Product Features ...............................................................................................................................................................1
Transportation and Lifting ..................................................................................................................................................3
Outdoor unit installation .....................................................................................................................................................4
Electric wiring and the application ...................................................................................................................................13
Installation and debugging...............................................................................................................................................17
Trial operation and the performance ...............................................................................................................................24
Important matters
• The company does not assume any responsibility for the
accidental damage caused by the operation of the air
conditioner in a particular environment.
• The air conditioner can only be used as an ordinary air
conditioner.
• Do not use this heat pump air conditioner for dry clothing,
frozen food, cooling or heating, etc.
• No part of this manual may be copied without permission.
• Bold text (warning, prohibition, attention) used to indicate
the degree of risk. The following is a descriptionof the
text and symbols in the explanatory notes:
WARNING:
Indicates a potentially hazardous situation
which, if not avoided, will result in death or
serious injury.
PROHIBIT:
Do not carry out the operation.
CAUTION:
Sometimes it can cause serious accidents.
• If you have any questions, please contact the dealer or
the service center designated by our company.
• Please install air conditioning in accordance with local
standards.
Warning
• If the supply cord is damaged, it must be replaced by
the manufacturer, its service agent or similarly qualied
persons in order to avoid a hazard.
• This appliance is not intended for use by persons
(including children) with reduced physical, sensory
or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or
instruction concerning use of the appliance by a person
responsible for their safety.
• Children should be supervised to ensure that they do
not play with the appliance.
• This appliance can be used by children aged from 8
years and above and persons with reduced physical,
sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or
instruction concerning use of the appliance in a safe
way and understand the hazards involved. Children
shall not play with the appliance. Cleaning and user
maintenance shall not be made by children without
supervision.
• The appliances are not intended to be operated by
means of an external timer or separate remote-control
system.
• Keep the appliance and its cord out of reach of children
less than 8 years.
Operation condition:
To use the air conditioner normally, please perform as to the below conditions.
Operating Range of Air Conditioner
Cooling
Indoor
dry
Outdoor
Indoor
Heating
Outdoor
Max. DB: 90°F(32°C) WB: 74°F(23°C)
Min. DB: 64°F(18°C) WB: 57°F(14°C)
Max. DB: 115°F(48°C) WB: 79°F(26°C)
Min. DB: 23°F(-15°C)
Max. DB: 80°F(27°C)
Min. DB: 59°F(15°C)
Max. DB: 75°F(24°C) WB: 59°F(15°C)
Min. DB: -4°F(-20°C)
Page 3
Product Features
• The outdoor uint adopts "simultaneous control" type, all indoors should be heating or cooling simultaneously.
• To protect compressor,before startup,the unit should be electried for 12 hours.If the unit is not used for a long time,
please cut off the power to save energy, or the unit will consume the power.
This manual describes the installation and installation of outdoor units. For the installation of the indoor machine, please
refer to the instruction manual of the indoor unit.
Please read the installation instructions carefully before installation, according to the instructions of the installation
construction.
Safety precautions
• This manual should be saved and stored close to this air conditioning equipment.
• There are two types of indications, " WARNING" and " CAUTION" The indication preventing from death or heavy
injury is lister as " WARNING".Even the indication listed as " CAUTION" may also cause serious accident. Both of
them are related to safety, and should be strictly follwed.
• After installation and start-up, please give the manual to the user. The manual should be kept in safe place and close to
the unit.
WARNING
• Installation or maintenance should be performed by an authorized agency. Wrong operation of this air conditioning
equipment may cause water leakage, electric shock or re.
• Please install the unit on the top of a solid foundation or structure which is strong enough to support the unit.
• The installation of this air conditioning equipment should follow local construction codes.
• Use the right cable size, secure the terminal rmly, organize the cables neatly and make sure no tension is added on
cables. Cable insulation should not be damaged. The incorrect installation may lead to overheating or re.
• When installing or moving the unit, the refrigerant system should be vacuumed and recharged with R-410A refrigerant.
If any other gas enters the system, it may lead to abnormal high pressure which may cause damage or injury.
• Please use the proper manifolds or branches during the system installation. The wrong parts may cause refrigerant
leakage.
• Keep the drain pipe away from toxic gas vents to prevent possible pollution of indoor environment.
• During or after the installation, please check whether there is a refrigerant leakage. If any leakage, please take any
measures for ventilation. The refrigerant may be toxic at some concentration levels.
• The unit is not explosion-proof. Please keep it away from ammable gases.
• The drain pipe should be installed per this manual to ensure proper drainage. The pipe should be well insulated to avoid
condensation. Incorrect installation may lead to water leakage.
• Both liquid pipe and the gas pipe should be well insulated. Not enough insulation may lead to system performance
deterioration or humidity formation.
• This air conditioning equipment is not intended to be operated by persons with lack of experience and training, unless
they have supervision or instruction concerning use of this air condition equipment.
• Please keep children away from this air conditioning equipment.
• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent orsimilarly qualied persons in
order to avoid a hazard.
• This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety.
• Children should be supervised to ensure that they do not play with the appliance.
PROHIBIT
• This system uses R410A refrigerant, do not use oxygen, acetylene or any other ammable/toxic gases near the unit.
These gases are dangerous and may cause explosion. It is recommended to use compressed air, nitrogen or refrigerant
for such tests.
• Keep water away from the indoor and outdoor units. These products are equipped with electrical components, which
may cause serious electric shock if exposed to water.
• Do not modify the safety devices in the indoor or outdoor unit. Modifying these devices can cause serious accidents.
1
Page 4
Safety precautions
• The maintenance cover plate of the indoor or outdoor unit should not be removed when the main circuit power supply
on. Shut off power before removing.
• Refrigerant leakage can cause breathing problems. In the event of a refrigerant leak, close the main valve, extinguish
any ame and contact a local servicer immediately.
• Use the proper breaker and surge protector. If not used, an electric shock or re may cause injury or damage.
• The installation and service technician shall ensure that refrigerant leaks comply with local laws and regulations.
CAUTION
• Grounding wire should be connected with the grounding bar. The grounding wire can not be connected to the gas pipe,
water pipe, lightening rod or the telephone grounding wire. Improper grounding may cause electric shock.
• Don't install the unit in a location with ammable gas or it may cause re.
• Install the water drainage pipe according to the manual, improper installation will cause water leakage and damage.
• The outdoor fan should not blow towards gardens/vegetation or the air will dry out the plants.
• Please ensure proper clearances, if not, service technicians will not have room to service.
• When installing the unit on a roof or other high places, to prevent injury to the service technician, please set a xed
ladder and railing at the installation site.
• Use a wrench and fasten the nut. Use a torque wrench to tighten at at proper torque spec. Don't over tighten the nut or
you risk damaging the are. Will cause refrigerant leaks.
• Be sure to insulate the refrigerant pipe, or there will be water leakage or water dripping causing damage.
• After installing the refrigerant pipe, test for leaks by charging with nitrogen.
• Don't use the other refrigerants except for R410A. The R410A pressure is 1.6 times higher than R22 pressure. R410A
tanks are marked with pink.
• We changed the stop valve diameter of the R410A unit to enhance the compression consistency. We also changed the
ared pipe dimension. Adjust the R410A specially tools according to the below table.
