Haier HSU 24H03Z, HSU 24C03Z Schematic

Page 1
Domestic Air Conditioner
SERVICE MANUAL
Models :
HSU-24H03/Z HSU-24C03/Z
l Features
l
Comfortable:wide-angle airflow
l
Health air purifying Quiet operation
l l
Serial Number: 00105 5
Versio n:00.00 Edition:
5
2005-5-21
Page 2
1
Domestic Air Conditioner
Model:
HSU-24H03/Z HSU-24C03/Z
Content
1. Description of product model coding and series introduction
2. Specifications
3. Curves of performance
4. Description,net dimensions and functions of main component s and accessories
5. Knock-down drawings and part lists
6. Brief introduction to electrical control functions
7. Abnormity diagnose
8. Wiring diagram
9. Circuit diagram
Trouble shooting
10.
11. Refrigerating cycle diagram
12. Noise level test chart and air veloc ity distribution
13. Installation manual
Page 3
Domestic Air Conditioner
Model:
HSU-24H03/Z HSU-24C03/Z
DESCRIPTION OF
PRODUCT MODEL CODING
& SERIES INTRODUCTION
2
Page 4
3
A. Description of coding rules of unit model
Domestic Air Conditioner
Coding rules and descriptions are as follows:
1
2
3
4
5
6
7
8
Applicable frequency:0(50HZ),1(60HZ)
Developing sequence :A,B,C,D...
Function code
Nominal cooling capacity (BTU/h)with the first two numbers based on thousand unit
Model:
9
10 11
HSU-24H03/Z HSU-24C03/Z
Refrigerant type:R1(R407C),R2(R410A)
Applicable voltage:3(220~230V),4(240V)
L/C-cooling only R/H-heat pump E-electric aided heating
The structure code of indoor & outdoor unit:
S(wall-mounted),W(window type),P (cabinet type)
H-Abbreviation of Haier
Examples: HSU-24H03/Z,It represents wall-mounted split type heat pump air conditioner.The cooling capacity is 24000BTU/h,and the power supply is 220-230V/50Hz,”Z” means the developing
sequence.
B.Standard Situation/Conditions
No.
1
2
3
Operating condition
Norminal cooling
Norminal heating
Norminal electrical heating
indoor air status
DBOC WBOC
27OC
20OC
---
19OC 35OC 24OC
15OC
--- ---
outdoor air status
DBOC WBOC
7OC 6OC
---
4
Page 5
C.Series brief introduction
1.High energy efficient
Domestic Air Conditioner
Model:
HSU-24H03/Z HSU-24C03/Z
The design of inner-grooved copper tube greatly increases the refrigerant contact area and the
efficiency of cooling/heating functions.Using the R410A refrigerant and the refrigerating system optimizing design make both the EER and COP reach the B class according to the european energy efficient standard.
2.Comfortable:wide-angle airflow The vertical dual-flap and horizontal wide-angle louvers ensure the cool/warm air reaches every corner of the room.
3.Health air purifying An air purifying filter with deodorizing and disinfecting functions keeps the air clean and users healthy.
4.Quiet operation Fan with random-pitched blades. Random-pitched blades help reduce operating noise while maintaining a high airflow rate.
5.Convenience Auto restart and washable panel: The grille can be removed easily and washed when necessary.Any series have the function then even if the power falls when the unit is operating unit will automatically return to the operating settings in use before the power failure when power is restored.
6.Wide variety of functions 24-Hour Timer: 24-hour timer allows users to select the exact time they would like the air conditioner to turn on and to turn off.Timers on previous models operation based on the number of hours of desired operation.
7.Night-set models When the air conditioner is operating on the timer-off circuit.The preset room temperature gradually rises(going down in heating)before the unit stops as shown
below.Users can sleep
comfortably without sudden change in temperature.
8.Program”dry” This function automatically reduces the level of humidity while maintaining the preset indoor
temperature.
