THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS
MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITHOUT NOTICE.
3/4" NPT JUNCTION BOX
3
DRENCH HOSE ACTIVATION
VALVE ASSEMBLY
MOUNTING LOCATION
FOR OPTIONAL
AREA LIGHT
43 1/4"
1098mm
36-1/2"
927mm
POWER CONNECTION
6 3/4"
171mm
MOUNTING LOCATION
FOR OPTIONAL
INDICA TOR L IG HT
1-1/4" IPS SUPPLY UNION (INLET)
TOP SUPPLY SHOWN. SEE STEP 2
OF THE INSTALLATION PROCEDURE
IN THE OPERATION & MAINTENANCE
MANUAL (PAGE 2) TO CONVERT
TO A BOTTOM SUPPLY UNIT.
20-1/2"
521mm
IMPORTANT
SUPPLY MUST BE HEAT
TRACED AND INSULATED
1 of 4
PAGE
85-1/2"
2172mm
95-1/2"
2426mm
90-1/2"
2299mm
67-1/4"
1708mm
DRENCH HOSE
41-3/4"
1060mm
6"
FLOOR LINE
152mm
NOTES:
1. DIMENSIONS MAY VARY BY ± 1/2 INCH [13mm].
2. TO COMPLY WITH ANSI Z358.1-2009 FOR EMERGENCY EYEWASH OR EYE/FACE WASH AND SHOWER EQUIPMENT:
- UNIT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND ACCEPTABLE PLUMBING PRACTICES.
- EYEWASH OR EYE/FACE WASH SHALL BE POSITIONED WITH NOZZLES NOT LESS THEN 83.8 CM (33 IN.) AND NO GREATER THAN
114.3 CM (45 IN.) FROM SURFACE ON WHICH USER STANDS AND 15.3 CM (6 IN.) MINIMUM FROM WALL OR NEAREST OBSTRUCTION.
- SHOWER SHALL BE POSITIONED SO THAT SHOWER HEAD IS NOT LESS THAN 208.3 CM (82 IN.) NOR MORE THAN 243.8 CM (96 IN.)
FROM SURFACE ON WHICH USER STANDS.
- SHOWER SPRAY PATTERN SHALL HAVE A MINIMUM DIAMETER OF 50.8 CM (20 IN.) AT 152.4 CM (60 IN.) ABOVE SURFACE ON WHICH
USER STANDS, AND CENTER OF SPRAY PATTERN SHALL BE LOCATED AT LEAST 40.6 CM (16 IN.) FROM ANY OBSTRUCTION.
3. DO NOT USE REGULAR PIPE SEALANT. IF NECESSARY USE DOW CORNING 832 SEALANT PLACING 5 SMALL
BEADS ON THE MALE THREADS, JUST ABOVE THE FIRST THREAD.
(NOTES CONTINUED ON SHEET 2 OF 4.)
C
Haws Corporation - All Rights Reserved.
2014
HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation.
R
REMOVABLE
ABS JACKET
7"
178mm
DRAWN:
RTM
APPROVED:
FV
REVISE D PER
ECN:
4921
DATE:
03/29/05
DATE:
BY:ECN NO.
CHK'D.:
10/21/14
14"
355mm
MODEL(S)
FV
SCALE:
30°
NOTE: PULL ROD AND HANDLE NOT
ASSEMBLED. ORIENTATION OF HANDLE
6-3/4"
171mm
MUST BE IN UP POSITION WHEN FULLY
CLOSED AND PULL ROD INSERTED IN
HOLE SHOWN.
SP158B FREEZE PROTECTION VALVE
(SEE NOTES ON SHEETS 2 & 3 FOR
INSTALLATION INSTRUCTIONS.)
THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS
MAKE SPECIFICATIONS AND MEASU REM ENTS SUBJECT TO CHANGE WITHOUT NOTICE.
NOTES: (CONTINUED FROM SHEET 1 OF 4)
4
. FREEZE PROTECTION VALVE INSTALLATION INSTRUCTIONS:
INSTALL VALVE SUB-ASSEMBLY INTO FEMALE SECTION OF UNION AND TIGHTEN WATER-TIGHT.
A
FORM HEAT TRACE CABLE AROUND VALVE AND PLUG, APPLY 2X CABLE-TIES TO HEAT TRACE CABLE, AS SHOWN, ENSURING
B
THAT HEAT TRACE CABLE IS PRESSED FIRMLY AGAINST SIDES OF VALVE (PUSH ANY LOOSE HEAT TRACE CABLE BACK INSIDE
JACKET THROUGH RUBBER GROMMET). TRIM EXCESS CABLE-TIE STRAPPING.
