HAWS warrants that this specific product is guaranteed against defective material or poor workmanship for a period of one year from date of shipment. HAWS liability under this warranty shall be discharged by furnishing without charge F.O.B. HAWS Factory any goods, or part thereof, which shall appear to the Company upon inspection to be of defective material or not of first class workmanship, provided that claim is made in writing to Haws within a reasonable period after receipt of the product. Where claims for defects are made, the defective part or parts shall be delivered to the Company, prepaid, for inspection. HAWS will not be liable for the cost of repairs, alterations or replacements, or for any expense connected therewith made by the owner or his agents, except upon written authority from HAWS, Sparks, Nevada. HAWS will not be liable for any damages caused by defective materials or poor workmanship, except for replacements, as provided above. Buyer agrees that Haws has made no other warranties either expressed or implied in addition to those above stated, except that of title with respect to any of the products or equipment sold hereunder and that HAWS shall not be liable for general, special, or consequential damages claimed to arise under the contract of sale.
The emergency equipment manufactured by HAWS is warranted to function if installation and maintenance instructions provided are adhered to. The units also must be used for the purpose for which they were intended. This product is intended to supplement first-aid treatment. Due to widely varying conditions, Haws cannot guarantee that the use of this emergency equipment will prevent serious injury or the aggravation of existing or prior injuries.
Combination Shower Eye/Face Wash
LIMITED WARRANTY
NO OTHER WARRANTIES EXPRESSED OR IMPLIED ARE AUTHORIZED, PROVIDED
No. 2080174(23)
SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF THIS MODEL PLEASE CALL:
TECHNICAL SUPPORT: 1-800-766-5612 FOR CUSTOMER SERVICE: 1-888-640-4297
02/14 Model 8330 Page 1 of 5
LOCATION OF UNIT: The Model 8330 Stainless Steel combination Shower Eye/Face Wash should be installed in close proximity to potential accident areas. It should be clearly identified, free from obstructions and easy to access.
SUPPLY LINE: The minimum recommended line size is 1-1/4” IPS with 30-90 psi (2­6 ATM) flowing pressure. Where sediment or mineral content is a problem, an inlet filter is recommended.
PLUMBING CONNECTIONS: Inlet supply is female 1-1/4” IPS. Waste outlet is female 1-1/4” IPS.
INSTALLATION PROCEDURE
Refer to Installation Drawing for clarification. Check parts list to insure all required parts are included. Use pipe joint sealant PST #567 (Loctite) on all connections.
STEP 1: Prepare the emergency shower foundation by using the floor flange as a
template. Locate the three holes for the 3/8-16 UNC x 6” anchor bolts. (Not supplied). They should extend 1” above the floor level.
STEP 2: Once the concrete foundation is ready (dry), assemble the floor flange to
the anchor bolts; then securely fasten with 3/8-16 UNC Hex nuts and 3/8” washers (Not supplied). Seal and tighten floor flange and (1-1/4”) tee making certain the waste tee is facing the proper location and the foot control holes are facing side to side.
STEP 3: Assemble nipple (1-1/4” x 21-1/2”) to the tee and tighten with a pipe
wrench.
STEP 4: Assemble the eye/face wash loop assembly to the (21-1/2”) nipple from
Step three. Connect the pipe wrench to the nipple between the two tees to avoid damage.
STEP 5: Assemble in the following order: Attach nipple (1-1/4” x 24”) onto the loop assembly.
Attach nipple (1-1/4” x 24”) onto the tee. Attach tee (1-1/4” x 1-1/4” x 1”) onto nipple. Attach nipple (1” x 8”) and valve assembly onto tee. Attach street el (1”) and nipple (1” x 12-1/2”) onto valve.
STEP 6: Assemble showerhead onto street el (1”). If necessary, use Dow Corning
832 sealant placing 5 small beads on the male threads, just above the first thread.
STEP 7: Assemble the sign onto the unit. Use the strap, screws, washers and nuts
provided to mount the sign onto the upright. The sign should be positioned for maximum visibility.
STEP 8: Insert the plug into the optional supply line tee that is not used. Before
connecting the supply water line to the emergency shower; FLUSH THE LINE THOROUGHLY.