4
Page 6
Domestic Air Conditioner
Model:
HSU-24H03/Z HSU-24C03/Z
SPECIFICATIONS
5
Page 7
Model:
HSU-24H03/Z
Cooling capacity(W) Cooling coefficient(W/W)
Cooling power input(W)
Moiture removal(m /h)
3
Operating voltage range
O
C
Operating temp. range
( Variation of temp. adjust
Climate type:
)
Indoor unit noise
(
)
(A
B
d
(cooling) Indoor unit noise
)
)
(A
(
B
d
(heating)
)
(
Net dimensions
Packaging dimensions
mm
(
mm
(indoor unit)
Net/gross weight (kg)
(indoor unit)
Max. mounting height
difference(m)
Refrigerant charge(g)
(R22)
Frequency of filter cleaning Compressor model
Compressor oil charge
(cc)
Max . length of connecting
(m)
pipe
Tube type
Fan speed(H/M/L)(r/min)
(indoor unit)
Fan speed(r/min)
cool
heat
(outdoor unit)
Cut-off vavle(inch)
two-way
three-way
Max. operating pressure at
warm side(Mpa)
Domestic Air Conditioner
Model:
HSU-24H03/Z HSU-24C03/Z
6800
2.52
2700
3
-7-43 +
1
-
2.3X10
V( )
220-230~
)
O
C
(
)
T1
47/45/43
48/46/44
1155x308x224
)
1231x372x300
17/20.5
5
2300
Once/2 weeks
THU33
800
15
TP2Y
1320/1260/1180 1320/1260/1180
1050
1/4
1/2
2.8
Heating capacity(W)
Heating coefficient(W/W)
Heating power input(W)
Frequency range(Hz) Refrigerant type
Air sending angle Fan type
indoor unit
outdoor unit
Class of electric shock
)
)
A
(
Outdoor unit noise (cooling)
Outdoor unit noise
(
B
d
)
)
A
(
(
B
d
(heating) Net dimensions
(
mm
)
(outdoor unit)(indoor unit)
Packaging dimensions
(
mm
)
(outdoor unit)
Net/gross weight (kg)
(outdoor unit)
Piling layers
indoor unit
outdoor unit
Current entering side (indoor/outdoor)
Max. refrigerant charge
(g)
Compressor manufacturer Compressor protector type
drain hose
length(mm)
diametre(mm)
Type of tube of evaporator
and condenser
Size of tube of evaporator
and condenser(mm)
Appearance features of indoor
unit
Appearance features of outdoor
unit
Max. operating pressure at
cool side(Mpa)
7600
2.62 2900
50
R22
O
60
Cross flow fan
Axial flow fan
I
58/52
58/52
860x308x730
995x420x815
69/77
8
4
outdoor
2400
SHANGHAIRILI
internal
2000
16
Internal treaded
O7&O9.52
plastic
metal
2.8
6
Page 8
Model:
HSU-24C03/Z
Cooling capacity(W) Cooling coefficient(W/W)
Cooling power input(W)
Moiture removal(m /h)
3
Operating voltage range
O
C
Operating temp. range
( Variation of temp. adjust
Climate type:
)
Indoor unit noise
(
)
(A
B
d
(cooling) Indoor unit noise
)
)
(A
(
B
d
(heating)
)
(
Net dimensions
Packaging dimensions
mm
(
mm
(indoor unit)
Net/gross weight (kg)
(indoor unit)
Max. mounting height
difference(m)
Refrigerant charge(g)
(R22)
Frequency of filter cleaning Compressor model
Compressor oil charge
(cc)
