Haier AC182XCERA, AB142XCERA, AD092XLERA, AB122XCERA, AD122XLERA Service Manual

...
SERVICE MANUAL
X MULTI SERIES
4-WAY CASSETTE INDOOR UNIT
CONVERTIBLE INDOOR UNIT
CONSOLE INDOOR UNIT
DUCT INDOOR UNIT
WALL MOUNTED INDOOR UNIT
Haier Commercial Air Conditioner
Version: 200708
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
-2-
CONTENT
1.General information --------------------------------------------------------------------------------------------- 3
1.1 X Multi series line up -----------------------------------------------------------------------------------------
-
3
1.2 Operation temperature range -----------------------------------------------------------------------------
-
3
1.3 Product features ----------------------------------------------------------------------------------------------
-
4
2.Specifications ---------------------------------------------------------------------------------------------------- 6
3.Dimension --------------------------------------------------------------------------------------------------------
-
17
4.Pipe and wiring installation ----------------------------------------------------------------------------------- 21
4.1 Conbination of indoor and outdoor units ---------------------------------------------------------------
-
21
4.2 Wiring connection --------------------------------------------------------------------------------------------
-
31
4.3 Limitation on the installation ------------------------------------------------------------------------------- 34
4.4 Outdoor unit installation ------------------------------------------------------------------------------------
-
37
4.5 Cassette type installation ----------------------------------------------------------------------------------
-
44
4.6 Convertible type installation -------------------------------------------------------------------------------
-
51
4.7 Duct type installation ----------------------------------------------------------------------------------------
-
64
4.8 Console type installation -----------------------------------------------------------------------------------
-
74
4.9 Wall mounted type installation ----------------------------------------------------------------------------
-
81
5.PCB photo,wiring diagram and function description ---------------------------------------------------
-
85
5.1 Outdoor unit ----------------------------------------------------------------------------------------------------
-
85
5.1.1 Outdoor PCB photo ---------------------------------------------------------------------------------------
-
85
5.1.2 Outdoor wiring diagram ----------------------------------------------------------------------------------
-
86
5.1.3 PCB function description --------------------------------------------------------------------------------
-
90
5.2 Indoor unit ------------------------------------------------------------------------------------------------------
-
90
5.2.1 Cassette and duct type PCB photo -------------------------------------------------------------------
-
90
5.2.2 Cassette and duct type wiring diagram --------------------------------------------------------------
-
98
5.2.3 Convertible type PCB photo ----------------------------------------------------------------------------
-
100
5.2.4 Convertible type wiring diagram -----------------------------------------------------------------------
-
101
5.2.5 Converible type PCB function description ----------------------------------------------------------- 102
5.2.6 Console type PCB ----------------------------------------------------------------------------------------- 108
5.2.7 Console type wiring diagram ---------------------------------------------------------------------------
-
109
5.2.8 Console type PCB function description --------------------------------------------------------------
-
110
5.2.9 Wall mounted type PCB photo -------------------------------------------------------------------------
-
111
5.2.10 Wall mounted type wiring diagram ------------------------------------------------------------------
-
112
5.2.11 Wall mounted type PCB function description -----------------------------------------------------
-
114
6.Diagnostic code -------------------------------------------------------------------------------------------------
-
117
6.1.1 Outdoor unit diagnostic code ---------------------------------------------------------------------------
-
117
6.1.2 Cassette type and convertible type diagnostic code ---------------------------------------------
-
118
6.1.3 Duct type diagnostic code -------------------------------------------------------------------------------
