Haws 7603BLH, 7603BL240H Installation, Operation & Maintenance Instructions Manual

Page 1
No. 0510000806 (1)

Model 7603BLH/7603BL240H

INSTALLATION, OPERATION
&
MAINTENANCE INSTRUCTIONS

LIMITED WARRANTY

caused by defective materials or poor workmanship, except for replacements, as
NOTE TO INSTALLER: Please leave this information with the Maintenance Departm ent.
SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF
1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424
E-mail: haws@hawsco.com website: www.hawsco.com

Hazardous Location Heated Blanket for 7603 Portable Eyewash

HAWS warrants that this specific product is guaranteed against defective material or poor workmanship for a period of one year from date of shipment. HAWS liability under this warranty shall be discharged by furnishing without charge F.O.B. HAWS Factory any goods, or part thereof, which shall appear to the Company upon inspection to be of defective material or not of first class workmanship, provided that claim is made in writing to Haws within a reasonable period after receipt of the product. Where claims for defects are made, the defective part or parts shall be delivered to the Company, prepaid, for inspection. HAWS will not be liable for the cost of repairs, alterations or replacements, or for any expense connected therewith made by the owner or his agents, except upon written authority from HAWS, Sparks, Nevada. HAWS will not be liable for any damages
provided above. Buyer agrees that Haws has made no other warranties either expressed or implied in addition to those above stated, except that of title with respect to any of the products or equipment sold hereunder and that HAWS shall not be liable for general, special, or consequential damages claimed to arise under the contract of sale.
The emergency equipment manufactured by HAWS is warranted to function if installation and maintenance instructions provided are adhered to. The units also must be used for the purpose for which they were intended. This product is intended to supplement first-aid treatment. Due to widely varying conditions, Haws cannot guarantee that the use of this emergency equipment will prevent serious injury or the aggravation of existing or prior injuries
NO OTHER WARRANTIES EXPRESSED OR IMPLIED ARE AUTHORIZED, PROVIDED OR GIVEN BY HAWS.
THIS MODEL PLEASE CALL:
TECHNICAL SUPPORT: 1-800-766-5612
FOR CUSTOMER SERVICE: 1-888-640-4297
.
03/18 Model 7603BLH/7603BL240H Page 1 of 7
Page 2
CAUTION: A GROUND FAULT DEVICE MUST BE USED WITH THIS HE ATING DE VICE. ATTENTION: CE PRODUIT DOIT ÊTRE UTILISÉ AVEC UNE PROTECTION DE MISE À LA
TERRE. THIS HEATING BLANKET IS ONLY FOR USE WITH HAWS MO DEL 7603 PORTABLE
EYEWASH.
RECOMMENDED TOOLS: Assorted tools as needed for installing power cord LOCATION OF UNIT: The Model 7603BLH/7603BL240H heated blanket should be installed
over a 7603 tank in close proximity to potential accident areas. It should be clearly identified, free from obstruction, and easily accessible. NOTE: Personal eyewash unit Models
7603BLH/7603BL240H shall not be exposed to ambient temperatures exceeding 38C (100F). Models 7603BLH/7603BL240H are suitable for use in Class 1, Division 2 Group B, C, &
D, temperature rating T6 (85°C) and Class 2, Division 2, Group F, G, NEMA/TYPE 4 areas. ELECTRICAL SUPPLY FOR MODEL 7603BLH: 120VAC, 60 Hz, 1.38A. No power cord is
supplied. The junction box is undrilled; the user must drill an appropriate hole for a suitable hazardous-rated electrical fitting. The Model 7603BLH must use a ground fault protection device (30mA GFCI) for Heat Trace. Electrical fault currents may be insufficient to trip a conventional circuit breaker. Units are suitable for installation and use in Class 1, Division 2, Group B, C, D, T6, Class 2, Division 2, Group F, G, NEMA/TYPE 4 areas and MUST BE INSTALLED IN COMPLIANCE WITH LOCAL, STATE AND/OR FEDERAL CODES USING FLEXIBLE CONDUIT OR CABLE RATED FOR CLASS I, II, DIVISIO N 2 – NO RIGID CONNECTION PERMITTED. DURING POTENTIAL FREEZING PERIODS INSURE THAT UNIT IS