Max . length of connecting
(m)
pipe
Tube type
Fan speed(H/M/L)(r/min)
(indoor unit)
Fan speed(r/min)
cool
heat
(outdoor unit)
Cut-off vavle(inch)
two-way
three-way
Max. operating pressure at warm side(Mpa)
Domestic Air Conditioner
Model:
HSU-24H03/Z HSU-24C03/Z
6800
2.52
2700
3
-7-43 +
1
-
2.3X10
V( )
220-230~
)
O
C
(
)
T1
48/44/38
----
1155x308x224
)
1231x372x300
17/20.5
5
2200
Once/2 weeks
THU33
800
15
TP2Y
1320/1260/1180
1050
1/4
1/2
0.65
Heating capacity(W)
Heating coefficient(W/W)
Heating power input(W)
Frequency range(Hz) Refrigerant type
Air sending angle Fan type
indoor unit
outdoor unit
Class of electric shock
)
)
A
(
Outdoor unit noise (cooling)
Outdoor unit noise
(
B
d
)
)
A
(
(
B
d
(heating) Net dimensions
(
mm
)
(outdoor unit)(indoor unit)
Packaging dimensions
(
mm
)
(outdoor unit)
Net/gross weight (kg)
(outdoor unit)
Piling layers
indoor unit
outdoor unit
Current entering side (indoor/outdoor)
Max. refrigerant charge
(g)
Compressor manufacturer Compressor protector type
drain hose
length(mm)
diametre(mm)
Type of tube of evaporator
and condenser
Size of tube of evaporator
and condenser(mm)
Appearance features of indoor
unit
Appearance features of outdoor
unit
Max. operating pressure at
cool side(Mpa)
----
----
50
R22
O
60
Cross flow fan
Axial flow fan
I
58/52
----
860x308x730
995x420x815
69/77
8
4
outdoor
2400
SHANGHAIRILI
internal
2000
16
Internal treaded
O7&O9.52
plastic
metal
2.8
7
Page 9
8
Domestic Air Conditioner
Model:
HSU-24H03/Z HSU-24C03/Z
CURVES OF PERFORMANCE
OF COMPRESSOR
Page 10
5
PERFORMANCE CURVE
160 150 140 130 120 110 100
90
FLOW RATE (kg/h)
80
-5 0 5 10
2600
Domestic Air Conditioner
Model: HSU-24C03/Z
Model: HSU-24H03/Z
220V-50Hz-1 PHASE SUCTION GAS TEMP.---35℃ UNDER COOL-----------8.3℃ AMBIENT TEMP.---------3 RUNNING CAPACITOR--55μF
℃
45
55
50
60
60
)
W
(
INPUT
)
W
(
CAPACITY
2400
2200
2000
1800
)
A
(
CURRENT
8500 8000 7500 7000 6500 6000 5500 5000 4500 4000
-5 0 5 10
13.0
12.0
11.0
10.0
9.0
8.0
-5 0 5 10
-5 0 5 10
55
50
45
60
55
50
45
45
50
55 60
)
℃
CONDENSING TEMP. (
EVAPERATING TEMP. (℃)
9
Page 11
Domestic Air Conditioner
Model: HSU-24C03/Z Model: HSU-24H03/Z
DESCRIPTION,DIMENSION AND
FUNCTION OF MAIN COMPONENTS AND ACCESSORIES
10
Page 12
Indoor Unit
Inlet grill
Air filter
Vertical flap
Use remote controller to adjust up and down air flow. (Don't adjust it manually.)
Domestic Air Conditioner
Power indicator
Lights up when unit starts.
Model: HSU-24C03/Z Model: HSU-24H03/Z
Timer mode indicator
Lights up when Timer operation is selected.
Operation mode indicator
Lights up during compressor running .
