Haws 9001EXPC1D1 Installation, Operation & Maintenance Instructions Manual

No. 2077071(11)
Model 9001EXPC1D1 Alarm
INSTALLATION, OPERATION
&
MAINTENANCE INSTRUCTIONS
LIMITED WARRANTY
hereunder and that HAWS shall not be liable for general, special, or consequential
NOTE TO INSTALLER: Please leave this information with the Maintenance Department.
SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF THIS
1455 Kleppe Lane Sparks, NV 89431-6467  (775) 359-4712 Fax (775) 359-7424
E-mail: haws@hawsco.com website: www.hawsco.com
HAWS warrants that this specific product is guaranteed against defective material or poor workmanship for a period of one year from date of shipm ent. HAWS liability und er this warranty shall be discharged by furnishing without charge F.O.B. HAWS Factory any goods, or part thereof, which shall appear to the Company upon inspection to be of defective material or not of first class workmanship, provided that claim is made in writing to Haws within a reasonable period after receipt of the product. Where claims f or defects are made, the defective part or parts shall be delivered to the Company, prepaid, for inspection. HAWS will not be liable for the cost of repairs, alterations or replacements, or for any expense connected therewith made by the owner or his agents, except upon written authority from HAWS, Sparks, Nevada. HAWS will not be liable for any damages caused by defective materials or poor workmanship, except for replacements, as provided above. Buyer agrees that Haws has made no other warranties either expressed or implied in addition to those above stated, except that of title with respect to any of the products or equipment sold
damages claimed to arise under the contract of sale. The emergency equipment manufactured by HAWS is warranted to function if installation
and maintenance instructions provided are adhered to. T he units also must be used for the purpose for which they were intended. This product is intended to supplement first-aid treatment. Due to widely varying conditions, Haws cannot guarantee that the use of this emergency equipment will prevent serious injury or the aggravation of existing or prior injuries.
NO OTHER WARRANTIES EXPRESSED OR IMPLIED ARE AUTHORIZED, PROVIDED OR GIVEN BY HAWS.
MODEL PLEASE CALL:
TECHNICAL SUPPORT: 1-800-766-5612
FOR CUSTOMER SERVICE: 1-888-640-4297
08/17 Model 9001EXPC1D1 Page 1 of 7
TROUBLESHOOTING
PROBLEM
REPAIR CHECKLIST
1.
Alarm horn and lamp do not
1a.
Check incoming circuit for power and power
b.
Check that the direction of water flow
c.
Check that water flow is sufficient.
d.
Check all electrical connections for security,
e.
Faulty flow switch. Replace entire switch
f.
Faulty flasher module in alarm. Replace
2.
Horn sounds but lamp does not
2a.
Only replace lamp with Haws P/N
b.
Should replacement lamp also fail to operate,
3.
Lamp replacement.
3a.
Remove the guard/globe assembly from the
4.
Alarm stays on.
4a.
Check wiring connections.
b.
Disconnect flow switch wires and test for
RECOMMENDED TOOLS: Pipe joint sealant, screwdriver, pipe wrench, 14 AWG wire,
turbulence in switch.
3/4” conduit and basic electricians’ tools for power connection. LOCATION OF UNIT: The Model 9001EXPC1D1 Alarm may be mounted directly to the
upper stand pipe of a safety shower or wall mounted next to a shower or eyewash. The alarm should be clearly visible from several directions.
ELECTRICAL SUPPLY: 120 VAC 50/60 HZ, 23 Watts average power consumption. Suitable for use in Class I, Division 1, Group C, D areas; Temperature rating T4 (135°C). WARNING: Power shall be supplied by a dedicated circuit through a 10 AMP maximum breaker or fuse and should not supply any power to any other devices.
WATER SUPPLY: The flow switch requires a minimum of 2.4 GPM to activate. Mount flow switch in supply line with flow in horizontal direction and switch stem extending vertically from tee. Mount switch with at least 6” of straight pipe on both sides to minimize
operate.
flash.
from flow switch.
corresponds to the arrow on the flow switch body.
including those in alarm base.
assembly.
flasher module.
0003225505. (See Sheet 3 of Installation drawing)
replace flasher module.
light fixture to replace the lamp. Only replace lamp with Haws P/N 0003225505. (See Sheet 3 of Installation drawing)
08/17 Model 9001EXPC1D1 Page 2 of 7
continuity.
INSTALLATION PROCEDURE
*WARNING: EXPLOSION HAZARD – SUBSTITUTI ON OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS 1, DIVISION 1.
STEP 1: Choose a location for mounting the flow switch in the water supply line. The inlet
and outlet ports of the flow switch must be a minimum of 6 inches from any tees or elbows in the water supply line. See attached installation drawing.
STEP 2: Mount the flow switch assembly in the water supply line. The switch body must
be in the vertical position with the water pipe horizontal. The water flow must be in the direction marked by the arrow on the flow switch body. Use pipe sealing compound on all water pipe connections.
STEP 3: Choose a location for mounting the alarm assembly. The alarm housing should
be positioned along a vertical axis at least 7 feet above ground for best visibility. The alarm may be mounted directly to a water pipe using the supplied brackets. The alarm can also be bolted to a flat surface such as a wall, using flanges with appropriate fasteners (not supplied).
STEP 4: Using wire nuts, connect the flow switch to the alarm and power. The pink and
orange wires are connected to the second normally closed contact of the flow switch and may be used for remote alarm activation. The signal from the pink wire will be supply voltage, to be provided to orange wire by customer, when no water is flowing and zero voltage when the flow switch and local alarm are activated. If a remote alarm is not used, the pink and orange wires must be insulated at their free ends. Power to be routed using rigid conduit and a seal fitting or Class 1, Division1 rated armored cable and an appropriate gland fitting.
See Electrical Wiring Diagram provided on installation drawing. Follow all
instructions in installation drawing and NEC code when installing unit.
OPERATION AND TEST INSTRUCTIONS
Test weekly. Instruct all employees in the use of emergency showers and eyewashes.
STEP 1: Apply power to the alarm branch circuit. The alarm should remain OFF. STEP 2: Open the shower or eyewash flow valve. The alarm should sound and the light
should flash shortly after water flows from the system.
STEP 3: Shut off the flow valve. The alarm should turn off.
For more information about Haws products see our website: www.hawsco.com
© 2017 Haws® Corporation – All Rights Reserved HAWS
®
and other trademarks used in these materials are the exclusive property of Haws Corporation.
08/17 Model 9001EXPC1D1 Page 3 of 7