Installation Manual of Room Air Conditioner
Read this manual before installation Explain sufficiently the operating means to the user according to this manual.
Necessary Tools for Installation
1.Driver
2.Hacksaw
3.Hole core drill
4.Spanner(17,19 and 26mm)
Accessory parts
No. Accessory parts
1
2
3
4
5
Remote controller
R-03 dry battery
Mounting plate
Drain hose
4X50
Steel nail, cement
Number of articles
1
2
1
1
6
5.Torque wrench(17mm,22mm,26mm)
7.Flaring tool
8.Knife
9.Nipper 12.Reamer
10.Gas leakage detector or soap-and-
water solution
11.Measuring tape
Drawing for the installation of indoor and outdoor units
mc 5nahterom
Optional parts for piping
Mark
A
B
C
D
E
F
G
Parts name
Non-adhesive tape
Adhesive tape
Saddle(L.S) with screws
Connecting electric cable for indoor and outdoor
Drain hose
Heating insulating material
Piping hole cover
1nahterom
mc0
Attention must be paid to the rising up of drain hose
mc01nahterom
A
6
7
8
10
4X25
Screw
9
Plastic cap
Cover
Cushion
Pipe supporting plate
Drain-elbow
No.0010531057
4
1
4
1
Arrangement of piping directions
Rear left
Below
Rear right
Right
Left
nahterom
c01
m
mc01nahte
r
o
m
C
1
D
E
m
mc06na
ht
ero
m
G
The marks from to in the figure are the parts numbers.
A
The distance between the indoor unit and the floor should be more than 2m.
o
1nahter
mc5
Floor fixing dimensions of the outdoor unit (Unit:mm)
HSU-09H03/K(F)
HSU-12H03/K(F) HSU-12C03/K(F)
Selection of pipe
To this unit, both liquid and gas pipes shall be insulated
as they become Iow temperature in operation.
Use optional parts for piping set or pipes covered with
equivalent insulation material.
Liquid pipe ( )
Gas pipe ( )
For 09k For 12k
6.35mm(1/4")
9.52mm(3/8")
6.35mm(1/4")
12.7mm(1/2")
Indoor unit
1.Fitting of the Mounting Plate and Positioning of the wall Hole
When the mounting plate is first fixed
1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the wall, then temporarily fasten the plate with one steel nail.
2. Make sure once more the proper level of the plate, by hanging a thread with a weight from the central top of the plate, then fasten securely the plate with the attachment steel nail.
3. Find the wall hole location A using a measuring tape
B= 66mm
A=210mm
mm03
2.Making a Hole on the Wall and Fitting the Piping Hole Cover
Make a hole of 60 mm in diameter, slightly descending to outside the wall. Install piping hole cover and seal it off with putty after installation
Indoor side
Wall hole
66mm
(Section of wall hole)
2
G
Piping hole pipe
Outdoor side
Thickness of wall
Indoor unit
Connecting the indoor/outdoor Electric Cable
Removing the wiring cover
Remove terminal cover at right bottom corner of indoor unit, then take off wiring cover by removing its screws.
When connecting the cable after installing the indoor unit
1. Insert from outside the room cable into left side of the wall hole, in which the pipe has already existed.
2. Pull out the cable on the front side, and connect the cable making a loop.
When connecting the cable before installing the indoor unit
Insert the cable from the back side of the unit, then pull it out on the front side. Loosen the screws and insert the cable ends fully into terminal block, then tighten the screws. Pull the cable slightly to make sure the cables have been properly inserted and tightened. After the cable connection, never fail to fasten the connected cable with the wiring cover. Note: When connecting the cable, confirm the terminal number of indoor and outdoor units carefully. If wi is not correct, proper operation can not be carried out and will cause defect.
1. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person. The type of connecting wire is H05/07RN-F or 245IEC57(YZW).
2. If the fuse on PC board is broken please change it with the type of T. 3.15A/250V. If the fuse of outdoor unit on PC board is broken, please change it with the type of T. 25A/250V.
3. The wiring method should be in line with the local wiring standard.
4. After installation, the power plug should be easily reached.
A breaker should be incorporated into fixed wiring. The breaker should be all-pole switch and the
5.
distance between its two contacts should be not less than 3mm.
ring
HSU-09H03/K(F)
HSU-12H03/K(F)
HSU-12C03/K(F)
3
Outdoor unit
Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.
Outdoor unit
1.Connection of pipes
To bend a pipe, give the roundness as large as possible not to crush the pipe Connecting the pipe of gas side first ma The max
vertical distance between the indoor unit and the outdoor unit is 5 m.
Half union
kes working easier.
Flare
nut
Forced fastening without careful centering may damage the threads and cause a leakage of ga
s.
Spanner
Torque wrench
Pipe Diameter ( )
Liquid side 6.35mm(1/4")
Gas side 9.52mm(3/8") Gas side 12.7mm(1/2") 55N.m
2.Atta
ching Drain-Elbow
If the drain-elbow is used, please attach it as figure. (Note: Only for heat pump unit.)
3.Purging Method:
Push the air out of the indoor unit and piping as followes:
Tighten the caps on the valves with specified torque.
Tighten torque N.m
Valve rod
Valve cap
When connecting pipe exceeds 5 meters, 20g refrigerant shall be added per
exceeding meter. Charge according to the following list.
7-9
20-25
Fastening torque
18N.m 40N.m
Outdoor unit
Piping length
Additional amount
Indoor unit
A
B
Indoor unit
5m 7m
No need
A
Max.Elevation:B=5m
Max. Length: for 9k A=7m
for 12k A=10m
for 09k 12k
Outdoor unit
B
40g
4
10m
100g
Outdoor unit
A
B
CAUTION In case more than 5 metresoil trap
should be installed every 5~7m.
Oil trap
C
Indoor unit
C