All Hale products are quality components: ruggedly designed, accurately machined, precision inspected, carefully assembled
and thoroughly tested. In order to maintain the high quality of your unit, and to keep it in a ready condition, it is important to
follow the instructions on care and operation. Proper use and good preventive maintenance will lengthen the life of your unit.
ALWAYS INCLUDE THE UNIT SERIAL NUMBER IN CORRESPONDENCE.
HALE PRODUCTS, INC. l A Unit of IDEX Corporation l 700 Spring Mill Avenue l Conshohocken, PA 19428 l TEL: 610-825-6300 l FAX: 610-825-6440
Hale Products cannot assume responsibility for product failure resulting from improper maintenance
or operation. Hale Products is responsible only to the limits stated in the product warranty. Product
specifications contained in this material are subject to change without notice.
IMPORTANT: Warnings and cautions listed in Section 1 of this manual are necessary for safe
installation and operation of the Hale MIV. When developing individual apparatus operating
procedures make sure the warnings and cautions are incorporated as written.
Please provide a copy of the Hale Master Intake Valve manual to the end user of the equipment.
For additional manuals, contact Hale Products, Inc at (610) 825-6300.
Ask for Manual P/N 029-0020-28-0.
i
MASTER INTAKE VALVE
1
IMPORTANT NOTICE: Before attempting installation or operation of the Hale MIV read and
follow all safety precautions listed below. The warnings and cautions listed are necessary
for the safe installation and operation of the Hale MIV. When developing departmental
apparatus operating procedures make sure the warnings and cautions are incorporated
as written.
1. WARNING: The outlet of the relief valve
can flow large volumes of water under
pressure. Therefore, the discharge must
be piped in a manner that will not
expose personnel to high pressure water
streams.
2. WARNING: The suction of each
receiving pumper using large diameter
hose shall be equipped with a relief
valve with a maximum pressure setting
of not more than 10 PSI (0.7 BAR) over
the static pressure of the water source to
which it is connected or not more than
10 PSI (0.7 BAR) over the discharge
pressure of a supply pumper in relay. In
no event will the intake relief valve
pressure setting exceed the working
pressure of the hose being used.
3. WARNING: Per NFPA 1962 requirements,
large diameter hose marked “SUPPLY
HOSE” 3-½ to 5 inches (89 to 127 mm)
diameter shall not be used at operating
pressures exceeding 185 PSI (13 BAR).
4. WARNING: Per NFPA 1962 requirements,
large diameter hose marked “SUPPLY
HOSE” 6 inches (152 mm) diameter shall
not be used at operating pressures
exceeding 135 PSI (9 BAR).
5. WARNING: Never set intake relief valve
above hose manufacturers rated
pressure. Always use the lowest possible
relief valve setting to enhance operator
and equipment safety.
6. WARNING: Per NFPA 1962 requirements,
large diameter hose used to supply a
pumper from a hydrant or another
SAFETY
pumper shall be connected to the
pumper(s) and hydrant with a slight
downward bend to avoid kinking when
the water is turned on.
7. WARNING: Large diameter hose
presents a tripping hazard. Use care
when working around hose when in use.
8. WARNING: Male threads on relief valve
outlet are sharp and can cause severe
cuts. Be careful when working around
the exposed threads on the relief valve
outlet
9. WARNING: The relief valve spring is
under pressure and can cause a
projectile hazard. When disassembling
the relief valve, back relief valve
adjustment screw out to lowest setting to
relieve pressure on spring before
removing relief valve housing screws.
10. WARNING: Use tubing rated at the
maximum discharge pressure of the fire
pump, 500 PSI (34 BAR) minimum.
11. WARNING: Any electrical system has the
potential to cause sparks during
installation, service or repair. Take care
to eliminate explosive or hazardous
environments during installation, service
or repair.