-
119
6.1.4 Console type diagnostic code --------------------------------------------------------------------------
-
121
6.1.5 Wall mounted type diagnostic code ------------------------------------------------------------------- 122
6.2 Trouble shooting ---------------------------------------------------------------------------------------------
-
123
7.Assistant software ----------------------------------------------------------------------------------------------
-
126
8.Performance curves -------------------------------------------------------------------------------------------
-
127
9. Indoor air velocity and temperature distribution---------------------------------------------------------
-
133
9.1 AB092-182XCERA -------------------------------------------------------------------------------------------
-
133
9.2 AC142-182XCERA -------------------------------------------------------------------------------------------
-
135
9.3 AF092-122XCERA -------------------------------------------------------------------------------------------
-
139
9.4 Wall mounted type -------------------------------------------------------------------------------------------- 141
10. Air flow and static pressure chart -------------------------------------------------------------------------
-
142
-3-
.9773:1506 -5: .9825;5983:
JK@IB[LNVJ JKABB[LNVJ JKADB[LNVJ JKAHB[LNVJ
JLADB[LNVJ JLAHB[LNVJ
JM@IB[SNVJ JMABB[SNVJ JMADB[SNVJ JMAHB[SNVJ
JO@IB[LNVJ JOABB[LNVJ
JW@GB[YNVJ JW@IB[YNVJ JWABB[YNVJ JWAHB[YNVJ
A?C Ug`h\jbfe j`dg`h\jkh` h\ea`
JXAHB[ONVJ JXBBB[ONVJ
Lffcbea
Q`\jbea
Re_ffh
fkj_ffh
V\j`_ T\nbdkd Tbebdkd
BG CB AE
AI BC AD
CE DC >E
BD BF F
B@ BG A@
AD?E >> >>
G BC >A@
FAH >>
MK L
ZK L
MK L
ZK L
Re_ffh
fkj_ffh
MK L
ZK L
MK L
ZK L
bel`hj`h ibeac` kebj= ikg`h cfm \d]b`ej j`dg? ^ffcbea
JXBEB[PNVJ
JXBHB[QNVJ JXCDB[QNVJ JXCFB[QNVJ
,+ /383:06 5849:70;598
A?A rpqvtus i`hb`i cbe` kg
Commercial Air Conditioner
1 .3 Product features
High efficienct, universal outdoor unit
The outdoor unit can match with cassette type ,duct type, convertible type, console type and wall mounted type indoor unit. Outdoor unit can match with multiple indoor units. Even when you have already installed the air conditioner, if you want to add or reduce one unit, go ahead freely as long as your operation complies with our design. Greatly convenient for designer and installer.
Total indoor load can be up to 135% than the standard match
The total capacity of all indoor units can be 135% more than the nominal cooling capacity, but the total indoor cooling capacity will not be increased.
Newly designed V- appearance indoor unit
The wall mounted type indoor unit adopts the newly designed V appearance, more fashion, more beautiful. The unit is designed with the health airflow and sterilize function, which will make the air more healthy. Also the air blow direction can be set as step or stepless control, much convenient to control.
Newly designed guarding plate of valve
In order to protect the valve against the dust, the rain or the snow, etc. we add a guarding plate to the
valve.
Adopt the much friendlier refrigerant R410a
The air conditioner system adopts the greatly friendly refrigerant R410a, which is protective for the ozone layer and is good to avoid the earth getting warmer. Benefit for the environment.
Adopt the advanced DC inverter technology
The system adopts the advanced DC inverter technology, which can consume less power energy to realize the equal efficiency, saving money for you.
With air inlet filter, enhance the air quality
The high efficiency filter can collect the dirt and remove the bacterium, which can be installed on the easy-to-unload place, convenient to be cleaned.
Convenient infrared remote controller
This remote controller YR-H65 can realize the healthy air flow and sterilize function, it is mobile type appearance, so smart and compact. And the infrared controller can be equipped with the controller holder, convenient to fix the remote controller.
Auto
restart function (optional)
All indoor units have auto-restart function. When the power supply cut off suddenly, the unit will automatically recover the previous running mode once the power supply is on.
-4-
Commercial Air Conditioner
Self-diagnostic function
In the course of operation, if the failure occurs, the failure code will display on the wired controller
or on the operation panel. Then according to the failure code chart, you can eliminate the failure soon.
Central control function, if connected with a detector and a central controller
That is convenient for building management.