SLIDE INNER TUBE W/ PLUGGED END OVER VALVE WITH ADHESIVE SEAM FACING BOTTOM AND NON-PLUGGED END OF TUBE
C
BUTTED UP AGAINST UNION SURFACE. REMOVE 2X ADHESIVE TAPE FROM SEAM AND SQUEEZE ADHESIVE SEAMS TOGETHER
AROUND VALVE. APPLY 2X CABLE-TIES TO TUBE, IN APPROXIMATE LOCATIONS SHOWN. TRIM EXCESS CABLE-TIE STRAPPING.
(NOTES CONTINUED ON SHEET 3 OF 4)
2 OF 4
PAGE
RUBBER GROMMET
B
FEMALE SECTION OF UNION
(PART OF SHOWER UNIT)
MALE SECTION OF UNION
(PART OF VALVE SUB-ASSY)
HEAT TRACE CABLEB
JACKET SURFACE
E
CABLE-TIE, 15" / PN 0005972499 B
(SEE SHEET 3.)
VALVE, FREEZE (NO UNION) SP158B
BARBED CONNECTOR
UNION SURFACE
C
SP158B VALVE SHOWN CONNECTED TO BOTTOM UNION FOR
REFERENCE ONLY. VALVE CAN BE INSTALLED AT TOP OR BOTTOM.
C
2014
Haws Corporation - All Rights Reserv ed.
HAWS and other tradem arks used in thes e m aterials are the exclusive property of Haws Corporat ion.
R
A
A
CABLE - TIE, 15" / PN 0005972 499
INNER TUBE W/ PLUGGED END
PLUG GED END
ADHESIVE SEAM C
A
C
BY:ECN NO .
4632
DRAWN:
VWC
APPROVED:
FV
REVISED PER
ECN:
4921
DATE:
12/2/12
DATE:
10/21/14
HM
CHK'D.:
MODEL(S)
NA
SCALE:
C
C
D
1455 KLEPPE LANE
SPARKS, NEVADA 89431
(775) 359-4712 FAX (755) 359-7424
E-MAIL: HAWS @H AW SCO.COM
WEBSITE: WWW.HAWSCO.C OM
8317CTFP (120V) / 8317CTFP.2 20V
DRAWING TYPE:SIZE: A
INSTALLATION
PART NUMBER
0002081781.D
DRAW ING NO .
15201A
SHEETOF
24
REV
17
Page 3
THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS
MAKE SPECIFICATIONS AND ME ASUREMENTS SUBJECT TO CHANGE WITHOU T NOTICE.
NOTES: (CONTINUED FROM SHEE T 2 OF 4)
5.
FREEZE PROTECTION VALVE INSTALLATION INSTRUCTIONS (CONTINUED):
WRAP OUTER TUBE OVER INNER TUBE ENCAPSULATED VALVE WITH ADHESIVE SEAM ORIENTED PERPENDICULAR
D
TO SEAM OF INNER TUBE. PUSH OUTER TUBE UP AGAINST JACKET SURFACE. WHEN TUBE IS MOUNTED FIRMLY
AGAINST JACKET SURFACE, SQUEEZE TUBE AT BARBED CONNECTOR SUCH THAT BARBED NIPPLE PUSHES
THROUGH OUTER TUBE WALL. (PUSHING CONNECTOR THROUGH WALL WILL EXTRUDE A CYLINDRICAL PLUG OF
TUBING TO BREAK FREE. DISCARD PLUG.) PUSH TUBE DOWN EVEN FURTHER SO THAT HOLE IN TUBE STRETCHES
AROUND HEXAGONAL BOSS OF CONNECTOR. SQUEEZE OUTER TUBE TIGHT UNTIL ADHESIVE SEAMS ARE CLOSE
ENOUGH TO SEAL. REMOVE PROTECTIVE TAPE AND SEAL SEAMS.
E
TO ENSURE PROPER INSULATION OF UNION; THERE MUST BE NO SPACE BETWEEN OUTER TUBE AND JACKET
SURFACE (SEE SHEET 2 FOR SURFACE CALLOUT). THEREFORE, SLICE TWO PLACES, TOP SIDE AND BOTTOM SIDE,
COMPLETELY THROUGH OUTER TUBE TO A LENGTH EQUAL TO DEPTH OF TRIM SEAL. FORCE SLICED TUBE
AROUND TRIM SEAL AND PUSH TUBE TIGHTLY AGAINST JACKET, AS SHOWN. APPLY 2X CABLE-TIE HEAD, AND 2X
CABLE-TIE STRAP, TO TUBE, IN APPROXIMATE LOCATIONS SHOWN. TRIM EXCESS STRAPPING.
THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLIC AT IO N. CONTI NUED PRODUCT IMPROVEMENTS
MAKE SPECIFICATIONS AND MEASUREMENT S SUBJECT T O CHANG E WITH OUT NOTI CE.