12. WARNING: When a malfunction occurs
and the motor stalls the circuit breaker
will trip to disconnect electrical power to
the motor. If power remains to the valve
electrical system the motor and circuit
breaker could become extemely hot.
1
MASTER INTAKE VALVE
Care must be taken when removing
gearmotor cover.
13. WARNING: When initially charging large
diameter hose excessive air will be
present in the hose. This air must be bled
off while the hose is charging and prior
to opening the Hale MIV to prevent
receiving pump cavitation and possible
loss of prime.
14. WARNING: When the electric motor
driven valve is operated the manual
override handwheel will turn. Keep
hands, feet or loose clothing away from
the handwheel to prevent
entanglement.
15. WARNING: Keep hands and arms clear
of the valve disc when valve is being
operated without suction tube strainer or
suction tube in place.
16. WARNING: The Hale MIV is shipped with
a plastic plug in the ¾ inch NPT air
bleeder connection port. During
installation of the Hale MIV the plug must
be removed and an air bleeder control
valve, controllable at the pump
operator position, must be installed.
valve with a wrench while tightening
elbow.
19. CAUTION: Electric motor and wiring are
protected by a circuit breaker. DO NOT
remove or bypass the circuit breaker as
severe damage to the electric motor or
apparatus wiring could result during a
motor stall condition.
20. CAUTION: The Hale MIV is designed for
operation on 12 Volt DC negative
ground electrical systems only.
21. CAUTION: Follow NFPA requirements for
apparatus electrical wiring. Use
minimum 14 AWG, type SXL or GXL (SAE
J1128) wire. The wiring shall be
protected using 289
flame retardant, moisture resistant loom
or braid.
22. CAUTION: The stem on the top of the
valve disc extends approximately 1-½
inches into the operator assembly. The
bottom of the valve disc must be
removed first.
o
F (143 C) minimum
17. WARNING: If the optional Hale Air
Bleeder Valve (ABV) assembly IS NOT
installed, a warning placard must be
mounted on the operator panel next to
the air bleeder control stating:
“WARNING: ALL AIR MUST BE BLED FROM
INTAKE HOSE PRIOR TO OPENING MIV
VALVE .”
18. CAUTION: To prevent damage to the
valve body hold the hex outlet on the
2
MASTER INTAKE VALVE
2
GENERAL DESCRIPTION
The Hale Master Intake Valve is a NFPA
compliant large diameter intake valve that
is mounted in the pump suction tube
behind the pump operator panel. The valve
is a butterfly type valve that is available
either in manual or electric operation.
Safety features on the valve include an
integral relief valve and air bleeder valve
tap that vent to the atmosphere. The valve
assembly, less relief valve, is factory tested
to 600 PSI (41 Bar).
The Hale Master Intake Valve has a 6.4 inch
(163 mm) diameter bore with a butterfly
disc designed to provide minimum flow
restriction when the valve is open. The
unique design of the valve and butterfly
permits the valve to provide full water flow
up to 1500 GPM (5678 LPM) from draft
through a single 6 inch NST suction hose
when mounted on Hale pumps directly to
the main suction inlet under all standard
operating conditions. Due to the design of
the valve, there is minimum friction loss and
pressure drop across the valve.
When the valve is ordered as part of a Hale
Midship fire pump, the pump will pass UL
requirements up to 1500 GPM (5678 LPM)
from draft through a single 6 inch NST
suction hose with the valve in place. When
two valves are mounted to the fire pump
the pump can achieve UL flows up to 2000
GPM (7570 LPM) from draft through dual 6
inch NST suction hoses. The disc design also
permits easy maintenance and lubrication
of the valve disc. The disc is coated with
nitrile rubber material that is compatible
with most chemicals in use on the fire
ground.
