Model 7610
Eye/Face Wash
INSTALLATION, OPERATION
&
MAINTENANCE INSTRUCTIONS
NOTE TO INSTALLER: Please leave this information with the Maintenance Department.
SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF THIS
1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424
E-mail: haws@hawsco.com website: www.hawsco.com
HAWS warrants that this specific product is guaranteed against defective material or poor
workmanship for a period of one year from date of shipment. HAWS liability under t his
warranty shall be discharged by furnishing without charge F.O.B. HAWS Factory any
goods, or part thereof, which shall appear to the Company upon inspection to be of
defective material or not of first class workmanship, provided that claim is made in writing
to Haws within a reasonable per iod after receipt of the product. W here claims for defects
are made, the defective part or parts shall be delivered to the Company, prepaid, for
inspection. HAWS will not be liable for the cost of repairs, alterations or replacements, or
for any expense connected therewith made by the owner or his agents, except upon
written authority from HAWS, Sparks, Nevada. HAWS will not be liable for any damages
caused by defective materials or poor workmanship, except for replacements, as provided
above. Buyer agrees that Haws has made no other warranties either expressed or implied
in addition to those above stat ed, except that of title with respect to any of the products or
equipment sold hereunder and that HAWS shall not be liable for general, special, or
consequential damages claimed to arise under the contract of sale.
The emergency equipment manufactured by HAWS is warranted to function if installation
and maintenance instructions provided are adhered to. The units also must be used for the
purpose for which they were intended. This product is intended to supplement first-aid
treatment. Due to widely varying conditions, Haws cannot guarantee that the use of this
emergency equipment will prevent serious injury or the aggravation of existing or prior
injuries.
NO OTHER WARRANTIES EXPRESSED OR IMPLIED ARE AUTHORIZED, PROVIDED
MODEL PLEASE CALL:
TECHNICAL SUPPORT: 1-800-766-5612
LIMITED WARRANTY
FOR CUSTOMER SERVICE: 1-888-640-4297
06/17 Model 7610 Page 1 of 7
LOCATION OF UNIT: The Model 7610 Eye/Face wash should be installed in close
proximity to potential accident areas. It should be clearly identified, free from
obstructions and easy to access.
SUPPLY LINE: The minimum recommended line size is 1/2" IPS with 30-90 psi (2-6
ATM) pressure. Where sediment or mineral content is a problem, an inlet filter is
recommended.
PLUMBING CONNECTIONS: Inlet supply is 1/2" O.D. slip joint.
INSTALLATION INSTRUCTIONS
NOTES: Instructions apply to both models unless otherwise specified.
Refer to installation drawings to clarify installation procedure.
This product is shipped assembled for use as a 7610 Deck Mounted Eyewash. To
convert to 7610 Wall Mounted Eyewash, follow steps 1 and 2 below and refer to
diagrams on page 6 of 6. Otherwise, skip to Step 3.
STEP 1: Position arm in “Deck Mount Off Position” as shown in Step 1 on page 6 of 6.
STEP 2: Note depth of set screw (referenced during reassembly). Loosen set screw
from cap with 3/32” hex wrench. Rotate eyewash arm 90 degrees clockwise
while making sure to not rotate the spool. Ensure that set screw is aligned
with indent before tightening the set screw in the new arm position. Make sure
the set screw is tight and at its original depth. If the set screw is too shallow ,
this is an indication that it has not properly engaged its indent and the
eyewash will not function properly. Ensure cor r ect arm orient a ti on before
proceeding with installation instructions outlined below. See Page 6 of 6 for
reference drawings.
STEP 3: Remove the 1.25 O.D. flange nut and was her fro m val ve body.
STEP 4: After making sure that the surfaces around the drilled hole are clean and
free of grease, slide valve through drilled hole.
STEP 5: Reinstall the 1.25” O.D. flang e nut and washer. Connect slip joint
connection to complete installation.
STEP 6: Assemble eye/face wash assembly to arm, orient tab on assembly aw ay
from user.
06/17 Model 7610 Page 2 of 7
PROBLEM
REPAIR CHECKLIST
1. Check the main shut-off valve.
Verify minimum 30 psi (2 ATM)
flowing supply line pressure.
Probable clogging of flow control due
Eyewash stream does not meet
desired eye level.
Possible blocked flow control , s ee
above solution.
Possible non-leveled e yewash
assembly.
For more information about Haws products, see our website: www.hawsco.com
© 2017 Haws
HAWS
®
and other trademarks used in these materials are the exclusive property of Haws Corporation.
®
Corporation – All Rights Reserved
to inadequate line flushing. Unscrew
eye/face wash head and remove the
four screws to disassemble head.
Clean flow control and reassemble
06/17 Model 7610 Page 3 of 7