16
A B C
Indoor 2
Wired controller
A B C
A B C
A B C
Indoor 1
Wired controller
A B C
A B C
Indoor N
Wired controller
Indoor 15
Wired controller
Indoor 16
(master unit)
Wired controller
Control wiring of wired
controller, polar.
Wired controller
B: One Controller for up to 16 indoor
1. Cassette (AB…AL…MVAB…MVAL…)
Ducted (AD…AM24…MVAD…MVAH…)
MRV Wall Mount (MVAW…)
A B C
Indoor 2
Wired controller
A B C
A B C
A B C
Indoor 1
Wired controller
A B C A B C
Indoor N
Wired controller
Indoor 15
Wired controller
Indoor 16
(master unit)
Wired controller
Control wiring of wired
controller, polar.
Wired controller
2. Ducted (AM36...AM48…)
• Addressing Indoor Units
• Each indoor unit must hvae a unique
address.
• Compact Cassette (AB…) use SW02_1-4
• Large Cassette (AL…) use SW3_5-8
• Slim Duct (AD…) use SW03_1-4
• High Static Duct (AM24…) use SW03_5-8
• High Static Duct (AM36…AM48…) use
SW02_1-4
• All MRV indoor (MV…) use SW01_1-4
Dipswitch position Dipswitch position
Unit # 1 2 3 4 Unit # 1 2 3 4
5 6 7 8 5 6 7 8
0* o o o o 8 on o o o
1 o o o on 9 on o o on
2 o o on o 10 on o on o
3 o o on on 11 on o on on
4 o on o o 12 on on o o
5 o on o on 13 on on o on
6 o on on o 14 on on on o
7 o on on on 15 on on on on
* Unit 0 is connected directly to the control and is master