Haws 8300FP User Manual

Page 1
)
INS T A L L ATION, OP E RAT IO N
&
MAINTENANCE INSTRUCTIONS
1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424
E-mail: haws@hawsco.com website: www.hawsco.com
NOTE TO INSTALLER: Please leave this information with the Maintenance Department.
HAWS warrants that this specific product is guaranteed against defective material or poor workmanship for a period of one year from date of shipment. HAWS liability under this warranty shall be discharged by furnishing without charge F.O.B. HAWS Factory any goods, or part thereof, which shall appear to the Company upon inspection to be of defective material or not of first class workmanship, provided that claim is made in writing to Haws within a reasonable period after receipt of the product. Where claims for defects are made, the defective part or parts shall be delivered to the Company, prepaid, for inspection. HAWS will not be liable for the cost of repairs, alterations or replacements, or for any expense connected therewith made by the owner or his agents, except upon written authority from HAWS, Sparks, Nevada. HAWS will not be liable for any damages caused by defective materials or poor workmanship, except for replacements, as provided above. Buyer agrees that Haws has made no other warranties either expressed or implied in addition to those above stated, except that of title with respect to any of the products or equipment sold hereunder and that HAWS shall not be liable for general, special, or consequential damages claimed to arise under the contract of sale.
The emergency equipment manufactured by HAWS is warranted to function if installation and maintenance instructions provided are adhered to. The units also must be used for the purpose for which they were intended. This product is intended to supplement first-aid treatment. Due to
Model 8300FP Freeze Resistant
Combination Shower Eye/Face Wash
LIMITED WARRANTY
widely varying conditions, Haws cannot guarantee that the use of this emergency equipment will prevent serious injury or the aggravation of existing or prior injuries.
NO OTHER WARRANTIES EXPRESSED OR IMPLIED ARE AUTHORIZED, PROVIDED OR GIVEN BY HAWS.
No. 2080163 (15
SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF THIS MODEL PLEASE CALL:
TECHNICAL SUPPORT: 1-800-766-5612
FOR CUSTOMER SERVICE: 1-888-640-4297
05/16 Model 8300FP Page 1 of 5
Page 2
LOCATION OF UNIT: The Model 8300FP Freeze Resistant Shower/Eye/Face Wash should be installed in close proximity to potential accident areas. It should be clearly identified, free from obstructions and easy to access.
SUPPLY LINE: The minimum recommended line size is 1-1/4” IPS with 30-90 psi (2-6 ATM) flowing pressure. Where sediment or mineral content is a problem, an inlet filter is recommended.
PLUMBING CONNECTIONS: The main inlet supply connections are 1-1/4” male IPS for shower and 3/4” female IPS for eyewash. Waste outlet is 1-1/4” female IPS.
MAINTENANCE: In freezing conditions, wipe eye/face wash head and dust cover dry after each use to prevent unwanted ice buildup.
INSTALLATION PROCEDURE
Refer to Installation Drawing for clarification. Check parts list to insure all required parts are included. Use pipe joint sealant PST #565 (Loctite) on all connections.
STEP 1: Install the 1-1/4” and 3/4” supply line below the frost line. Provide porous fill with a minimum
size of 5 cubic feet for the supply line drain back.
STEP 2: Install the MK8A and MK81A freeze proof valves in their proper location (See Installation
Drawing). For proper operation, valves must be installed in a vertical position. Valves must not be bowed or bent as this may result in binding and improper function. Turn the water on and test for proper operation before burying the valves.
STEP 3: Prepare the emergency shower foundation by using the floor flange as a template. Locate the
three holes for the 3/8-16 UNC x 6" anchor bolts (not supplied). Anchor bolts should extend 1" above the floor level.
STEP 4: Once the concrete foundation is ready (dry), assemble the floor flange to the anchor bolts; and
then securely fasten with 3/8-16 UNC Hex Nuts and 3/8" washers, (Not supplied). Seal and tighten tee (1-1/4) tee to floor flange making certain the 1-1/4 tee is facing the proper location.
