PARTS LIST:
1 scald protection bleed valve,* 1 1/2" street elbow, 1 1/2" x 2” nipple (nipple and elbow are
intended to allow the scald prevention valve to remain vertical when connected to a vertical
piping run, if necessary).
INSTALLATION NOTES:
• Protect the valve with a y-strainer (20 mesh or finer) in the supply line. Scald
protection* is lost when the valve is plugged or fouled; damage may occur. Flush
lines before installing.
• See the Installation Drawing for suggested installation locations on Haws combination
showers.
• Locate the valve(s) in the plumbing as far from the supply line as possible, so that
when open, the valve can drain water from throughout the entire fixture. For optimum
scald protection,* minimize the plumbing legs in the fixture that can trap stagnant
water when the valve is open. Haws recommends a maximum stagnant leg length of
3 pipe diameters for uninsulated pipes and 6 pipe diameters for insulated pipes.
• Tubing, hosing, or piping is not supplied for the outlet of the valve, but may be used in
order to direct the flow as desired. Ensure that any outlet plumbing is suitable for the
high temperatures of the water that will pass through it.
• The outer surface of the valve should be protected from freezing in a manner similar
to the piping to which it is attached.
ACTUATION TEMPERATURES:
• Valve begins to open at: 98°F (37°F)
• Valve is fully open at: 105°F (41°F)
• Valve will be fully re-closed at: 95°F (35°C)
Once opened, the valve will discharge water warmer than 95° F (35°C). To stop flow
completely, the valve must be cooled below 95°F (35°C).
CLEANING INSTRUCTIONS:
1. Safely perform any required steps to release water pressure from the valve inlet.
2. Remove the valve and take it to a faucet with clean hot running water.
3. Use a pair of adjustable pliers (or other suitable device) to hold the valve under hot
(not to exceed 140°F) running water for several minutes, turning the valve all around
to distribute the heat.
4. Occasionally direct the flow into either end of the valve, until the thermostat opens
and the valve allows flow through it.
5. While the valve is warmed and open, direct flow through the valve in both directions
and observe any debris (hair, PTFE tape, rust, debris, etc.) that may exit the valve. If
no water can be observed flowing through the valve after 10 minutes of sustained
warming above 110°F, the valve may be defective and require replacement.
6. Cool the valve by running cold water over and through the valve until the valve closes
and no flow can be observed running through the valve.
7. Safely return the valve to service and check for unexpected leaking.