OPERATOR PANEL
PLACARD
TO +12 VDC
POWER SUPPLY
SUCTION
EXTENSION ON
MIDSHIP PUMP
ELECTRIC
MOTOR
PROTECTIVE
COVER
GEARBOX
AIR BLEEDER
CONNECTION
GEARBOX SHAFT
EXTENSION
(76 AND 81 INCH
PANELS)
OVERRIDE
PLACARD
OUTBOARD
PRIMING TAP
MANUAL
PANEL
Figure 1. Component Part Identification (Electric Valve)
RELIEF
VALVE
VALVE
BODY
VALVE
DISC
WATER DRAIN
CONNECTION
SUCTION
TUBE
MANUAL
OVERRIDE
HANDWHEEL
3
MASTER INTAKE VALVE
The valve is available configured for
manual operation using a panel mounted
handwheel (MIV-M) or for electric
operation using a panel mounted switch
(MIV-E) for remote control operation.
Whether the manual or electric operated
valve is installed, lights on the panel placard
will illuminate to indicate if the valve is
open, closed or traversing from one position
to the other.
Also provided with the electric valve is a
manual override handwheel that permits
valve operation from outside the operator
panel. No special tools or parts removal is
required.
The valve gear actuator, manual or electric,
is designed to move the valve disc from the
fully closed to full open position using 10
turns of the handwheel. The electric
operated valve will cycle from the fully
closed to full open position in no less than 3
seconds therefore meeting NFPA
requirements. The matched gear set is
designed to permit operation with minimal
torque even at high flows and pressures.
The design of the gear actuator also
permits the valve to be placed into a
partially open position if it is necessary to
gate the intake flow.
Master Intake Valves are provided with a ¾
inch NPT suction hose priming port. This port
is located near the relief valve mounting
flange on the valve body. During pump
operations when an MIV is installed on the
main pump suction it may be desirable to
pre-prime the suction hose so fire fighting
capabilities are not lost when switching from
tank to draft operations.
Since the valve mounts behind the operator
panel, between the suction tube extension
and the suction tube, or in-line for front and
rear suction piping, there is less panel
clutter, obstruction of valve handles or
chance for damage to the valve body due
to overhang beyond the apparatus running
board.
SUCTION
EXTENSION ON
MIDSHIP PUMP
GEARBOX
GEARBOX SHAFT
(76 AND 81 INCH
Figure 2. Component Part Identification (Manual Valve)
EXTENSION
PANELS)
POWER SUPPLY
TO +12 VDC
AIR BLEEDER
CONNECTION
OUTBOARD
PRIMING TAP
RELIEF
VALVE
VALVE
BODY
VALVE
DISC
WATER DRAIN
CONNECTION
SUCTION
TUBE
PANEL
PLACARD
HANDWHEEL
4
MASTER INTAKE VALVE
The surface between the mounting flanges
and Hale MIV valve body are sealed using
reliable o-ring seals in grooves machined in
the Hale MIV body.
Design of the relief valve permits the
discharge to be piped behind the operator
panel for increased operator and/or
bystander safety.
5
MASTER INTAKE VALVE
3
The unique design of the Hale Master Intake
Valve permits installation in the fire pump
suction tube behind the pump
compartment panel using a minimum of
space. The valve body is only 3-3/8 inches
(86 mm) wide and various suction tube
options are available to fit most standard
pump compartment widths. (Refer to Hale
Bulletin 596, reprinted in section 9 of this
manual, for various suction tube options.)
The side mounted valve is installed behind
the pump compartment panel between
the suction tube and suction tube extension
(Figures 1 and 2). The design of the relief
valve mounting flange permits rotation of
the relief valve to redirect the outlet of the
relief valve as necessary as well as remote
mounting. There are 2-½ inch female NPT
threads machined into the relief valve
mounting flange of the MIV valve to permit
remote mounting of the relief valve.
Bottom mounted valves are installed to
bottom of the suction tube extension for use
with front and/or rear suctions (Figure 4).
The valve may also be installed in-line or it
may be used with large auxiliary pumps.
Optional Hale 6 inch NPT threaded flanges
are available for use in these installations.
