INSTALLATION, OPERATION
&
MAINTENANCE INSTRUCTIONS

LIMITED WARRANTY

GIVEN BY HAWS.
NOTE TO INSTALLER: Please leave this information with the Maintenance Department.
SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF THIS
1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424
E-mail: haws@hawsco.com website: www.hawsco.com
HAWS warrants that this specific product is guaranteed against defective material or poor workmanship for a period of one year from date of shipment. HAWS liability under this warranty shall be discharged by furnishing without charge F.O.B. HAWS Factory any goods, or part thereof, which shall appear to the Company upon inspection to be of defective material or not of first class workmanship, provided that claim is made in writing to Haws within a reasonable period after receipt of the product. Where claims for defects are made, the defective part or parts shall be delivered to the Company, prepaid, for inspection. HAWS will not be liable for the cost of repairs, alterations or replacements, or for any expense connected therewith made by the owner or his agents, except upon written authority from HAWS, Sparks, Nevada. HAWS will not be liable for any damages caused by defective materials or poor workmanship, except for replacements, as provided above. Buyer agrees that Haws has made no other warranties either expressed or implied in addition to those above stated, except that of title with respect to any of the products or equipment sold hereunder and that HAWS shall not be liable for general, special, or consequential damages claimed to arise under the contract of sale.
The emergency equipment manufactured by HAWS is warranted to function if installation and maintenance instructions provided are adhered to. The units also must be used for the purpose for which they were intended. This product is intended to supplement first-aid treatment. Due to widely varying conditions, Haws cannot guarantee that the use of this emergency equipment will prevent serious injury or the aggravation of existing or prior injuries
NO OTHER WARRANTIES EXPRESSED OR IMPLIED ARE AUTHORIZED, PROVIDED OR
MODEL PLEASE CALL:
TECHNICAL SUPPORT: 1-800-766-5612
.
FOR CUSTOMER SERVICE: 1-888-640-4297
10/16 9001 Alarm Series Page 1 of 6
Page 2
TROUBLESHOOTING

