Haws 8300.158 User Manual

Page 1
(
INSTALLATION, OPERATION
&
MAINTENANCE INSTRUCTIONS
1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424
E-mail: haws@hawsco.com website: www.hawsco.com
NOTE TO INSTALLER: Please leave this information with the Maintenance Department.
HAWS warrants that this specific product is guaranteed against defective material or poor
workmanship for a period of one year from date of shipment. HAWS liability under this
warranty shall be discharged by furnishing without charge F.O.B. HAWS Factory any goods, or part thereof, which shall appear to the Company upon inspection to be of defective material or not of first class workmanship, provided that claim is made in writing to Haws within a reasonable period after receipt of the product. Where claims for defects are made, the defective part or parts shall be delivered to the Company, prepaid, for inspection. HAWS will not be liable for the cost of repairs, alterations or replacements, or for any expense connected therewith made by the owner or his agents, except upon written authority from HAWS, Sparks, Nevada. HAWS will not be liable for any damages caused by defective materials or poor workmanship, except for replacements, as provided above. Buyer agrees that Haws has made no other warranties either expressed or implied in addition to those above stated, except that of title with respect to any of the products or equipment sold hereunder and that HAWS shall not be liable for general, special, or consequential damages claimed to arise under the contract of sale.
The emergency equipment manufactured by HAWS is warranted to function if installation and maintenance instructions provided are adhered to. The units also must be used for the purpose for which they were intended. This product is intended to supplement first-aid treatment. Due to widely varying conditions, Haws cannot guarantee that the use of this emergency equipment will prevent serious injury or the aggravation of existing or prior injuries.
NO OTHER WARRANTIES EXPRESSED OR IMPLIED ARE AUTHORIZED, PROVIDED OR GIVEN BY HAWS.
Model 8300.158 Combination
Shower Eye/Face Wash
LIMITED WARRANTY
No. 2080167
SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF THIS MODEL PLEASE CALL:
14
TECHNICAL SUPPORT: 1-800-766-5612
FOR CUSTOMER SERVICE: 1-888-640-4297
2/16 Model 8300.158 Page 1 of 5
Page 2
LOCATION OF UNIT: The Model 8300.158 Emergency Shower should be installed in
close proximity to potential accident areas. It should be clearly identified, free from obstructions and easy to access.
SUPPLY LINE: The minimum recommended line size is 1 1/4” IPS with 30-90 psi (2-6
ATM) flowing pressure. Where sediment or mineral content is a problem, an inlet filter is recommended.
PLUMBING CONNECTIONS: Inlet supply is female 1 1/4” IPS. Waste outlet is female
1 1/4” NPT.
MAINTENANCE: In freezing conditions, wipe eye/face wash head and dust cover dry
after each use to prevent unwanted ice build up.
NOTE: To minimize excessive spillage from air gap when testing, unit must be opened and closed completely with one swift continuous motion.
INSTALLATION PROCEDURE
Refer to Installation Drawing for clarification. Check parts list to insure all required parts are included. Use pipe joint sealant PST #565 (Loctite) on all connections.
STEP 1: Prepare the emergency shower foundation by using the floor flange assembly as
a template. Locate the three holes for the 3/8 16 UNC x 6” anchor bolts (not supplied). They should extend 1” above the floor level.
STEP 2: Once the concrete foundation is ready (dry), assemble the floor flange assembly
to the anchor bolts; then securely fasten with 3/8 16 UNC Hex nuts and 3/8” washers (not supplied). Seal and tighten floor flange and tee making certain the waste tee is facing the proper location (as shown in installation drawing) and the foot control holes are facing side to side.
STEP 3: Assemble nipple (1 1/4” x 21 1/2”) to the floor flange assembly and tighten with a
pipe wrench.
STEP 4: Assemble the eye/face wash loop assembly to the 21 1/2” nipple from step three.
Connect the pipe wrench to the galvanized nipple between the two tees to avoid damage.