Adjustable heating temperature compensation
In heating mode, the temperature compensation can be adjusted by the remote controller. If you do not want the compensation, you can set the compensation as 0 degree.
Software for diagnostic installation
After installation, you can use file "X-MULTI Setup Assistant " to know the installation is OK or not, if system has error, software will give you trouble shooting.
-5-
2. Specifications
-6-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
——
Cooling Heating
W 5300 7000 W 1650 1800
A 7.3 8.0
W/W
3.21 3.89 W 1500 1800 W 500 500 W
5800 7300
W
2300 2300 —— A / A 10.2 10.2 —— 99% 99%
A Model / Manufacture —— Oil charge and type —— Type —— Number —— Type × Number —— Speed r/min Motor output/input power W Air-flows (H/M/L) m³/h Type / Diameter mm Face area m² External mm Package mm
—— ——
W Noise level H/M/L dB(A) Weight Net / Shipping kg / kg
Type / Charge kg No need to recharge m Recharge g/m Liquid mm Gas mm
—— Max.Drop between IU & OU m Max.Drop between IU & OU m Max.Drop between indoor units m Max.Piping length between IU & OU m Max.Total liquid piping length
m
2. Large drop and long piping installation will obviously reduce the totao capacity.
1. The above performance data are from the combination of AU182XFERA+2*AS092XVERA+AS122XVERA.
51/-/-
54 / 60
Piping
Refrigerant R410A / 2.0
Connecting method
Flared
30 20
10(indoor unit lower than outdoor unit)
25
15 (indoor unit higher than outdoor unit)
5
Pipe 3* Φ6.35
3* Φ9.52
45
35
Refrigerant control method PMVs Defrosting method Automatic by reversible cycle
Axial × 1
870CC, MEL 56
928/288/680
1015/405/760
850 / 700 / 500
35/85
about 3000
TP2M / 7.0
about 0.52
Compressor
Dimension (WxDxH)
Heat exchanger
Crankcase heater power
TNB175FLBM / MELCO
Twin Rotary (DC inverter)
1
25
Item Model AU182XFERA
Function
Power source 1PH, 220-230V~, 50Hz
Rating capacity
Maximum capacity Power input (indoor + outdoor)
EER / COP
Between I.U &O.U
Power input (indoor + outdoor)
Minimum capacity Power input
Power facor(under rating power input)
Max.Running current (indoor + outdoor)
Current input (indoor + outdoor)
Fan
Fuse size (recommended size)
Outdoor unit
-7-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
——
Cooling Heating
W 6400 7300 W 2100 2000
A 9.3 8.9
W/W
3.04 3.65
W 1500 1800 W 500 500 W
6800 7500
W
2900 2900
—— A / A 12.9 12.9 —— 99% 99%
A Model / Manufacture —— Oil charge and type —— Type —— Number —— Type × Number —— Speed r/min Motor output/input power W Air-flows (H/M/L) m³/h Type / Diameter mm Face area m² External mm Package mm
—— ——
W Noise level H/M/L dB(A) Weight Net / Shipping kg / kg
Type / Charge kg No need to recharge m Recharge g/m Liquid mm Gas mm
—— Max.Drop between IU & OU m Max.Drop between IU & OU m Max.Drop between indoor units m Max.Piping length between IU & OU m Max.Total liquid piping length
