1. Description of product model coding and series introduction
2. Specifications
3. Curves of performance
4. Description,net dimensions and functions of main component s
and accessories
5. Knock-down drawings and part lists
6. Brief introduction to electrical control functions
7. Abnormity diagnose
8. Wiring diagram
9. Circuit diagram
Trouble shooting
10.
11. Refrigerating cycle diagram
12. Noise level test chart and air veloc ity distribution
13. Installation manual
Page 3
Domestic Air Conditioner
Model:
HSU-24H03/Z
HSU-24C03/Z
DESCRIPTION OF
PRODUCT MODEL CODING
& SERIES INTRODUCTION
2
Page 4
3
A. Description of coding rules of unit model
Domestic Air Conditioner
Coding rules and descriptions are as follows:
1
2
3
4
5
6
7
8
Applicable frequency:0(50HZ),1(60HZ)
Developing sequence :A,B,C,D...
Function code
Nominal cooling capacity (BTU/h)with the first two
numbers based on thousand unit
Model:
9
1011
HSU-24H03/Z
HSU-24C03/Z
Refrigerant type:R1(R407C),R2(R410A)
Applicable voltage:3(220~230V),4(240V)
L/C-cooling only
R/H-heat pump
E-electric aided heating
The structure code of indoor & outdoor unit:
S(wall-mounted),W(window type),P (cabinet type)
H-Abbreviation of Haier
Examples:
HSU-24H03/Z,It represents wall-mounted split type heat pump air conditioner.The cooling
capacity is 24000BTU/h,and the power supply is 220-230V/50Hz,”Z” means the developing
sequence.
B.Standard Situation/Conditions
No.
1
2
3
Operating condition
Norminal cooling
Norminal heating
Norminal electrical
heating
indoor air status
DBOCWBOC
27OC
20OC
---
19OC35OC24OC
15OC
------
outdoor air status
DBOCWBOC
7OC6OC
---
4
Page 5
C.Series brief introduction
1.High energy efficient
Domestic Air Conditioner
Model:
HSU-24H03/Z
HSU-24C03/Z
The design of inner-grooved copper tube greatly increases the refrigerant contact area and the
efficiency of cooling/heating functions.Using the R410A refrigerant and the refrigerating system
optimizing design make both the EER and COP reach the B class according to the european
energy efficient standard.
2.Comfortable:wide-angle airflow
The vertical dual-flap and horizontal wide-angle louvers ensure the cool/warm air reaches every
corner of the room.
3.Health air purifying
An air purifying filter with deodorizing and disinfecting functions keeps the air clean and users
healthy.
4.Quiet operation
Fan with random-pitched blades.
Random-pitched blades help reduce operating noise while maintaining a high airflow rate.
5.Convenience
Auto restart and washable panel:
The grille can be removed easily and washed when necessary.Any series have the function then
even if the power falls when the unit is operating unit will automatically return to the operating
settings in use before the power failure when power is restored.
6.Wide variety of functions
24-Hour Timer:
24-hour timer allows users to select the exact time they would like the air conditioner to turn on
and to turn off.Timers on previous models operation based on the number of hours of desired
operation.
7.Night-set models
When the air conditioner is operating on the timer-off circuit.The preset room temperature
gradually rises(going down in heating)before the unit stops as shown
below.Users can sleep
comfortably without sudden change in temperature.
8.Program”dry”
This function automatically reduces the level of humidity while maintaining the preset indoor
temperature.