CONNECTED TO A CONTINUOUS POWER SUPPLY. ELECTRICAL SUPPLY FOR MODEL 7603BL240H: 240VAC, 50/60 Hz, 0.64A. No power cord
is supplied. The junction box is undrilled; the user must drill an appropriate hole for a suitable hazardous-rated electrical fitting. The Model 7603BL240H must use a ground fault protection device (30mA GFCI) for Heat Trace. Electrical fault currents may be insufficient to trip a conventional circuit breaker. Units are suitable for installation and use in Class 1, Division 2, Group B, C, D, T6, Class 2, Division 2, Group F, G, NEMA/TYPE 4 areas and MUST BE INSTALLED IN COMPLIANCE WITH LOCAL, STATE AND/OR FEDERAL CODES USING FLEXIBLE CONDUIT OR CABLE RATED FOR CLASS I , II, DIVISION 2 – NO RIGID CONNECTION PERMITTED. DURING POTENTIAL FREEZING PERIODS INSURE THAT
UNIT IS CONNECTED TO A CONTINUOUS POWER SUPPL Y. AMBIENT TEMPERATURE RATING:
-20°F (-29°C) TO 100°F (38°C)
03/18 Model 7603BLH/7603BL240H Page 2 of 7
Page 3
INSTALLATION PROCEDURE
NOTE: Instructions apply to all models unless otherwise specified. STEP 1: Unpack the blanket. Lay flat with inner surface (silver) up.
STEP 2: MODEL 7603BLH/7603BL240H: Install the power cord in the junction box using a
suitable hazardous-rated electrical fitting and either rigid or flexible metallic conduit. The junction box is undrilled; the user must drill the appropriate size hole for the electrical fitting used. Wire the power cord to terminal block referencing the supplied electrical drawing. The cord and fittings selected must have the appropriate hazardous rating required for the installation location. The Model 7603BL240H/7603BL240H must use a ground fault protection device (30mA GFCI) for Heat Trace.
NOTICE: MODEL 7603BLH/ 7603BL240H REQUIRES MINIMUM NEMA/TYPE 4 COMPLIANT EQUIPMENT. ALL POWER CONNECTIONS MUST BE MADE ACCORDING TO NEC/ CEC CODE USING FLEXIBLE CONDUIT OR CABLE RATED FOR CLASS I, II, DIVISION 2 – NO RIGID CONNECTION PERMITTED. THE CORD AND FITTINGS SELECTED MUST HAVE THE APPROPRIATE HAZARDOUS LOCATIO N RATING REQUIRED FOR THE INSTALLATION LOCATION.
STEP 3: Set empty 7603 tank on top ensuring tank lip is resting on plastic feet and not
crushing the heat trace.
03/18 Model 7603BLH/7603BL240H Page 3 of 7
Page 4
STEP 4: Wrap the side blanket around the tank and attach the bottom and side Velcro
closures.
STEP 5: Fill tank in accordance with 7603 instructions and attach the eyewash plumbing.
STEP 6: Attach the end of heat trace the eyewash plumbing below the ball valve with supplied
cable tie. Ensure the heat trace does not interfere with the push flag operation. Remove the adhesive backing from Velcro strip on the back of the junction box and secure the junction box to the top of the tank.
STEP 7: Attach junction box to tank handle with supplied cable tie.
03/18 Model 7603BLH/7603BL240H Page 4 of 7
Page 5
STEP 8: Attach grounding clamp to tank handle. Attach second ground clamp around metal
hub on the junction box. Connect the two ground clamps with the supplied grounding wire.
STEP 9: Attach conical top blanket with Velcro closures. Align the seam of the top blanket with
the push flag. The electrical cord may exit across the Velcro seem at any location.
IMPORTANT SAFETY NOTICE
THE NATIONAL ELECTRICAL CODE REQUIRES GROUND-FAULT EQUIPMENT PROTECTION ON EACH HEATING CABLE BRANCH CIRCUIT. TO REDUCE THE RISK OF FIRE CAUSED BY DAMAGE OR IMPROPER INSTALLATION, CIRCUIT BREAKERS SUCH AS SQU ARE D QO-EPD AND QOB-EPD OR EQUIVALENT, WITH A 30mA TRIP LEVEL, SHOULD BE USED. PLEASE SUBSTITUTE THESE BREAKERS WHEREVER REFERENCE IS MADE TO CONVENTIONAL BREAKERS IN THIS DOCUMENT. ALTERNATIVE DESIGNS PROVIDING COMPARABLE LEVELS OF GROUND-FAULT PROTECTION MAY ALSO BE ACCEPTABLE.
03/18 Model 7603BLH/7603BL240H Page 5 of 7
Page 6