STEP 5: Assemble (1-1/4” x 21-1/2”) nipple to the (1-1/4”) tee and tighten with a pipe wrench. STEP 6: Assemble the eye/face wash assembly to the waste bend, then assemble the 1-1/4” tee and
the 1-1/4” x 4” plugged nipple with the plugged side on top, then attach the other 1-1/4” tee to the 1-1/4” x 4” plugged nipple. Attach this assembly to nipple (1-1/4” x 21-1/2") nipple.
STEP 7: Assemble in the following order: Attach nipple (1-1/4” x 52-1/2”) onto the eye/face wash assembly.
Attach elbow (1-1/4” x 1”) onto nipple. Attach nipple (1x 24-5/8”) onto elbow. Attach street elbow (1”) onto nipple. Attach nipple (1-1/4” x 6”) onto tee (1-1/4”). Attach union (1-1/4”) onto nipple (1-1/4” x 6”). Attach nipple (1-1/4” x 6”) onto the outlet of MK81A Valve, then connect both nipples (1/4” x 9”)
with the (1/4”) union. Attach nipple (1/4” x 9”) onto the eye/face wash assembly. Attach union (1/4”) onto nipple (1/4” x 9). Attach nipple (1/4” x 9”) onto the outlet of MK8A Valve (use the reducer bushing), then connect
both nipples (1/4” x 9”) with the (1/4”) union. STEP 8: Assemble the sign onto the unit. Use the strap, screws, washers and nuts provided to mount
the sign onto the upright. The sign should be positioned for maximum visibility.
STEP 9: Attach the showerhead. Water test and make the final check up.
05/16 Model 8300FP Page 2 of 5
Page 3
TROUBLESHOOTING
PROBLEM
1. No flow. 1. Check the main shut-off valve.
REPAIR CHECKLIST
2. Water leak between joints or fittings.
3. Insufficient water flow, shower and eyewash.
4. Water does not drain properly.
5. Insufficient water flow on eye/face wash, however, shower is sufficient.
6. Eye/face wash streams do not meet desired eye level.
2. Tighten loose connections. If leak persists, the application of hot water will sometimes reseat improperly applied joint compound. After 30 minutes wait and retest, a persistent leak will necessitate reassembly and additional sealant.
3. Verify minimum 30 psi (2 ATM) flowing supply line pressure.
4. Check your drain system for debris. Check the main waste line of your building to see if it does handle the capacity required for the entire drainage system.
5. Probable clogging of flow control due to inadequate line flushing. Unscrew eye/face wash head and adapter. Disassemble adapter to gain access and clean rubber flow control.
6. Possible blocked flow control, see above solution. Possible non-leveled eye/face wash assembly.
7. Water flows through check valve while valve is open.
8. Water seeping at the shower or eye/face wash.
9. Insufficient water flow at the showerhead, however, eye/face wash is sufficient.
7. Insure that push plate is fully depressed.
8. Shut off the water; remove the inner stem assembly and plunger. Check for damaged seat or ‘O’ rings, then flush thoroughly. If problem persists order the VRKMK81A for the shower or the VRKMK8A for the eye/face wash.
9. Probable clogging of flow control inside showerhead. Unscrew showerhead off of elbow and clean rubber flow control.
© 2016 Haws® Corporation – All Rights Reserved HAWS® and other trademarks used in these materials are the exclusive property of Haws Corporation.
05/16 Model 8300FP Page 3 of 5
Page 4
THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS MAKE SPECIFICATIONS AND MEASURE M ENTS SUBJECT TO CHANGE WITHOUT NOTICE.
PARTS BREAKDOWN
2
ITEM DESCRIPTION
SHOWER HEAD
1 2 SHOWER SIGN
FLOOR FLANGE
3 4 FREEZE PROOF VA LVE
5 EYEWASH HEADS 7 SS BOWL
8 EYEWASH DUST COVERS 9 FREEZE PROOF VA LVE
10 GREEN & YELLOW LABEL
PUSH PLATE W/ LABELS
11 12
TEST TAG
--
1
VALVE REPAIR KIT MK81A
--
VALVE REPAIR KIT MK8A
PART NO.
8129FC SP178 SP75 MK8A SP11FC
SP90 9095 MK81A
SP185 SP218 SP170
VRKMK81A
VRKMK8A
12
7
10
11
2 PLS
TOP VIEW
8
9
4
3
5
BYECN NO.