4
Page 6
Domestic Air Conditioner
Model:
HSU-24H03/Z
HSU-24C03/Z
SPECIFICATIONS
5
Page 7
Model:
HSU-24H03/Z
Cooling capacity(W)
Cooling coefficient(W/W)
Cooling power input(W)
Moiture removal(m /h)
3
Operating voltage range
O
C
Operating temp. range
(
Variation of temp. adjust
Climate type:
)
Indoor unit noise
(
)
(A
B
d
(cooling)
Indoor unit noise
)
)
(A
(
B
d
(heating)
)
(
Net dimensions
Packaging dimensions
mm
(
mm
(indoor unit)
Net/gross weight (kg)
(indoor unit)
Max. mounting height
difference(m)
Refrigerant charge(g)
(R22)
Frequency of filter cleaning
Compressor model
Compressor oil charge
(cc)
Max . length of connecting
(m)
pipe
Tube type
Fan speed(H/M/L)(r/min)
(indoor unit)
Fan speed(r/min)
cool
heat
(outdoor unit)
Cut-off vavle(inch)
two-way
three-way
Max. operating pressure at
warm side(Mpa)
Domestic Air Conditioner
Model:
HSU-24H03/Z
HSU-24C03/Z
6800
2.52
2700
3
-7-43
+
1
-
2.3X10
V( )
220-230~
)
O
C
(
)
T1
47/45/43
48/46/44
1155x308x224
)
1231x372x300
17/20.5
5
2300
Once/2 weeks
THU33
800
15
TP2Y
1320/1260/1180
1320/1260/1180
1050
1/4
1/2
2.8
Heating capacity(W)
Heating coefficient(W/W)
Heating power input(W)
Frequency range(Hz)
Refrigerant type
Air sending angle
Fan type
indoor unit
outdoor unit
Class of electric shock
)
)
A
(
Outdoor unit noise
(cooling)
Outdoor unit noise
(
B
d
)
)
A
(
(
B
d
(heating)
Net dimensions
(
mm
)
(outdoor unit)(indoor unit)
Packaging dimensions
(
mm
)
(outdoor unit)
Net/gross weight (kg)
(outdoor unit)
Piling layers
indoor unit
outdoor unit
Current entering side
(indoor/outdoor)
Max. refrigerant charge
(g)
Compressor manufacturer
Compressor protector type
drain hose
length(mm)
diametre(mm)
Type of tube of evaporator
and condenser
Size of tube of evaporator
and condenser(mm)
Appearance features of indoor
unit
Appearance features of outdoor
unit
Max. operating pressure at
cool side(Mpa)
7600
2.62
2900
50
R22
O
60
Cross flow fan
Axial flow fan
I
58/52
58/52
860x308x730
995x420x815
69/77
8
4
outdoor
2400
SHANGHAIRILI
internal
2000
16
Internal treaded
O7&O9.52
plastic
metal
2.8
6
Page 8
Model:
HSU-24C03/Z
Cooling capacity(W)
Cooling coefficient(W/W)
Cooling power input(W)
Moiture removal(m /h)
3
Operating voltage range
O
C
Operating temp. range
(
Variation of temp. adjust
Climate type:
)
Indoor unit noise
(
)
(A
B
d
(cooling)
Indoor unit noise
)
)
(A
(
B
d
(heating)
)
(
Net dimensions
Packaging dimensions
mm
(
mm
(indoor unit)
Net/gross weight (kg)
(indoor unit)
Max. mounting height
difference(m)
Refrigerant charge(g)
(R22)
Frequency of filter cleaning
Compressor model
Compressor oil charge
(cc)
Max . length of connecting
(m)
pipe
Tube type
Fan speed(H/M/L)(r/min)
(indoor unit)
Fan speed(r/min)
cool
heat
(outdoor unit)
Cut-off vavle(inch)
two-way
three-way
Max. operating pressure at
warm side(Mpa)
Domestic Air Conditioner
Model:
HSU-24H03/Z
HSU-24C03/Z
6800
2.52
2700
3
-7-43
+
1
-
2.3X10
V( )
220-230~
)
O
C
(
)
T1
48/44/38
----
1155x308x224
)
1231x372x300
17/20.5
5
2200
Once/2 weeks
THU33
800
15
TP2Y
1320/1260/1180
1050
1/4
1/2
0.65
Heating capacity(W)
Heating coefficient(W/W)
