Haws 8317CTFP.220V Installation Manual

C
Haws Corporation - All Rights Reserved.
2014
MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITHOUT NOTICE.
NOTES:
1. DIMENSIONS MAY VARY BY ± 1/2 INCH [13mm].
2. TO COMPLY WITH ANSI Z358.1-2009 FOR EMERGENCY EYEWASH OR EYE/FACE WASH AND SHOWER EQUIPMENT:
- UNIT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND ACCEPTABLE PLUMBING PRACTICES.
- EYEWASH OR EYE/FACE WASH SHALL BE POSITIONED WITH NOZZLES NOT LESS THEN 83.8 CM (33 IN.) AND NO GREATER THAN
114.3 CM (45 IN.) FROM SURFACE ON WHICH USER STANDS AND 15.3 CM (6 IN.) MINIMUM FROM WALL OR NEAREST OBSTRUCTION.
- SHOWER SHALL BE POSITIONED SO THAT SHOWER HEAD IS NOT LESS THAN 208.3 CM (82 IN.) NOR MORE THAN 243.8 CM (96 IN.)
FROM SURFACE ON WHICH USER STANDS.
- SHOWER SPRAY PATTERN SHALL HAVE A MINIMUM DIAMETER OF 50.8 CM (20 IN.) AT 152.4 CM (60 IN.) ABOVE SURFACE ON WHICH
USER STANDS, AND CENTER OF SPRAY PATTERN SHALL BE LOCATED AT LEAST 40.6 CM (16 IN.) FROM ANY OBSTRUCTION.
3. DO NOT USE REGULAR PIPE SEALANT. IF NECESSARY USE DOW CORNING 832 SEALANT PLACING 5 SMALL
BEADS ON THE MALE THREADS, JUST ABOVE THE FIRST THREAD.
(NOTES CONTINUED ON SHEET 2 OF 4.)
2426mm
95-1/2"
THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS
HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation.
152mm
6"
DRENCH HOSE
DRENCH HOSE ACTIVATION
VALVE ASSEMBLY
3
3/4" NPT JUNCTION BOX
FLOOR LINE
R
2299mm
90-1/2"
2172mm
85-1/2"
67-1/4"
1708mm
41-3/4"
1060mm
178mm
7"
APPROVED:
DRAWN:
RTM
FV
REVISED PER
ECN:
DATE:
03/29/05
4921
DATE:
10/21/14
BY:ECN NO.
CHK'D.:
FV
SCALE:
MODEL(S)
355mm
14"
ABS JACKET
REMOVABLE
MOUNTING LOCATION
AREA LIGHT
FOR OPTIONAL
927mm
36-1/2"
1098mm
43 1/4"
1/20
8317CTFP(120V)/ 8317CTFP.220V
DRAWING TYPE: SIZE: A
INSTALLATION
0002081781.D
PART NUMBER
DRAWING NO.
SHEET OF
15201A00
14
REV
17
MOUNTING LOCATION
FOR OPTIONAL
INDICATOR LIGHT
6-3/4"
HOLE SHOWN.
171mm
MUST BE IN UP POSITION WHEN FULLY
NOTE: PULL RO D AND HANDLE NOT
ASSEMBLED. ORIENTATION OF HANDLE
TRACED AND INSULATED
SUPPLY MUST BE HEAT
Ø9"
Ø203mm
Ø8"
B.C.
30°
3X
Ø10mm
Ø3/8"
Ø229mm
INSTALLATION INSTRUCTIONS.)
SP158B FREEZE PROTECTION VALVE
(SEE NOTES ON SHEETS 2 & 3 FOR
(775) 359-4712 FAX (755) 359-7424
E-MAIL: HAWS@HAWSCO.COM
WEBSITE: WWW.HAWSCO.COM
SPARKS, NEVADA 89431
1455 KLEPPE LANE
IMPORTANT
20-1/2"
521mm
MANUAL (PAGE 2) TO CONVERT
TO A BOTTOM SUPPLY UNIT.
PAGE
IN THE OPERATION & MAINTENANCE
OF THE INSTALLATION PROCEDURE
TOP SUPPLY SHOWN. SEE STEP 2
1-1/4" IPS SUPPLY UNION (INLET)
1 of 4
171mm
6 3/4"
C
Haws Corporation - All Rights Reserved.
2014
HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation.
R
MAKE SPECIFICATIONS AND MEASURE M ENTS SUBJECT TO CHANGE WITHOUT NOTICE.
THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION. CONTINUED PRODUCT IM PROVEMENTS
NOTES: (CONTINUED FROM SHEET 1 OF 4)
. FREEZE PROTECTION VALVE INSTALLATION INSTRUCTIONS:
INSTALL VALVE SUB-ASSEMBLY INTO FEMALE SECTION OF UNION AND TIGHTEN WATER-TIGHT.
FORM HEAT TRACE CABLE AROUND VALVE AND PLUG, APPLY 2X CABLE-TIES TO HEAT TRACE CABLE, AS SHOWN, ENSURING
THAT HEAT TRACE CABLE IS PRESSED FIRMLY AGAINST SIDES OF VALVE (PUSH ANY LOOSE HEAT TRACE CABLE BACK INSIDE
JACKET THROUGH RUBBER GROMMET). TRIM EXCESS CABLE-TIE STRAPPING.
SLIDE INNER TUBE W/ PLUGGED END OVER VALVE WITH ADHESIVE SEAM FACING BOTTOM AND NON-PLUGGED END OF TUBE
BUTTED UP AGAINST UNION SURFACE. REMOVE 2X ADHESIVE TAPE FROM SEAM AND SQUEEZE ADHESIVE SEAMS TOGETHER
AROUND VALVE. APPLY 2X CABLE-TIES TO TUBE, IN APPROXIMATE LOCATIONS SHOWN. TRIM EXCESS CABLE-TIE STRAPPING.
REFERENCE ONLY. VALVE CAN BE INSTALLED AT TOP OR BOTTOM.
(NOTES CONTINUED ON SHEET 3 OF 4)
C
B
4
A
SP158B VALVE SHOWN CONNECTED TO BOTTOM UNION FOR
E
HEAT TRACE CABLEB
JACKET SURFACE
(SEE SHEET 3.)
CABLE-TIE, 15" / PN 0005972499 B
UNION SURFACE
MALE SECTION OF UNION
(PART OF VALVE SUB -ASSY)
FEMALE SECTION OF UNION
(PA RT OF SHO WER U NIT)
RUBBER GROMMET
BARBED CONNECTOR
VALVE, FREEZE (NO UNION) SP158B
C
C
APPROVED:
DRAWN:
4632
VWC
FV
REVISED PER
ECN:
DATE:
12/2/12
4921
DATE:
10/21/14
BY:ECN NO.
CHK'D.:
HM
SCALE:
MODEL(S)
NA
8317CTFP(120V) / 8317CTFP.220V
DRAWING TYPE:
ADHESIVE SEAM
PLUGG ED END
A
C
INNER TUBE W/ PLUGGED END
CABLE-TIE, 15" / PN 0005972499
A
C
B
A
C D
INSTALLATION
SIZE: A
0002081781.D
PART NU M BER
DRAWING NO.
SHEET OF
15201A 17
24
REV
WEBSITE: WWW.HAWSCO.COM
(775) 359-4712 FAX (755) 359-7424
E-MAIL: HAWS@HAWSCO.COM
SPARKS, NEVADA 89431
1455 KLEPPE LANE
PAGE
2 OF 4
Loading...