STEP 5: Assemble in the following order: Attach nipple (1 1/4” x 24”) to loop assembly.
Attach coupling (1 1/4”) to nipple.
Attach nipple (1 1/4” x 24) to coupling.
Attach tee (1 1/4” x 1 1/4” x 1”) to nipple.
Attach nipple (1” x Close) to tee.
Attach ball valve/handle assembly to nipple. Note: Refer to installation Drawing (Sheet 5 of O&M) for correct orientation of ball valve.
Attach nipple (1” x 19 1/2”) to ball valve/handle assembly. Attach elbow (1”) to nipple and attach showerhead to elbow.
STEP 6: Assemble the (1”) elbow onto the horizontal nipple (1” x 19 ½”), and attach the
showerhead onto the elbow.
2/16 Model 8300.158 Page 2 of 5
Page 3
STEP 7: Assemble the sign onto the unit. Use the strap, screws, washers and nuts
provided to mount the sign onto the upright. The sign should be positioned for maximum visibility.
STEP 8: Air Gap Assembly: The 7” hose is connected to the SP158B valve, the 8” hose is
connected to the 3 way valve, and tube at bottom (8”) is connected to barb fitting on elbow at the bottom of shower.
STEP 9: Before connecting the supply water line to the emergency shower, FLUSH THE
LINE THOROUGHLY.
TROUBLESHOOTING
PROBLEM
1. No flow. 1. Check the main shut-off valve.
2. Insufficient water flow 2. Verify minimum 30 psi (2 ATM) flowing
REPAIR CHECKLIST
supply line pressure.
3. Insufficient water flow on eye/face wash, however, shower is sufficient.
4. Eye/face wash streams do not meet at desired eye level.
5. Insufficient water flow at the showerhead, however, eye/face wash is sufficient.
6. Water does not drain properly 6. Check your drain system for debris.
7. Water leaks between joints or fittings 7. Tighten loose connections. If leak
3 Probable clogging of flow control due to
inadequate line flushing. Unscrew eye/face wash head and adapter. Disassemble adapter to gain access and clean rubber flow control.
4. Possible blocked flow control, see above solution. Possible non-leveled eye/face wash assembly.
5. Probable clogging of flow control inside showerhead. Unscrew showerhead off of elbow and clean rubber flow control.
Check the main waste line of your building to see if it does handle the capacity required for the entire drainage system.
persists, the application of hot water will sometimes reseat improperly applied joint compound. After 30 minutes wait and retest. A persistent leak will necessitate reassembly and additional sealant.
8. Water flows from 3-way bleed valve when in closed position.
9. Continuous water flow from SP158B when in closed position.
For more information about Haws products, see our website: www.hawsco.com
8. Remove nut and flag. Rotate stem 180◦ and reassemble flag and nut.
9. Replace thermostat sub assembly.
© 2016 Haws® Corporation – All Rights Reserved HAWS® and other trademarks used in these materials are the exclusive property of Haws Corporation.
2/16 Model 8300.158 Page 3 of 5
Page 4
THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITHOUT NOTICE.
ITEM DESCRIPTION
1BOWL
PART NO.
SP90
PARTS BREAKDOWN
3
10
2 EYEWASH DUST COVERS
SHOWER HEAD
3 4 PULL ROD 5 EYEWASH HEADS 6 F LOOR FLANGE 7 FREEZE PROTECTED BLEED VALVE
8 STRIPE TAPE
9 VALVE, 3 WAY WITH FLAG
10
VALVE ASSEMBLY
11
SHOWER SIGN
12
TEST TAG
13
11
12
9095 SP829 SP200 SP11FC SP75 SP158B SP185 SP229.158 SP260.158 SP178 SP170
0005960580THERMOSTAT SUB ASSEMBLY
8
4
7
1
9
13
6
2
5
BYECN NO.
REVISED PE R
ECN:
5055
DATE
DRAWN
CLF
WHEN ORDERING PARTS PLEASE SPECI FY MODE L NUMBER.