Heating power input(W)
Frequency range(Hz)
Refrigerant type
Air sending angle
Fan type
indoor unit
outdoor unit
Class of electric shock
)
)
A
(
Outdoor unit noise
(cooling)
Outdoor unit noise
(
B
d
)
)
A
(
(
B
d
(heating)
Net dimensions
(
mm
)
(outdoor unit)(indoor unit)
Packaging dimensions
(
mm
)
(outdoor unit)
Net/gross weight (kg)
(outdoor unit)
Piling layers
indoor unit
outdoor unit
Current entering side
(indoor/outdoor)
Max. refrigerant charge
(g)
Compressor manufacturer
Compressor protector type
drain hose
length(mm)
diametre(mm)
Type of tube of evaporator
and condenser
Size of tube of evaporator
and condenser(mm)
Appearance features of indoor
unit
Appearance features of outdoor
unit
Max. operating pressure at
cool side(Mpa)
----
----
50
R22
O
60
Cross flow fan
Axial flow fan
I
58/52
----
860x308x730
995x420x815
69/77
8
4
outdoor
2400
SHANGHAIRILI
internal
2000
16
Internal treaded
O7&O9.52
plastic
metal
2.8
7
Page 9
8
Domestic Air Conditioner
Model:
HSU-24H03/Z
HSU-24C03/Z
CURVES OF PERFORMANCE
OF COMPRESSOR
Page 10
5
PERFORMANCE CURVE
160
150
140
130
120
110
100
90
FLOW RATE (kg/h)
80
-50510
2600
Domestic Air Conditioner
Model: HSU-24C03/Z
Model: HSU-24H03/Z
220V-50Hz-1 PHASE
SUCTION GAS TEMP.---35℃
UNDER COOL-----------8.3℃
AMBIENT TEMP.---------3
RUNNING CAPACITOR--55μF
℃
45
55
50
60
60
)
W
(
INPUT
)
W
(
CAPACITY
2400
2200
2000
1800
)
A
(
CURRENT
8500
8000
7500
7000
6500
6000
5500
5000
4500
4000
-50510
13.0
12.0
11.0
10.0
9.0
8.0
-50510
-50510
55
50
45
60
55
50
45
45
50
55
60
)
℃
CONDENSING TEMP. (
EVAPERATING TEMP. (℃)
9
Page 11
Domestic Air Conditioner
Model: HSU-24C03/Z
Model: HSU-24H03/Z
DESCRIPTION,DIMENSION AND
FUNCTION OF MAIN COMPONENTS
AND ACCESSORIES
10
Page 12
Indoor Unit
Inlet grill
Air filter
Vertical flap
Use remote controller to
adjust up and down air flow.
(Don't adjust it manually.)
Brief introduction to electrical control functions
BRIEF INTRODUCTION TO
ELECTRICAL CONTROL FUNCTIONS
41
Page 20
room ambient temperature.
compressor
four-way valve
outdoor fan
163838
38
19
Domestic Air Conditioner
Model: HSU-24C03/Z
Model: HSU-24H03/Z
1. Introduction of electric control function
1.1 Brief introduction of electric control function
(1) Auto running (available for cooling and heating type)
When Auto running starts for the first time, selection of running mode follows the
conditions below:
Tr > 23℃ Select cooling mode Set temperature: 26℃
Tr≤23℃ Select heating mode (with temperature compensation) Set temperature: 23℃
In auto mode, running mode shifts between cooling and heating with the variation of
(2) Room temperature control
Compressor ON Compressor OFF
Heating
Set temperature
Compressor OFF Compressor ON
Cooling
Set temperature
(3) Dry running
Compressor, outdoor fan and indoor fan run as follows (Tr, room temperature, Ts, set
temperature). When dry mode starts for the first time, compressor, outdoor fan and indoor
fan will run following the rules below:
① Tr>Ts+2℃, compressor, outdoor fan run successively, indoor fan run at set speed,
this working area is defined as area A.