m
2. Large drop and long piping installation will obviously reduce the totao capacity.
Between I.D &O.D
5 25 45
1. The above performance data are from the combination of AU222XFERA+AS092XVERA+2*AS122XVERA.
Connecting method
Flared
10(indoor unit lower than outdoor unit)
15 (indoor unit higher than outdoor unit)
55/-/-
54 / 60
Piping
Refrigerant R410A / 2.0
30 20
Pipe 3* Φ6.35
3* Φ9.52
Defrosting method
Automatic by reversible cycle
Crankcase heater power 35
Dimension (WxDxH)
928/288/680
1015/405/760
Refrigerant control method PMVs
about 3200
Heat exchanger TP2M / 7.0
about 0.52
Outdoor unit
Compressor
TNB175FLBM / MELCO
870CC, MEL 56
Twin Rotary (DC inverter)
1
Fan
Axial × 1
960 / 700 / 500
35/100
Max.Running current (indoor + outdoor) Power facor(under rating power input) Fuse size (recommended size)
25
Maximum capacity Power input (indoor + outdoor) Power source
1PH, 220-230V~, 50Hz
Power input (indoor + outdoor)
EER / COP Minimum capacity Power input
Current input (indoor + outdoor)
Item Model AU222XFERA
Function Rating capacity
——
Cooling Heating
W 7250 8000 W 2250 2200
A 10.4 10.4
W/W
3.22 3.64
W 1500 1800 W 500 500 W
8200 9000
W
3200 3000
—— A / A 14.3 13.5 —— 99% 99%
A Model / Manufacture —— Oil charge and type —— Type —— Number —— Type × Number —— Speed r/min Motor output/input power W Air-flows (H/M/L) m³/h Type / Diameter mm Face area m² External mm Package mm
—— ——
W Noise level H/M/L dB(A) Weight Net / Shipping kg / kg
Type / Charge kg No need to recharge m Recharge g/m Liquid mm Gas mm
—— Max.Drop between IU &OU m Max.Drop between IU & IU m Max.Drop between IU & OU
m Max.Piping length between IU & OU m Max.Total length
m
Item Model AU252XGERA
Function Rating capacity Power input (indoor + outdoor) Current input (indoor + outdoor) EER / COP Minimum capacity Power input Maximum capacity Power input (indoor + outdoor) Power source
1PH, 220-230V~, 50Hz
Max.Running current (indoor + outdoor) Power facor(under rating power input) Fuse size (recommended size)
30
Outdoor unit
Compressor
TNB175FLBM / MELCO
870CC
DC TWIN ROTARY
1
Fan
Axial × 1
930 / 700 / 500
98/200
about 3400
Heat exchanger TP2M / 7.0
about 0.67
Dimension (WxDxH)
976/335/732
1065/420/815
Refrigerant control method PMVs Defrosting method Automatic by reversible cycle Crankcase heater power 35
1. The above performance data are from the combination of AU252XGERA+3*AD092XLERA
2. Large drop and long piping installation will obviously reduce the total capacity.
Connecting method
Flared
5
Piping
Refrigerant
60
Pipe 4* Φ6.35
Between I.D &O.D
15 (indoor unit higher than outdoor unit)
57/-/-
58 / 64
R410A / 2.5
30 20
4* Φ9.52
25
10(indoor unit lower than outdoor unit)
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
-8-
-9-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
——
Cooling Heating
W 8000 10000 W 2480 2700
A 11.0 11.9
W/W
3.22 3.70
W 1500 1800 W 550 550 W
9500 11000
W
3800 3800
——
A / A 16.8 16.8
—— 99% 99%
A Model / Manufacture —— Oil charge and type —— Type —— Number —— Type × Number —— Speed r/min Motor output/input power W Air-flows (H/M/L) m³/h Type / Diameter mm Face area m² External mm Package mm