OPERATING INSTRUCTIONS

TROUBLESHOOTING

PROBLEM

REPAIR CHECKLIST

breaker.
on junction box.
sunlight or excess ambient temperature.
thermostat can be installed.
The 7603BLH/7603BL240H can be connected to power year-around. The non-adjustable thermostat will shut off heat cable when air temperature rises to 82°-72°F (28°-22°C). Heat cycle will repeat when air temperature drops to between 62°-72°F (16°-22°C). Periodic check of water temperature of eyewash will confirm normal operating temperatures between 62°-95°F (16°-35°C).
Heat trace cable used on this blanket heats slowly and may take several hours to warm cold water into ANSI recommend temperature range of 60°F (15°C) to 100°F ( 38°C).
1. Heat trace does not turn on. 1. a. No power. Check GFCI and circuit
b. If ambient temperature is high and
doesn’t allow the blanket temperature to drop below 67°F (19°C) the heater may not switch on. Heater settings are: Non­adjustable thermostat preset to switch on at 67°± 5°F (17°± 3°C) and switch off 77°± 5°F (25°± 3°C). Test the thermostat and heater function by applying ice thermostat for approximately 3-5 minutes. The heat trace cable should become warm to the touch when operating properly. Thermostat is located
2. Eyewash water is above 100°F (38°C).
1. a. Ambient air temperature is above 100°F (38°C). Relocate eyewash out of direct
b. Shut off electric power. All electric
connections are made inside the junction box. Thermostat is mounted on the side of junction box. Disconnect thermostat leads from terminal block and wire nut in junction box. Check thermostat continuity: open circuit above 82°F (28°C), closed below 62°F (16°C). Thermostat is not adjustable and should be replaced if either of the continuity checks are incorrect. If unit is subject to freezing temperatures, temporarily disconnect thermostat and reconnect wiring to bypass thermostat and protect eye wash from freezing until replacement
For more information on Haws products, see our website: www.hawsco.com
© 2018 Haws HAWS
®
®
Corporation – All Rights Reserved
and other trademarks used in these materials are the exclusive property of Haws Corporation.
03/18 Model 7603BLH/7603BL240H Page 6 of 7
Page 7
THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITHOUT NOTICE.
7 of 7
POWER IN
GROUND
GREEN BLACK WHITE (120V) / RED (240V)
120 VAC MODEL 7603BLH 240 VAC MODEL 7603BL240H
THERMOSTAT
MODEL 7603BLH / 7603BL240H
ELECTRICAL DETAIL
TERMINAL
BLOCK
SHIELD
HEAT TRACE CABLE
TANK GROUND
PAGE
FOR MODELS 7603BLH & 7603BL240H:
1. ALL MODELS MUST HAVE A GROUND FAULT PROTECTION DEVICE (30mA GFCI) FOR HEAT TRACE. ELECTRICAL CURRENTS MAY BE INSUFFICIENT TO TRIP A CONVENTIONAL CIRCUIT BREAKER. ALL INSTALLATIONS MUST BE INSTALLED IN COMPLIANCE WITH LOCAL, STATE, AND/OR FEDERAL CODES.
2. ALL POWER CONNECTIONS MUST BE MADE ACCORDING TO NEC/ CEC CODE USING FLEXIBLE CONDUIT OR CABLE RATED FOR CLASS I, II, DIVISION 2 – NO RIGID CONNECTION PERMITTED. MODEL 7603BLH/ 7603BL240H REQUIRES MINIMUM NEMA/TYPE 4 COMPLIANT EQUIPMENT. THE CORD AND FITTINGS SELECTED MUST HAVE THE APPROPRIATE HAZARDOUS LOCATION RATING REQUIRED FOR THE INSTALLATION LOCATION.
C
2018
Haws Corporation - All Rights Reserved.
HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation.
R
5235
DRAWN:
CC
APPROVED:
MJ
REVISED PER
ECN:
5235
DATE: 12/28/17
DATE:
BY:ECN NO. CHK'D.:
05/29/18
MODEL(S)
CC MJ
SCALE:
(775) 359-4712 FAX (775) 359-7424
E-MAIL: HAWS@HAWSCO.COM WEBSITE: WWW.HAWSCO.COM
7603BLH / 7603BL240H
ELECTRICAL SCHEMATIC
1:1
DRAWING TYPE: SIZE: A
ELECTRICAL
1455 KLEPPE LANE
SPARKS, NEVADA 89431
PART NUMBER
0510000806.D
REVISION
SHEET OF
1
11