Haier AU182XFERA, AU222XFERA User Manual

Page 1
R410A MULTI SPLIT SERIES ROOM AIR CONDITIONER
OUTDOOR UNIT
INSTALLATION MANUAL
AU182XFERA AU222XFERA
NO.0010576791B
Please read this manual carefully before installing the units. Please keep this manual safely for future use.
Page 2
Contents
Cautions .......................................................................................................................
Installation accessories..................................................................................................
Choose the installation place.........................................................................................
Installation dimensions(mm)..........................................................................................
Installation drawings of indoor and outdoor units.........................................................
Power source.................................................................................................................
Matching of the indoor and outdoor units
Limitations on the installation
Purging method: to use vacuum pump.........................................................................
......................................................................................
.....................................................................
1-2
3
4
4
4
5
6
6
6-7
8-9
10
Wiring work...............................................................................................................
Test running..................................................................................................................
Items to confirm...........................................................................................................
Trouble shooting...........................................................................................................
11-13
14
14
15
Page 3
Cautions
Disposal of the old air conditioner
Before disposing an old air conditioner that goes out of use, please make sure it's inoperative and safe. Unplug the air conditioner in order to avoid the risk of child entrapment.
It must be noticed that air conditioner system contains refrigerants, which require specialized waste disposal. The valuable materials contained in a air conditioner can be recycled. Contact your local waste disposal center for proper disposal of an old air conditioner and contact your local authority or your dealer if you have any question. Please ensure that the pipework of your air conditioner does not get damaged prior to being picked up by the relevant waste disposal center, and contribute to environmental awareness by insisting on an appropriate, anti-pollution method of disposal.
Disposal of the packaging of your new air conditioner
All the packaging materials employed in the package of your new air conditioner may be disposed without any danger to the environment.
Consult your local authorities for the name and address of the waste materials collecting centers and waste paper disposal services nearest to your house.
Safety Instructions and Warnings
Before starting the air conditioner, read the information given in the User's Guide carefully. The User's Guide contains very important observations relating to the assembly, operation and maintenance of the air conditioner.
The manufacturer does not accept responsibility for any damages that may arise due to non-observation of the following instruction.
Damaged air conditioners are not to be put into operation. In case of doubt, consult your supplier.
Use of the air conditioner is to be carried out in strict compliance with the relative instructions set forth in the User's Guide.
Installation shall be done by professional people, don't install unit by yourself.
The cardboard box may be broken or cut into smaller pieces and given to a waste paper disposal service. The wrapping bag made of polyethylene and the polyethylene foam pads contain no fluorochloric hydrocarbon.
All these valuable materials may be taken to a waste collecting center and used again after adequate recycling.
For the purpose of safety, the air conditioner must be properly grounded in accordance with specifications.
Always remember to unplug the air conditioner before opening inlet grill. Never unplug your air conditioner by pulling on the power cord. Always grip plug firmly and pull straight out from the outlet.
1
Page 4
Cautions
All electrical repairs must be carried out by qualified electricians. Inadequate repairs may result in a major source of danger for the user of the air conditoiner.
Do not damage any parts of the air conditioner that carry refrigerant by piercing or perforating the air conditioner's tubes with sharp or pointed items, crushing or twisting any tubes, or scraping the coatings off the surfaces. If the refrigerant spurts out and gets into eyes, it may result in serious eye injuries.
Do not obstruct or cover the ventilation grille of the air conditioner. Do not put fingers or any other things into the inlet/outlet and swing louver.
Do not allow children to play with the air conditioner. In no case should children be allowed to sit on the outdoor unit.
4. The wiring method should be in line with the local wiring standard.
5. The power cable and connecting cable are self­provided. The requirement of the power cable to the outdoor unit: H05RN-F 3G 4.0mm
Model
AU182XFERA AU222XFERA
H05RN-F 3G 4.0mm
2
Cable type
2
All the cables shall have got the local authentication certificate.
6. The breaker of the air conditioner should be all­pole switch; and the distance between its two contacts should be no less 3mm. Such means for disconnection must be incorporation in the fixed wiring.