—— ——
W Noise level H/M/L dB(A) Weight Net / Shipping kg / kg
Type / Charge kg No need to recharge m Recharge g/m Liquid mm Gas mm
—— Max.Drop between IU &OU m Max.Drop between IU & IU m Max.Drop between IU & OU
m Max.Piping length between IU & OU m Max.Total length
m
1. The above performance data are from the combination of AU282XHERA+2*AS092XVERA+2*AS122XVERA.
2. Large drop and long piping installation will obviously reduce the total capacity.
Item Model AU282XHERA
Function Rating capacity Power input (indoor + outdoor)
EER / COP Minimum capacity Power input Maximum capacity Power input (indoor + outdoor) Power source
1PH, 220-230V~, 50Hz
Max.Running current (indoor + outdoor) Power facor(under rating power input) Fuse size (recommended size)
30
Compressor
TNB220FLBM / MELCO
870CC
Twin Rotary (DC inverter)
1
about 4000
Heat exchanger TP2M / 7.0
about 0.75
Fan
Axial × 1
850 / 700 / 500
60/150
Dimension (WxDxH)
1068x340x830 1100x440x979
Refrigerant control method
PMVs
Defrosting method
Automatic by reversible cycle
Crankcase heater power
35
74 / 89
Piping
Refrigerant R410A / 2.6
40 20
Pipe 4* Φ6.35
4* Φ9.52
Outdoor unit
Between I.D &O.D
Current input (indoor + outdoor)
Connecting method
Flared
5
10(indoor unit lower than outdoor unit)
15 (indoor unit higher than outdoor unit)
25
60
58/-/-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
-10-
——
Cooling Heating
W 10000 11000 W 3200 3200
A 14.3 14.3
W/W
3.13 3.44
W 1500 1800 W 550 550 W
11000 11500
W
4000 4000
—— A / A 18.1 18.1 —— 99% 99%
A Model / Manufacture —— Oil charge and type —— Type —— Number —— Type × Number —— Speed r/min Motor output/input power W Air-flows (H/M/L) m³/h Type / Diameter mm Face area m² External mm Package mm
—— ——
W Noise level H/M/L dB(A) Weight Net / Shipping kg / kg
Type / Charge kg No need to recharge m Recharge g/m Liquid mm Gas mm
——
Drop between IU & OU
m
Piping length between IU & OU
m
Total liquid piping length
m Max.Drop between IU &OU m Max.Drop between IU & IU m Max.Piping length between IU & OU m Max.Total length
m
Item Model AU342XHERA
Function Rating capacity Power input (indoor + outdoor) Current input (indoor + outdoor) EER / COP Minimum capacity Power input Maximum capacity Power input (indoor + outdoor) Power source
1PH, 220-230V~, 50Hz
Max.Running current (indoor + outdoor) Power facor(under rating power input) Fuse size (recommended size)
30
Outdoor unit
Compressor
TNB220FLBM / MELCO
870CC
Twin Rotary (DC inverter)
1
Fan
Axial × 1
990/ 840/ 590
130/300
about 4300
Heat exchanger TP2M / 7.0
about 0.75
Dimension (WxDxH)
1068x340x830 1100x440x979
Refrigerant control method PMVs
60
Defrosting method
Automatic by reversible cycle
Crankcase heater power 35
Pipe 4* Φ6.35
4* Φ9.52
25
10(indoor unit lower than outdoor unit)
1. The above performance data are from the combination of AU342XHERA+2*AD092XLERA+2*AD122XLERA.
2. Large drop and long piping installation will obviously reduce the total capacity.
Connecting method
Flared
Between I.D &O.D
51040
Piping
Refrigerant
15 (indoor unit higher than outdoor unit)
59/-/-
74 / 89
R410A / 3.0
40 20
——
Cooling Heating
W 10000 11000 W 3200 3200
A 14.3 14.3
W/W
3.13 3.44
W 1500 1800 W 550 550 W
11000 11500
W
4000 4000
——
A / A 18.1 18.1
—— 99% 99%
A Model / Manufacture —— Oil charge and type —— Type —— Number —— Type × Number —— Speed r/min Motor output/input power W Air-flows (H/M/L) m³/h Type / Diameter mm Face area m² External mm Package mm
—— ——
W Noise level H/M/L dB(A) Weight Net / Shipping kg / kg
Type / Charge kg No need to recharge m Recharge g/m Liquid mm Gas mm
——
Drop between IU & OU
m
Piping length between IU & OU
m
Total liquid piping length
m Max.Drop between IU &OU m Max.Drop between IU & IU m Max.Piping length between IU & OU m Max.Total length
m
Item Model AU362XHERA
Function Rating capacity Power input (indoor + outdoor) Current input (indoor + outdoor) EER / COP Minimum capacity Power input Maximum capacity Power input (indoor + outdoor) Power source
1PH, 220-230V~, 50Hz
Max.Running current (indoor + outdoor) Power facor(under rating power input) Fuse size (recommended size)
30
Outdoor unit
Compressor
TNB220FLBM / MELCO
870CC
Twin Rotary (DC inverter)
1
Fan
Axial × 1
990/ 840/ 590
130/300
about 4300
Heat exchanger TP2M / 7.0
about 0.75
Dimension (WxDxH)
1068x340x830 1100x440x979
Refrigerant control method PMVs
60
Defrosting method
Automatic by reversible cycle
Crankcase heater power 35
Pipe 5* Φ6.35
5* Φ9.52
25
10(indoor unit lower than outdoor unit)