PROBLEM

REPAIR CHECKLIST

operate.
from flow switch.
body.
box is in the “on” position.
d.
Check for continuity through the switch.
e.
Check all electrical connections.
f.
Check that water flow is sufficient.
assembly.
flash.
b.
Replace flashing light.
sound.
the “on” position.
4.
Alarm stays on.
4.
a.
Check wiring connections.
RECOMMENDED TOOLS: Pipe joint sealant, screwdriver, pipe wrench, 14 AWG wire, 1/2"conduit and basic electricians’ tools for power connection.
LOCATION OF UNIT: The Model 9001 Alarm Series may be mounted directly to the upper standpipe of a safety shower or wall mounted next to a shower or eyewash. The alarm should be clearly visible from several directions.
ELECTRICAL SUPPLY:
Model 9001 & 9001.5 120 VAC 50/60 HZ. 14 watts average power consumption. WARNING: Power shall be supplied by a dedicated circuit through a 10 AMP maxim um breaker or fuse and should not supply power to any other devices. NOT FOR USE IN CLASSIFIED AREAS.
WATER SUPPLY:
Model 9001 2.4 gpm minimum required to activate flow switch. Model 9001.5 1.5 gpm minimum required to activate flow switch. Mount flow switch in supply line with flow in horizontal direction and switch stem extending vertically from tee. Mount switch with at least 6” of straight pipe on both sides to minimize turbulence in switch.
1. Alarm horn and light do not
1. a. Check incoming circuit for power and power
b. Check that the direction of water flow
corresponds to the arrow on the flow switch
c. Check that the switch located on the junction
g. Faulty flow switch. Replace entire switch
2. Horn sounds but light does not
3. Light flashes but horn does not
2. a. Check wiring connections.
3.
a. Check wiring connections.
b. Make sure the alarm silencing switch is in
10/16 9001 Alarm Series Page 2 of 6
b. Disconnect flow switch wires and test for
continuity.
Page 3
INSTALLATION PROCEDURE
STEP 1: Choose a location for mounting the flow switch in the water supply line. The inlet and
outlet ports of the flow switch must be a minimum of 6 inches from any tees or elbows in the water supply line. See attached installation drawing.
STEP 2: Mount the flow switch assembly in the water supply line. The switch body must be in
the vertical position with the water pipe horizontal. The water flow must be in the direction marked by the arrow on the flow switch body. Use pipe sealing compound on all water pipe connections.
STEP 3: Choose a location for mounting the alarm assembly. The alarm housing should be
positioned along a vertical axis at least 7 feet above ground for best visibility. The alarm may be mounted directly to a water pipe using the supplied bracket, washers and nuts. The alarm can also be bolted to a flat surface such as a wall using appropriate fasteners (not supplied).
STEP 4: Using the wire crimp terminals (supplied), connect the alarm to the power supply per
attached installation drawing. The purple wire is connected to the second normally closed contact and the pink wire to the second common contact of the flow switch and may be used for remote alarm activation. The signal from the purple wire will be zero voltage when water is flowing and supply voltage when no water is flowing. If a remote alarm is not used, the purple wire must be insulated at its free end. Leaving the two crimp terminals (supplied) connected will be sufficient insulation.
NOTICE: ALL POWER CONNECTIONS MUST BE MADE ACCORDING TO NEC CODE
USING TYPE 4 COMPLIANT EQUIPMENT.
OPERATION AND TEST INSTRUCTIONS
Test weekly. Instruct all employees in the use of emergency showers and eyewashes.
STEP 1: Apply power to the alarm branch circuit. The alarm should remain OFF. STEP 2: Open the shower or eyewash flow valve. The alarm should sound and the light
should flash shortly after water flows.