7. The waste battery shall be disposed properly.
Specifications
The refrigerating circuit is leak-proof.
The machine is adaptive in following situation
1. Applicable ambient temperature range:
Cooling
Heating
Indoor
Outdoor
Indoor
Outdoor
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agentor a similar qualified person.
3. If the fuse on PC board is broken please change it with the type of T 3.15A /250VAC or T 25A/250VAC. Please check the circuit diagram about the fuse replaced.
Maximum:D.B/W.B 32 C/23 C Minimum:D.B/W.B Maximum:D.B 43 C/26 C Minimum:D.B Maximum:D.B 27 C Minimum:D.B Maximum:D.B/W.B 24 C/18 C Minimum:D.B/W.B
18 C/14 C
10 C/6 C
20 C
-15 C
2
Page 5
Safety precautions
To ensure proper installation, please read this safety precautions carefully before the installation. After installation, start the unit correctly and ensure that you show the customer how to operate and maintain the units.
WARNING! CAUTION!
Installation work must be carried out by professional qualified people, do not install the unit by yourself. Incorrect installation will cause water leakage, electric shock and potentially fire. Install the unit as per the manual. Incorrect installation will cause water leakage, electric shock or fire risk. Be sure to use specified accessories and parts. Otherwise, water leakage, electric shock, fire risk or unit falling down may occur . Mounting position must be strong enough to hold the unit. Or, the unit will potentially fall down causing injuries. When installing the unit, take in consideration storms and high winds. Incorrect installation may cause the unit to fall down. All electric work should be carried out by experienced personnel as per current regulations and this manual. Incorrect installation or undersized electric cable may cause electric shock or fire risk. All circuits must be earthed. Ensure that no external forces will affect the terminal block and electric cable. Poor wiring and installation may cause fire risk. Arrange wire connection between connecting the indoor and outdoor power supply correctly. Fix terminal cover firmly to avoid overheating, electric shock or even fire risk. In the case of a refrigerant leakage during unit installation, keep the room well ventilated. Check the unit upon installation. Be sure there is no leakage. Refrigerant will induce a poisonous gas subject to heat. Isolate power supply before touching terminal block.
Incorrect operations may result in severe consequences of death or serious injuries. Incorrect operations may result in injuries or machine damages; in some cases may cause serious consequences.
WARNING
WARNING
All units shall be earthed. The earth must not be connected to a gas pipe, water pipe, or telephone line. Poor earthing could cause electric shock. Be sure to install a circuit breaker to avoid electric shock. Arrange water drainage according to this manual. Cover pipe with insulation materials to prevent condensation occuring. Improper installation of water drainage will cause water leakage.
To maintain good picture or reduce noise, keep the unit at least 1m from T.V. or radio, when installing the communication wire and power supply. (If the radio wave is relatively strong, 1m is not enough to reduce the interference). Do not install the unit in following places: (a) Oil mist or oil gas exists, such as kitchen, or, plastic parts may age, or water leakage. (b) Where there is corrosive gas. Copper tube and welded part may be damaged due to corrosion causing leakage.
3
Page 6
(c) Where there is strong radiation. It will affect the unit's control system, causing malfunction of the unit. (d) Where there are flammable gas, dirt, and volatile matter (thinner, gasoline) exist, these items will cause a fire risk.
Installation accessories
The following accessories are supplied together with the outdoor unit.
No.
1
2
3
Drawing
Name of parts
Drainage elbow
Rubber cushion
Clap
Quantity
1
4
1
Choose the installation place
Place, robust not causing vibration, where the body can be supported sufficiently. Place, not affected by heat or steam generated in the vicinity, where inlet and outlet of the unit are not disturbed. Place, possible to drain easily, where piping can be connected with the outdoor. Place,where cold air can be spread in a room entirely. Place, nearby a power receptacle, with enough space around.(Refer to drawings). Place, where the distance of more than 1m from televisions, radios, wireless apparatuses and fluorescent lamps can be left. In the case of fixing the remote controller on a wall, place where the indoor unit can receive signals when the fluorescent lamps in the room are lightened.