② Ts≤Tr≤Ts+2℃, compressor, outdoor fan will run for 10 minutes and stop for 6
minutes, indoor fan will run at low speed, this working area is defined as area B.
③ Tr<Ts, compressor, outdoor fan will stop running, indoor fan will run at low
speed, this area is defined as area C.
In dry mode, system will shift between area A, B and C variation with room ambient
temperature. When Tr<Ts+1, system will shift from area A to B; when Tr>Ts, system
will shift from area C to B; when Tr>Ts+3, system will shift from B to A; when
Tr<Ts-1, system will shift from area A to C.
(4)Cool-air proof in heating
In heating, every time starts compressor, indoor fan will stop running if room coil
temperature is less than 28℃; indoor fan will run at low speed if room coil temperature is
equal to or more than 28℃ and less than 38℃; indoor fan will run at set fan speed if
room coil temperature is more than 38℃ or compressor has run more than 4 minutes.
(5) Residual heat air discharging in heating
In heating, compressor stops, indoor fan stops after a 30-second low running.
(6) Defrosting control
Page 21
Indoor fan
Run on cool air
-
proof
4-way
0
20
(1)
Domestic Air Conditioner
a. After the state of Tp-Tr<18℃ is continued for 5 minutes, the accumulated
running time of the compressor exceeds 45 minutes, the continuous running
time of the compressor exceeds 20 minutes;
b. The accumulated running time of the compressor exceeds 3 hours, the
continuous running time of the compressor exceeds 20 minutes, indoor unit’s Tp
<42℃;
c. The continuous running time of the compressor exceeds 20 minutes, the
temperature of indoor coil pipe decreases 1℃ every 6 minutes, which lasts for
more than 3 times, indoor unit’s Tp <42 ℃;
d. When the indoor unit is in the state of overload protection and the outdoor unit
ceases, when the rerunning time of outdoor unit exceeds10 minutes, the
accumulated running time of the compressor exceeds 45 minutes, the
continuous running time of the compressor is over 20 minutes, and Tp <42℃.
Defrosting will begin if one of the above conditions is met.
(2) Defrosting finishing condition:
If the defrosting time exceeds 9 minutes, the original heating state will be
resumed;
Defrosting process is as follows:
Compressor
Outdoor fan
55s
9min
1min
Model: HSU-24C03/Z
Model: HSU-24H03/Z
55s
1min
Page 22
21
Domestic Air Conditioner
Model: HSU-24C03/Z
Model: HSU-24H03/Z
(7) Temperature compensation.
Auto temperature compensation condition: when reach temperature condition, cut-off
time of compressor is less than 5 minutes. Temperature compensation rules are as
follows:
When Ts+4-Tr≥2℃, ΔT=2℃; when Ts+4-Tr=1℃, ΔT=1℃;
When Ts+4-Tr≤0℃, ΔT=0℃.
When heating mode starts for the first time, ΔT=0℃.
With temperature compensation function, if push temperature increasing and decreasing
button on remote controller, ΔT=0; if push temperature increasing button on remote
controller, ΔT will maintain previous value.
(8) Overcool protection in cooling.
In cooling, 9 minutes after the start of compressor, check room coil temperature. when
indoor coil temperature is less than 0℃,compressor and outdoor fan will stop running.
When the two following conditions are meet, compressor and outdoor fan will restart:
① Cut-off time is more than 3 minutes;
② Indoor coil temperature is more than 7℃.
(9) 3-minutes delay
When compressor stop running arose from transmitter OFF, ON-OFF or breakdown,
compressor will stop for 3-minutes.
(10) Overcharging protection in heating
Overcharging protection: in HEAT mode, if room coil temperature>56℃, outdoor fan will
stop running and resume when inner coil temperature ≤ 53 ℃ ;if room coil
temperature>68℃ and last 10 seconds, compressor and outdoor fan will strop running;
compressor and outdoor fan will resume normal operation when room coil
temperature<46℃.
