Haws 8317CTFP User Manual

)
INS T ALLATIO N , OPERA T ION
&
MAINTENANCE INSTRUCTIONS
1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424
E-mail: haws@hawsco.com website: www.hawsco.com
NOTE TO INSTALLER: Please leave this information with the Maintenance Department.
HAWS warrants that this specific product is guaranteed against defective material or poor workmanship for a period of one year from date of shipment. HAWS liability under this warranty shall be discharged by furnishing without charge F.O.B. HAWS Factory any goods, or part thereof, which shall appear to the Company upon inspection to be of defective material or not of first class workmanship, provided that claim is made in writing to Haws within a reasonable period after receipt of the product. Where claims for defects are made, the defective part or parts shall be delivered to the Company, prepaid, for inspection. HAWS will not be liable for the cost of repairs, alterations or replacements, or for any expense connected therewith made by the owner or his agents, except upon written authority from HAWS, Sparks, Nevada. HAWS will not be liable for any damages caused by defective materials or poor workmanship, except for replacements, as provided above. Buyer agrees that Haws has made no other warranties either expressed or implied in addition to those above stated, except that of title with respect to any of the products or equipment sold hereunder and that HAWS shall not be liable for general, special, or consequential damages claimed to arise under the contract of sale.
The emergency equipment manufactured by HAWS is warranted to function if installation and maintenance instructions provided are adhered to. The units also must be used for the purpose for which they were intended. This product is intended to supplement first-aid treatment. Due to widely varying conditions, Haws cannot guarantee that the use of this emergency equipment will prevent serious injury or the aggravation of existing or prior injuries.
NO OTHER WARRANTIES EXPRESSED OR IMPLIED ARE AUTHORIZED, PROVIDED OR GIVEN BY HAWS.
SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF THIS MODEL PLEASE CALL:
TECHNICAL SUPPORT: 1-800-766-5612
FOR CUSTOMER SERVICE: 1-888-640-4297
Model 8317CTFP (120V) &
8317CTFP.220V
LIMITED WARRANTY
No. 2081781 (17
09/14 Model 8317CTFP (120V) & 8317CTFP.220V Page 1 of 9
RECOMMENDED TOOLS: Pipe joint sealant, screwdriver, pipe wrench, three (3) rust resistant anchors (3/8” diameter), silicone caulking, level.
LOCATION OF UNIT: The Model 8317CTFP (120V) & 8317CTFP.220V Emergency Shower Eye / Face Wash should be installed in close proximity to potential accident areas. It should be clearly identified, free from obstructions and easy to access. Suitable for use in Class 1, Division 2 Group B,C,& D areas. Temperature rating T6 (85º C).
ELECTRICAL SUPPLY FOR MODEL 8317CTFP: Electrical power required for standa rd heat traced unit is 120 VAC. Average power consumption at 50º F (10º C) ambient temperature is 125 watts. Maximum less lighting is 150 watts. Connection at input junction box is 3/4” NPT. DURING
POTENTIALLY FREEZING PERIODS; INSURE THAT UNIT IS CONNECTED TO A CONTINUOUS POWER SUPPLY.
ELECTRICAL SUPPLY FOR MODEL 8317CTFP.220V: Electrical power required for standard heat
traced unit is 220 VAC. Average power consumption at 50º F (10º C) ambient temperature is 125 watts. Maximum less lighting is 150 watts. Connection at input junction box is 3/4" NPT. DURING
POTENTIALLY FREEZING PERIODS; INSURE THAT UNIT IS CONNECTED TO A CONTINUOUS POWER SUPPLY.
WATER SUPPLY: The minimum recommended line is 1-1/4” IPS with 30-90 psi (2-6 ATM ) flowin g
pressure. An inlet filter is recommended where sediment or mineral content is a problem. Inlet connection is 1-1/4” IPS. WATER SUPPLY MUST BE FREEZE PROTECTED.
MAINTENANCE: In freezing conditions, wipe eye/face wash head and dust cover dry after each use to prevent unwanted ice buildup. SP158B Freeze Protection Valve is a field serviceable item Refer to SP158B Manual for more information.
WARNING: Fire and shock hazards: Must use a ground fault electrical protection device (30mA GFEPD) for Heat Trace. Electrical fault currents may be insufficient to trip a conventional circuit breaker.
