Before using the air conditioner,please read this manual carefully.
Please keep this manual properly for future use.
No. 0010576506C
CONTENTS
Name of Parts------------------------------------------------------------------1
Safety Cautions--------------------------------------------------------------2-7
Read Before Installation--------------------------------------------------8-12
Installation Procedure---------------------------------------------------13-22
Name of Parts
AU182AFERA AU242AGERAAU122AEERA
Air inlet
Air outlet
Compressor
(Inside of unit)
AU282AHERA
AU362AHERA
AU36NAHERA
Air inlet
Air outlet
Compressor
(Inside of unit)
Air inlet
Air outlet
Compressor
AU422AIERA
AU42NAIERA
AU522AIERA
AU52NAIERA
(Inside of unit)
Air inlet
Air outlet
Compressor
(Inside of unit)
1
Safety Cautions
Carefully read the following information in order to operate the air conditioner
correctly.
Below are listed three kinds of Safety Cautions and Suggestions.
WARNING!
CAUTION!
INSTRUCTIONS:
Symbols used in the illustrations
:Indicates an action that must be avoided.
:Indicates that important instructions must be followed.
!
:Indicates a part which must be grounded.
:Beware of electric shock (This sumbol is displayed on the main unit label.)
After reading this handbook, hand it over to those who will be using the unit.
The user of the unit should keep this mamual at hand and make it available to those who will
be performing repairs or relocating the unit.
Also, make it available to the new user when the user changes hands.
Be sure to conform with the following important Safety Cautions.
Incorrect operations may result in severe consequences of death or serious injuries.
Incorrect operations may result in injuries or machine damages; in some cases may
cause serious consequences.
These information can ensure the correct operation of the machine.
WARNING!
If any abnormal phenomena is found
(e. g.smell of firing), please cut off the
power supply immediately, and contact
the dealer to find out the handling
method.
In such case, to continue using the
conditioner will damage the conditioner,
and may cause electrical shock or fire
hazard.
switch
off
After a long time use of air-conditioner
the base should be checked for any
damages.
If the damaged base is not repaired, the
unit may fall down and cause accidents.
Don't dismantle the outlet of the
outdoor unit.
The exposure of fan is very dangerous
whichmay harm human beings.
When need maintenance and repairment,
call dealer to handle it.
Incorrect maintenance and repairment
may cause water leak, electrical shock
and fire hazard.
2
Safety Cautions
WARNING!
Installed electrical-leaking circuit
breaker.
It easily cause electrical shock without
circuit breaker.
Air-conditioner can't be installed in
the environment with inflammable
gases because the inflammable gases
near to air-conditioner may cause fire
hazard.
Please let the dealer be responsible for
installing the conditioner.
Incorrect installation may cause water
leak, electrical shock and fire hazard.
Call the dealer to take measures to
prevent the refrigerant from leaking.
If conditioner is installed in a small
room be sure to take every measure in
order to prevent suffocation accident
even in case of refrigerant leakage.
When conditioner is deinstalled or
reinstalled dealer should be
responsible for them.
Incorrect installation may cause water
leaking, electrical shock and fire hazard.
No goods or nobody is permitted to
placed on or stand on outdoor unit.
The falling of goods and people may
cause accidents.
Don't operate the air-conditioner with
damp hands.
Otherwise will be shocked.
Only use correctly-typed fuse.
May not use wire or any other materials
replacing fuse, other-wise may cause
faults or fire accidents.
Connect earthing wire.
Earthing wire should not be connected to the gas pipe, water pipe,
lightning rod or phone line, incorrect earthing may cause shock.
Earthing
Use discharge pipe correctly to ensure
efficient discharge.
Incorrect pipe use may cause water
leaking.
3
Safety Cautions
Warning !
Have the unit professionally installed.
Improper installation by an unqualified person
may result in water leak, electric shock, or fire.
Place the unit on a stable, level surface that
withstands the weight of the unit to prevent
the unit from tipping over or falling causing
injury as a result.
Only use specified cables for wiring.Securely
connect each cable, and make sure that the
cables are not straining the terminals.
Cables not connected securely and properly may
generate heat and cause fire.
Take necessary safety measures against
typhoons and earthquakes to prevent the
unit from falling over.
Do not make any changes or modifications
to the unit. In case of problems, consult the
dealer.
If repairs are not made properly, the unit may
leak water and present a risk of electric shock, or
it may produce smoke or cause fire.
Be sure to carefully follow each step in this
handbook when installing the unit.
Improper installation may result in water leak,
electric shock, smoke or fire.
Have all electrical work performed by a
licensed electrician according to the local
regulations and the instructions given in
this manual. Secure a circuit designated
exclusively to the unit.
Improper installation or a lack of circuit capacity
may cause the unit to malfunction or present a
risk of electric shock, smoke,and fire.
Securely attach the terminal cover(panel)
on the unit.
If installed improperly, dust and/or water may
enter the unit and present a risk of electric shock,
smoke, or fire.
Only use refrigerant R410A as indicated
on the unit when installing or relocating
the unit.