3 electronic balance for charging R410Acan not use the measurable charging tank
4 torque spanner
5 are tool
6 copper pipe gauge for adjusting projecting margin
7 vacuum pump adaptermust be with reverse stop valve
8 leakage detectorcan not use freon leakage detector, but the He detector
• When charging refrigerant, the refrigerant must be taken out in liquid state from the tank.
• When installing the power cord and the connecting line must be a least 1m from the TV or radio, so as to avoid image
interference or noise.
• In the room with uorescent lamp (reverse or fast start type), remote control signal transmission distance may not reach
the predetermined value, so the indoor unit installed away from the uorescent lamp as far as possible.
• Please use the fuse to meet the capacity requirements.
• To prevent the destruction of wires, electrical components, etc. by rats or other animals.
• Recommended room ventilation every 3 to 4 hours.
Arrival inspection
• After receiving the unit, should check whether there is transport damage. If any damage is found on the surface or=
inside, it shall be reported immediately to the shipping company in writing.
2
Page 5
Transportation and Lifting
Lifting
Please do not remove the packaging until the unit is close to
the installation location.
CAUTION
Do not place anything on the device
•
Use two ropes for lifting the outdoor unit
•
Hoisting method
Hoist the unit slowly and ensure that it is level.
Removal of the outer packing is strictly prohibited
①
Hoist outdoor unit packaging as shown using two ropes.
②
CAUTION
To ensure safety, slowly lift while keeping the unit level.
•
Do not use a forklift to move the unit without the unit
•
packaging.
Padding should be used to protect the unit while lifting it.
•
Over 60 degrees
rope
2.3~3.3 ft
Do not remove
packing tape and
packing box.
As shown in the
rope through
the wood base
around the lifting
hole.
Manual handling
CAUTION
In the installation and commissioning, the outdoor machine do not put any irrelevant material, to ensure that there is
•
no debris inside the machine, or there may be a fire or accident.
Follow these points when moving the unit by hand:
Do not destroy the wood base.
①
In order to prevent the outdoor unit from tipping note the units center of gravity as shown in the gure.
②
Use two or more people to carry and move the outdoor unit.
③
Unit maximum tilt angle 20
degrees.
Handles
Center of
gravity
Wood base
3
Page 6
Outdoor unit installation
In installation, please check specially the below items:
• If the connected units quantity and the total capacity is in the allowable range?
• If the refrigerant pipe length is in the limited range?
• If the pipe size is proper? And if the pipe is installed horizontally?
• If the branch pipe is installed horinzontally or vertically?
• If the additional refrigerant is counted correctly and weighed by the standard balance?
• If there is refrigerant leakage?
• If all the indoor power supplies can be on/off simultaneously?
• If the power voltage is in compliance with the data marked on the rating label?
• If the address of indoors has been set?
(1) Before installation
1) Before installation, check if the model, power supply, pipe, wires and parts purchased respectively are correct.
2) Check if the indoors and outdoors can be combined as the following.
OutdoorIndoor
Capacity
(1000Btu/h)
36Single618-46
48Single824-62
56Single927-72
Notice:
Total capacities of indoor units being used ≤ 100% of
rated capacities of outdoor unit.
Combination
type
Indoor
qty
Total indoor capacity
(1000Btu/h)
Indoor capacity
(1000Btu/h)
07
09
12
18
24
32
36
42
48
Notice:
The branch pipe should be installed horizontally, the
maximum error angle should not exceed 10 degrees.
total indoor
capacity
(1000Btu/h)
less than 114FQG-B335A
branch pipe (optional)
(2) Installation place selection
Air-conditioner can't be installed
in the place with inammable
gas. Or it will cause re hazard.
The unit should be installed in a
place where the cold/hot air or
noise will not interfere with the
neighbors.
The unit should be installed at the
place with good ventilation. No
obstacle at the air inlet/outlet. And no
strong wind blows the unit.
The installation space refers to the
latter info.
• A place where the water can drain
easily.
• A place where no other heat
sources will affect the unit.
• Consider snow depth when
installing outdoor unit.
• Install the anti-vibration rubber
between the unit and the bracket.
The unit should be installed at the strong
enough place. Or it will cause vibration and
noise.
• The unit should not be installed at the
below places or it will cause damage.
• A place where there is corrosive gas
(spa area etc). A place blowing salty air
(seaside etc).
• A place with strong coal smoke.
• A place with high humidity.
• A place where there is device emitting
electrical interference.
• A place where voltage uctuations
• occur.
4
Page 7
Installation instruction
Note:
1. In snowy areas, install the unit on a bracket or under a snow-proof cover to prevent the accumulation of
snow.
2. Do not install the unit at a place where ammable gas exists.
3. Install the unit in a sturdy location.
4. Install the unit in a level location.
5. When being installed in a location with strong winds, set the air outlet of the unit perpendicular to the
wind direction. Also secure the unit with the bolts.
6. When opening the electric box cover for maintenance, please secure the cover with screws.
(3) Installation and maintenance space
Selection of installation location of outdoor
(1) Single-unit installation (unit: in.(mm))
The top and two side surfaces must be exposed to open space, and barriers on at least one side of the front and back
shall be lower than the outdoor unit.
(2) Multi-unit installation (unit: in.(mm))
5
Page 8
Installation instruction
(3) Multi-unit installation in front and back (unit: in.(mm))
The top and two side surfaces must be exposed to open
space, and barriers on at least one side of the front and back
Above 120(3000)
• The installation service spaces shown in the illustrations are based on an air intake temperature of 95°F(35°C)(DB)
for COOL operation. In regions where the air intake temperature regularly exceeds 95°F(35°C)(DB), or if the heat load
of outdoor units is expected to regularly exceed the maximum operating capacity, reserve a larger space than that
indicated at the air intake side of units.
• Regarding the required air outlet space, position the units with consideration to the space required for the onsite
refrigerant piping work as well. Consult your dealer if the work conditions do not match those in the drawings.
(4) Precautions on installation
NOTICE
If drain holes of the outdoor unit are covered by a mounting base or by oor surface, raise
the unit in order to provide a free space of more than 5in.(130mm) under the outdoor unit.
Foundation work
• Check the strength and level of the installation ground so that the unit will not cause any
operating vibration or noise after installation.
• In accordance with the foundation drawing in the gure, x the unit securely by means of
the foundation bolts.
• It is best to screw in the foundation bolts until their length are 0.8in.(20mm) from the
foundation surface.
flow out
shall be lower than the outdoor unit.
screw nut
1
0.8in. (20mm)
• Fix the outdoor unit to the foundation bolts using nuts with resin washers(1) as shown in the gure.
• Avoid strong wind blowing directly to the outdoor fan and heat exchanger.If there is no need to install the outdoor
machine in the open space of the building or the enclosure, the following two ways can be used to avoid the fan reversal
or damage caused by strong wind blowing.
Sketch of machine installation
and strong wind direction
Fierce wind
concrete
(1) Using the windshield
foundation bolt M12
fill in mortar
(2) Near wall installation
Wind
deector
Fierce wind
More than 80inch (2000mm)
˃5in.(130mm)
Fierce wind
6
Page 9
Installation instruction
If the coating on the fastening area is stripped off, the nuts rust easily.