INSTALLATION PROCEDURE
Refer to Installation Drawings for clarification. Use pipe joint sealant on all connections. STEP 1: Prepare the emergency shower foundation locating three 3/8” anchors (not supplied), for
shower floor flange. Note flange hole positions so shower head eye/face wash and su pply inlet will be in proper direction. Raise shower into position and shim under floor flange if required to
STEP 2: Connect water supply as follows: This model is designed for either a top water supply or a
maintain upright vertical.
bottom water supply. This model is shipped with a complete 1-1/4” IPS union connected at the top supply inlet. At the bottom supply inlet there is only half of a 1-1/4” IPS union. The other half of the union is connected to a freeze protection bleed valve located inside the shipping carton. Remove outer half of the 1-1/4” union from the top water inlet. Assemble the half union onto 1-1/4” IPS male thread of either the top or bottom water supply.
Complete supply connection at the desired 1-1/4” union. Attach the other half union with the freeze valve attached to the other unused union and complete the connection. Refer to SP158B Freeze Protection Valve installation instructions on Sheets 2 and 3 of installation drawing.
Turn on water supply and check for leaks, then operation of eye/face wash and shower together. If flow of either is inadequate check troubleshooting chart. Heat trace (supplied), insulate and weather seal inlet union and above ground supply (by others). If flow switch is used, heat-trace and insulate 6” above flow switch tee.
09/14 Model 8317CTFP (120V) & 8317CTFP.220V Page 2 of 9
INSTALLATION PROCEDURE...
STEP 3: Connect electrical power supply conduit to input junction box using suitable conduit
fitting into 3/4” NPT inlet. Install optional area light and indicator light, if desired. For MODEL 8317CTFP (120V): connect 120 volt AC line to 16 gauge shower wires as
follows: Black = 120 VAC, White = Neutral, Green = Ground.
For MODEL 8317CTFP.220V:
Connect 220 volt AC line to 16 gauge shower wires as follows: Black = 220 VAC,
Red = 2 Electrical Schematic Drawing, Sheet 4 of Installation Drawing).
nd
Hot, Green = Ground. Turn on power supply to complete installation. (See
OPERATING INSTRUCTIONS
Power to the 8317CTFP (120V) & 8317CTFP.220V may be left on year round. The non­adjustable thermostat will shut off heat cable when air temperature rises to 55
Heat cycle will repeat when air temperature drops to between 45º -55º F (7º - 13ºC).
C).
Periodic check of water temperature from shower or eye/face wash will confirm normal operating temperatures between 45
º- 95ºF (7º-35ºC).
This unit is heated by low power heat trace cable suitable for freeze protection but not suitable for providing a warm shower from a cold water supply. Moments after activating shower, water temperature will drop to supply temperature.
º - 65º F (12º - 18º
ANSI recommends a comfortable shower temperature range of 60
ºF (15ºC) to 100ºF (38ºC). For
the protection of the user, we strongly recommend that some system be installed to provide tempered (warm) water to this shower and eye/face wash. Heat trace cable used on this shower heats slowly and may take 90 minutes to complete a full heat cycle.
No drain connection at bleed valve(s) is normally required. Valve(s) will remain closed unless power outage, high ambient temperature (with optional scald protection valve, only) or malfunction occurs (see Troubleshooting).
NOTE: IF GROUND WATER IS BELOW 38ºF (3.3ºC) SIMPLY TESTING SHOWER MIGHT CAUSE BLEED VALVE TO OPEN. ONCE OPENED, COLD GROUND WATER WILL KEEP BLEED VALVE OPEN. SEE TROUBLESHOOTING GUIDE FOR PROCEDURE TO CLOSE BLEED VALVE ONCE OPENED.
Periodic tests for proper function of shower and eye/face wash should be performed and recorded on inspection tags attached to unit or in separate maintenance logbook (preferred).
IMPORTANT SAFETY NOTICE
THE NATIONAL ELECTRICAL CODE REQUIRES GROUND-FAULT EQUIPMENT PROTECTION ON EACH HEATING CABLE BRANCH CIRCUIT. TO REDUCE THE RISK OF FIRE CAUSED BY DAMAGE OR IMPROPER INSTALLATION, CIRCUIT BREAKERS SUCH AS SQUARE D QO-EPD AND QOB-EPD OR EQUIVALENT, WITH A 30mA TRIP LEVEL, SHOULD BE USED. PLEASE SUBSTITUTE THESE BREAKERS WHEREVER REFERENCE IS MADE TO CONVENTIONAL BREAKERS IN THIS DOCUMENT. ALTERNATIVE DESIGNS PROVIDING COMPARABLE LEVELS OF GROUND-FAULT PROTECTION MAY ALSO BE ACCEPTABLE.
09/14 Model 8317CTFP (120V) & 8317CTFP.220V Page 3 of 9