Installation dimensions(mm)
680
319.5
113.5 583
4
113.5
Page 7
Installation drawings of indoor and outdoor units
1. Do not connected the embedded branch piping and the outdoor unit when only carrying out piping work without connecting the indoor unit in ordor to add another indoor unit later. Make sure no dirt or mositure gets into eigher side of the embedded branch piping.
2.It is impossible to connect the indoor unit for one room only. Be sure to connect at least 2 rooms.
Arrangement of piping directions
Rear left
Rear right
Below
Attention must be paid to the rising up of drain hose
Right
More than 10cm
Wrap the insulation pipe with the finishing tape from bottom to top.
Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no gap is left in the insulation pipe's cut line.
More than 5cm
Left
more than 10cm
more than 10cm
more than 25cm
more than 60cm
If there is the danger of the unit falling or overturning, fix the unit with foundation bolts, or with wire or other means. If the location does not have good drainage, place the unit on a level mounting base(or a plastic pedestal). Install the outdoor unit in a level position. Failure to do so may result in water leakage or accumulation.
5
Page 8
Power source
Before inserting power plug into receptacle, check the voltage without fail. The power source is the same as the corresponded name plate. Install an exclusive branch circuit of the power. A receptacle shall be set up in a distance where the power cable can be reached. Do not extend the cable by cutting it.
Matching of the indoor and outdoor units
AU182XFERA
Combination
1:2
1:3
A 07 12 09 09 09 12 12 07 07 07 07 07 09 07 07 12 07 09 09 07 09 12 09 09 09 09 09 12
B C
12
Remark
* * *
AU222XFERA
Combination
1:2
1:3
A 07 1 09 09 1 12 07 07 09 07 07 12 07 09 09 07 09 12 09 09 09 09 09 12 09 12 12
B C
4
12
4
12
Remark
* * * *
WARNING!
Combinations those marked * can not be applied where the temperature in winter is too low and in summer is too higher to avoid bad heating or cooling effect.
Limitations on the installation
1.Precautions on installation Check the strength and level of the installation ground so that unit will not cause any operating vibration or noise after installation. In accordance with the foundation drawing in fix the unit securely by means of the foundation bolts. It is best to screw in the foundation bolts unit their length are 20 mm from the foundation surface.
2.Selecting a location for installation of the indoor units The maxinum allowable length of refrigerant piping, and the maxmum allowable height
difference between the outdoor and indoor units, are listed below. (The shorter the refrigerant piping, the better the performance. Connect so that the piping is as short as possible. Shortest allowable length per room is 3m)
6
Page 9
Limitations on the installation
3. Limitations values on the piping work .
L1
L2
A
h
B
H +
L3
The piping length information, please refer the following table.
Item A, B, Cliquid pipe A, B, C Gas pipe L1 (one way) L2 (one way) L3 (one way) L1+L2+L3 m Total liquid piping length h
H + H -
Unit mm
Size of the liquid side connection pipe
mm
Size of the gas side connection pipe
m
Pipe length when the compressor connects with two indoor units
m
Pipe length when the compressor connects with two indoor units
m
Pipe length when the compressor connects only one indoor unit
m
Drop between every two indoor units
m
Drop between the outdoor unit and the indoor unit
m
Drop between the outdoor unit and the indoor unit
Descriptions
C
Standard
6.35
9.52
*10 *10
*10 *30 *45
*1
*5 *5
Maximum
H -
/ /
*25 *25
*25
*5
*15 *10
7
Page 10
Refrigerant piping work
1. Selection of pipe
To this unit, both liquid and gas pipes shall be insulated as they become low temperature in operation. Use optional parts for piping set or pipes covered with equivalent insulation material.
Liquid pipe
Gas pipe
2. Connection of pipe
Apply refrigerant oil on half union and flare nut. To bend a pipe, give the roundness as large as possible not to crush the pipe. Connecting the pipe of gas side firstly makes working easier.