1. The above performance data are from the combination of AU362XHERA+2*AD092XLERA+2*AD122XLERA.
2. Large drop and long piping installation will obviously reduce the total capacity.
Connecting method
Flared
Between I.D &O.D
51040
Piping
Refrigerant
15 (indoor unit higher than outdoor unit)
59/-/-
74 / 89
R410A / 3.0
40 20
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
-11-
-12-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
——
Cooling Heating Cooling Heating
W
2000 2300 2500 2900 —— ——
10³×m³/h
1.0 / 1.0 /
N, V, Hz
A / A 0.15 0.15 0.15 0.15
Type × Number —— Speed r/min Motor output/input power W Air-flows (H/M/L) m³/h Type / Diameter mm Face area m² External mm Package mm
Drainage pipe material, diameter mm
—— ——
Noise level H/M/L dB(A) Weight Net / Shipping kg / kg Refrigerant
Type —— Liquid mm Gas mm
——
——
Cooling Heating Cooling Heating
W
3200 3800 5000 5500
10³×m³/h
1.6 / 2.0 / —— ——
N, V, Hz
A / A 0.15 0.15 0.25 0.25
Type × Number —— Speed r/min Motor output/input power W Air-flows (H-M-L) m³/h Type / Diameter mm Face area m² External mm Package mm
Drainage pipe material, diameter mm
—— ——
Noise level H/M/L dB(A) Weight Net / Shipping kg / kg Refrigerant
Type —— Liquid mm Gas mm
——
Piping
Pipe
Connecting method
7.6/10.6 R410A
Flared
Refrigerant control
PMV on outdoor unit
12/15
Fan
Heat exchanger
Dimension (L×W×H)
Controller type
962*365*312
Controller type
TP2M / 7×0.35
16/40 25/40
39/36/33 42/40/37
PVC, 11.4/16.4
795×197×265
870*225*305
880×315×330
Infrared (YR-H65)
1250/1150/1050 1200/1050/950
550/480/430 600/550/500
1, 220~230, 50
CROSS×1 CROSS×1
Running current
Fan
Heat exchanger
Dimension (L×W×H)
about 0.20 about 0.20
Function Capacity Dehumidifying capacity
Power source
Power cable
6.35
9.52
Item
AS122XVERA AS182XVERA
Piping
Pipe
Connecting method
6.35
9.52
PMV on outdoor unit
7.6/10.6 7.6/10.6
36/33/30 38/34/31
Item Model
16/40
480/430/380 520/450/390
Power source
1,220-230~, 50
Running current
CROSS×1 CROSS×1
1150/1050/950
R410A R410A
Capacity
Dehumidifying capacity
about 0.15 about 0.15
TP2M / 7×0.35
880×315×330
PVC, 11.4/16.4
Refrigerant control
795*197*265 795×197×265
880×315×330
Function
AS072XVERA AS092XVERA
1200/1100/1000
16/40
Flared
R410A
6.35 6.35
9.52 12.7
3 × (1.0~1.5mm2 )
Communication cable
2x(0.75~1.25mm2 ), must be shieled
Power cable
3 × (1.0~1.5mm2 )
Communication cable
2x(0.75~1.25mm2 ), must be shieled
Flared Flared
Infrared (YR-H65)
-13-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
——
Cooling Heating Cooling Heating
W
2500 2900 3500 3800
10³×m³/h
1.0 / 1.2 / —— ——
N, V, Hz