Whether installing the valve during new
construction or installing the valve as a
retrofit proper planning and equipment
layout will ensure smooth installation. The
Hale MIV has been designed to mount onto
a Hale midship pump without interference
to other suction and discharge connections
on the pump. The current revision of Plates
814A, 815A, 841A and 842A, reprinted in
Section 9 of this manual, provide the overall
mounting dimensions for various
configurations of the Hale MIV.
When ordered as part of a new midship fire
pump the valve will be pre-installed on the
INSTALLATION
fire pump and tested at the factory per
NFPA requirements. When installing the
midship pump on the apparatus it will be
necessary to install the relief valve
discharge piping, air bleeder, suction hose
priming and drain valve (steps A through J
in this section).
The following steps shall be followed when
installing the valve on a midship fire pump.
Steps A and B can be eliminated if the Hale
MIV is installed on the midship pump at the
factory.
A. MOUNTING OF SIDE SUCTION
VALVES (when not ordered as part of
midship pump)
NOTE: When installing the Hale MIV as a
retrofit it is highly recommended that the
standard suction extension be replaced
with the Hale P/N 178-0063-00-0 suction
extension. This is especially important on
apparatus with panel widths of 70, 72
and 74 inches to minimize panel
modification required. Refer to Section
9 of this manual for mounting dimension
drawings for assistance in planning
retrofit installations.
1. Determine the location of interferences
on the fire pump and the pump
operator panel. Proper planning and
layout of the pump operator panel will
reduce the potential interferences for
other operating equipment. The current
revision of Plate 814A and Plate 815A,
reprinted in Section 9 of this manual,
provide the overall mounting dimensions
for the Hale MIV.
2. Remove the cap screws that hold the
suction tube to the suction tube
extension. Remove the suction tube
from the pump. Be sure to remove all
old gasket or sealing material from the
6
GEARBOX
MASTER INTAKE VALVE
RELIEF
VALVE
STUD OR CAP
SCREW NOT USED
IN THIS HOLE
STUD OR CAP
SCREW NOT USED
IN THIS HOLE
STUDS PLACED IN
THESE HOLES
LOOKING INTO SUCTION TUBE FROM OUTSIDE PUMP
Figure 3. Stud Placement for MIV Installation
suction tube extension and suction tube
mating surfaces.
NOTE: Use only7/16-14 UNC X 4-¾ inches
long grade 5 zinc plated steel cap
screws,7/16-14 UNC X 5-¼ inches long
grade 5 zinc plated steel studs and7/1614 UNC zinc plated steel nuts to install
the Master Intake Valve and suction
tube to the suction tube extension.
NOTE: All cap screws, studs and nuts
must be locked in place using Loctite
#242 or equal thread sealing
compound.
NOTE: When the valve body is installed
make sure the valve disc is next to the
suction tube extension. The relief valve,
drain valve, air bleeder valve and
priming valve must be located on the
inlet side of the valve. When the Hale
MIV is properly orientated for installation
the gearbox will be located on the left
and the relief valve will be located at
the upper right. (See figure 3)
PANEL
3. Apply a coating of Loctite #242 or equal
thread sealing compound and install the
7
/16-14 UNC X 5-¼ inch long studs into
two holes of the suction tube extension.
Torque the studs to 40 lb-ft (54 N-m).
These studs are used to support the
valve and suction tube during
installation. The studs are installed in the
holes located at the 1 o’clock and 7
o’clock position on the suction tube
extension. (See figure 3)
4. Make sure the o-ring seals are seated in
the grooves on the valve body and coat
all sealing surfaces with a light coat of
general purpose grease.
5. Install the valve body and suction tube
over the studs taking care not to
damage the threads on the studs.
Apply a coat of Loctite #242 or equal
thread sealing compound and insert the
(8)7/16 -14 UNC x 4-¾ inch long grade 5
zinc plated steel cap screws through the
holes in the suction tube and thread into
the holes on the suction tube extension.
