Haws 9001 Alarm, 9001.5 Alarm Installation Operation & Maintenance

No. 2080202(31)
Model 9001, 9001.5 Alarm
INSTALLATION, OPERATION
&
MAINTENANCE INSTRUCTIONS
LIMITED WARRANTY
or part thereof, which shall appear to the Company upon inspection to be of defective
NOTE TO INSTALLER: Please leave this information with the Maintenance Department.
SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF THIS
1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424
E-mail: haws@hawsco.com website: www.hawsco.com
HAWS warrants that this specific product is guaranteed against defective material or poor workmanship for a period of one year from date of shipment. HAWS liability under this warranty shall be discharged by furnishing without charge F.O.B. HAWS Factory any goods,
material or not of first class workmanship, provided that claim is made in writing to Haws within a reasonable period after receipt of the product. Where claims for defects are made, the defective part or parts shall be delivered to the Company, prepaid, for inspection. HAWS will not be liable for the cost of repairs, alterations or replacements, or for any expense connected therewith made by the owner or his agents, except upon written authority from HAWS, Sparks, Nevada. HAWS will not be liable for any damages caused by defective materials or poor workmanship, except for replacements, as provided above. Buyer agrees that Haws has made no other warranties either expressed or implied in addition to those above stated, except that of title with respect to any of the products or equipment sold hereunder and that HAWS shall not be liable for general, special, or consequential damages claimed to arise under the contract of sale.
The emergency equipment manufactured by HAWS is warranted to function if installation and maintenance instructions provided are adhered to. The units also must be used for the purpose for which they were intended. This product is intended to supplement first-aid treatment. Due to widely varying conditions, Haws cannot guarantee that the use of this emergency equipment will prevent serious injury or the aggravation of existing or prior injuries
NO OTHER WARRANTIES EXPRESSED OR IMPLIED ARE AUTHORIZED, PROVIDED OR
MODEL PLEASE CALL:
TECHNICAL SUPPORT: 1-800-766-5612
.
FOR CUSTOMER SERVICE: 1-888-640-4297
10/17 9001 Alarm Series Page 1 of 6
TROUBLESHOOTING
PROBLEM
REPAIR CHECKLIST
operate.
from flow switch.
body.
box is in the “on” position.
d.
Check for continuity through the switch.
e.
Check all electrical connections.
f.
Check that water flow is sufficient.
assembly.
flash.
b.
Replace flashing light.
sound.
the “on” position.
4.
Alarm stays on.
4.
a.
Check wiring connections.
RECOMMENDED TOOLS: Pipe joint sealant, screwdriver, pipe wrench, 14 AWG wire, 1/2"conduit and basic electricians’ tools for power connection.
LOCATION OF UNIT: The Model 9001 Alarm Series may be mounted directly to the upper standpipe of a safety shower or wall mounted next to a shower or eyewash. The alarm should be clearly visible from several directions.
ELECTRICAL SUPPLY:
Model 9001 & 9001.5 120 VAC 50/60 HZ. 14 watts average power consumption. WARNING: Power shall be supplied by a dedicated circuit through a 10 AMP maxim um breaker or fuse and should not supply power to any other devices. NOT FOR USE IN CLASSIFIED AREAS.
WATER SUPPLY:
Model 9001 2.4 gpm minimum required to activate flow switch. Model 9001.5 1.5 gpm minimum required to activate flow switch. Mount flow switch in supply line with flow in horizontal direction and switch stem extending vertically from tee. Mount switch with at least 6” of straight pipe on both sides to minimize turbulence in switch.
1. Alarm horn and light do not
1. a. Check incoming circuit for power and power
b. Check that the direction of water flow
corresponds to the arrow on the flow switch
c. Check that the switch located on the junction
g. Faulty flow switch. Replace entire switch
2. Horn sounds but light does not
3. Light flashes but horn does not
2. a. Check wiring connections.
3.
a. Check wiring connections.
b. Make sure the alarm silencing switch is in
10/17 9001 Alarm Series Page 2 of 6
b. Disconnect flow switch wires and test for
continuity.