11
Page 13
Domestic Air Conditioner
Model: HSU-24C03/Z Model: HSU-24H03/Z
KNOCK-DOWN DRAWINGS
12
Page 14
13
Domestic Air Conditioner
Model:
HSU-24H03/Z HSU-24C03/Z
Page 15
14
No. in
exploded
view
Spare parts number
Spare parts description in
english
Model Qty Price list
Model:
Failure
rate(%)
HSU-24H03/Z HSU-24C03/ZDomestic Air Conditioner
Edition:2005/05/21 The proportion of
the spare part
stock
Remark
1 001A1231360 Front grillle HSU-24H03/Z HSU-24C03/Z 1* 2 0010800070 Front panel assy. 3 001A2400136 Air filter 4 0010802048 Seperating plate(L) 5 0010704157 Heat exchanger assy. 6 001A0300060 Bearing 7 001A2300098 Fan 8 001A1301857 Left support
9 0010200074 Cushion 10 0010200075 Cushion 11 001A1301856 Mounting plate 12 001A14311029 Fix plate 13 001A1231361 Bottom plate 14 001A14311047 Control box 15 001A3900059 Temperature sensor 16 0010401745 Displaying panel 17 001A3000273 Swing motor 18 001A14361036 Support plate 19 001A0900011 Drain hose
HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 3* HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1* HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1* HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1* HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1
20 0010800156 Drain pan assy. 21 001A14361035 Link 22 001A14431044 Bearing support 23 001A14361031 Vane 24 001A1231357 Flap 25 001A1231358 Flap 26 0010200036 Wnd shield 27 001A14361030 Dew-prevent 28 001A1741744 Heat-insulation tube 29 001A14311041 Seperating plate(R ) 30 0010401531 PC board 30 0010401590 PC board 31 —————— Power switch 32 0010401536 Terminal block 33 —————— Switch 34 001A14311043 Motor cover 35 0010400576 Motor 36 001A1301858 Right support
HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 10 HSU-24H03/Z HSU-24C03/Z 15 HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1 HSU-24H03/Z HSU-24C03/Z 1
HSU-24H03/Z 1* HSU-24C03/Z 1*
HSU-24H03/Z HSU-24C03/Z —— HSU-24H03/Z HSU-24C04/Z 1 HSU-24H03/Z HSU-24C05/Z —— HSU-24H03/Z HSU-24C06/Z 1 HSU-24H03/Z HSU-24C07/Z 1* HSU-24H03/Z HSU-24C08/Z 1
37 0010401599 Remote controller 37 0010401603 Remote controller 38 —————— Drain hose
HSU-24H03/Z HSU-24C09/Z 1* HSU-24H03/Z HSU-24C10/Z 1* HSU-24H03/Z HSU-24C11/Z ——
Page 16
15
Domestic Air Conditioner
Model: HSU-24C03/Z
Model: HSU-24H03/Z
Page 17
The
p
r
16
c Air Conditioner
No. in
exploded
view
1 001A1236199 Front grille HSU-24H03/Z HSU-24C03/Z 1 2 001A1101106 Front panel HSU-24H03/Z HSU-24C03/Z 1 3 0010202161 Fan HSU-24H03/Z HSU-24C03/Z 1 4 0010402046 Motor HSU-24H03/Z 1 4 0010402157 Motor HSU-24C03/Z 1 5 001A1301427 Motor support assy. HSU-24H03/Z 1 5 0010801921 Motor support assy. HSU-24C03/Z 1 6 001A5701063 Heat exchanger fixing HSU-24H03/Z HSU-24C03/Z 1 7 0010704366 Heat exchanger assy. HSU-24H03/Z HSU-24C03/Z 1 8 —— Temperature sensor sup
9 001A1231361 Back grille HSU-24H03/Z HSU-24C03/Z 1 10 001A0100656 Side panel (L) assy. HSU-24H03/Z HSU-24C03/Z 1 11 001A1436182 Handle HSU-24H03/Z HSU-24C03/Z 1 12 001A0100651 Top panel assy. HSU-24H03/Z HSU-24C03/Z 1 13 001A0100652 Side panel (R) assy. HSU-24H03/Z HSU-24C03/Z 1 14 001A0100125 Wiring cover assy. HSU-24H03/Z HSU-24C03/Z 1 15 001A2500015 Four-way valve HSU-24H03/Z 1 16 0010703916 Capillary tube assy. HSU-24H03/Z 1 16 0010704436 Capillary tube assy. HSU-24C03/Z 1 17 0010702454 Two-way stop valve HSU-24H03/Z HSU-24C03/Z 1 18 0010702420 Three-way stop valve HSU-24H03/Z HSU-24C03/Z 1 19 0010402047 Wires HSU-24H03/Z HSU-24C03/Z 1 20 0010702609 Compressor HSU-24H03/Z HSU-24C03/Z 