Forced fastening without careful centering may damage the threads and cause a leakage of gas.
6.35mm ( 1/4'' ) x 0.8mm
9.52mm ( 3/8'' ) x 0.8mm
Flare nutHalf union
Torque wrenchSpanner
Pipe Diameter ( ) Liquid Side 6.35mm (1/4'') Gas Side 9.52mm (3/8'') 50N.m
3. Attaching Drain-Elbow
If the drain-elbow is used, please attach it as figure.
Drain elbow
Fastening Torque
18N.m
Hose
8
Page 11
Refrigerant piping work
4.Cutting and Flaring work of piping
Pipe cutting is carried out with a pipe cutter and burs must be removed. After inserting the flare nut, flaring work is carried out.
A
Pipe diameter*
Liquid side Gas side
Flare tooling die
Correct
Incorrect
Lean Damage of flare Crack Partial Too outside
5.On drainage
Please install the drain hose so as to be downward slope without fail. Please don't do the drainage as shown below.
6.35mm(1/4")
9.52mm(3/8")
Less than 5cm
Size A (mm)
0.8~1.5
1.0~1.5
It becomes high midway. The end is immersed in
water
It waves. It gap with the ground
ts too small.
There is the bad smell from a ditch.
Please pour water in the drain pan of the indoor unit, and confirm that drainage is carried out serely to outdoor. In case that the attached drain hose is in a room, please apply heat insulation to it without fail.
9
Page 12
Purging method: to use vacuum pump
Liquid stop valve
1 .Detach the service portis cap of 3-way valve, the valve rod's cap for 2-way valve and 3-way valves, connect the service port into the projection of charge hose (low) for gaugemanifold. Then connect the projection of charge hose (center) for gaugemanifold into vacuum pump.
2 .Open the handle at low in gaugemanifold, operate vacuum pump. If the scale-moves of gause (low) reach vacuum condition in a moment, check 1 again.
3 .Vacuumize for over 15min. And check the level gauge which should read -0.1MPa (-76 cm Hg) at low pressure side. After the completion of vacuumizing, close the handle 'Lo' in the vacuum pump. Check the condition of the scale and hold it for 1-2min. If the scale-moves back in spite of tightening, make flaring work again, then return to the beginning of 3 .
4 .Open the valve rod for the 2-way valve to and an angle of anticlockwise 90 degree. After 6 seconds, close the 2­way valve and make the inspection of gas leakge.
5 .No gas leakage?
In case of gas leakage, tighten parts of pipe connection. If leakage stops, then proceed 6 steps.
6 .Detach the charge hose from the service port, open 2­way valve and 3-way. Turn the valve rod anticlockwise until hitting lightly.
7 .To prevent the gas leakage, turn the service ports cap, the valve rodis cap for 2-way valve and 3-way's a little more than the point where the torque increases suddenly.
2 way valve 3 way valve
Open
Close
2 way valve
If it does not stop gas leakage, discharge whole refrigerants from the service port. After flaring work again and vacuumize, fill up prescribed refrigerant from the gas cylinder.
2 way valve
3 way valve
2 way valve
3 way valve
Gas stop valve
Gauge maifold(R410A)
Vacuum pump(R410A)
0
90
Service port cap
3 way valve
Service port
0
90
for 6 sec.
6
6
Valve rod cap Valve rod cap
CAUTION: If the refrigerant of the air conditioner leaks, it is necessary to make all the refrigerant out. Vacuumize first, then charge the liquid refrigerant into air conditioner according to the amount marked on the name plate.