Dimensions (bottom view) (unit of measurement: mm)
A leg pitch1
B leg pitch2
C Front grill (air outlet side)
D Drain hole
E Bottom frame
F Knock-out hole (for piping line)
(5) Refrigerant pipe connection
Pipe connection method:
• To ensure correct efciency, the pipe should be as short as possible.
• Coat refrigerant oil on the connector and the are nut.
• When bending the pipe, the bend diameter should be as large as
possible to prevent the pipe from breaking or kinking.
• When connecting the pipe, center it and thread the nut by hand.
• Then tighten it with the double spanners.
• Don't let any debris such as sand, water etc into the pipe.
Cautions in piping installation:
• When welding the connector use hard solder, charge nitrogen into the pipe to prevent oxidation. If not the oxygen lm in
the pipe will clog the capillary and the expansion valve. May even cause a deadly accident.
• The refrigerant pipe should be clean. If water or any other impurities enter the pipe, charge with nitrogen to clean the
pipe. The nitrogen should ow around the pressure of 72.5PSI(0.5Mpa). When charging the nitrogen, stop up the end of
the pipe by hand to enhance the pressure in the pipe, then move your hand to stop up the other end of the pipe.
• The piping installation should be done while the stop valves are closed.
• Before welding the valve and the pipes, use a wet cloth to cool down the valve and the pipes.
• When the connection pipe and branch pipe need to be shortened, please use special shears. Do not use a saw.
Pipe material and specs selection
1. Please select the refrigerant pipe of the below material.
Material: the phosphoric oxidize seamless copper pipe, model: C1220T1/2H (diameter is over 19.05); C1220T-0 (diameter is below 15.88).
2. Th i c k n e s s a n d s p e c s :
Conrm the pipe thickness and specs according to the pipe selection
method(the unit is with R410A, if the pipe over 19.05 is 0-type, the
pressure preservation will be bad, thus it must be 1/2H type and over
the min. thickness.
3. The branch pipe must be from Haier.
4. When installing the stop valve, refer to the relative operation instruction.
5. The pipe installation should be in the allowable range.
6. The installation of branch pipe and gather pipe should be performed
according to the relative manual.
When fastening and loosing the nut,
operate with double spanners, because
only one spanner cannot execute rmly.
Spanner
Connector
Nut
Spanner
If threading the nut as not aiming at
the center, the screw thread will be
damaged, further it will cause leakage.
Drain pipe disposal
• Make sure the drain works properly.
• In regions where buildups of snow can
be expected, the accumulation and
freezing of snow in the space between
the heat exchanger and external plate
may lower operating efciency.
• After punching the knock-out hole, the
application of repair-type paint on the
surface around the edge sections is
recommended to prevent rust.
7
Page 10
Installation instruction
Pipe specication:
1. Pipe "a" diameter (between indoor and branch pipe) (depends on indoor pipe)
Please refer to the indoor air conditioner manual.
2. Pipe "b" diameter (between branch pipes)
Total indoor capacity after the branch pipe (x1000Btu/h) Gas pipe (in) Liquid pipe (in)
X<38Ø5/8Ø3/8
38≤X< 80Ø3/4 Ø3/8
3. Pipe "c" diameter ( outdoor pipe diameter)
Outdoor capacity
(x1000Btu/h)
36Ø5/8Ø3/8
48Ø5/8Ø3/8
56Ø5/8Ø3/8
Note:
• When the distance from outdoor to the longest indoor is
over 98ft, the main pipe should be the enlarged diameter.
• If pipe b diameter is larger than main pipe c,enlarge main
pipe c diameter to be the same as pipe b.
Piping connection method:
Gas pipe (in) Liquid pipe (in)
Copper pipe selection:
hardnesssoftness
Outer diameter (in)Ø1/4Ø3/8Ø1/2Ø5/8
Min. thickness (in)0.0310.0310.0390.039
hardnessHalf-hardness
Outer diameter (in)Ø3/4Ø7/8Ø1 Ø1 1/8
Min. thickness (in)0.0390.0430.0470.055
Note: If the copper pipe with outer diameter 19.05 is coil
pipe, the thickness should be over 1.1.
b
c
a
a
a
b
a
Pipes can be connected in four directions
charging valve
A
liquid pipe
Enlarged diagram
F
E
B
gas pipe
C
A, B, C, D:Copper pipe hole
E:Power cord hole (with its own cable sheath)
F:Communication line hole
As shown in the gure, the piping can be connected from four directions. Through the front / rear hole piping piping on
the cover hole or crack directly across the oor.
From the outdoor machine unloading piping cover with a screwdriver and hammer knock off holes along the guide wire
break. Then, trim the edges of the holes, and mounted on the insulating sleeve (site) to protect the piping and wiring.
8
D
Page 11
Installation instruction
Long pipe and high drop
1. Allowable pipe length and height difference
Outdoor unit
First branch piping
Length of the longest piping L
Length of the longest piping after the
rst branch piping L
Drop height between indoor and outdoor units
Maximal length and drop height permissible of refrigerant piping
Permissible valuePiping part
Total length of piping (actual length)492ft.(150m)L1+L2+L3+L4+a+b+c+d+e
Piping
length
Drop
height
Unit pipe spec and connection method (unit: in.(mm))
Piping length of indoor unit which is furthest to the rst branch
Drop height between indoor and outdoor unit
Longest piping L Actual length230ft.(70m)L1+L2+L3+L4+e
piping L (*)
H
Drop height between indoor units h49ft.(15m)——
Indoor unit
h≤49ft.(15m)
indoor units
Drop height between
131ft.(40m)L2+L3+L4+e
Up outdoor98ft.(30m)——
Under outdoor66ft.(20m)——
A. Outdoor unit
Model
MVHP036MV2AA Ø5/8"15.88
MVHP056MV2AA Ø5/8"15.88Ø3/8"9.52
B. Indoor unit
Please refer to the indoor air conditioner manul.
Connecting method: Flared joint
1. When connecting the pipe to the outdoor unit, please pay attention to the outdoor pipe dimension.
2. When changing the diameter between pipes and between the units, please change on the branch pipe side.
3. Be sure to blow nitrogen when welding. If not, oxides will be produced and cause heavy damage. Take precautions to
prevent water and dust from getting into the pipe.
Cut off pipe with the cutter
Adhesive side
Prepare on eld
Insulation:
• Gas pipe and liquid pipe should be insulated separately.
• The insulation material for gas pipe should be rated for temperatures over
248°F (120°C). The liquid pipe should be for over 158°F (70°C).
• The insulation should be over 0.39in.(10mm) thick, when the ambient
temp. is 86°F (30°C)When the relative humidity is over Liquid pipe 80%,
the insulation thickness should be over 0.59in. (15mm).
• The material should be snug against the pipe without a gap,
then be wrapped with adhesive tape. The connection wire can
not be wrapped with the insulation material and should be at
least 7.87in.(20cm) from the insulation.
Secure refrigerant piping
• During operation, the pipe will vibrate, expand or shrink. If not being secured, the refrigerant will focus on one part and
cause the pipe to break.
• To prevent stressing the pipe, secure the pipe every 6.56-9.84ft.(2-3m).
