1.Fitting of the Mounting Plate and Positioning of the wall Hole
When the mounting plate is first fixed
1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be
fixed against the wall, then temporarily fasten the plate with one steel nail.
2. Make sure once more the proper level of the plate, by hanging a thread with a weight from
the central top of the plate, then fasten securely the plate with the attachment steel nail.
3. Find the wall hole location A using a measuring tape
24K
18K
HSU-12LEK03-Y5(6)
HSU-12LH03
A=145mm
B=
A=145mm
9K 12K
HSU-108CH09
HSU-138CH09
B= 60mm
A=145mm
30mm
HSU-18HH03
HSU-18HEG03
HSU-18LEK03-Y6
2.Making a Hole on the Wall and Fitting the Piping Hole Cover
B= 60mm
30mm
60mm
30mm
Make a hole of 60 mm in diameter,
slightly descending to outside the wall.
Install piping hole cover and seal it
off with putty after installation
Indoor side
Wall hole
60mm
(Section of wall hole)
2
G
Piping hole pipe
Outdoor side
Thickness
of wall
Page 3
Indoor unit
Connecting the indoor/outdoor Electric Cable
Removing the wiring cover
Remove terminal cover at right bottom corner of indoor unit, then
take off wiring cover by removing its screws.
When connecting the cable after installing the indoor unit
1. Insert from outside the room cable into left side of the wall hole, in which
the pipe has already existed.
2. Pull out the cable on the front side, and connect the cable making a loop.
When connecting the cable before installing the indoor unit
Insert the cable from the back side of the unit, then pull it out on the front side.
Loosen the screws and insert the cable ends fully into terminal block, then tighten the screws.
Pull the cable slightly to make sure the cables have been properly inserted and tightened.
After the cable connection, never fail to fasten the connected cable with the wiring cover.
Note: When connecting the cable, confirm the terminal number of indoor and outdoor units carefully. If wi
is not correct, proper operation can not be carried out and will cause defect.
1. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar
qualified person. The type of connecting wire is H05/07RN-F or 245IEC57(YZW).
2. If the fuse on PC board is broken please change it with the type of T. 3.15A/250V.
If the fuse of outdoor unit on PC board is broken, please change it with the type of T. 25A/250V.
3. The wiring method should be in line with the local wiring standard.
4. After installation, the power plug should be easily reached.
A breaker should be incorporated into fixed wiring. The breaker should be all-pole switch and the
5.
distance between its two contacts should be not less than 3mm.
To bend a pipe, give the roundness as large as possible not to crush the pipe
Connecting the pipe of gas side first makes working easier.
The max vertical distance between the indoor unit and the outdoor unit is 5 m.
Half union
Flare nut
Forced fastening without careful centering
may damage the threads and cause a
leakage of gas.
Fastening torque
Spanner
Torque wrench
Be careful that matters, such as wastes of sands, etc.
shall not enter the pipe.
Pipe Diameter ( )
Liquid side 6.35mm(1/4")
Liquid side 9.52mm(3/8")
Gas side 9.52mm(3/8")
Gas side 12.7mm(1/2")
Gas side 15.88mm(5/8")
2.Attaching Drain-Elbow
If the drain-elbow is used, please attach it as
figure. (Note: Only for heat pump unit.)
3.Purging Method:
Push the air out of the indoor unit and piping as followes:
Tighten the caps on the valves with specified torque.
Tighten torque N.m
Valve rod
Valve cap
When connecting pipe exceeds 5 meters, 20g or 60g(only for 22k24k) refrigerant shall be
added per exceeding meter. Charge according to the following list.
7-9
20-25
18N.m
40N.m
40N.m
50N.m
60N.m
for 5k 7k 9k 10k 12k 13k 18k
Piping length
Additional amount
Outdoor unit
Max.Elevation:
Max. Length: for 5K 7K 9K 10K: A=7m
for 12K 13K: A=10m
for 18K 22K 24K: A=20m
5m7m
No need40g
Indoor unit
A
B
for 5K 7K 9K 10K 12K 13K: B=5m
for 18K 22K 24K: B=10m
Indoor unit
for 22k 24k
10m
100g
A
Outdoor unit
B
4
Piping length
Additional amount
Outdoor unit
CAUTION
In case more than 5 metresˈoil trap
should be installed every 5~7m.
5m7m
No need
A
B
120g
C
10m
300g
Oil trap
Indoor unit
20m
900g
C