The use of any other refrigerant or an
introduction of air into the unit circuit may
cause the unit to run an abnormal cycle and
abnormal cycle and cause the unit to burst.
4
Safety Cautions
Warning !
Do not touch the fins on the heat exchanger
with bare hands:they are sharp and
dangerous.
When installing the unit in a small room,
safeguard against hypoxia that results from
leaked refrigerant reaching the threshold
level.
In the event of a refrigerant gas leak,
Consult the dealer for necessary measures to take.
provide adequate ventilation to the room.
If leaked refrigerant gas is exposed to a heat
source, noxious gases may form.
With All-Fresh type air cinditioners, outdoor
air may be directly blown into the room
upon thermo off. Take this into consideration
when installing the unit.
Direct expesure to outdoor air may present a
health hazard, and it may also cause food items
to deteriorate.
Do not try to defeat the safety features of
the devices, and do not change the settings.
Defeating the safety features on the unit such as
the pressure switch and temperature switch or
using parts other than the dealer or specialist
may result in fire or explosion.
When relocating the air conditioner,
consult the dealer or a specialist.
Improper installation may result in water leak,
electric shock, or fire.
After completing the service work, check
for a refrigerant gas leak.
If leaked gas refrigerant is exposed to a heat
source such as fan heater,stove,and electric grill,
noxious gases may form.
Only use specified parts.
Have the unit professionally installed.
Improper installation may cause water leak,
electric shock,smoke, or fire.
Precautions for handling Units for Use with R410A
Caution!
Do not use the existing refrigerant piping
The old refrigerant and refrigerator oil in the
existing piping contain a large amount of
chlorine, which will cause the refrigerator oil in
the new unit to deteriorate.
R410A is a high-pressure refrigerant,and the use
of the existing piping may result in bursting.
Keep the inner and outer surfaces of the
pipes clean and free of contaminants such
as sulfur, oxides, dust/dirt shaving particles,
oils,and moisture.
Contaminants inside the refrigerant piping will
cause the refrigerant oil to deteriorate.
Use a vacuum pump with a reverse-flowcheck valve.
If other types of valves are used, the vacuum
pump oil will flow back into the refrigerant cycle
and cause the refrigerator oil to deteriorate.
Do not use the following tools that have
been used with the conventional
refrigerants. prepare tools that are for
exclusive use with R410A.
(Gauge manifold, charging hose, gas leak
detector,reverse-flow check valve,
refrigerant charge base,vacuum gauge,
and refrigerant recovery equipment.)
If refrigerant and/or refrigerant oil left on these
tools are mixed in with R410, or if water is
mixed with R410A, it will cause the refrigerant
to deteriorate.
Since R410A does not contain chlorine, gas-leak
detectors for conventional refrigerators will not
work.
5
Safety Cautions
Caution!
Store the piping to be used during
installation indoors, and keep both ends of
the piping sealed until immediately before
brazing.(keep elbows and other joints
wrapped in plastic.)
If dust, dirt, or water enters the refrigerant cycle,
it may cause the oil in the unit to deteriorate or
may cause the compressor to malfunction.
Use a small amount of ester oil,ether oil, or
alkylbenzene to coat flares and flange
connections.
A large amount of mineral oil will cause the
refrigerating machine oil to deteriorate.
Use lipuid refrigerant to charge the system.
Charge the unit with gas refrigerant will cause
the refrigerant in the cylinder to change its
composition and will lead to a drop in
performance
Before Installing the Unit
Warning!
Do not use a charging cylinder.
The use of charging cylinder will change the
composition of the refrigerant and lead to power
loss.
Exercise special care when handling the
tools.
An introduction of foreign objects such as dust,
dirt, or water into the refrigerant cycle will cause
the refrigerating machine oil to deteriorate.
Only use R410A refrigerant.
The use of refrigerants containing chlorine(i.e.
R22) will cause the refrigerant to deteriorate.
Do not install the unit in a place where there
is a possibility of flammable gas leak.
Leaked gas accumulated around the unit may
start a fire.
Do not use the unit to preserve food,
animals, plants,artifacts, or for other special
purposes.
The unit is not designed to provide adepuate
conditions to preserve the quality of these items.
Do not use the unit in an unusual
environment
The use of the unit in the presence of a large
amount of oil, steam,acid, alkaline solvents,or
special types of sprays may lead to a remarkable
drop in performance and/or malfunction and
presents a risk of electric shock, smoke, or fire.
The presence of organic solvents, corroded gas
(such as ammonia,sulfur compounds,and acid
may cause gas or water leak.)
When installing the unit in a hospital,take
necessary measures against noise.
High-frequency medical equipment may interfere
with the normal operation of the air conditioning
unit or the air conditioning unit may interfere
with the normal operation of the medical
equipment
Do not place the unit on or over things that
may not get wet.
When humidity level exceeds 80% or when the
drainage system is clogged, indoor units may drip
water.
Installation of a centralized drainage system for
the outdoor unit may also need to be considered
to prevent water drips from the outdoor units.
6