Pipe installation
Seal the connection and wrap the
heat insulator with adhesive tape
Liquid pipe
Cut off at the middle
Connection wire
over 7.87in.(20cm)
Adhesive tape
Gas pipe
Heat insulator
When doing the piping connection, please do the following:
• Be careful not to damage any parts or pipes while connecting to the unit.
• Close the valves fully when connecting the pipes
• Protect the pipe from getting water or other impurities in them (welding after being laid down, or being sealed with
adhesive tape).
• Use large diameter bends when possible(over 4 times of the pipe diameter).
• The connection between outdoor liquid pipe and the distributing pipe is ared type. Please are the pipe with a tool used
with R410A after installing the are nut. If the pipe length has been adjusted with the copper pipe gauge, you can use
the original tool to are the pipe.
• The oil is ester oil, not the mineral oil, since the unit uses R410A.
• When connecting the pipe, fasten the pipes using a spanner. The torque refers to the former info.
• The outdoor gas pipe and the refrigerant distributing pipe, as well the refrigerant distributing pipe and the branch pipe
should be welded with hard solder.
A
Projecting length of pipe to be expanded: B(mm)
When it is hard pipe
Pipe outer diameter
Ø1/4(6.35)
Ø3/8"(9.52)
Ø1/2"(12.7)
Ø5/8"(15.88)
Special tool
for R410A
0-1/51"
(0-0.5)
The former
tool
1/25"-1/17"
(1.0-1.5)
10
Page 13
Installation instruction
• Weld the pipe while charging with nitrogen or it will cause impurities (including
a lm of oxidation) to clog the capillary and the expansion valve which may lead
to deadly accidents.
• Protect the pipe ends from getting water and other impurities into
the pipes (from welding, led or being sealed with adhesive tape).
Flat
Brazing
• The refrigerant pipe should be clean. The nitrogen should ow at
pressure around 29PSI(0.2Mpa) and when charging the nitrogen,
stop up the end of the pipe by hand to increase the pressure in the
pipe, then move your hand and stop up the other end.
• Close the valves fully when connecting the pipes.
• When welding the valve and pipes, use a wet cloth to cool down the valve and
pipes.
Adhesive tape
Source valve
Seal the pipe end with
adhesive tape or the stopper
to increase the resistance, ll
up the pipe with nitrogen.
Taping
1st side
<N2>
Only nitrogen gas
can be used
2nd side
Hand
Brazing
29PSI
(0.2MPa)
(6) Leakage test
1. The outdoor unit has been tested for leakages from the factory. After connecting the distributing pipe, test for leakages
from the outdoor check valve and the indoor pipe. While testing, the valves should be close.
2. Refer to the below gure to charge nitrogen into the unit to test. Never use chlorine, oxygen, ammable gas for the
leakage test. Apply pressure on both the gas pipe and the liquid pipe.
3. Apply the pressure step by step to the target pressure.
a. Pressurize to 72.5PSI(0.5MPa) for more than 5 minutes, check if pressure goes down.
b. Pressurize to 217.5PSI(1.5MPa) for more than 5 minutes, check if pressure goes down.
c. Pressurize to the target pressure 580PSI(4.0MPa), record the temp. and the pressure.
d. Leave it at 4.0MPa for 1 day or more, if the pressure does not go down, the test is complete.
Note that when the temp. changes
by 1degree, pressure will change
1.45PSI(0.01MPa). Correct
the pressure as needed.
e. After performing a~d, if the pressure
goes down, there is leakage. Check
any brazed and ared connections
using soapy water. Fix the leakage and
perform test again.
4. After the leakage test evacuate the
system.
Nitrogen
(7) Evacuation
Evacute at the liquid service valve and both sides of the gas service valve.
Operation procedure:
To indoor
Gauge manifold
Lo
Lo handle
Hi
Hi handle
Check valve
Gas pipe
Gas pipe
Check hole
Outdoor
after reaching -14.645PSI
(101KPa) or less (below
-755mmHg), let the vacuum
Leakage test passed
Evacuation begins
pump run continuously for 1
hour or more.
if vacuum needle rises, it shows there is water or leakage in the
system, please correct the problem and then evacuate again.
11
leave it for over 1
hour, vacuum
gauge does not arise.
Evacuation ends
Check vacuum
Charge refrigerant
Page 14
Installation instruction
The unit is charged with R410A refrigerant. The details below should be paid attention to:
• To prevent different oils from getting into the pipe, please use the specic tool for R410A, especially for manifold gauge
and charging hose.
• To prevent the compressor oil from getting into the refrigerant cycle, please use the anti-counter-ow adapter.
(8) Check vale operation
• Remove the valve cap.
• Turn the liquid stop valve and the gas stop valve with hexangular spanner until it stops. If the valve is opened with too
For gas pipeless than 61.9(7)less than 265.2(30)114.9(13)
For liquid pipe69.4(7.85) (MAX138.8(15.7))260(29.4)(MAX346.5(39.2))77.8(8.8) (MAX130(14.7))
(9) Additional refrigerant charging
Add additional refrigerant under the liquid state with the gauge.
If the additional refrigerant can not all be added, when the outdoor stops, charge it using trial mode.
If the unit runs for a long period undercharged, the compressor will eventually fail.(charging must
be nished within 30 minutes especially when the unit is running while charging).
A. Charge amounts from the factory exclude the refrigerant in the pipes.
B. The unit is charged with a standard amount of refrigerant (distributing pipe length is 0).
Additional charge amount=actual length of liquid pipe x additional amount per meter liquid pipe
Additional charge amount=L1×0.113+L2×0.073+L3×0.037+L4×0.015
L1: total length of 5/8"(15.88) liquid pipe L2: total length of 1/2"(12.7) liquid pipe
L3: total length of 3/8"(9.52) liquid pipe L4:total length of 1/4"(6.35) liquid pipe
C. Refrigerant charging and additional charge
Additonal refrigerant charging per Ib (Ib/ft.)
Ø5/8"Ø1/2"Ø15.88Ø3/8"Ø1/4"Ø6.35
0.1130.0730.0370.110.0150.022Refer to label
Charge when out of factory
Note:
• To prevent adding different oils into the pipe, please only use a gauge manifold and charging hose for R410A.
• Tank color for R410A is pink.
• Do not use a charging cylinder because R410A will change when transferring to the cylinder.
• When charging refrigerant, the refrigerant should be taken out from the tank as liquid state. Mark the refrigerant amount
added that was calculated by the pipe length on the unit label.
Secure refrigerant piping
• During operation, the pipe will vibrate, expand or shrink. If not being secured, the refrigerant will focus on one part and
cause the pipe to break.
• To prevent stressing the pipe, secure the pipe every 6.56-9.84ft.(2-3m).
GWP: 2088
The product contains uorinated greenhouse gases and its functioning relies upon such gases.
(10) Refrigerant recovery
• Start: press Start and Stop keys on the main control board at the same time for 5 seconds. The unit will start automatic
recovery mode. The compressor starts, the right side of the unit C0 and Ps LEDs start ashing, runs for around 3
minutes.
• Operation: when the LEDs C1 and Ps alternately ash, manually shut off the liquid pipe valve
• Off valve: when Ps < 1kg, LED displays C2, quickly close the shut-off valve, after 5 seconds the system will shut down.