1 21 —— Compressor heating-set HSU-24H03/Z HSU-24C03/Z —— 22 001A1762341 Cushion HSU-24H03/Z HSU-24C03/Z 1 23 —— Wires HSU-24H03/Z HSU-24C03/Z —— 24 0010250255 Cushin HSU-24H03/Z HSU-24C03/Z 1 25 ---- PC board HSU-24H03/Z HSU-24C03/Z 1 26 0010806226 Controller box HSU-24H03/Z HSU-24C03/Z 1 27 001A4000107 Terminal block HSU-24H03/Z HSU-24C03/Z 1 28 001A2500004 4-way valve coil HSU-24H03/Z HSU-24C03/Z 1 29 —— Transformer HSU-24H03/Z HSU-24C03/Z —— 30 —— Sensor HSU-24H03/Z HSU-24C03/Z —— 31 001A4000011 Terminal block HSU-24H03/Z HSU-24C03/Z 1 32 001A1301418 Tube plate(R ) HSU-24H03/Z HSU-24C03/Z 1 33 0010400334 AC contactor HSU-24H03/Z HSU-24C03/Z 1 34 0010100001 Capacitor clip HSU-24H03/Z HSU-24C03/Z 1 35 0010401954 Capacitor for compresso 36 001A3600218 Capacitor for motor HSU-24H03/Z HSU-24C03/Z 1 37 001A0100753 Seperating plate assy. HSU-24H03/Z HSU-24C03/Z 1 38 001A1101110 Bottom plate assy. HSU-24H03/Z HSU-24C03/Z 1
Spare parts
number
Spare parts description
in english
Model
HSU-24H03/Z HSU-24C03/Z ——
HSU-24H03/Z HSU-24C03/Z 1
Qty
Price
list
HSU-24H03/Z
HSU-24C03/ZModel:Domesti
Edition:2005/03/31
Failure rate(%)
proport
ion of
Rem
ark
Page 18
17
REMOT
Domestic Air Conditioner
E CONTROLLER
Model: HSU-24C03/Z Model: HSU-24H03/Z
FUNCTIONS CONVERTION
30
Page 19
18
Domestic Air Conditioner
Model: HSU-24C03/Z Model: HSU-24H03/Z
Brief introduction to electrical control functions
BRIEF INTRODUCTION TO
ELECTRICAL CONTROL FUNCTIONS
41
Page 20
room ambient temperature.
compressor
four-way valve
outdoor fan
163838
38
19
Domestic Air Conditioner
Model: HSU-24C03/Z Model: HSU-24H03/Z
1. Introduction of electric control function
1.1 Brief introduction of electric control function (1) Auto running (available for cooling and heating type) When Auto running starts for the first time, selection of running mode follows the conditions below:
Tr > 23℃ Select cooling mode Set temperature: 26℃  Tr≤23℃  Select heating mode (with temperature compensation) Set temperature: 23℃ 
In auto mode, running mode shifts between cooling and heating with the variation of
(2) Room temperature control Compressor ON Compressor OFF
Heating
Set temperature
Compressor OFF Compressor ON
Cooling
Set temperature
(3) Dry running Compressor, outdoor fan and indoor fan run as follows (Tr, room temperature, Ts, set temperature). When dry mode starts for the first time, compressor, outdoor fan and indoor fan will run following the rules below:
① Tr>Ts+2℃, compressor, outdoor fan run successively, indoor fan run at set speed,
this working area is defined as area A.
② Ts≤Tr≤Ts+2℃, compressor, outdoor fan will run for 10 minutes and stop for 6
minutes, indoor fan will run at low speed, this working area is defined as area B.
③ Tr<Ts, compressor, outdoor fan will stop running, indoor fan will run at low
speed, this area is defined as area C. In dry mode, system will shift between area A, B and C variation with room ambient temperature. When Tr<Ts+1, system will shift from area A to B; when Tr>Ts, system will shift from area C to B; when Tr>Ts+3, system will shift from B to A; when Tr<Ts-1, system will shift from area A to C.
(4) Cool- air proof in heating In heating, every time starts compressor, indoor fan will stop running if room coil temperature is less than 28℃; indoor fan will run at low speed if room coil temperature is
equal to or more than 28℃ and less than 38℃; indoor fan will run at set fan speed if room coil temperature is more than 38℃ or compressor has run more than 4 minutes.
