Hayward Aqua Solar, Aqua Solar TC, Aqua Solar AQ-SOL-LV, Aqua Solar AQ-SOL-LV-TC, Aqua Solar AQ-SOL-LV-SP Operation And Installation Manual

Temperature/Resistance /Voltage
All Hayward controls use a 10K thermistor sensors. When disconnected from the control, the sensor will read 10K ohms at 25ºC/77ºF. Refer to the chart below for the resistance at other temperatures. For a given temperature, the resistance reading should be accurate to ±1%. For a given resistance reading, the tempera­ture reading should be accurate to ±0.5ºF. All voltage measurements (DC) must be made with the sensor connected to the control and should be accurate to ± 2%.
°F OhmsVolts °F OhmsVolts °F OhmsVolts °F OhmsVolts
1 82,719 4.46 41 25,391 3.59 81 9,076 2.38 121 3,679 1.34 2 80,142 4.45 42 24,704 3.56 82 8,861 2.35 122 3,602 1.32 3 77,656 4.43 43 24,037 3.53 83 8,651 2.32 123 3,527 1.30 4 75,255 4.41 44 23,391 3.50 84 8,447 2.29 124 3,454 1.28 5 72,937 4.40 45 22,764 3.47 85 8,249 2.26 125 3,382 1.26 6 70,698 4.38 46 22,156 3.45 86 8,056 2.23 126 3,312 1.24 7 68,535 4.36 47 21,566 3.42 87 7,867 2.20 127 3,244 1.22 8 66,447 4.35 48 20,993 3.39 88 7,684 2.17 128 3,177 1.21
9 64,428 4.33 49 20,438 3.36 89 7,506 2.14 129 3,112 1.19 10 62,479 4.31 50 19,900 3.33 90 7,333 2.12 130 3,049 1.17 11 60,595 4.29 51 19,377 3.30 91 7,164 2.09 131 2,987 1.15 12 58,774 4.27 52 18,870 3.27 92 6,999 2.06 132 2,926 1.13 13 57,014 4.25 53 18,377 3.24 93 6,839 2.03 133 2,867 1.11 14 55,313 4.23 54 17,899 3.21 94 6,683 2.00 134 2,809 1.10 15 53,669 4.21 55 17,435 3.18 95 6,530 1.98 135 2,752 1.08 16 52,078 4.19 56 16,985 3.15 96 6,382 1.95 136 2,697 1.06 17 50,541 4.17 57 16,548 3.12 97 6,238 1.92 137 2,643 1.05 18 49,054 4.15 58 16,123 3.09 98 6,097 1.89 138 2,591 1.03 19 47,616 4.13 59 15,711 3.06 99 5,960 1.87 139 2,539 1.01 20 46,225 4.11 60 15,310 3.02 100 5,827 1.84 140 2,489 1.00 21 44,879 4.09 61 14,921 2.99 101 5,697 1.81 141 2,440 0.98 22 43,577 4.07 62 14,543 2.96 102 5,570 1.79 142 2,392 0.97 23 42,318 4.04 63 14,176 2.93 103 5,446 1.76 143 2,345 0.95 24 41,099 4.02 64 13,820 2.90 104 5,326 1.74 144 2,299 0.93 25 39,919 4.00 65 13,473 2.87 105 5,208 1.71 145 2,254 0.92 26 38,777 3.97 66 13,136 2.84 106 5,094 1.69 146 2,210 0.90 27 37,671 3.95 67 12,809 2.81 107 4,982 1.66 147 2,167 0.89 28 36,601 3.93 68 12,491 2.78 108 4,873 1.64 148 2,125 0.88 29 35,565 3.90 69 12,182 2.75 109 4,767 1.61 149 2,084 0.86 30 34,561 3.88 70 11,882 2.72 110 4,664 1.59 150 2,044 0.85 31 33,590 3.85 71 11,589 2.68 111 4,563 1.57 151 2,005 0.84 32 32,648 3.83 72 11,305 2.65 112 4,464 1.54 152 1,966 0.82 33 31,737 3.80 73 11,029 2.62 113 4,368 1.52 153 1,929 0.81 34 30,853 3.78 74 10,761 2.59 114 4,274 1.50 154 1,892 0.80 35 29,998 3.75 75 10,500 2.56 115 4,183 1.47 155 1,856 0.78 36 29,169 3.72 76 10,246 2.53 116 4,094 1.45 156 1,821 0.77 37 28,365 3.70 77 9,999 2.50 117 4,007 1.43 157 1,787 0.76 38 27,587 3.67 78 9,758 2.47 118 3,922 1.41 158 1,753 0.75 39 26,832 3.64 79 9,525 2.44 119 3,839 1.39 159 1,720 0.73 40 26,100 3.61 80 9,297 2.41 120 3,758 1.37 160 1,688 0.72
Electronic Solar Control Center
Operation and Installation
Manual
AQ-SOL-LV AQ-SOL-LV-TC AQ-SOL-LV-SP
092008F RevG
Copyright © 2010 Hayward Inc.
www.haywardnet.com
620 Division St. Elizabeth, NJ 07207
Aqua Solar
12
IMPORTANT SAFETY INSTRUCTIONS
When using this electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL INSTRUCTIONS
Disconnect all AC power during installation.
Warning – To reduce the risk of injury do not permit children to use this
product unless they are closely supervised at all times.
A green colored terminal marked “EARTH” is located inside the wiring compartment. To reduce the risk of electrical shock, this terminal must be connected to the grounding means provided in the electrical supply service panel with a continuous copper wire equivalent in size to the circuit conductors supplying the equipment.