10
2 way valve
3 way valve
2 way valve
3 way valve
2 way valve
90
10s
3 way valve
6.35mm
To indoor unit A
(1/4")
9.52mm
(3/8")
6.35mm
To indoor unit B
(1/4")
9.52mm
(3/8")
6.35mm
o
(1/4")
9.52mm
(3/8")
To indoor unit C
Page 13
Wiring work
1. Electric wiring Note:
The air conditioner must use special circuit , and wiring by the qualified electrician according to the wiring rules specified in national standard. The grounding wire and the neutral wire shall be strictly separated. Connect the neutral wire with grounding wire is incorrect. The electric leakage breaker must be installed. All the electric wire must be copper wire.When wiring,there shall keep a proper distance between the power line and communication wire to avoid twist together. Otherwise,signal disturbance will occur,and the air conditioner can not operate normally. Power supply: 1PH, 220-230V~, 50Hz. The wiring method of power line is Y connection. If the power line is damaged, in order to avoid risk of electric shock, it must be replaced by the manufacturer or its repair center or other similar qualified person.The connecting cable must be shielded. Fuse: T3.15A 250VAC T25A 250VAC (Please check with the outdoor unit wiring diagram.) Please check the circuit diagram about the fuse replaced.
2. Wiring method Wiring method of orbicular terminals For the connection wire with orbicular terminals, its wiring method is as shown in the right figure: remove the connecting screw, put the screw through the ring on the end of the wire, then connect to the terminal block and fasten screw. Wiring method of straight terminals For the connection wire without orbicular terminals, its wiring method is: loosen the connection screw, and insert the end of the connection wire completely into the Terminal block, then fasten the screw. Slightly pull the wire outwards to confirm it is firmly held.
Correct Pressing
Wrong Pressing
Terminal
block
Wiring Method for
Ring Terminal Block
Pressing
Clamps
Crimp connection method for wires without terminals
Connect the wire with same diameter to the two sides of the terminal
Do not connect the wire with same diameter to the same side
11
Do not connect the wire with different diameters
Page 14
Wiring work
Crimp connection method for connection wire After connection,the wire must be fastened by wire cover. The wire cover shall press on the protection coat of the connection wire,as shown in right top figure. Note:When connecting the wiring,confirm the terminal number of indoor and outdoor units carefully. Incorrect wiring will damage the controller of air conditioner or the unit can not operate.
3. Wiring method of outdoor unit: Power line
Remove the repair board of the outdoor unit and loosen the wire cover A,then put the live wire, neutral wire and grounding wire through the wire cover ,and connect them to terminal block correspon dingly. After connection, fasten wire cover to its previous state. Communication wire of indoor unit. Loosen wire cover , put the communication wire through the wire cover B, and connect them to terminal block correspondingly. After connection, fasten wire cover B to its previous state. Note: Power line and communication wire are provided by consumers themselves.
Terminal block Wire cover A Wire cover B
Valve cover
4. Wiring method of indoor unit
Loosen wire cover and connect the power line and communication wire of indoor unit to the terminal correspondingly. Note: When connecting power line to power supply terminal, please pay attention to the following items: Do not connect the power line with different dimensions to the same connection wire end. Improper contact will cause heat generation. Do not connect the power line with different dimensions to the same grounding wire end. Improper contact will affect protection. Keep a proper distance between the communication wire and the power line. Otherwise, abnormal communication will occur because of disturbance. Do not connect the power line to the connecting end of communication wire. Incorrect connection will cause damage to the connected unit.
12
Page 15
Wiring work
5. Example wiring diagram.
1(L) 2(N)
Indoor unit C
P
Q
Indoor unit B Indoor unit A
BA
C
L N N L
Q
P
(P Q)
20A
1PH, 220-230V~, 50Hz
Power supply cable: H05RN-F 3G 4.0mm Communication cable (Shield wire): H05RN-F 2X1.5mm
Connecting cable : H05RN-F 3G 2.5mm
Outdoor unit
2
2
2
Please refer to the indoor unit installation manual to find detailly how to set and check the communication address. Incorrect address setting will cause abnormal to the system.
The distance between the signal wires and the power cabes should be at least 50mm.
6. After installation, please fill in the following table for easy daily maintenance: Indoor unit NO.
Model of indoor unit Serial no.Room name
A B C
13
Page 16
Test running
Before starting the test running, please confirm the following works have been done successfully.
1) Correct piping work;
2) Correct wiring work;
3) Correct match of indoor and outdoor unit;
4) Proper recharge of refrigerant if needed;
5)Correct indoor unit addresses setting. Make sure that all the stop valves are fully open. Check the voltage supplied to the outdoor and indoor units, please cinfirm that is 230V.