(5) Residual heat air discharging in heating In heating, compressor stops, indoor fan stops after a 30-second low running. (6) Defrosting control
Page 21
Indoor fan
Run on cool air
-
proof
4-way
0
20
(1)
Domestic Air Conditioner
a. After the state of Tp-Tr<18℃ is continued for 5 minutes, the accumulated
running time of the compressor exceeds 45 minutes, the continuous running time of the compressor exceeds 20 minutes;
b. The accumulated running time of the compressor exceeds 3 hours, the
continuous running time of the compressor exceeds 20 minutes, indoor unit’s Tp <42℃;
c. The continuous running time of the compressor exceeds 20 minutes, the
temperature of indoor coil pipe decreases 1℃ every 6 minutes, which lasts for more than 3 times, indoor unit’s Tp <42 ℃;
d. When the indoor unit is in the state of overload protection and the outdoor unit
ceases, when the rerunning time of outdoor unit exceeds10 minutes, the accumulated running time of the compressor exceeds 45 minutes, the continuous running time of the compressor is over 20 minutes, and Tp <42℃.
Defrosting will begin if one of the above conditions is met.
(2) Defrosting finishing condition:
If the defrosting time exceeds 9 minutes, the original heating state will be
resumed;
Defrosting process is as follows:
Compressor 
Outdoor fan
55s
9min
1min
Model: HSU-24C03/Z Model: HSU-24H03/Z
55s
1min
Page 22
21
Domestic Air Conditioner
Model: HSU-24C03/Z Model: HSU-24H03/Z
(7) Temperature compensation. Auto temperature compensation condition: when reach temperature condition, cut-off time of compressor is less than 5 minutes. Temperature compensation rules are as follows: When Ts+4-Tr≥2℃, ΔT=2℃; when Ts+4-Tr=1℃, ΔT=1℃;
When Ts+4-Tr≤0℃, ΔT=0℃.  When heating mode starts for the first time, ΔT=0℃. With temperature compensation function, if push temperature increasing and decreasing button on remote controller, ΔT=0; if push temperature increasing button on remote controller, ΔT will maintain previous value. (8) Overcool protection in cooling.
In cooling, 9 minutes after the start of compressor, check room coil temperature. when indoor coil temperature is less than 0℃,compressor and outdoor fan will stop running.
When the two following conditions are meet, compressor and outdoor fan will restart:
① Cut-off time is more than 3 minutes; ② Indoor coil temperature is more than 7℃.
(9) 3-minutes delay When compressor stop running arose from transmitter OFF, ON-OFF or breakdown, compressor will stop for 3-minutes. (10) Overcharging protection in heating Overcharging protection: in HEAT mode, if room coil temperature>56℃, outdoor fan will
stop running and resume when inner coil temperature ≤ 53 ℃ ;if room coil temperature>68℃ and last 10 seconds, compressor and outdoor fan will strop running; compressor and outdoor fan will resume normal operation when room coil temperature<46℃. 
Over-current protection: in HEAT mode, outdoor fan will stop running if working current measured with current transformer is continuously more than 14A in 2 seconds; if current is less than 13A, outdoor fan will resume operation; if working current is more than 26A after a 5-minutes running and last 10 seconds, compressor will stop and resume normal operation 3 minutes after; indoor fan will run on cool-air proof condition. If over-current protection occurs twice in 30 minutes, compressor won’t restart any more. System will turn into over-current fault alarm. (11) Power failure compensation function. Power failure compensation function will be set by remote controller. To cancel power failure function, push SLEEP button 10 times in 5 seconds, buzzer will sound twice "BEEP"; To set power failure function, push SLEEP button 10 times in 5 seconds, buzzer will sound four times "BEEP". When main panel has power failure compensation function, it will memorize running parameter in the case of sudden power failure (not cut by remote controller), if unit didn’t receive remote signal 3 minutes after power resume, it will call automatically memory information and continue to run in previous state. Memory includes operation mode, fan speed, set temperature, air door state, health; timing and sleep mode not included. (12) Emergency switch and forced cooling. Push down emergency ON/OFF button, buzzer will sound once "beep", release it 5 seconds after, unit will perform starting function; if ON/OFF button is pressed continuously for more than 5 seconds, buzzer will sound twice "beep", and unit will perform forced cooling function. Here operational mode is set as cooling, fan speed is set as high; forced cooling will finish 30 minutes after. After having pushed down mode button, fan speed button, temperature increasing and decreasing button, sleep button,
Page 23
22
Domestic Air Conditioner
Model: HSU-22HC03/R2
WIRING DIAGRAM
47
Page 24
23
Domestic Air Conditioner
Model: HSU-24C03/Z Model: HSU-24H03/Z
WIRING DIAGRAM OF INDOOR UNIT
CN4
CN7
M
SW1
CN9CN8
ION GENERATOR
COMP
N
L
FAN MOTOR
M
CN1
CN2
CN3
REV
PCB
CN10
CN12
NOTING:
1
ONLY COOLING TYPE DOESN'T HAVE THE  DOTTED LINE. THE DASHED UNIT IS OPTIONAL UNIT.