Over-current protection: in HEAT mode, outdoor fan will stop running if working current
measured with current transformer is continuously more than 14A in 2 seconds; if current
is less than 13A, outdoor fan will resume operation; if working current is more than 26A
after a 5-minutes running and last 10 seconds, compressor will stop and resume normal
operation 3 minutes after; indoor fan will run on cool-air proof condition. If over-current
protection occurs twice in 30 minutes, compressor won’t restart any more. System will
turn into over-current fault alarm.
(11) Power failure compensation function.
Power failure compensation function will be set by remote controller. To cancel power
failure function, push SLEEP button 10 times in 5 seconds, buzzer will sound twice
"BEEP"; To set power failure function, push SLEEP button 10 times in 5 seconds, buzzer
will sound four times "BEEP".
When main panel has power failure compensation function, it will memorize running
parameter in the case of sudden power failure (not cut by remote controller), if unit didn’t
receive remote signal 3 minutes after power resume, it will call automatically memory
information and continue to run in previous state. Memory includes operation mode, fan
speed, set temperature, air door state, health; timing and sleep mode not included.
(12) Emergency switch and forced cooling.
Push down emergency ON/OFF button, buzzer will sound once "beep", release it 5
seconds after, unit will perform starting function; if ON/OFF button is pressed
continuously for more than 5 seconds, buzzer will sound twice "beep", and unit will
perform forced cooling function. Here operational mode is set as cooling, fan speed is set
as high; forced cooling will finish 30 minutes after. After having pushed down mode
button, fan speed button, temperature increasing and decreasing button, sleep button,
For the abnormal phenomenon occurred, please conduct trouble analysis and troubleshooting
according to the following table:
NoReason of troublePhenomenaRemarks
1The sensor of indoor ambient
temperatureis in short circuit or
broken circuit
2The temperature sensor of
indoorcoil pipe is in short
circuit or broken circuit
The compressor indictor
and
timing
extinguish,
running indicator flickers
The compressor indictor
and timing indicator are
on,andtherunning
indicator flickers
indicator
andthe
3The indoormotoris damaged,or the
computer board is damaged
The power indicator and
running indicator of indoor
unit flicker twice, thepower
indicator, running indicator
and timing indicator flicker
togetherfor 1 second,then
repeating the cycle.
The motorhasno signal
feedback of Hall unit
48
Page 29
28
Domestic Air Conditioner
Model: HSU-24H03/Z
HSU-24C03/Z
49
Page 30
29
Domestic Air Conditioner
Model: HSU-24C03/Z
Model: HSU-24H03/Z
REFRIGERATING CYCLE DIAGRAM
50
Page 31
30
Domestic Air Conditioner
Model: HSU-24C03/Z
Model: HSU-24H03/Z
Page 32
31
Domestic Air Conditioner
Model: HSU-24C03/Z
Model: HSU-24H03/Z
INSTALLATION MANUAL
52
Page 33
32
26
Domestic Air Conditioner
Model: HSU-24C03/Z
Model: HSU-24H03/Z
26
53
Page 34
33
Domestic Air Conditioner
Model: HSU-24C03/Z
Model: HSU-24H03/Z
54
Page 35
553456
Page 36
35
Page 37
36
Page 38
37
58
Page 39
1.Cut pipe
3.Insert the flare nut
4.Flare pipe
2.Remove burs
Flare tool for R410A
Clutch-type
clutch-type(Rigid-type)
Conventional flare tool
Wing-nut type (Imperial-type)
0~0.5mm1.0~1.5mm1.5~2.0mm
38
Page 40
Domestic Air Conditioner
Model: HSU-24C03/Z
Model: HSU-24H03/Z
39
Page 41
Sincere Forever
Haier Group
Haier Industrial Park, No.1, Haier Road
266101, Qingdao, China