• End: manually power down the system to reset the program.
• Note: in heating, standby or while shutdown: the outdoor unit is forced into refrigeration operation.
12
Page 15
Electric wiring and the application
WARNING
• Turn off the main power switch of the indoor
and outdoor unit for 1 minute or more before
wiring or servicing.
• To prevent damaging the wires and electrical
components, avoid installing around animals. It
may lead to the occurrence of re.
• To prevent damaging the wires, avoid contact
with refrigerant pipes, steel edges and electrical
components. It may lead to the occurrence of
re.
CAUTION
• Secure the power cord with a wire tie in the
unit.
Note:
when the outdoor unit is not using a circuit, it
should be sealed with a rubber blocker.
CAUTION
• When using 3 phase 5 wire power, the
power supply of the indoor machine must be
connected using L1 and N. Do not use L1-L2,
L1-L3, otherwise the unit electrical components
will be damaged.
Signal wiring:
The outdoor unit and all the indoor units are
connected in parallel through with shielded two
wire cord.
Inspect
• Conrm that the electrical equipment used on the installation site
• (main power switch, circuit breaker, wire, conduit and wiring
terminals, etc.) have been selected according to current data, to
ensure that the device in line with national standards.
• Conrm that the power supply voltage is within +/-10% of the
rated voltage and that the unit is properly grounded to prevent
damage to the electrical components.
• Check for correct voltage. Otherwise, the compressor will not start
if the voltage is too low.
• Measure the resistance between the ground and the electrical
terminals and ensure that there is more than 1MΩ. Otherwise, the
system will not start. Fix the issue prior to operating the system.
Connection
• Connect the power cord to the terminal of the indoor unit and the
outdoor electrical box, connect the ground wire to the grounding
bolt of the outdoor unit and the indoor electrical box.
• Connect the outdoor and indoor communication wire to the 1 and
2 terminals on the terminal block. If the power cord is connected
to the communication terminals, the circuit board will be damaged.
• Use shielded twisted pair wire.
• Do not screw to the front of the cover.
• The power wire must be made of copper wire, and the power
supply must conform with IEC 60245 requirements. If the power
cord length exceeds 20m
• use a larger gauge wire.
• Use a round terminal connection on the wire with an insulating
protective sleeve.
• Secure the wire away from any sharp edges and materials that
may damage the wire to prevent damage and causing a re or
damage.
Communication wiring gure
Outdoor
P Q
Indoor 1
P Q A B C
Communication wire with polarity
Indoor 2
Indoor 3Indoor 4Indoor 5Indoor 6
P Q A B CP Q A B CP Q A B C
A B C
wired
controller
A B C
wired
controller
A B C
wired
controller
13
P Q A B C
A B C
P Q A B C
A B C
wired
controller
wired
controller
A B C
wired
controller
Page 16
Electric wiring and the application
The outdoor and all indoor units are connected in parallel through 2 non-polar wires. Three wiring options between the
wired controller and indoor unit:
A. One wired control to control multiple units, i.e. 2-6 indoor units, as shown in the above gure, (1-2 indoor units). The
indoor unit 2 is the wire controlled main unit and others are the wired controlled sub units. The remote control and the
main unit (directly connected to the indoor unit of wired control) are connected via three wires with polarity.
B. One wired control controls one indoor unit, as shown in the above gure (indoor unit 3-5). The indoor units and the
wired control are connected via three lines with polarity.
C. Two wired controls control one indoor unit, as shown in the gure (indoor unit 6). Either of the wired controls can be set
to be the master wired control while the other is set to be the auxiliary wired control. The master wired control and
indoor units, and the master and auxiliary line controls are connected via three lines with polarity.
Power wiring gure
outdoor
L1(L) L2(N)
power source: 208/230V~, 60Hz
indoor 1
(wall mounted unit)
L1(L) L2(N)
power source: 208/230V~, 60Hz
indoor 2
(wall mounted unit)
L1(L) L2(N)
power source: 208/230V~, 60Hz
indoor 3
(non wall mounted unit)
L1(L) L2(N)
power source: 208/230V~, 60Hz
Indoor and outdoor use their individual power source. All indoors use one power source. Must install the leakage breaker
and the over current breaker, or electric shock will occur.
Outdoor power source and power cable
Item
Model
MVHP036MV2AA
MVHP048MV2AA
power
MVHP056MV2AA
Individual
Rated current of residual
circuit breaker (A)
Ground fault interruptor (mA)
response time (S)
Power
source
Power cable
section
Circuit
breaker
(A)
208/230V~, 60Hz7AWG5050A 30mA below 0.1S7AWG
Ground wire
Section
2
)
(mm
Screw
3/16”
(M5)
• Power cable must be xed rmly.
• To avide electrical shock, make sure to disconnect the power supply 1 minute or more before servicing the electrical
parts.Even after 1 minute,always measure the voltage at the terminals of main circuit capacitors or electrical parts and
before touching, make sure that those voltages are 50VDC or less.
• To persons in charge of electrical wiring work: Do not oerate the unit until the refrigerant piping is complete.(Running it
before the piping is ready will break the compressor)
• Each outdoor must be earthed well.
• When power cable exceeds the range, thichen it appropriately.
• The appliance shall be installed in accordance with national wiring regulations.
• All wiring must be performed by an authorized electrician.
• Be sure to install an earth leakage circuit breaker in accordance with applicable legislation.Failure to do so many
cause electrical shock.
14
Page 17
Electric wiring and the application
Indoor power source and communication wiring
WARNING
• Power lines must be copper wire.
• All indoor and outdoor units must be grounded properly. The ground wire must not be grounded using a gas pipe,
water pipe, lightning rod or telephone wire. If the grounding is correct it may cause electric shock or re.
• Power supply must be installed with an earth leakage circuit breaker, otherwise it may cause electrical shock or re.
• The operation and maintenance of the electrical equipment shall be carried out with the power supply off.
• The indoor and outdoor units each get their own independent power supply.
• The communication line and the power line must be separate.
Item
Indoor
total
current (A)
<1014AWG75.5(23)2020A, 30mA, below 0.1s
≥10 and <1511AWG78.7(24)3030A, 30mA, below 0.1s
≥15 and <229AWG88.6(27)4040A, 30mA, below 0.1s
≥22 and <277AWG137.8(42)5050A, 30mA, below 0.1s
• Power cable and communication wire must be rmly connected.
• Each indoor unit must be properly grounded.
• When power cable exceeds the range, use a larger gauge as required.
• The Shielded layer of the communication wires must be connected together and be grounded at at each point.
• Communication wire total length cannot exceed 1000m.
<328(100)22AWG ×(3-core) shielded wire ≥984(300)and <1312(400) 16AWG ×(3-core) shielded wire
≥328(100) and <656(200) 19AWG×(3-core) shielded wire ≥1312(400) and <1968(600) 14AWG ×(3-core) shielded wire
≥656(200) and <984(300) 18AWG ×(3-core) shielded wire
• Shielded layer of communication wire must be grounded at one end.
• The total length cannot exceed 600m.