DO NOT tighten the cap screws until all
7
MASTER INTAKE VALVE
threads are started. Apply Loctite #242
or equal to the threads on the studs and
install the
7
/16-14 UNC grade 5 zinc
plated steel nuts on the studs.
NOTE: When installing the Hale Master
Intake Valve 8 suction tube cap screws,
2 studs and 2 nuts will be used. Cap
screws cannot be inserted where the
gearbox adapter (9 o’clock position)
and trunnion (3 o’clock position) are
located. See figure 3.
6. Tighten all suction tube cap screws and
nuts. Torque to 40 lb-ft (54 N-m) using a
cross pattern.
B. MOUNTING OF BOTTOM (FRONT/
REAR) SUCTION VALVES (when not
ordered as part of midship pump)
The Hale MIV-E can be mounted to the
bottom opening of Hale suction tube
extension P/N 178-0063-01-0 for use in front
and/or rear suctions. The bottom opening
of this extension is machined to accept
Hale 2417 series 12 bolt flanges. A special 6
inch NPT threaded flange Hale P/N 1150441-00-0 must be used when mounting the
Hale MIV-E on the bottom opening of this
suction tube extension. Ordinary flanges will
not provide proper clearance for the valve
disc.
When installing the Hale MIV-E in front or
rear suction piping do the following:
1. Determine the location of interference
on the fire pump and the pump
operator panel. Proper planning and
layout of the pump operator panel will
reduce the potential interference with
other operating equipment. Refer to the
current revision of Plate 841A and Plate
842A, reprinted in Section 9 of this
manual, for the overall mounting
dimensions for the Hale MIV.
NOTE: Use only 7/16-14 UNC x 5-¾ inch
long grade 5 zinc plated steel cap
screws, 7/16-14 UNC x 6-¼ inch long
grade 5 zinc plated steel studs and 7/1614 UNC zinc plated steel nuts to install
the Master Intake Valve and flange to
the suction tube extension.
TO OPERATOR
PANEL PLACARD
ELECTRIC
MOTOR
PROTECTIVE
COVER
GEARBOX
GEARBOX SHAFT
(76 AND 81 INCH
SUCTION EXTENSION
ON MIDSHIP PUMP
OUTBOARD
PRIMING TAP
AIR BLEEDER
6 INCH NPT
2417 FLANGE
EXTENSION
PANELS)
GEARBOX SHOWN LEFT SIDE FRONT
MANUAL
OVERRIDE
OPERATOR
SHAFT
MANUAL
OVERRIDE PANEL
PLACARD
OR RIGHT SIDE REAR
CONNECTION
Figure 4. Bottom Opening Mounting
RELIEF
VALVE
SUCTION EXTENSION
ON MIDSHIP PUMP
VALVE
BODY
WATER DRAIN
CONNECTION
TO OPERATOR
PANEL PLACARD
GEARBOX
6 INCH NPT
2417 FLANGE
GEARBOX SHOWN LEFT SIDE REAR
OR RIGHT SIDE FRONT
GEARBOX SHAFT
EXTENSION
(76 AND 81 INCH
PANELS)
MANUAL
OVERRIDE
OPERATOR
SHAFT
MANUAL
OVERRIDE PANEL
PLACARD
8
MASTER INTAKE VALVE
NOTE: All cap screws, studs and nuts
must be locked in place using Loctite
#242 or equal thread sealing
compound.
NOTE: When the valve body is installed
make sure the valve disc is next to the
suction tube extension. The relief valve,
drain valve, air bleeder valve and
priming valve must be located on the
inlet side of the valve. When the Hale
MIV is properly orientated for installation
the gearbox will be located towards the
front or rear of the apparatus
depending on which side of the pump
the valve is located. See figure 4.
2. If necessary the gearbox may be
rotated for proper installation. Refer to
Part J of this section for instructions on
how to rotate gearbox.
