Model 8111FP
Drench Shower
INSTALLATION, OPERATION
&
MAINTENANCE INSTRUCTIONS
LIMITED WARRANTY
NOTE TO INSTALLER: Please leave this information with the Maintenance Department.
SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF THIS
1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424
E-mail: haws@hawsco.com website: www.hawsco.com
HAWS warrants that this specific product is guaranteed against defective material or poor
workmanship for a period of one year from date of shipment. HAWS liability under t his
warranty shall be discharged by furnishing without charge F.O.B. HAWS Factory any
goods, or part thereof, which shall appear to the Company upon inspection to be of
defective material or not of first class workmanship, provided that claim is made in writing
to Haws within a reasonable per iod after receipt of the product. W here claims for defects
are made, the defective part or parts shall be delivered to the Company, prepaid, for
inspection. HAWS will not be liable for the cost of repairs, alterations or replacements, or
for any expense connected therewith made by the owner or his agents, except upon
written authority from HAWS, Sparks, Nevada. HAWS will not be liable for any damages
caused by defective materials or poor workmanship, except for replacements, as provided
above. Buyer agrees that Haws has made no other warranties either expressed or implied
in addition to those above stated, except that of title with respect to any of the products or
equipment sold hereunder and that HAWS shall not be liable for general, special, or
consequential damages claimed to arise under the contract of sale.
The emergency equipment manufactured by HAWS is warranted to function if installation
and maintenance instructions provided are adhered to. The units also must be used for the
purpose for which they were intended. This product is intended to supplement first-aid
treatment. Due to widely varying conditions, Haws cannot guarantee that the use of this
emergency equipment will prevent serious injury or the aggravation of existing or prior
injuries.
NO OTHER WARRANTIES EXPRESSED OR IMPLIED ARE AUTHORIZED, PROVIDED
MODEL PLEASE CALL:
TECHNICAL SUPPORT: 1-800-766-5612
FOR CUSTOMER SERVICE: 1-888-640-4297
03/17 Model 8111FP Page 1 of 4

PROBLEM
REPAIR CHECKLIST
1. Check the main shut-off valve.
Verify minimum 30 psi (2 ATM)
flowing supply line pressure.
Probable clogging of flow control
LOCATION OF UNIT: The Model 8111FP Drench Shower should be installed in
close proximity to potential accident areas. It should be clearly identified, free from
obstructions and easy to access.
SUPPLY LINE: The minimum recommended line size is 1” IPS with 30-90 psi (2-6
ATM) flowing pressure. Where sediment or mineral content is a problem, an inlet
filter is recommended.
PLUMBING CONNECTIONS: Inlet supply is female 1” IPS.
inside showerhead. Unscrew
showerhead off of elbow and clean
For more information about Haws products, see our website: www.hawsco.com
© 2017 Haws® Corporation – All Rights Reserved
HAWS® and other trademarks used in these materials are the exclusive property of Haws Corporation.
03/17 Model 8111FP Page 2 of 4

THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS
MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITHOUT NOTICE.
PARTS BREAKDOWN
SP829
SHOWER HEAD
SUPPORT
ASSEMBLY
SP177
SHOWER SIGN
0003167764
LABEL (2 REQUIRED)
SP170
TEST TAG
0002347420
FLAG ONLY
(NO LABELS)
0004594040
PLUG 1" SQ HD
0006575900
BALL VALVE
0005872577
TEE 1"
ECN:
5186
DATE
03/08/93
DATE
BYECN NO.
CHKD
04/24/17
MODEL(S)
CC
SCALE:
8111FP DRENCH SHOWER
8:1
DRAWING TYPE: SIZE: A
PARTS BREAKDOWN
REVISED PER
DRAWN
WHEN ORDERING PARTS PLEASE SPECIF Y MODEL NUMBER.
C
2017
Haws Corporation - All Rights Reserved
HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation.
R
CLF
APPROVED
FV
1455 KLEPPE LANE
SPARKS, NEVADA 89431
(775) 359-4712 FAX (775) 359-7424
E-MAIL: HAWS@HAWSCO.COM
WEBSITE: WWW.HAWSCO.COM
PAGE
PART NUMBER
0002080111
DRAWING NO.
11472C00
SHEET OF
11
3 of 4
REV
14

C
Haws Corporation - All Rights Reserved.
2017
5 DO NOT USE REGULAR PIPE SEALANT. IF NECESSARY USE DOW CORNING 832 SEALANT PLACING 5 SMALL
BEADS ON THE MALE THREADS, JUST ABOVE THE FIRST THREAD.
3 FOLLOWING THESE DIMENSIONS WILL AUTOMATICALLY PROVIDE ADHERENCE TO ANSI REQUIREMENTS STATED ABOVE.
4 1" IPS GALVANIZED PIPE NOT SUPPLIED.
MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITHOUT NOTICE.
NOTES:
1. DIMENSIONS MAY VARY BY ± 1/2 INCH [13mm].
2. TO COMPLY WITH ANSI Z358.1-2014 FOR EMERGENCY SHOWER EQUIPMENT:
- UNIT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND ACCEPTABLE PLUMBING PRACTICES.
- SHOWER SHALL BE POSITIONED SO THAT SHOWER HEAD IS NOT LESS THAN 208.3 CM (82 IN.) NOR MORE THAN 243.8 CM (96 IN.)
FROM SURFACE ON WHICH USER STANDS.
- SHOWER SPRAY PATTERN SHALL HAVE A MINIMUM DIAMETER OF 50.8 CM (20 IN.) AT 152.4 CM (60 IN.) ABOVE SURFACE ON WHICH
USER STANDS, AND CENTER OF SPRAY PATTERN SHALL BE LOCATED AT LEAST 40.6 CM (16 IN.) FROM ANY OBSTRUCTION.
THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS
2083mm TO 2438mm
5-11/16"
144mm
82" TO 96"
5
5
HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation.
R
1676mm
FLOOR LINE
66" MAX
GUIDE SLEEVE THROUGH
WALL BY OTHERS
VALVE STEM
SHOWER SUPPORT
(FEMALE)
4
1" NPT
23-15/16" MIN
608mm
5/8" 16mm
1 3/4"
FACE
WALL
APPROVED:
DRAWN:
TRF
.
FV
REVISED PER
ECN:
DATE:
05/23/91
5186
DATE:
04/24/17
BY:ECN NO.
CHK'D.:
CC
SCALE:
MODEL(S)
WALL MOUNTED FREEZE RESISTANT
8:1
8111FP DRENCH SHOWER
DRAWING TYPE:
1" NPT (FEMALE)
INSTALLATION
(775) 359-4712 FAX (775) 359-7424
E-MAIL: HAWS@HAWSCO.COM
WEBSITE: WWW.HAWSCO.COM
SPARKS, NEVADA 89431
1455 KLEPPE LANE
SUPPLY
1" NPT (FEMALE)
4
AREA
HEATED
DRAIN
12"
305mm
SLOPE PIPE DOWNWARD
FOR DRAINAGE
MAX WALL
THICKNESS
SIZE: A
0002080111.D
DRAWING NO.
PART NUMBER
SHEET OF
09438A00
11
REV
14
PAGE
4 of 4