Haier HSU-09HEA103/R2, HSU-12HEA103/R2 User Manual

Installation Manual of Room Air Conditioner
Preparation
Necessary Tools for Installation
Torque wrench
Driverƽ Nipperƽ Hacksawƽ Pipe cutterƽ Hole core drillƽ Flaring toolƽ Spanner(17,19 and 26mm)ƽ Knifeƽ Gas leakage detector orƽ soap-and-water solution
ƽ
(17mm,22mm,26mm)
Measuring tapeƽ Reamerƽ
Power Source
ƽ
Before inserting power plug into receptacle, check the voltage without fail. The power
Install an exclusive branch circuit of the power.
ƽ
Areceptacleshallbesetupin a distancewherethepowercablecanbe
ƽ
reached.
sourceisthesameasthe
Donotextendthecablebycuttingit.
correspondingnameplate.
Drawing for the installation of indoor and outdoor units
ThemodelsadoptHFCfreerefrigerantR410A
more than 5cm
more than 10cm
Selection of Installation Place
Indoor Unit
Place,robustnotcausingvibration,wherethebodycanbesupportedsufficiently.ƽ Place, not affected by heat or steam generated in the vicinity, where inlet and outlet of the
ƽ
unit are not disturbed. Place,possibletodraineasily,wherepipingcanbeconnectedwiththeoutdoorunit.ƽ Place,wherecoldaircanbespreadin a roomentirely.ƽ Place, nearby a power receptacle, with enough space around. (Refer to drawings).ƽ Place where the distance of more than lm from televisions, radios, wireless apparatuses
ƽ
and fluorescent lamps can be left. In the case of fixing the remote controller on a wall, place where the indoor unit can
ƽ
receive signals when the fluorescent
lamps in the room are lightened.
Outdoor Unit
Place, which is less affected by rain or direct sunlight and is sufficiently ventilated.ƽ Place, possible to bear the unit, where vibration and noise are not increased.ƽ Place, where discharged wind and noise do not cause a nuisance to the neighbors.ƽ Place, where a distance markedƽ
Attention must be paid to
the rising up of drain hose
isavailableasillustratedintheabovefigure.
Optional parts for piping
Non-adhesive tape
A
B
Saddle (L.S) with screws
G
C
Connecting electric cable
D
forindoorandoutdoor
E
Drain hose
F
Heating insulating material
Piping hole cover
G
Arrangement of piping directions
Left
Rear left
Rear
more than 10cm
F
A
right
Right
Below
The marks from to
ƽ
G
in the figure are the
more than 10cm
A
more than
10cm
C
parts numbers. The distance between
ƽ
the indoor unit and the
D
floor should be more than 2m.
more than
60cm
E
more than15cm
Please be subject to the actual product purchased , the above picture is just for your reference.
Read this manual before installation Explain sufficiently the operating means to the user according to this manual
NO.0010531113
Floor fixing dimensions of the
outdoor unit (Unit:mm)
Fixing of outdoor unit
Fix the unit to concrete or blockƽ with bolts (10mm) and nuts firmly and horizontally. When fitting the unit to wall
ƽ
surface, roof or rooftop, fix a supporter surely with nails or wires in consideration of earthquake and strong wind. If vibration may affect the
ƽ
house, fix the unit by attaching a vibration-proof mat.
Remote controller (1)
R-03 dry battery (2)
Mounting plate (1)
Plastic cap (4)
Ø4X25 Screw
NOTE˖The thickness of the pipe must be 0.8mm at least.
(4)
Liquid pipe (Ø) 6.35mm(1/4”)
Gas pipe (Ø)
Indoor unit
Fitting of the Mounting Plate and
Accessory parts
Drainhose(1)
Cushion (4)
Drain-elbow (1)
Pipe supporting plate (1)
Selection of pipe
9.52mm(3/8”)
Positioning of the wall Hole
1. Insert the drain hose into the dent of heat insulation
2. Insert the indoor/outdoor electric cable from backside of outonthefrontside,thenconnect them.
3.Coattheflaringsealfacewithrefrigerantoilandconnect Cover the connection part with heat insulation materials closely, and make sure fixingwithadhesivetape
Lid for right piping
Lid for under piping pipe
Fix with adhesive tape
ƽ
Indoor/outdoorelectriccableanddrainhosemustbeboundwithrefrigerant
piping by protecting tape.
