Hans Grohe 26396001 User Manual

Installation Instructions / Warranty
ShowerArc
26396001
ShowerArc 26396001
Minimum ceiling height – 90 1/2”
2
Installation Considerations
For best results, Hansgrohe recommends
• that this unit be installed by a licensed, professional plumber.
Please read over these instructions thor-
• oughly before beginning installation. Make sure that you have all tools and sup­plies needed to complete the installation.
Inspect the ShowerArc thoroughly for ship-
• ping damage before beginning installation.
The installation shown on page 2 is ideal
• for users of approx. 5’11” in height The installation height may be increased, if desired. All measurements, including the minimum ceiling height, must be increased as well.
The ShowerArc requires 1/2” NPT female
• fittings, one for the hot supply and one for the cold supply, recessed 3/8”
behind the surface of the finished wall.
The thermostatic mixing valve may be
• installed on either side of the shower. For proper operation of the thermostatic mixing valve, the hot supply must enter the valve
on the left and the cold supply must enter the valve on the right. If the valve is cross­connected, it cannot function correctly.
The difference in water pressure between
• the hot and cold supplies should not exceed 10 psi or the thermostatic mixing valve cannot work properly.
The hot and cold supplies must be thor-
• oughly flushed before installation of the ShowerArc.
The finished wall surface (tile,
• etc) must be installed before the ShowerArc can be installed.
Use caution when drilling the mounting
• holes. Be careful not to drill into water lines!
Protection against backflow is provided by
• check valves. The check valves should be removed and cleaned yearly -- please see the maintenance note on page 29.
The ShowerArc is not for use with an
• instantaneous water heater.
Technical Information
Recommended water pressure 43.5 - 72.5 psi Minimum water pressure 43.5 psi Max. water pressure 145 psi
Recommended hot water temp. 120� - 140� F* Max. hot water temp 165�F*
Flow rate - showerhead 2.5 gpm bodysprays 0.6 gpm each handshower 2.5 gpm The thermostatic mixing valve has a high temperature limit stop which may be reset to comply with local plumbing codes -- see page 23. This unit is listed by IAPMO.
*Please know and follow all applicable local plumbing codes when setting the temperature on the water heater. In Massachusetts, the water heater may be set no higher than 112�F.
3
Installation in 90º corner:
Instructions begin on page 5
Wall-to-wall installation
Requires 26397000 installation kit (included): Instructions begin on page 13.
Roughing-in
The ShowerArc requires 1/2” NPT female fittings, recessed 3/8” behind the surface of the finished wall, for the hot and cold water supplies for the thermostatic mixing valve.
4
Installation in 90º corner
Only one set of supplies is required – do not install two sets of supplies.
The thermostatic mixing valve may be installed on either wall. This diagram shows both possible positions for the installation.
5
Installation in 90º Corner
Seal the wall around the supplies with waterproof sealant.
Failure to seal the wall can lead to possible water damage.
1
2
3 4
6
5
6
7
8
Seal the wall around the anchors with waterproof sealant.
Failure to seal the wall can lead to possible water damage.
7
11
9
10
Seal the wall around the anchors with waterproof sealant.
Failure to seal the wall can lead to possible water damage.
Be careful not to drill into water lines!
12
6 mm
8
13 14
15 16
9
17 18
10
19
20
1
2
6 mm
Loading...
+ 22 hidden pages