2
1
2 3 4 5
TO OUTDOOR  UNIT
THE WIRING DIAGRAM FOR OUTDOOR UNIT IS ONLY FOR HSU-24H03/Z
WIRING DIAGRAM OF OUTDOOR UNIT
R:RED W:WHITE B:BLACK
THE WIRING DIAGRAM FOR OUTDOOR UNIT IS ONLY FOR HSU-24C03/Z
Page 25
24
CIRC
Domestic Air Conditioner
UIT DIAGRAM
Model: HSU-24C03/Z Model: HSU-24H03/Z
47
Page 26
27
25
Domestic Air Conditioner
Model: HSU-24C03/Z Model: HSU-24H03/Z
+12
远程通讯输入
CN3
+5
C11
104
CN4
加热带 外风机 四通阀
+12V
LED面板
REV
N
L
T3.15A 250VAC
R27 10K
DQ6 9014
R101
R45
5.1K
DQ3 9014
EZ1
C7
104
R11 10K
DL1
103N
L101
L102
L103
R102
IC4
T600D
C1
0.1UF/275V
IC7 LM358
DQ7
9014
C101
+5
3 1
2
LX1
LX102
C35 104
DQ2 9014
R47
5.1K
CN101
R28 10K
+12
C21 104
0.1UF/275VF1
10
C2
R52 10K
R26 10K
CN9
+5
NTC 5D-15
+12
R13 10K
DQ4 9014
+5R4610K R405.1K
R105.1K
DQ8
R48 R5.1K
9014
R25 R24 R23
R22220
D7
1N4148
C24
4.7UF/50V
R34
5.1K
R33 1K
7
11
DQ9
R49
5.1K
9014
220 220 220
+5
R12 10K
R541K
R29 1K
B1
KBJ406
C3
100UF/400V
12
C29 103
+5
13 14 15 16
M1
IC2 93C46
5 6 7 8
C22 104
C23 103
18
TOP226Y
D
C
S
DO4GND
DI
RS
SK
NC
CS
VCC
6
C34 103
R3010M
OSC
8MHZ
8
C19
103
31
C13
471/2KV
R1 10
C5
47UF/25V
3 2 1
风机
+5
R53 2K
+5 IC8
LM358
R57
100K/2W
C30
222/2KV
R31
+5
10K
C12
100UF/16V
1
P77
2
P76
3
P75
4
P74
5
P73
6
P72
7
P71
8
P70
9
P07
10
P06
11
P05
12
P04
13
P03
14
P02
15
P01
16
P00
17
TEST
18
RESET
19
XIN
20
XOUT VSS21VAREF
CN2
100UF/16V
D2
P6KE200
PC3 TLP521-1
1 2
R38
D6
1M
1N4148
36
IC1
TMP87PH46N
VCC
P22 P21 P20 P17 P16 P15 P14 P13 P12 P11 P10 P67 P66 P65 P64 P63 P62 P61 P60
C17
470UF/100V
470UF/100V
R3 10K
R551K
C14
R2 5.1K
D4 UF4005
4 3
+5
R32 51K
+5
42 41 40 39 38 37 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22
+5
C25 104
C18
+5
DQ1 9012
D8 1N4148
C4
0.1UF/50V
CN5
R15 51K
R39
5.1K
35
C33 104
+5
R44 10K
C15 104
VDD
R50 10K
BK-JN02
+5
LCD面板
CN6
C37
104
100UF/16V C36
J24
J
1 2 3 4 5 6 7
R59 1K
SW2
JSS 1271
+12
JK1
JQ1aP-12V
R563.3K
T1
39
IC3 ULN2003A
A1
Q1
A2
Q2
A3
Q3
A4
Q4
A5
Q5
A6
Q6
A7
Q7
GND8VCC
+5
R5810K
A
A-B码转换
B
CA1
IC5
TL431
104 R9
62K
D1 UF106
VDD
D5 BYW29-200F
+5
16 15 14 13 12 11 10
9
R36 51K
JTP 1236A
R14
SW1
10K
+5
R41 10K
J
4140
38 37
+12
C26 104
R8 510C16
应急按键
J19
R171K
R19 10K
R21 10K
R37 20K
C10
330UF/50V
+5
1
R51
5.1K
10K
R35
C6 104
+12
DQ5 2N5551
IC6
3
7805
1
C9 104
DC12V负离子发生器
XT