C
2016
Haws Corporation - All Rights Reser ved
HAWS and other trademarks used in these mater ials are the exclusive property of Haws Corporation.
R
APPROVED
FV
03/17/93
DATE
04/04/16
HM
CHKD
RVH
MODEL(S)
1:1
SCALE:
8300.158 SHOWER
EYEWASH COMBO
DRAWING TYPE: SIZE: A
PARTS BREAKDOWN
1455 KLEPPE LANE
SPARKS, NEVADA 89431
(775) 359-4712 FAX (775) 359-7424
E-MAI L : HA W S@HAWSC O. C O M WEBSITE: WWW.HAWSCO.COM
PAGE
PART NUMBER
0002080167
REVISION
14
SHEET OF
11
4 of 5
Page 5
MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITHOUT NOTICE.
NOTES:
1. DIMENSIONS MAY VARY BY ± 1/2 INCH [13mm].
2. TO COMPLY WITH ANSI Z358.1-2014 FOR EMERGENCY EYEWASH OR EYE/FACE WASH AND SHOWER EQUIPMENT:
- UNIT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND ACCEPTABLE PLUMBING PRACTICES.
- EYEWASH OR EYE/FACE WASH SHALL BE POSITIONED WITH NOZZLES NOT LESS THEN 83.8 CM (33 IN.) AND NO GREATER THAN
114.3 CM (45 IN.) FROM SURFACE ON WHICH USER STANDS AND 15.3 CM (6 IN.) MINIMUM FROM WALL OR NEAREST OBSTRUCTION.
- SHOWER SHALL BE POSITIONED SO THAT SHOWER HEAD IS NOT LESS THAN 208.3 CM (82 IN.) NOR MORE THAN 243.8 CM (96 IN.)
FROM SURFACE ON WHICH USER STANDS.
- SHOWER SPRAY PATTERN SHALL HAVE A MINIMUM DIAMETER OF 50.8 CM (20 IN.) AT 152.4 CM (60 IN.) ABOVE SURFACE ON WHICH
USER STANDS, AND CENTER OF SPRAY PATTERN SHALL BE LOCATED AT LEAST 40.6 CM (16 IN.) FROM ANY OBSTRUCTION.
3 DO NOT USE PIPE SEALANT. IF NECESSARY USE DOW CORNING 832 SEALANT PLACING 5 SMALL BEADS ON THE MALE THREADS.
JUST ABOVE THE FIRST THREAD.
C
Haws Corporation - All Rights Reserved.
2016
THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS
MINIMUM
2083mm
82"
279mm
11"
1092mm
43"
VALVE
DRAIN
SELF
FLOOR
LINE
171mm
HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation.
R
6-3/4"
1 1/4" IPS
AIR GAP
WASTE
10-3/16"
259mm
PROTECTION VALVE
SP158B FREEZE
SELF DRAIN
VALVE
778mm
3
30-5/8"
1 1/4" IPS
SUPPLY
2242mm
88-1/4"
APPROVED:
DRAWN:
CH
FV
REVI SED PER
ECN:
DATE:
07/91
5055
DATE:
04/04/16
CHK'D.:
BY:ECN NO.
HM
FV
SCALE:
MODEL(S)
1:1
DRAWING TYPE: SIZE: A
EYEWASH COMBO
8300.158 SHOWER
MOUNTING DETAIL
30°
Ø229mm
Ø9"
INSTALLATION
Ø203mm
(775) 359-4712 FAX (775) 359-7424
E-MAIL : HAW S@ HAWSCO.C OM
WEBSITE: WWW.HAWSCO.COM
SPARKS, NEVADA 89431
1455 KLEPPE LANE
Ø8"
3X
Ø3/8"
Ø10mm
BC
0002080167.D
REVISION
PART NUMBER
SHEET OF
11
14
PAGE
5 of 5