3. Coat the threads on one end of two
7/16-14 x 6-¼ inch long grade 5 studs
with Loctite #242 or equal and insert into
threaded holes on bottom of suction
tube extension. Torque studs to 40 ft-lb
(54 N-m). The studs are installed in holes
located at the 1 o’clock and 7 o’clock
positions, when viewed from below, on
the suction tube extension. See figure 3.
4. Orient valve so the relief valve and
gearbox are located as shown in figure
4.
5. Make sure the o-ring seals are seated in
the grooves on the valve body and coat
all sealing surfaces with a light coat of
general purpose grease.
Loctite #242 or equal and insert through
holes in the flange and thread into
bottom opening of suction tube
extension. Torque cap screws and nuts
to 40 ft-lb (54 N-m).
C. PLUMBING RELIEF VALVE
WARNING: Male threads on relief valve
outlet are sharp and can cause severe
cuts. be careful when working around
the exposed threads on the relief valve
outlet
WARNING: The outlet of the relief valve
can flow large volumes of water under
pressure. Therefore, the discharge must
be piped in a manner that will not
expose personnel to high pressure water
streams.
NOTE: The relief valve is attached to the
Hale MIV when shipped from the
factory. Apparatus configuration may
require that the relief valve be mounted
in a remote location. Step 1 below
provides procedures for mounting relief
valve in a remote location.
1. To Mount the relief valve in a remote
location do the following:
a. Remove the four7/16-14 UNC X 1-¼
inch long hex head cap screws that
secure the relief valve adapter and
relief valve to the mounting pad on the
Hale MIV body. (See figure 5)
RELIEF VALVE
MOUNTING
ADAPTER
ADJUSTMENT
LOCKING
SETSCREW
6. Carefully slide the valve and flange over
the studs making sure the studs align
with the holes in the valve body.
7. Apply Loctite #242 or equal to threads
on the studs and install two 7/16-14 nuts.
8. Coat the threads of eight 7/16-14 x 5-¾
inch long grade 5 cap screws with
ADJUSTMENT
2-½ INCH NPT
WATER OUTLET
CONNECTION
CAP SCREW
Figure 5. Relief Valve Adjustment
9
MASTER INTAKE VALVE
b. The relief valve mounting pad on the
Hale MIV valve body has 2-½ inch NPT
female threads, install a 2-½ inch NPT
threaded pipe nipple into the mounting
pad.
c. Screw a 2-½ inch NPT Hale type 115
4-3/8 inch bolt circle flange (Hale P/N
115-0070-00-0) onto the pipe nipple.
d. Making sure the relief valve
discharge is pointing down and away
from the operator position, attach the
relief valve adapter and relief valve to
the Hale 115 flange using a gasket, four
7
/16-14 UNC X 2-½ inch long grade 5 zinc
plated steel hex head cap screws and
four7/16-14 UNC zinc plated steel nuts.
Torque the cap screws and nuts to 40 lbft (54 N-m).
2. Attach a pipe or hose to the 2-½ inch
NPT outlet of the relief valve to direct the
discharge of the relief valve away from
the operator position. DO NOT restrict
the flow of water through this pipe.
Make sure the pipe is properly supported
to withstand the potential force of water
that can flow from the relief valve.
3. Two aluminum relief valve warning
placards, one wired to the relief valve
adjustment screw and the other with the
installation kit, are provided with the
Hale MIV. One of the placards must be
permanently affixed near the relief valve
adjustment screw and the other must be
mounted on the access panel for the
relief valve.
D. SUCTION HOSE WATER DRAIN
NOTE: On bottom mount valves the
drain connection on the valve is not
used. Remove the plastic shipping plug
and install a ¼ inch NPT pipe plug.
NOTE: Coat all pipe threads with a
suitable sealant before connections are
made.
1. Remove the plastic plug from the ¼ inch
NPT water drain connection on the
bottom of the valve body
2. Installa¼inchNPTx3/8inchtube
compression fitting or elbow into drain
hole.