Lid for left piping
materials of indoor unit.
Heat insulation material
Drain hose
indoor unit, and pull it
pipes.
Indoor/outdoor electric cable
Piping
Pipe supporting plate
[ Other direction piping ]
ƽ
Cut away, with a nipper, the lid for piping according to the piping direction and
then bend the pipe according to theposition of wall hole. When bending, be careful not to crash
ƽ
Connect beforehand the indoor/outdoor electric cable,
connected to the heat insulation of connecting part specially.
pipes.
andthenpulloutthe
Fixing the indoor unit body
When the mounting plate is first fixed
1. Carry out, based on the neighboring pillars or lintels, a to be fixed against the wall, then
2. Make sure once more the proper level of the plate, by
weight from the central top of the plate, then fasten securely the plate with the attachment steel nail.
3. Find the wall hole location A using a measuring tape
A=145mm
temporarily fasten the plate with one steel nail.
B= 60mm
30mm
B= 60mm
A=150mm
proper leveling for the plate
hanging a thread with a
A=145mm
30mm
When the mounting plate is fixed side bar and lintel
Fixtosidebarandlintel a mountingbar,Whichisseparatelysold,andthen
ƽ
fasten the plate to the fixed mounting bar.
Refer to the previous article, “ When the mounting plate is
ƽ
position of wall hole.
Making a Hole on the Wall and Fitting the Piping Hole Cover
Make a hole of 60 mm in diameter, slightly descending to outside the wall.
ƽ
Installpipingholecoverandsealit offwithputty afterinstallation
ƽ
(Section of wall hole)
Installation of the Indoor Unit
Wall hole
Ø60mm
Indoor side
Thickness of wall
Piping hole pipe
G
Outdoor side
first fixed “, for the
B= 60mm
30mm
Hang surely the unit body onto the upper notches of the
ƽ
mounting plate. Move the body from side to side to verify its secure fixing.
Inordertofixthebodyontothemountingplate,holdup
ƽ
thebodyaslantfromtheundersideandthenputitdown perpendicularly.
Unloading of indoor unit body
When you unload the indoor unit,please use
ƽ
your hand to arise the body to leave agraffe, then lift the bottom of the body outward
slightly and lift the unit aslant until it leaves the mounting plate.
agraffe
Connecting the indoor/outdoor Electric Cable
Removingthewiringcover
Remove terminal cover at right bottom corner of indoor unit, then takeƽ
offwiringcoverbyremovingitsscrews.
When connecting the cable after installing the indoor unit
1.Insertfromoutsidetheroomcableintoleftside of thewall hole,inwhichthepipehasalreadyexisted.
2.Pulloutthecableonthefrontside,andconnectthecable
making a loop.
When connecting the cable before installing the indoor unit
Insertthecablefromthebackƽ
ƽ
Loosen the screws and insert
tighten the screws.
Pull the cable slightly to
ƽ
tightened.
After the cable connection,
ƽ
wiring cover.
side of the unit, then pull it out the cable ends fully into
make sure the cables have
neverfailtofastentheconnectedcablewiththe
been properly inserted and
mounting plate
mounting plate
on the front side.
terminal block, then
Drawing of pipe
[ Rear piping ]
Drawpipesandthedrainhose,thenfastenthemwiththeadhesivetape
ƽ
[Left・Left-rear piping ]
ƽ
In case of left side piping, cut away, with a nipper, the lid for left piping.
Incase of left-rearpiping,bendthepipesaccordingtothepipingdirectionto
ƽ
the mark of hole for left-rear piping which is marked on heat insulation materials.
2
When connecting the cable, confirm the terminal number of indoor and
Note
outdoor units carefully. If wiring is not correct, proper operation can not
becarriedoutandwillcausedefect.
