which does not comply with local building codes; (3) shipping, improper handling, improper operation, abuse, misuse, accident or unworkmanlike repairs; (4) environ­mental conditions, inadequate ventilation or drafting caused by tight sealing construction of the structure, air handling de­vices such as exhaust fans or forced air furnaces, or other causes; (5) use of fuels other than those specified in the Operating Instructions; (6) installation or use of components not supplied with the Fireplace or any other components not expressly authorized and approved by HTI; and/or (7) modification of the Fireplace not expressly authorized and approved by HTI in writing. This warranty is limited to only the component parts manufactured or supplied by HTI.
B. During the first year of the Limited Warranty, HTI will, at its sole option, repair or replace any covered defective component
and will provide replacement parts at no charge. And will pay reasonable labor and freight costs. During the second through the fifth years of the Limited Warranty (if applicable), HTI will provide replacement parts free of charge for any cov­ered defective component, but will not pay for freight or labor costs related to the shipment of the parts or the actual repair or replacement. After the fifth anniversary of the Installation date, HTIs sole obligation and your exclusive remedy is set forth in HTIs Replacement Parts Advantage described above. In no event shall HTI be liable for any incidental or
consequential damages caused by defects in your Fireplace.
C. EXCEPT TO THE EXTENT PROVIDED BY LAW, HTI MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY
SPECIFIED HEREIN. THE DURATION OF ANY IMPLIED WARRANTY IS LIMITED TO DURATION OF THE WARRANTY SPECI­FIED ABOVE.
D. Some states do not allow exclusions or limitations of incidental or consequential damages, so those limitations may not apply
to you. This warranty gives you specific rights; you may also have other rights which vary from state to state.
How to Obtain Service.
To obtain service under this warranty you must:
1. Send written notice of the claimed condition to Heatilator Technical Service Department, Hearth Technologies Inc., 1915 W. Saunders Street, Mt. Pleasant, Iowa 52641-1563. You may also register your claim online at www.heatilator.com/contact.asp.
2. Provide proof of purchase, model number, serial number, and manufacturing date code to HTI.
3. Provide HTI reasonable opportunity to investigate the claim, including reasonable opportunity to inspect the Appliance prior to any repair or replacement work and before the Appliance or any component of the Appliance has been removed from the place of original installation.
4. Obtain HTIs consent to any warranty work before the work is done.
ADDITIONAL INFORMATION. If you would like information on current HEATILATOR products or want to locate a dealer in your area, call 1-800-843-2848.
ã2001 Heatilatorâ is a Registered Trademark of Hearth Technologies Inc.
12538 Rev D 32 02-02