3. Using 3/8 inch OD tubing rated at
maximum pressure of fire pump (500 PSI
(34 BAR) minimum) connect to an
individual drain valve located on the
pump operator panel.
E. AIR BLEEDER VALVE
WARNING: The Hale MIV is shipped with
a plastic plug in the ¾ inch NPT air
bleeder connection port. During
installation of the Hale MIV the plug must
be removed and an air bleeder control
valve, controllable at the pump
operator position, must be installed.
WARNING: If the optional Hale Air
Bleeder Valve (ABV) assembly IS NOT
installed, a warning placard must be
mounted on the operator panel next to
the air bleeder control stating:
“WARNING: ALL AIR MUST BE BLED FROM
INTAKE HOSE PRIOR TO OPENING MIV
VALVE .”
1. Remove the plastic shipping plug from
the ¾ inch NPT air bleed connection
that is located on the top of the valve
body and install an air bleeder control
valve that is controllable by the pump
operator. The discharge of the air
bleeder must be directed away from the
pump operator position. If the optional
Hale Air Bleeder Valve (ABV) is used,
refer to figure 6 and do the following:
2. Install ¾ inch NPT X ¼ inch NPT bushing
into the ¾ inch NPT tapped hole on the
valve body.
3. Install one of the ¼ inch NPT X3/8 inch
tube compression fittings into the ¼ inch
10
MASTER INTAKE VALVE
NPT threaded hole in the bushing.
4. Install the remaining ¼ inch NPT X
3
/8 inch
tube compression fitting into inlet of the
air bleeder valve body. Hold the valve
with a wrench.
CAUTION: To prevent damage to the
valve body hold the hex outlet on the
valve with a wrench while tightening
elbow.
5.Install the ¼ inch NPT X3/8 inch tube
compression elbow into the hex outlet of
the air bleeder valve. To prevent
damage to the valve body hold the hex
DISCHARGES TO
3/8 INCH O.D. TUBING
(PROVIDED BY INSTALLER
ATMOSPHERE
¼ INCH NPT x 3/8 INCH
TUBE COMPRESSION
FITTING
6. Using a
7. Remove the retaining nut from the valve
8. Insert the valve body into the panel
AIR BLEEDER
VALVE BODY
outlet on the valve with a wrench while
tightening elbow. Make sure the outlet
of the elbow is facing away from the
valve handle.
3
/32 inch Allen wrench, loosen the
setscrew and remove the valve handle
from the valve body.
body.
placard making sure the elbow is
oriented towards the top of the placard.
¼ INCH NPT x 3/8 INCH TUBE
COMPRESSION ELBOW
HOLD THIS HEX WHEN
TIGHTENING ELBOW
¼-20 UNC NUT
PANEL
PLACARD
¼-20 UNC x 1 INCH LONG
SCREW
AIR BLEEDER VALVE
RETAINING NUT
VALVE
HANDLE
¼ INCH NPT x 3/8 INCH
TUBE COMPRESSION
FITTING
¾ INCH NPT x ¼ INCH NPT
BUSHING
¾ INCH NPT AIR
BLEED TAPPED HOLE
ON VALVE BODY
Figure 6. Hale Air Bleeder Valve (ABV) Installation
¾ INCH NPT
OUTBOARD
PRIMING TAP
11
MASTER INTAKE VALVE
9. Install and tighten the retaining nut on
the valve body making sure the valve
remains in the correct orientation.
2.25 IN.
(57 MM)
0.75 IN.
(19 MM)
0.25 IN. (6 MM)
RADIUS TYPICAL
3.66 IN.
2.75 IN.
(70 MM)
0.28 IN. (7 MM)
DIAMETER HOLE
(4 PLACES)
0.25 IN.
(6 MM)
2.75 IN.
(70 MM)
(93 MM)
10. Install the valve handle and tighten
setscrew with allen wrench.