Outdoor unit
Installation of Outdoor Unit
4
3
2(N) ) 1(L
Indoor unit
Power cable: ≥3G1.0mm
2
Connecting wiring: 1(L) ǃ2(N) ǃ
3ǃ4
HSU-09RM03/R2 HSU-12RM03/R2 HSU-12HR03/R2
)43 N
( 2 ) L
(
1
Indoor unit
Power cable: ≥3G1.0mm Connecting wiring:
HSU-09H EK03/R2
HSU-12H EK03/R2 HSU-07HEA03 /R2 HSU-09HEA03/R2 HSU-12HEA03 /R2 HSU-09HEA103/R2 HSU-12HEA103/R2
HSU-07HR03/R2 HSU-09HR03/R2
2
≥3G1.0mm
HSU-09HRA03/R2 HSU-12HRA03/R2 HSU-12HVA03/R2 HSU-09HEA03 /R2-I HSU-12HEA03 /R2-I
HSU-09RH03/R2 HSU-12RH03/R2
4
Outdoor unit
3G1.0mm
2G0.75mm
2
2
1
( L )
2 (
N
)
Outdoor unit
2
(For: L N )+2x0.75mm
Install according to Drawing for the installation of indoor and
Connection of pipes
Tobend a pipe,givetheroundnessaslargeaspossiblenottocrushthepipe,
ƽ
andthebendingradiusshouldbe30to40
ƽ
Connecting the pipe of gas side first makes working easier. TheconnectionpipeisspecializedforR410A.ƽ
Half union
Spanner
Becarefulthatmatters,suchaswastesofsands,etc.shallnotenterthepipe. Thestandardpipelengthis5m.Ifitisover7m,thefunctionoftheunitwillbe
affected.Ifthepipehas according to 20 g/m. But the charge of refrigerant must
sional air conditioner engineer. Before adding additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum
charge additional refrigerant.
Flare nut
Torque wrench
Forced fastening without careful centering may damage the threads and cause a leakage of gas.
Liquid side6.35mm(1/4") 18N.m
Liquid/Gas side9.52mm(3/8") 42 N.m
Gasside12.7mm(1/2") 55N.m
Gas side 15.88mm(5/8") 60 N.m
to be lengthened, the refrigerant should be charged,
mm or longer.
Pipe Diameter(ǿ) Fastening torque
outdoor units
be conducted by profes-
pump,then
CAUTION
Outdoor unit
Indoor unit
2
Outdoor unit
Outdoor unit
B
A
Max.Elevation:
In case the elevation A is more than 5m, oil trap shoud be installed every 5~7m Max. Length:
Oil trap
B
A
Indoor unit
Incasethepipelength B is more than 7m, the refrigerant should be charged, according to 20 g/m.
B
A
Bmax=15m
Indoor unit
Amax=10m
1.Ifthesupplycordisdamaged,itmustbereplacedbythemanufacturerorits service agent or a similar qualified person. The type of connecting wire is H05RN-F
2.IfthefuseonPCboardisbrokenpleasechangeitwiththe T. 3.15 A/ 25 0V.
3.Thewiringmethodshouldbeinlinewiththelocalwiringstandard.
4. After installation, the power plug should be easily reached.
5. A breakershouldbeincorporatedintofixedwiring.Thebreakershouldbe
all-pole than 3mm.
or H07RN-F.
type of
switch and the distance between its two contacts should be not less
Connection
Use the same method on indoor unit. Loosen the screws onƽ insert the plugs fully into terminal block, then tighten the screws. Insertthecableaccordingto terminalnumberinthesamemannerastheindoor
ƽ
unit. If wiring is not correct, proper operation can not be carried out and controller
ƽ
may be damaged. Fix the cable with a clamp.ƽ
Attaching Drain-Elbow
If the drain-elbow is used,ƽ please attach it as figure. (Note: Only for heat pump unit.)
PurgingMethod:Tousevacuumpump
1.
Detach the service port’s cap of and3-way’s,connecttheserviceportintothe
for gaugemanifold.
gemanifold
2.
Open the handle at Iow in
moves of gause (Iow) reach vacuum condition in a moment, check 1. again.
Vacuumize for over 15min.And check the level gauge which should read -0.1MPa
3.
(76 cm Hg) at Iow
handle ‘Lo’ in gaugemanifold and stop the operation of the vacuum pump. Check
condition of the scale and hold it for 1-2min. If the scale-moves back in spite of
tightening,makeflaring workagain,thereturntothebeginning of 3 .
Openthevalverodforthe2-wayvalvetoanangle of4.
