![](/html/49/4970/49700bcf52156f4c2e908a5211519cca9a30d8b0f315c795b61e7d5e7fc3c5df/bg1.png)
INSTALLATION, OPERATION
&
MAINTENANCE INSTRUCTIONS
1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424
E-mail: haws@hawsco.com website: www.hawsco.com
No. 2080170(19)
NOTE TO INSTALLER: Please leave this information with the Maintenance Department.
HAWS warrants that this specific product is guaranteed against defective material or poor
workmanship for a period of one year from date of shipment. HAWS liability under this
warranty shall be discharged by furnishing without charge F.O.B. HAWS Factory any
goods, or part thereof, which shall appear to the Company upon inspection to be of
defective material or not of first class workmanship, provided that claim is made in writing
to Haws within a reasonable period after receipt of the product. Where claims for defects
are made, the defective part or parts shall be delivered to the Company, prepaid, for
inspection. HAWS will not be liable for the cost of repairs, alterations or replacements, or
for any expense connected therewith made by the owner or his agents, except upon
written authority from HAWS, Sparks, Nevada. HAWS will not be liable for any damages
caused by defective materials or poor workmanship, except for replacements, as provided
above. Buyer agrees that Haws has made no other warranties either expressed or implied
in addition to those above stated, except that of title with respect to any of the products or
equipment sold hereunder and that HAWS shall not be liable for general, special, or
consequential damages claimed to arise under the contract of sale.
The emergency equipment manufactured by HAWS is warranted to function if installation
and maintenance instructions provided are adhered to. The units also must be used for the
purpose for which they were intended. This product is intended to supplement first-aid
treatment. Due to widely varying conditions, Haws cannot guarantee that the use of this
emergency equipment will prevent serious injury or the aggravation of existing or prior
injuries.
NO OTHER WARRANTIES EXPRESSED OR IMPLIED ARE AUTHORIZED, PROVIDED OR
GIVEN BY HAWS.
SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF THIS
MODEL, PLEASE CALL:
Model 8320-8325/8320CRP
Shower and Eye/Face Wash
LIMITED WARRANTY
1-800-766-5612
FOR PARTS CALL:
1-888-640-4297
04/14 Model 8320-8325/8320CRP Page 1 of 5
![](/html/49/4970/49700bcf52156f4c2e908a5211519cca9a30d8b0f315c795b61e7d5e7fc3c5df/bg2.png)
LOCATION OF UNIT: The Model 8320/8320CRP/8325 Emergency Shower should
be installed in close proximity to potential accident areas. It should be clearly
identified, free from obstructions and easy to access.
SUPPLY LINE: The minimum recommended line size is 1-1/4” IPS with 30-90 psi
(2-6 ATM) flowing pressure. Where sediment or mineral content is a problem, an
inlet filter is recommended.
PLUMBING CONNECTIONS: Inlet supply is female 1-1/4” IPS. Waste outlet is
female
1-1/4” IPS.
INSTALLATION PROCEDURE
Refer to Installation Drawing for clarification. Use pipe joint sealant PST #565 (Loctite)
on all connections.
STEP 1: Prepare the emergency shower foundation by using the floor flange
assembly as a template.
STEP 2: Once the foundation is ready, fasten the floor flange to the foundation.
Use minimum 3/8” fasteners (not supplied).
STEP 3: Assemble lower tee (1-1/4”) to the floor flange.
STEP 4: Attach nipple (1-1/4” x 21-1/2”) and eyewash loop assembly to lower tee
and tighten, grabbing the waste bend of loop assembly for leverage.
STEP 5: Attach nipple (1-1/4” x 24”) and tee (1-1/4”) to loop assembly and tighten.
STEP 6: Attach nipple (1-1/4” x 24”) and tee (1-1/4” x 1-1/4” x 1”) and tighten.
STEP 7: Attach valve assembly with nipple (1” x 9”) to tee and tighten with a spud
wrench.
STEP 8: Assemble the street elbow (1”) onto nipple (1” x 12-1/2”).
Attach nipple onto valve.
STEP 9: Attach showerhead onto street elbow (1”).
STEP 10: Assemble the sign onto the unit. Use the strap, screws, washers and nuts
provided to mount the sign onto the upright. The sign should be positioned
for maximum visibility.
STEP 11: Insert the plug into the optional supply line tee that is not used. Before
connecting the supply water line to the emergency shower, FLUSH THE
LINE THOROUGHLY.
04/14 Model 8320-8325/8320CRP Page 2 of 5