Haier HB4200VA1M25, HB3600VC1M25, HB4800VA1M25, HB6000VA1M25, HB6000VC1M25 User Manual

Installation & Operation Manual
Air Handler
10 to 12 SEER 3 to 5 Tons
Models:
HB4800VA1M25
CARBON MONOXIDE (REFERED TO AS CO) CAN CAUSE PERSONAL INJURY OR DEATH
FAILURE T O FOLLOW THESE INSTRUCTIONS, LOCAL CODES OR NATIONAL CODES MAY CAUSE FIRE, EXPLOSION, ELECTRICAL SHOCK, PERSONAL INJURY OR PROPERTY DAMAGE.
FOLLOW ALL LOCAL CODES. IN THE ABSENCE OF LOCAL CODES REFER TO : NATIONAL ELECTRICAL CODE NFPA 70
NFPA 90A & 90B UNIFORM MECHANICAL CODE
HB3600VC1M25 HB4200VA1M25
HB6000VA1M25
WARNING
WARNING
WARNING
HB6000VC1M25
READ THESE INSTRUCTIONS COMPLETELY BEFORE ATTEMPTING TO INSTALL OR SERVICE THIS APPLIANCE.
ONLY FACTORY AUTHORIZED KITS OR ACCESSORIES SHOULD BE USED WHEN INSTALLING OR MODIFYING THIS APPLIANCE, UNLESS OTHERWISE NOTED IN THESE INSTRUCTIONS.
SOME LOCALITIES MAY REQUIRE THE INSTALLER/SERVICER TO BE LICENSED. IF IN DOUBT CONTACT YOUR LOCAL AUTHORITIES.
These instructions should be retained and kept adjacent to the unit for future reference.
MODEL # HB 00VA1M25 MODEL # HB 00VC1M25 INSTALLATION DATE
The information contained in this booklet is subject to change without notice.
No. 0010575351 E
INDEX
TOPIC PAGE
General Physical dimensions Replacement Parts Source Installation Requirements Air Flow Orientation Horizontal Left-Hand Instructions Downflow Instructions Refrigerant Tubing Condensate Removal Electrical Connections Thermostat Wiring Orifice Change Circulating Air Duct Blower Performance Start-up Regular Maintenance Model Number Explanation
1 2 3 3 4 5 6 7 7 8 9 11 11 12 13 13 14
The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction and disposal of refrigerants introduced into this unit.Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. These regulations may vary due to the passage of new laws, it is recommended that any work on this unit be done so by a certified technician. Should questions arise contact the local EPA office.
THIS APPLIANCE IS NOT APPROVED FOR OUTDOOR INSTALLATION THIS APPLIANCE IS NOT TO BE USED AS A CONSTRUCTION HEATER
GENERAL
This appliance was designed certified and must be installed in accordance with published codes.In the absence of local codes please refer to the following codes:
NFPA 90A NFPA 90B National Electrical Code NFPA 70 Uniform Mechanical Code
Prior to shipment, this appliance was tested and inspected for damage at the factory.Unpack carefully and if damage is found, report it immediately to the transportation company.
This appliance is approved for installation in alcoves, basements, attics or crawlway, and is designed for connection to air distribution ductwork.
2
PHYSICAL DIMENSIONS
D
0.8" [2.1cm]
C
PLASTIC BREAKER COVER
B
E
12.2" [31 cm]
5.1" [13 cm]
F
2.4" [ 6 cm]
1.2" [ 3 cm]
A
PRIMARY & SECONDARY CONDENSATE DRAINS­HORIZONTAL 3/4" NPT
2" [5.08 cm]
K
G
H
INLET FRONT VIEW
PRIMARY & SECONDARY CONDENSATE DRAINS­UPFLOW 3/4" NPT-FEMALE
1.1" [2.9 cm]
5" [12.7 cm]
2" [5.08 cm] TYPICAL
SUCTION LINE
LIQUID LINE
J
INLET RIGHT SIDE VIEW
1" [2.54cm]
For: HB3600VC1M25
A B C D E F G H J K
53.3 22.1 23.5 25.2 9.1 8.3 4.7 22.2 19.8 3.6 [135.5cm] [56.1cm] [59.8cm] [64.0cm] [23cm] [21.2cm] [12cm] [56.5cm] [50.4cm] [9.05cm]
For: HB42-6000VA1M25 HB6000VC1M25
A B C D E F G H J K
59.4 22.1 23.5 25.2 9.1 8.3 4.7 22.2 19.8 3.6 [151cm] [56.1cm] [59.8cm] [64.0cm] [23cm] [21.2cm] [12cm] [56.5cm] [50.4cm] [9.05cm]
3
REPLACEMENT PARTS SOURCE
Replacement parts are available through local distributors.When ordering replacement parts, give the COMPLETE model and serial numbers shown on the rating plate.
INSTALLATION REQUIREMENTS
Before installing this appliance insure that it is properly sized and adequate power is available.
This appliance can be installed in the vertical or right horizontal position without modification. The horizontal left and downflow positions require product modification.
This product is designed for zero inch (0") clearance; however, adequate access for service or replacement must be considered without removing permanent structure. This unit can be installed on a platform when deemed necessary.
In an attic installation a secondary drain pan must be provided by the installer and placed under the entire unit with a separate drain line properly sloped and terminated in an area visible to the owner. This secondary drain pan is required in the event that there is a leak or main drain blockage. Closed cell insulation should be applied to the drain lines in unconditioned spaces where sweating may occur.
Appliances installed in garages, warehouses or other areas where they may be subjected to mechanical damage must be suitably guarded against such damage by installing behind protective barriers, being elevated or located out of the normal path of vehicles. When installed on a base, the base must also be protected by similar means.
Heating and cooling equipment located in garages, which may generate a glow, spark or flame capable of igniting flammable vapors, must be installed with the ignition source at least 18" above the floor level.
When more than one appliance is installed in a building, permanently identify the unit as to the area or space serviced by that applice.
4
AIR FLOW ORIENTATION
*Horizontal Right Discharge Tube and Drain conn. front
Downflow discharge (with plastic vertical pan only) (see page 7)
Horizontal Left Discharge Tube and Drain conn. front (see page 6)
Important: Remove the horizontal pan when unit is installed in unconditioned i.e. (Garage, Attic ) application, or downflow applications, and install insulation kit on vertical ( donut shape ) drain pan.
*Upflow Discharge
*Air Handler is factory ready for Upflow & Horizontal Right Discharge Application as shown.
5