After 6 seconds, close the
Then connect
into vacuum pump.
pressure side. After the
3-way valve, the valve rod’s cap for 2-way valve
the projection of charge hose (center) for gau-
gaugemanifold, operate
2-way valve and make the
projection of charge hose (Iow)
vacuum pump. If the scale-
completion of vacuumizing, close the
terminal block and
anticlockwise 90 degrees. inspection of gas leakage.
3
No gas leakage?5.
In case of gas leakage, tighten parts of pipe connection. If
leakage stops, then proceed 6. steps
Close
from the service
rod’s cap for 2-way
2-way valve 3-way valve
2-way valve
3-way valve
Valve rod c ap
Valve rod c ap
If it does not stop gas leakage, discharge whole refrigerants
port. After flaring work again and vacuumize, fill up prescribed
Detach the charge hose6. the valve rod anticlockwise until hitting lightly.
To prevent the gas
7.
valve and 3-way’s a little more
After attaching the each
8.
Step 1.
Tube(for R410A)
Step 4.
Open 90
2-way valve
2-way valve Liquid Side
3-way valve Gas Side
O
3-way valve
refrigerantfromthegascylinder.
from the service port,
leakage, turn the service
than the point where the torque increases suddenly.
caps, check the gas
Gaugemanifold(for
Anti countercurrent joint
Vacuum pump(for R410A)
2-way valve
3-way valve
open2-wayvalveand3-way.Turn
port’s cap, the valve
leakagearoundthecaps.
Step 2.
Open
R410A)
Step 3.
Step 6.
Step 7.
Service port cap
CAUTION
ƽ
If the refrigerant of the air conditioner leaks, it is necessary to discharge all the refrigerant. Vacuumize first, then neraccordingtotheamountmarkedonthenameplate.
ƽ
Please do not let other cooling medium, except specified one (R410A), or air
enter into the cooling circulation system. Otherwise, there will be abnormal
highpressureinthesystemtomakeitcrackandleadtopersonalinjuries.
Power Source Installation
ƽ
The power source must be exclusively used for air
ƽ
In the case of installing an air conditioner in a moist place, rth leakage breaker.
ƽ
For installation in other places, use a circuit breaker as far
Cutting and Flaring Work of Piping
ƽ
Pipe cutting is carried out with a pipe cutter and burs must
After inserting the flare nut, flaring work is carried out.
ƽ
FlaretoolforR410A Conventionalflaretool
Clutch-type clutch-type(Rigid-type) Wing-nut type (Imperial-type)
A 0~ 0.5mm 1.0~1.5mm 1.5~2.0mm
Flare tooling die
charge the liquid refrigerant into air conditio-
conditioner. (Over I0A)
please install an ea-
as possible.
be removed.
1.Cut pipe
3.Inserttheflarenut
2.Remove burs
4.Flare pipe
On Drainage
Pleaseinstallthedrainhosesoastobedownwardslopewithoutfail.
ƽ
Please don’t do the drainage as shown below.
ƽ
Less than
5cm
It becomes
high midway.
Please pour water in the drain pan of the indoor unit, and
ƽ
is carried out surely to outdoor.
In case that the attached drain hose is in a room, please
ƽ
it without fail.
The end is imm­ersedinwater.
It waves.
The gap with the
ground is too small.
confirm that drainage
apply heat insulation to
There is the bad smell from a ditch
Refrigerant charge labelƵ
Contains fluorinated greenhouse gases covered by the Kyoto Protocol
R410A
2
1=
2=
1
1+2=
FE
kg
kg
kg
A
B
C
D
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent into the atmosphere. Refrigerant type:R410A GWP* value:1975 GWP=global warming potential Please fill in with indelible ink,
• 1 the factory refrigerant charge of the product
• 2 the additional refrigerant amount charged in the field and
• 1+2 the total refrigerant charge on the refrigerant charge label supplied with the product. The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop value cover). A contains fluorinated greenhouse gases covered by the Kyoto Protocol B factory refrigerant charge of the product: see unit name plate C additional refrigerant amount charged in the field D total refrigerant charge E outdoor unit F refrigerant cylinder and manifold for charging
Ƶ
Check for Installation and Test Run
Please kindly explain to our customers how to operate
Ƶ
through the instruction manual.
CheckItemsforTestRun
Put check mark
Gasleakfrompipeconnecting? Heat insulation of pipe connecting? Are the connecting wirings of indoor and outdoor firmly inserted to the terminal block?