Power cable
section
Wire length
ft.(m)
Rated current
of overcurrent
breaker
(A)
Rated current of residual
circuit breaker(A)
Ground fault interruptor(mA)
response time(S)
Communication wire section
Outdoor/indoor Indoor/indoor
2-core × (18-14AWG)
shielded wire
15
Page 18
Electric wiring and the application
Outdoor unit electrical wiring diagram
Ground wire
Power cord
Communication line
Secure the power line and communication
line with a wire clip on the terminal block
Power lines and communication
lines need to be ame retardant
and use high temperature
resistant insulation
Use plastic pipe insulation
on the refrigerant pipe
Protect the power line and
communication line hole with
a wire sheath
Cable sheath
Communication
line
Power cord
Power line and piping need to be
wrapped with ame retardant tape
ErrorCorrect
When using a single terminal without a terminal connector, the wire
can not be directly connected without ux. It will cause abnormal
heating of the terminal connector. If a single core wire is used for the
wiring, it can be connected directly as shown in the diagram.
16
Page 19
Installation and debugging
1. Installation and debugging method of outdoor machine
SW01SW02Seven segment digital tube display content
Outdoor machine fault code
The machine units are not locked and no fault, in turn cycle "in the machine number, machine
capacity, power supply type".
0
(1) The connection machine number: display "U" + machine units.
Such as "U08" means that the machine is connected to the 8 internal machine .
(2) Outdoor mechanism cold capacity: such as 48 machine display 48(uint:KBtu/h).
(3) Power supply type: 1PH represents a single phase, and the 3PH represents a three-phase).
Compressor target frequency.(according to Start 5 seconds, into the manual frequency control, Up/
Down adjustment frequency, according to Stop for 5 seconds, exit the manual frequency control.
4
Manual control, the frequency of ashing display, non manual control, the frequency of normal
display.
5Actual frequency of compressor
0
1
6In machine units
7The machine units
8Outdoor machine capacity (unit:KBtu/h)
9External fan 1 (FAN1) speed (unit: RPM, maximum display of 999)
AExternal fan 2 (FAN2) speed (unit: RPM, maximum display of 999)
BThe average Tc2 temperature of the internal machine (unit: Fahrenheit)
CThe actual average Tc2 temperature of the unit (unit: Fahrenheit)
DSuperheat of heating target (unit: Fahrenheit)
Special running state of the mach:
First bit: power supply type (0- single phase 1- three-phase);
E
Second place: Mute (0- off, 1- open);Third place: the air to run (0- off, 1- open)
(101: three phase power supply, mute off, open the gas)
Forced fan running, no mandatory display "FAN" (according to Start 5 seconds into the fan manual
F
control, Up/ Down adjust the fan gear, according to the Stop 5 seconds, exit fan manual control),
mandatory display "0-15", this function is not affected by external fault inuence
0Td: exhaust gas sensor (unit: Fahrenheit)
1Ta: ring temperature sensor (unit: Fahrenheit)
2Ts: suction sensor (unit: Fahrenheit)
3Te: defrost sensor (unit: Fahrenheit)
5Pd: High pressure pressure (unit: psi)
6Ps: Low pressure (unit: psi)
7Outdoor machine PMV opening (unit: pls, maximum display 999)
Valve state First bit: 4WV (0- closed, 1- open); Second bit: SV1 (0- closed, 1- open); the third bit:
8
SV2 (0- off, 1- open) (example 101 indicates that the 4WV is turned on, the SV1 is turned off, the
SV2 is turned on)
First:high voltage switch HPS (0-disconnect,1-closed); second:low voltage switch LPS
9
(0-disconnect,1-closed);third:heating belt(0-closed,1-open)(101:HPS LPS closed off, open the heating
zone)
ATn: module temperature (unit: Fahrenheit)
BPress current (unit: A, 1 decimal)
DModule DC voltage (unit: V)
CT current (unit: A, 1 decimal)
E
Forced refrigeration alternately display "CCC" (press Start 5 seconds to enter, all internal cooling
operation, according to Stop 5 seconds exit).
17
Page 20
Installation and debugging
SW01SW02Seven segment digital tube display content
1F
20-FCommunication shows the program version (1 decimal), or "---"
30-F
40-FIf there is a failure to show the internal fault code, otherwise, "---"
50-FIndoor machine capability (unit:KBtu/h)
60-F
70-FIndoor machine PMV opening (unit: pls, maximum display 999)
80-F
90-FIndoor machine TA: ambient temperature value (unit: Fahrenheit)
A0-FIndoor TC1: air temperature value (unit: Fahrenheit)
B0-FIndoor machine TC2: liquid pipe temperature (unit: Fahrenheit)
Forced heat alternating display "HHH" (according to Start 5 seconds to enter, all the internal
mechanism of hot running, press Stop to exit for 5 seconds).
The machine type: (0:common indoor machine; 1:wall hanging; 2:Fresh air machine ; 3:heat
exchanger, 4/5/6/7:common indoor machine).
First and the second: indoor machine current mode of operation,
(00: off, 01: air supply, 02: cooling, 03: dehumidication, 04: heating) , the third: external machine
capacity requirements (0: No, 1: Yes)
Indoor unit of air conditioner:
First: oat switch (0- disconnect, 1- closed)
Second place: water pump (0- closed, 1- open)
Third place: electric heating (0- closed, 1- open)
(110 oat switch is closed, the water pump is opened, the electric heating off)
1Super cooled valve plate program version (1 decimal)
2Target opening of the expansion valve of the supercooling valve plate(unit: pls, max: 999)
3The current opening of the expansion valve of the cold valve plate (unit: pls, max: 999)
D
4Tc1 temperature of supercooling valve plate (unit: Celsius)
5Tc2 temperature of supercooling valve plate (unit: Celsius)
6Set aside (display "---")
7Set aside (display "---")
8Set aside (display "---")
9Set aside (display "---")
18
Page 21
Installation and debugging
3. Outdoor unit PCB dipswitch setting(Pay attention to the identication of the computer board).
In the following table, 1 is ON, 0 is OFF.
BM1 introduction
BM1_1 Indoor searching after startup
BM1_2 Celsius/Fahrenheit area selection
BM1_3 External static pressure
BM1_4 Energy saving or refrigeration effect priority
BM1_5 Indoor simultaneous control
BM1_6 Defrosting condition selection
BM1_7 Defrosting level
BM1_8 Silent operation selection
0Begin to search indoor
1Stop searching indoor and lock the quantity
0Celsius area
1Fahrenheit area
0High
1Low
0Energy saving priority
1Refrigeration effect priority
0No
1Yes
0Not easy to frost area
1Easy to frost area
0Ordinary
1Strengthen
0Forbidden(without silent operation)
1Allow (with silent operation)
BM2 introduction
[1]Cold only or heat pump
BM2_1 Cold only or heat pump
BM2_2
BM2_3
BM2_4
BM2_5 Power source selected
BM2_7
BM2_8
Note: Either indoor unit unlocked or the locked quantity different with actual connecting number, it cannot run.
Short it before power ON-- PCB check its function (used for factory production).
Short it after power ON-- time short function, 60 seconds become to 1 second.