2P
R5 100
+5
R42 10K
LM2575-12
5
Vin
Vout
GND
2
D9 IN4007
+12V
CN1
PS144DP02B-T
+12
R4 1K
R43 10K
L2 331
R20 20K
L3331
R18 20K
4
2
+12
BUZ
L4
331
3
Z1 1N6189
+5
C8 220UF/16V
JK3 JQ1aP-12V
+12
+12
L1 101
C27
4.7UF/50V
C28
4.7UF/50V
+12
C20 104
CN1
N
L
JK2 G4A-1A-E
压机
步进电机
CN7
+5
室内环境温度
室内盘管温度
CN8
C31
1000UF/25V
AC220V负离子发生器
Page 27
26
Domestic Air Conditioner
Model: HSU-22HC03/R2
ABNORMALITY DIAGNOSING
47
Page 28
27
Domestic Air Conditioner
Model: HSU-24C03/Z Model: HSU-24H03/Z
For the abnormal phenomenon occurred, please conduct trouble analysis and troubleshooting according to the following table:
No Reason of trouble Phenomena Remarks
1 The sensor of indoor ambient
temperatureis in short circuit or broken circuit
2 The temperature sensor of
indoor coil pipe is in short circuit or broken circuit
The compressor indictor and
timing extinguish, running indicator flickers
The compressor indictor and timing indicator are on, and the running indicator flickers
indicator
and the
3 The indoormotoris damaged,or the
computer board is damaged
The power indicator and running indicator of indoor unit flicker twice, thepower indicator, running indicator and timing indicator flicker togetherfor 1 second,then repeating the cycle.
The motorhasno signal feedback of Hall unit
48
Page 29
28
Domestic Air Conditioner
Model: HSU-24H03/Z
HSU-24C03/Z
49
Page 30
29
Domestic Air Conditioner
Model: HSU-24C03/Z Model: HSU-24H03/Z
REFRIGERATING CYCLE DIAGRAM
50
Page 31
30
Domestic Air Conditioner
Model: HSU-24C03/Z Model: HSU-24H03/Z
Page 32
31
Domestic Air Conditioner
Model: HSU-24C03/Z Model: HSU-24H03/Z
INSTALLATION MANUAL
52
Page 33
32
26
Domestic Air Conditioner
Model: HSU-24C03/Z Model: HSU-24H03/Z
26
53
Page 34
33
Domestic Air Conditioner
Model: HSU-24C03/Z Model: HSU-24H03/Z
54
Page 35
553456
Page 36
35
Page 37
36
Page 38
37
58
Page 39
1.Cut pipe
3.Insert the flare nut
4.Flare pipe
2.Remove burs
Flare tool for R410A
Clutch-type
clutch-type(Rigid-type)
Conventional flare tool
Wing-nut type (Imperial-type)
0~0.5mm 1.0~1.5mm 1.5~2.0mm
38
Page 40
Domestic Air Conditioner
Model: HSU-24C03/Z Model: HSU-24H03/Z
39
Page 41
Sincere Forever
Haier Group
Haier Industrial Park, No.1, Haier Road
266101, Qingdao, China