REVISED PER
ECN:
CLF
5080
DATE
03/10/93
FV
DRAWN
WHEN ORDERING PARTS PLEASE SPECIFY MODEL NUMBER.
C
2016
Haws Corporation - All Rights Reserved
HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation.
R
APPROVED
DATE
06/09/16
HM
CHKD
RVH
MODEL(S)
SCALE:
1:1
8300F P S HOWER
EYEWASH COMBO
DRAWING TYPE: SIZE: A
PARTS BREAKDOWN
1455 KLEPPE LANE
SPARKS, NEVAD A 89431
(775) 359-4712 FAX (775) 359-7424
E-MAIL: HAWS@HAWSCO.COM WEBSITE: WWW.HAWSCO.COM
PAGE
PART NUMBER
0002080163
REVISION
15
SHEET OF
11
4 of 5
Page 5
C
Haws Corporation - All Rights Reserved.
2016
MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITHOUT NOTICE.
NOTES:
1 SPECIFY BURY DEPTH FOR FREEZE RESISTANT VALVE, STANDARD BURY DEPTHS ARE:
- 24" [610mm] AND 42" [1 067mm].
2. DIMENSIONS MAY VARY BY ± 1/2 INCH [13mm].
3. TO COMPLY WITH AN SI Z358.1- 2009 FOR EMERGENCY EYEWASH OR EYE/FAC E WASH AND SHOW ER EQUIPMENT:
- UNIT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND ACCEPTABLE PLUMBING PRACTICES.
- EYEWASH OR EYE/FACE WASH SHALL BE POSITIONED WITH NOZZLES NOT LESS THEN 83.8 CM (33 IN.) AND NO GREATER T H AN
114.3 CM (45 IN.) FROM SURFACE ON WHICH USER STANDS AND 15.3 CM (6 IN.) MINIMUM FROM WALL OR NEAREST OBSTRUCTION.
- SHOWER SHALL BE POSIT IONED SO THA T SHOWER HEAD IS NOT LESS THAN 208.3 C M (82 IN.) NOR MORE THAN 243.8 CM (96 IN.)
FROM SURFACE ON WHICH USER STANDS.
- SHOW ER SPRAY PATTERN SHALL HA VE A M INIMUM DIA M ET ER OF 50.8 CM (20 I N.) AT 152.4 CM (6 0 IN .) ABOVE SURFACE ON WHICH
USER STANDS, AND CENTER OF SPRAY PATTERN SHALL BE LOCATED AT LEAST 40.6 CM (16 IN.) FROM ANY OBSTRUCTION.
4. WHEN INSTALLING THIS UNIT, LOCAL, STATE OR FEDERAL CODES SHOULD BE ADHERED TO.
THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS
FROST LINE
2184mm
FEMALE
SUPPLY
3/4" IPS
908mm
35-3/4"
POROUS FILL
(BY OTHERS)
86"
5 FT.
HAWS and other trademarks use d in these ma terials are the exclusive property of Haws Corporatio n.
3
R
MALE SUPP LY
1-1/4" IPS
1
922mm
36-5/16"
POSITION
PUSH PL ATE
SHOWN IN
CLOSED
CHECK/DRAIN
VALVE
FLOOR
LINE
3X
Ø10mm
MOUNTING DETA IL
Ø3/8"
30°
1067mm
42"
Ø229mm
APPROVED:
DRAWN:
CH
FV
REVISE D PER
ECN:
DATE:
05/91
5080
DATE:
06/09/16
CHK'D.:
BY:ECN NO.
RVH
HM
SCALE:
MODEL(S)
Ø203mm
Ø8"
Ø9"
806mm
31-3/4"
1:1
DRAWING TYPE: SIZE: A
EYEWASH COMBO
8300FP SHOWER
INSTALLATION
0002080163.D
PART NUMBER
REVISION
SHEET OF
11
15
470mm
B.C.
18-1/2"
1-1/4" IPS
FEMALE
WASTE
167mm
6-9/16"
TOP VIEW
(775) 359-4712 FAX (775) 359-7424
E-MAIL: HAWS@HAWSCO.COM
WEBSITE: WWW.HAWSCO.COM
SPARKS, NEVADA 89431
1455 KLEPPE LANE
806mm
31-3/4"
406mm
16"
PAGE
5 of 5