Istheconnectingwiring of indoorandoutdoorfirmlyfixed? Is drainage securely carried out? Is the earth line securely connected? Istheindoorunitsecurelyfixed? Is power source voltage abided by the code? Is there any noise?
Is the lamp normally lighting? Arecoolingandheating(wheninheatpump)performednormally? Is the operation of room temperature regulator normal?
in boxes
Correct Incorrect
Lean
Damage of flare Crack Partial Too outside
4
Manual de instalación de aparato de aire acondicionado
Preparación
Herramientas necesarias para realizar la instalación
Destornillador
Alicate
Sierra para metales
Broca de tubo
Llave (17, 19 y 26 mm)
Detector de fugas de gas o agua
jabonosa
Llave dinamométrica
(17 mm, 22 mm, 26 mm)
Sierra de tubos
Herramienta de conicidad
Cuchilla
Metro
Avellanador
Fuente de alimentación
Antes de insertar el enchufe de alimentación en la toma, compruebe que el voltaje
no falla. La fuente de alimentación es la que figura en la placa de datos nominales. Instale el aparato en un circuito dedicado de alimentación.
Debe existir una toma al alcance del cable de alimentación. No trate de prolongar
el cable cortándolo.
Diagrama para la instalación de aparatos interiores y exteriores
Los modelos cumplen la norma R410A sobre refrigerantes libres de HFC
más de 5cm
Selección del lugar de instalación
Unidad interior
● Coloque la unidad sobre una superficie que pueda soportarla correctamente y no provoque vibraciones.
● Asegúrese de que el lugar no se ve afectado por calor o vapor generado en las cercanías y donde la unidad pueda funcionar sin perturbaciones.
● Asegúrese de que el lugar permita un drenaje sencillo y en el que puedan conectarse los tubos a la unidad exterior.
● Asegúrese de que el aire frío pueda distribuirse uniformemente por la sala.
● Coloque la unidad interior cerca de una toma de suministro eléctrico con espacio suficiente alrededor. (Consulte los diagramas).
● Coloque la unidad interior de modo que se encuentre a más de 1m de televisiones, radios, aparatos inalámbricos y lámparas fluorescentes.
● En el caso de fijar el control remoto a una pared, colóquelo donde la unidad interior pueda recibir su señal mientras estén encendidas las lámparas fluorescentes de la sala.
Unidad exterior
● Seleccione el lugar menos afectado por la lluvia o la luz solar directa y suficientemente ventilado.
● Elija un lugar que permita soportar el peso de la unidad y que no amplifique el ruido y las vibraciones.
● Seleccione un lugar en el que los residuos y el viento generado por la unidad no cause una molestia a los vecinos.
● Coloque la unidad en un lugar en el que pueda disponerse de la distancia de
separación marcada en la figura anterior.
Debe prestarse atención a la pendiente de la manguera de drenaje
Componentes opcionales para la instalación de los tubos
más de 10cm
Organización de la dirección de los tubos
Izquierda trasera
Izquierda
Las marcas de
que se muestran en la figura representan los componentes. La distancia entre la unidad
interior y el suelo debe ser superior a 2m.
Derecha trasera
Derecha
Inferior
a
más de 60cm
más de 10cm
más de 10cm
más de 10cm
Cinta no adhesiva
Cinta adhesiva
G
F
A
C
Soporte (L.S) con tornillos Conexión de cable eléctrico para interior
y exterior
Manguera de drenaje Material aislante de calor
Cubierta de orificio de entubación
Dimensiones de fijación al suelo de la unidad exterior (Unidad :mm)
Fijación de la unidad exterior
● Fije la unidad a un bloque de cemento con pernos (10mm) y tuercas firme y horizontalmente.
● Si instala la unidad sobre una pared, techo o tejado, instale un soporte con clavos o cables
D
E
considerando la posibilidad de terremotos o viento fuerte.
● Si la vibración afectase a la casa, fije la unidad instalando una alfombra de absorción de vibraciones.
más de 15cm
Recuerde que la ilustración anterior podría no reflejar fielmente el producto adquirido y debe utilizarse únicamente como referencia. Lea este manual antes de la instalación Explique el uso del aparato al usuario siguiendo las instrucciones de este manual.
5
Loading...
+ 11 hidden pages