Test running.
1) If the temperature is lower than 16 OC, it is impossible to test cooling with remote controller, and also when the temperature is higher than 30 OC, it is impossible to test heating.
2) To test cooling, set the lowest temperature at 16 OC. To test heating,set the highest temperature, at 30OC.
3) Please check both cooling and heating operation of each unit individually and then also check the simultaneous operation of all indoor units.
4)After ruuning the unit for about 20 minutes, check the indoor unit outlet temperature.
5) After the unit is stopped, or working mode changed, the system will not start again for about 3 minutes.
6)During cooling operation, frost may ocur on the indoor unit or pipes, this is normal.
7) Operate the unit according to the operation manual. Please kindly explain to our customers how to operate through the instruction manual.
Items to confirm
Check items for test run, put mark " in ".
Gas leakage from pipe connection? Heat insulation treatment of pipe connection? Are the connection wiring of indoor and outdoor unit firmly inserted into the terminal block? Is the connection wiring of indoor and outdoor firmly fixed? Is drainage securely arranged? Is the ground wire securely and firmly connected? Is power supply voltage abided by electric code? Is there any noise? Does cooling perform normally? Does room temperature regulator operate normally?
14
Page 17
Trouble shooting
FAILURE CODE
1 Faulty defrost sensor Te Sensor disconnected, or broken, or short circuit 2
3
4
5
6
9
10
11
12
13
15
16
STATE OF LED 5-4-3-2-1
TROUBLE SHOOTING
Faulty sensor Tao Sensor disconnected, or broken, or short circuit
Faulty sensor Ts Sensor disconnected, or broken, or short circuit Faulty sensor Td Sensor disconnected, or broken, or short circuit
Over current of the system, or broken of the current
Input overcurrent
Abnormal communication between indoor and outdoor units
System high pressure protection
System low pressure protection
IPM protection
EEPROM fault Faulty outdoor unit PCB Over hot protection of
compressor
DC fan motor fault Faulty 4-way valve
switching on
sensor,or malfunction with indoor or outdoor fan motors, or faulty PCB. Wrong connection, or the wires be disconnected, or wrong address setting of indoor units, or faulty PCB, or faulty power supply High pressure switch is disconnected, or high pressure switch worked, or Tc too high and faulty outdoor fan motor when cooling, or faulty indoor fan motors when heating, or refrigerant overabundance
Low pressure switch is disconnected, or low pressure switch worked, or Te too low and faulty outdoor fan motors when heating, or faulty indoor fan motor when cooling, or refrigerant shortage
IPM over current, or short circuit, or IPM temperature too high, or IPM input voltage too low,or faulty SPDU.
Serious lack of refrigerant of the system, or the ambient temperature too high, or PMVs be blocked
Fan is blocked, or the terminal is disconnected from the PCB
Coil of 4-way valve is disconnected, or faulty outdoor PCB
POSSIBLE REASONS
17
21
25
26 27 28 29
30 31
Take off the plastic valve cover, you can find the LEDs near to the communication terminal. Symbol means the LED is ON. Symbol means the LED is OFF.
Faulty sensor Tc Sensor disconnected, or broken, or short circuit
Faulty sensor Toci Sensor disconnected, or broken, or short circuit Abnormal communication
between main PCB and SPDU
Compressor be locked Faulty compressor or SPDU Compressor vibration too big Compressor lose position Faulty SPDU Faulty compressor start Faulty compressor or SPDU
Faulty position checking circuit
Compressor broken Faulty compressor or SPDU
Communication cables broken, or not be well connected, or faulty main PCB, or faulty SPDU
Faulty compressor
Faulty SPDU
15
Page 18
HAIER GROUP Qingdao Haier Air Conditioner Electric Co., Ltd. Address: Haier Garden, Qianwangang Road, Economic Development Zone, Qingdao, Shandong 266500, P.R.China Web Site: http://www.haier.com
Loading...