CJ2: Reserved
19
Page 22
Failure code
Inverter outdoor unit failure code
Digital tube
indication
on master
unit
2020-0
2121
2222
2323
2626-0
26-126-1
26-226-2
2828
291D
3030
3333EEPROM failureEEPROM failure
3434
3535
39-039-0
Indication
on wired
controller
(hex)
Failure code
denition
Defrosting temp
sensor Te1 failure
Ambient temp.
sensor Ta failure
Suction temp.
sensor Ts failure
Discharging temp.
sensor Td failure
Indoor
communication
failure
High pressure
sensor Pd failure
Low pressure
sensor Ps failure
High pressure
switch HPS failure
Discharging temp.
too high protection
(Td)
4-way valve
reversing failure
Low pressure
sensor Ps too low
protection
Failure descriptionRemarks
AD value is below 11(open circuit) or over 1012(short circuit)
for 60seconds, in cooling mode, if the sensor is abnormal,
the unit operate in defrosting and within 3 minutes after
defrosting, no alarm
AD value is below 11(open circuit) or over 1012(short
circuit) for 60seconds, in defrosting and within 3 minutes
after defrosting, no alarm
AD value is below 11(open circuit) or over 1012(short
circuit) for 60seconds, in defrosting and within 3 minutes
after defrosting, no alarm
After compressor is running for 5 minutes, AD value is below
11(open circuit) or over 1012(short circuit) for 60seconds,
in course of startup, defrosting and within 3 minutes after
defrosting, no alarm
For continuous 200 cycles, can not nd connected indoors
For continuous 300seconds, the searched indoor quantity is
less than the set quantity.
For continuous 300seconds, the searched indoor quantity is
more than the set quantity.
AD value is below 11(open circuit) or over 1012(short
circuit) for 30seconds, in defrosting and within 3 minutes
after defrosting, no alarm
AD value is below 11(open circuit) or over 1012(short
circuit) for 30seconds, in defrosting and within 3 minutes
after defrosting, no alarm
If disconnect for 50ms continuously, alarm. If alarm 3 times
in an hour, conrm the failure
Td≥239°F(115°C) at interval of 25msec for twice
continuously, and over the set value, then stop and alarm;
3 minutes later, resume automatically. If it occurs 3 times in
an hour, conrm the failure.
After 4-way valve is electried for 3 minutes, if the below
conditions can be met for continous 10 seconds, that is
conversing successfully:
1. this outdoor compressor is running normally
2. Pd-Ps≥87PSI(0.6MPa), Otherwise, the system alarms
reversing failure.
After compressor is running (except for residual operation),
if in cooling, Ps<0.05Mpa; in heating, Ps<0.03Mpa; in oil
return, Ps<0.03Mpa for continuous 5 minutes, alarm and
stop. 2 minutes and 50 seconds later, resume automatically,
if it occurs 3 times in an hour, conrm the failure.
Resumable
Resumable
Resumable
Resumable
Resumable
Resumable
Resumable
Once
conrmation,
un-resumable
Once
conrmation,
un-resumable
Once
conrmation,
un-resumable
Once
conrmation,
un-resumable
Once
conrmation,
un-resumable
20
Page 23
Failure code
Digital tube
indication
on master
unit
39-139-1
39-239-2
4040
4343
4646
5353
5454
5757
5858
5959
6060
6161
Indication
on wired
controller
(hex)
Failure code
denition
Compression ratio
too high protection
Compression ratio
too low protection
High pressure
sensor Pd too high
protection
Discharging temp.
sensor Td too low
protection
Communication
with inverter board
failure
CT current is too
low or current
sensor fault
Valve plate module
communication
fault
Communication
failure between
valve plate
module and host
computer(sending
by valve plate)
Tc1 temp sensor
of valve plate
error(sending by
valve plate)
Tc2 temp sensor
of valve plate
error(sending by
valve plate)
Valve plate module
error(sending by
valve plate)
Valve plate module
error(sending by
valve plate)
Failure descriptionRemarks
After compressor is running, compression ratio 8. for
continuous 5 minutes stop and alarm.2 minutes and 50
seconds later, resume automatically, if it occurs 3 times in
an hour, conrm the failure.
In normal operation, compression ratio <1.8 for continuous
5 minutes stop and alarm.2 minutes and 1 seconds later,
resume automatically, if it occurs 3 times in an hour, conrm
the failure.
In normal operation, Pd>=4.15Mpa for continuous 50ms,
alarm and stop. 2 minutes and 50 seconds later, resume
automatically, if it occurs 3 times in an hour, conrm the
failure.
In normal operation, if Td<CT+50°F
(10°C) for continuous 5 minutes, the unit stops and alarms.2
minutes and 50 seconds later, resume automatically. If it
occurs 3 times in an hour, conrm the failure. After xed
frequency compressor alarms, inverter compressor will
continue to run. If xed frequency compressor has been
locked for 3 times, the unit will stop and alarm.
No communication within 30 seconds continuouslyResumable
3 minutes after recovery
Cannot receive valve plate module signal in 200 continuous
rounds or receive wrong data,recover automatically when
received right data.
Communication failure between valve plate module and
host computer
Tc1 temp. sensor cannot connect with valve plate moduleResumable
Tc2 temp. sensor cannot connect with valve plate moduleResumable
ReservedResumable
ReservedResumable
Once
conrmation,
un-resumable
Once
conrmation,
un-resumable
Once
conrmation,
un-resumable
Once
conrmation,
un-resumable
3 times in an
hour, conrm
failure; once
conrmation,
un-resumable
Resumable
Resumable
21
Page 24
Failure code
Digital tube
indication
on master
unit
6262
6363
6464
71-071-0
71-171-1
7575-0
75-475-4
7878Lack of refrigerant
8181
8282
8383
108108
109109
110110
111111
112112
113113
Indication
on wired
controller
(hex)
Failure code
denition
Valve plate module
error(sending by
valve plate)
Valve plate dial
setting error
CT current is too
high
Upper DC motor
blocked
Lower DC motor
blocked
No pressure drop
between high
pressure and low
pressure
Too small pressure
drop between high
pressure and low
pressure
IPM modular temp.
too high protection
Compressor
current protection
Outdoor model set
error
Transient over
current in IPM
module rectier
side software
Current detection
circuit abnormality
IPM modular
protection (F0)
Compressor out of
control
Radiator of
transducer temp.
too high
Transducer
overload
Failure descriptionRemarks
ReservedResumable
No valve plate module dial but the valve plate module is
detected.
CT current exceeds specied value, 3 minutes after
recovery
Running at speed below 20rpm for 30s, or at speed of
70% lower than the target for 2 minutes, 2 minutes and 50
seconds later after stop, resume automatically. It occurs 3
times in an hour, conrm the failure.
In 1 minute after INV compressor starts up, Pd-Ps≤0.1MPa,
then stop. 180 seconds later, resume automatically. If it
occurs 3 times in an hour, conrm the failure.
If Pd-Ps≤0.2MPa for 5 minutes, the outdoor unit protection
stop.
• 3 minutes after stopping protection, restart. If it occurs 3
times in an hour, conrm the failure.
Compressor running in cooling mode, Ps<0.2MPa for 30
minutes; compressor running in heating mode, Tsi - ET>20;
LEV will fully open for 60 minutes, the unit will output lack of
refrigerant alarm,unit will not stop.