All field installed metal components such as rails, ladders, drains, or other similar hardware within 3 meters of the pool, spa or hot tub shall be bonded to the equipment grounding bus with copper conductors not smaller than 8 AWG US/ 6 AWG Canada.
SAVE THESE INSTRUCTIONS
5-Year Limited Solar Warranty
This Five Year Limited Warranty statement is only applicable to Solar controls and accessories sold and installed within the USA and Canada* and supersedes any warranty statements dated prior to November 1, 2010.
Hayward warrants its Hayward solar products to be free from defects in material or workmanship, under normal use and service for 5 years from date of manufacture, providing it is installed according to the installation instructions and specifications. The datecode stamped on the outside of the product and also coded on the printed circuit board will be the sole determination of manufacturing date.
To obtain warranty service or repair, please contact the place of purchase or the nearest Hayward authorized warranty service center. For more information, please contact the Hayward Technical Service Support Center or visit us on the web at www.haywardnet.com. Hayward will not assume any of the cost incurred in removal or reinstallation of the product. One year outside the USA and Canada.
The express warranty above constitutes the entire warranty of Hayward Pool Products with respect to its solar products and IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING A WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL HAYWARD BE RESPONSIBLE OR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES OF ANY NATURE WHATSOEVER.
No wholesaler, agent, dealer, contractor, or other person is authorized to give any warranty on behalf of Hayward. This warranty is void if the product has been altered in any way after leaving
the factory.
Charges
Years 1-3:no charge Years 4-5 60% of current list price plus $5.00 shipping and handling
Unless a copy of the original purchase invoice is enclosed, the manufacturing datecode on the product will be used to determine the repair charges. Hayward reserves the right to charge a nominal fee to cover inspection, test, and return freight for all controls where no faults or problems are detected. All charges will be COD (COD charge will be included) unless you already have an open account in good standing with Hayward. If the product returned can not be repaired, Hayward will offer and equivalent credit towards the purchase of any new Hayward product. Products that exhibit evidence of abuse, misuse, field damage (water/fire damage, line voltage applied to low voltage terminals, missing parts, etc.) or installed for more than the warranty period are not eligible for warranty repair replacement.
11
On continuously indicates a probable open circuit in the "POOL" sensor or wiring. Flashing indicates a probable short circuit in the "POOL" sensor or wiring. In either case digital pool temperature display will show as "PErr". The solar heating and cooling functions will remain off until this problem is fixed, however, the recirculate freeze protection (if enabled by the jumper) will still operate properly. Use the chart on the back cover to check the "POOL" sensor with a voltmeter (you don't need to disconnect the sensor). Alternatively, you can disconnect the sensor and measure the sensor resistance. Replace the sensor or fix the wiring as required. If the sensor and wiring are both good, then the main circuit PCB may have a problem.
7. "Solar Sensor" LED on or flashing "Err" on the solar temperature display:
On continuously indicates a probable open circuit in the "SOLAR" sensor or wiring. Flashing indicates a probable short circuit in the "SOLAR" sensor or wiring. In either case digital pool temperature display for the "SOLAR" sensor will show as "CErr". The solar heating and cooling functions will remain off until this problem is fixed, however, the recirculate freeze protection (if enabled by the jumper) will still operate properly.
Use the chart on the back cover to check the "SOLAR" sensor with a voltmeter (you don't need to disconnect the sensor). Alternatively, you can disconnect the sensor and measure the sensor resistance. Replace the sensor or fix the wiring as required. If the sensor and wiring are both good, then the main circuit PCB may have a problem.
8. "Aux Sensor" LED flashing "Err" on the Aux temperature display:
Flashing indicates a probable short circuit in the "AUX" sensor or wiring. The digital pool temperature display for the "AUX" sensor will show as "AErr". This error indication only occurs when the "AUX" sensor is being used for recirculate freeze protection. When the Aux sensor is shorted, the Aqua Solar will use the "SOLAR" sensor as a backup freeze sensor and turn the recirculate freeze protection on when the temperature is less than 60ºF.
Use the chart on the back cover to check the "AUX" sensor with a voltmeter (you don't need to disconnect the sensor). Alternatively, you can disconnect the sensor and measure the sensor resistance. Replace the sensor or fix the wiring as required. If the sensor and wiring are both good, then the main circuit PCB may have a problem.
Table of Contents
SPECIFICATIONSSPECIFICATIONS
SPECIFICATIONSSPECIFICATIONS
SPECIFICATIONS
Specifications Specifications
Specifications Specifications
Specifications ......................................................................1
OPERATIONOPERATION
OPERATIONOPERATION
OPERATION
Controls Controls
Controls Controls
Controls ...............................................................................2
Temperature Display Temperature Display
Temperature Display Temperature Display
Temperature Display ........................................................3
INSTALLATIONINSTALLATION
INSTALLATIONINSTALLATION
INSTALLATION
Mounting Mounting
Mounting Mounting
Mounting ..............................................................................4
Wiring Wiring
Wiring Wiring
Wiring ..................................................................................4
Jumper Settings Jumper Settings
Jumper Settings Jumper Settings
Jumper Settings ..................................................................9
TROUBLESHOOTINGTROUBLESHOOTING
TROUBLESHOOTINGTROUBLESHOOTING
TROUBLESHOOTING
Troubleshooting Troubleshooting
Troubleshooting Troubleshooting
Troubleshooting ...............................................................10
WARRANTYWARRANTY
WARRANTYWARRANTY
WARRANTY
WarrantyWarranty
WarrantyWarranty
Warranty.............................................................................12
Loading...
+ 5 hidden pages