STEP 3: Shut off the flow valve. The alarm should turn OFF.
For more information on Haws products, see our website: www.hawsco.com
© 2016 Haws HAWS
®
®
Corporation – All Rights Reserved
and other trademarks used in these materials are the exclusive property of Haws Corporation.
10/16 9001 Alarm Series Page 3 of 6
Page 4
THIS DOCU MENT IS TRUE AN D CORRECT AT TIME OF PUBL ICATION. CO NT INUED PRODUCT IMPROVEMENTS MAKE SPECIFICATIONS AND MEA SUREMENTS SUB J ECT TO CHANGE WITHO UT NOTICE.
ITEM DESCRIPTION
1FLOW SWITCH
2 120V LIGHT 3 SELECTOR SWITCH
FLOW SWITCH 4 LEGEND PLATE5
PIEZO ALARM6
3 5
PART NO.
SP154DPDT 0003225300
0005726705.3 0005726850
0004465585.2 0210000283
2
1 4
6
9001
9001.5
BYECN NO.
REVISED PER
ECN:
5149
CLF
DATE
3/17/93
DATE
FV
DRAWN
WHEN ORDERING PARTS PLEASE SPECI FY MO DEL NUMBER.
C
2016
Haws Corporation - All Rights Reserved
HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation.
R
APPROVED
CHKD
11/03/16
VWC
MODEL(S)
1:2.5
SCALE:
9001/9001.5 ALARM
DRAWING TYPE: SIZE: A
PARTS BREAKDOWN
1455 KLEPPE LANE
SPARKS, NEVADA 89 43 1
(775) 359-4712 FAX (755) 359-7424
E-MAIL: HAWS@HAWSCO.COM WEBSITE: WWW.HAWSCO.COM
PAGE
PART NUMBER
0002080202
DRAWING NO.
A
SHEET OF
11
4 of 6
REV
30
Page 5
C
Haws Corporation - All Rights Reserved.
2016
MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITHOUT NOTICE.
2. INSTALLER MUST USE A THREAD SEALANT, SUCH AS APPLETON
TLC3, RECO MMEND ED FOR USE O N ELECTRICAL COMPONENTS ON
ALL ELECTRICAL NPT CONNECTIONS.
(CUSTOMER)
LOAD
FLOW SWITCH
(DPDT)
THE PINK WIRE MUST BE INSULATED AT ITS FREE END. LEAVING THE
TWO CRIMP TERMINALS (SUPPLIED) CONNECTED WILL DO THIS.
1. THE SIGNAL FROM THE PINK WIRE WILL BE SUPPLY VOLTAGE WHEN NO
WATER IS FLOWING AND ZERO VOLTAGE WHEN THE FLOW SWITCH AND
LOCAL ALARM ARE ACTIVATED. IF A REMOTE ALARM IS NOT USED,
THIS DOCUM EN T IS TR UE AND CORRECT AT TIM E OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS
HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation.
(PURPLE)
(CUSTOMER)
(PINK)
POWER SOURCE
NC
FL LT
(BLK)
(BLK)
NO
COM
GROUND
(GRN)
NC
HOT
(BLK)
(WHT)
R
HORN
(RED)
(RED)
SWITCH
(WHITE)
NO
NEUTRAL
FOR MODEL 9001.5
(BY OTHERS
1/2" UNIONS
RECOMMENDED)
COM
(RED)
CUSTOMER 120 VAC
POWER SOURCE
DO NOT DISASSEMBLE OR ROTATE
THIS ASSEMBLY AT ANY JOINT
A S DAMAGE WILL OCCUR
APPROVED:
DRAWN:
CH
FV
DATE:
01/09/01
DATE:
11/03/16
CHK'D.:
VWC
SCALE:
1:1
DRAWING TYPE: SIZE: A
9001/9001.50 ALARM
INSTALLATION
REVISED PER
ECN:
5149
BY:ECN NO.
VWC
MODEL(S)
WEBSITE: WWW.H AWSCO.COM
OR1-1/4" UNIONS
FOR MODEL 9001.5
WATER SUPPLY
OR 1/2" IPS
1-1/4 IPS
FOR CLAMP ASSEMBLY DETAIL
FLEX CONDUIT
STRAIGHT
(3-5/8")
152mm
6"MIN.
SEE SHEET 2
STRAIGHT
152mm
6"MIN.
(775) 359-4712 FAX (775) 359-7424
E-MAIL: HAWS@HAWSCO.COM
SPARKS, NEVADA 89431
1455 KLEPPE LANE
ARROW
NOTE FLOW
DIRECTION
0002080202.D
REVISION
PART NUMBER
SHEET OF
12
30
(13")
SHOWER
(REF)
PAGE
5 of 6
Page 6
C
Haws Corporation - All Rights Reserved.
2016
HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation.
BOX DOOR
MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITHOUT NOTICE.
3 NUTS TO BE INSTALLED TO A TORQUE OF 12 IN-LBS MAX.
TO 3 IN/LBS TORQUE
LID TO BE INSTALLED
1 SNAP CLAMP TO BE INSTALLED FIRST FOR VERTICAL SUPPORT.
2 SCREWS INSTALLED FROM FRON T, WITH BOX DOOR OFF.
THIS DOCUM EN T IS TR UE AND CORRECT AT TIM E OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS
R
APPROVED:
FV
DATE:
11/03/16
SCALE:
1:1
DRAWING TYPE: SIZE: A
DRAWN:
CH
DATE:
01/09/01
CHK'D.:
VWC
9001/9001.5 ALARM
REVISED PER
ECN:
5149
BY:ECN NO.
VWC
MODEL(S)
4X WASHER
2
4X 8-32 SCREW
SNAP CLAMP
4X HEX NUT
Ø1 5/8"
MAX PIPE SIZE
4X WASH ER
2X PIPE CLAMP
2
INSTALLATION
0002080202.D
REVISION
PART NUMBER
SHEET OF
22
30
WEBSITE: WWW.H AWSCO.COM
1
(775) 359-4712 FAX (775) 359-7424
E-MAIL: HAWS@HAWSCO.COM
SPARKS, NEVADA 89431
1455 KLEPPE LANE
3
PAGE
6 of 6