IPM modular temp.≥185°F(85°C)
Compressor current exceeds specied value, 3 minutes
after recovery
Model and the number of fans do not matchUn-resumable
Transient over current in IPM module rectier side software
Current detection circuit abnormality
IPM modular over current, in short circuit, over heat, voltage
too low of control circuit.
In the course of compressor startup or running, the unit can
not detect the rotor position, or not connecting compressor.
Radiator temp. too high
Output current of transducer is too high
Once
conrmation,
un-resumable
3 times in an
hour, conrm
failure; once
conrmation,
un-resumable
Once
conrmation,
un-resumable
Once
conrmed,
unresumable
Once
conrmed,
unresumable
--
3 times in an
hour, conrm
failure; once
conrmation,
un-resumable
3 times in an
hour, conrm
failure; once
conrmation,
un-resumable
22
Page 25
Failure code
Digital tube
indication
on master
unit
114114
115115
116116
117117
118118
119119
120120
121121
122122
123123
Indication
on wired
controller
(hex)
Failure code denitionFailure descriptionRemarks
Voltage too low of DC bus
line of transducer
Voltage too high of DC
bus line of transducer
Communication abnormal
between transducer and
control PCB
Transducer over current
(software)
Compressor startup
failure
Detecting circuit of
transducer current is
abnormal
Power supply of
transducer abnormal
Power supply of inverter
board is abnormal
Radiator temp.sensor of
transducer abnormal
Transient over current in
IPM module rectier side
hardware
Voltage of power source is too low
Voltage of power source is too high
Communication is disconnectedResumable
Compressor startup fails for 5 times continuously, or
compressor is running down till stops caused by over
current or over heat
The sensor used for current detecting of transducer
is abnormal, disconnected or incorrectly connection
Current detection sensor of frequency controller is
abnormal or unconnected or connected wrongly.
Power supply of transducer is broken down instantly
Power supply of inverter board is broken down
instantly
Resistor of temp.sensor abnormal or temp.sensor
disconnected
Transient over current in IPM module rectier side
hardware
3 times in an
hour, conrm
failure; once
conrmation,
un-resumable
3 times in an
hour, conrm
failure; once
conrmation,
un-resumable
3 times in an
hour, conrm
failure; once
conrmation,
un-resumable
When there is no failure, if the starting condition can not be met, digital tube on master unit will display stand-by code:
555.0
555.3
Indoor failure code list
Indication on
Standby state of capacity
overmatch
Outdoor ambient temperature
too high (heating)
Outdoor ambient temperature
too high or too low (cooling)
Indication on wired
master unit
01011Indoor ambient temp. sensor Ta failure
02022Indoor coil temp. sensor Tc1 failure
03033Indoor coil temp. sensor Tc2 failure
04044Indoor TW sensor failure
05055Indoor EEPROM failure
06066Communication between indoor and outdoor failure
07077Communication between indoor and wired controller failure
08088Indoor drainage failure
09099Indoor repeated address
0A0A10Indoor repeated central control address
Outdoor
failure code
controller
Outdoor failure
code
When capacity is over 130% or lower than 50%, the system is
standby.
Ta>80.6°F, Standby
Ta>129.2°F or Ta<14°F, Standby
Flash times of LED5 on
indoor PCB/timer LED
on remote receiver
20Outdoor corresponding failure
Failure code denition
Resumable555.1
23
Page 26
Trial operation and the performance
Conrm the type of outdoor machine and the number of inside machine
• After installation, please conrm that the outdoor computer board BM1_1 is in the 0 state and then check the digital
display. If the number of indoor units, the outdoor unit type and the power supply voltage is correct, change the BM1_1
dial to the 1 state. If it is not correct, please check the dial machine communication code and models, do not force the
BM1_1 dial to the 1 state, it may cause system failure.
5-minute delay function
• If starting up the unit after being powered off, the compressor will run about 5 minutes later against being damaged.
Cooling/heating operation
• Indoor units can be controlled individually, but cannot run in cool and heat mode at the same time. If cool mode and the
heat mode set at the same time, the unit set last will be set to standby, and the unit set rst will run normally. If the A/C
manager sets the unit to allow only cooling or only heating mode, the unit can not run at the other modes.
Heating mode characteristic
• While operating, if the outdoor temp. rises, the indoor fan motor will run at a low speed or stop.
Defrosting in heating mode
• In heating mode, defrosting will affect the heating efciency. The unit will defrost for about 2~10 minutes automatically.
During defrost, any frost will melt and condensate will ow from outdoor unit. While defrosting vapor will appear at the
outdoor unit, which is normal. The indoor motor will run at low speed or stop, and the outdoor motor will stop.
The unit operation condition
• Please only operate the unit under the specied temperature range. If operating outside of the range, protection modes
will cause the unit to stop operating.
• The relative humidity should be lower than 80%. If the unit runs while the humidity is over 80% for a long period, the
dew on the unit will drop down and vapor will be blown from air outlet.
Protection device (such as high pressure switch)
• The unit has a high pressure switch which can stop system operation to protect the unit from damage. When the high
pressure switch activates, cooling/heating mode will stop but the running LED on the wired controller will still be lit. The
wired controller will also display an error code. The high pressure switch can be triggered by the following:
In cooling mode, air outlet and air inlet of the outdoor unit are clogged.
In heating mode, the indoor lter is full of dust; indoor air outlet is clogged.
When the protection mode goes off, please turn off the power and re-start the unit after eliminating the problem.
When power failure
• When there is a power failure while the unit is running, all the operations will stop.
• After being powered again, if the re-start up function is enabled, the unit can resume to the last state before losing
power; if the re-satrt up function is disabled, the unit needs to be switched on again manually.
• When abnormal operation occurs while running because of the storms, radio interference, etc, please turn off the power
source. After eliminating the interference, press the "ON/OFF" button to start up the unit again.
Heating capacity
• A heat pump in heating mode absorbs the outdoor heat energy and releases it indoor. As the outdoor temperature goes
down, the heating capacity will decrease.
System marks
• When multiple MRVII-S systems are installed, to identify the matching outdoor and indoor, please label on the outdoor
electric control box cover to indicate the connected indoor unit as shown in the below gure:
Indoor model:
Room No.
e.g. Indoor A, system 1, Floor 2 2F-1A
24
Page 27
Trial operation and the performance
Trial operation
• Before trial operation:
Before being powered on, measure the resistance between the power terminal block (live wire and neutral wire) and
the ground point with a multimeter. Check if it is over 1M Ω. If it is not, the unit will not operate.
To protect the compressor, power the outdoor unit for at least 12 hours before running the unit. If the crankcase
heater is not powered on for 6 hours, the compressor will not work.
Conrm the bottom of the compressor is getting hot.
Except for when there is only one master unit connected (no slave unit), for all other conditions, fully open the outdoor
service valves (gas side, liquid side). If the unit is operated without opening the valves, compressor failure will occur.
Conrm all indoor units are powered. If not, water leakage will occur.
Measure the system pressure while the unit is operating.
• Trial operation
During trial operation, refer to the information in the performance section. If the unit can not start up at the current
room temperature, enter trial operation at the outdoor unit.
25
Page 28
Qingdao Haier Air Conditioner Electric Co.,Ltd.
Haier Industrial Park,Qianwangang Road,Eco-Tech Development Zone,Qingdao 266555,
Shandong,P.R.C.