A 0.45 0.45 0.45 0.45 Type × Number —— Speed r/min Motor output/input power W Air-flows (H/M/L) m³/h Type / Diameter mm Face area m² Temp. scope
External mm Package mm
Drainage pipe material, diameter mm
—— —— mm
—— Noise level H/M/L dB(A) Weight Net / Shipping kg / kg Refrigerant
Type —— Liquid mm Gas mm
——
External mm Package mm
Weight Net / Shipping
kg / kg
——
Cooling Heating Cooling Heating
W
4100 4600 5000 5500
10³×m³/h
1.6 / 2 / —— ——
N, V, Hz
A 0.45 0.45 0.45 0.45 Type × Number —— Speed r/min Motor output/input power W Air-flows (H/M/L) m³/h Type / Diameter mm Face area m² Temp. scope
External mm Package mm
Drainage pipe material, diameter mm
—— —— mm
—— Noise level H/M/L dB(A) Weight Net / Shipping kg / kg Refrigerant
Type —— Liquid mm Gas mm
——
External mm Package mm
Weight Net / Shipping
kg / kg
* o.d.=outer diameter; i.d.=inner diameter
Connecting method Flared Flared
Panel
Dimension 700/700/60 700/700/60
740/750/115 740/750/115
2.8/4.8 2.8/4.8
19/23.5 19/23.5
Piping
R410A R410A
Pipe 6.35 6.35
12.7 12.7
Electricity Heater / /
44/40/37 44/40/37
PMV on outdoor unit
Fresh air hole dimension 100 100
570/570/260
718/680/380 718/680/380
PVC, 32/26(o.d./I.d.*) PVC, 32/26(o.d./I.d.*)
670/600/550
Heat exchanger 7 7
about 0.273 about 0.273
cooling: 6~7 / heating: 43~60
CENTRIFUGAL × 1
750/650/540 750/650/540
38/95 38/95
Running current
Fan CENTRIFUGAL × 1
670/600/550
Dimension (L×W×H)
570/570/260
Controller type Infrared YR-H71 or wired YR-E12 Refrigerant control
3 × 0.75mm
2
Communication cable
2x(0.75~1.25mm2 ), must be shieled
Power source 1, 220~230, 50
Function Capacity Dehumidifying capacity Power cable
2.8/4.8
Item Model
AB142XCERA AB182XCERA
Connecting method Flared Flared
Panel
Dimension (L×W×H)
700/700/60 700/700/60
740/750/115 740/750/115
2.8/4.8
17/20 17/20
Piping
R410A R410A
Pipe 6.35 6.35
9.52 9.52
Electricity Heater / /
41/39/38 44/40/37
PMV on outdoor unit
Fresh air hole dimension 100 100
570/570/260
718/680/380 718/680/380
PVC, 32/26(o.d./I.d.*) PVC, 32/26(o.d./I.d.*)
670/600/550
Heat exchanger 7 7
about 0.273 about 0.273
cooling: 6~7 / heating: 43~60
CENTRIFUGAL × 1
650/570/520 750/650/540
38/95 38/95
Running current
Fan CENTRIFUGAL × 1
620/560/530
Dimension (L×W×H)
570/570/260
Controller type Infrared YR-H71 or wired YR-E12 Refrigerant control
Communication cable
2x(0.75~1.25mm2 ), must be shieled
Power source 1, 220~230, 50
Capacity Dehumidifying capacity Power cable
3 × (1.0~1.5mm2 )
Item Model
AB092XCERA AB122XCERA
Function
-14-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
——
Cooling Heating Cooling Heating
W
2500 2900 3500 3800
10³×m³/h
1.0 / 1.2 /
—— ——
N, V, Hz
A 0.35 0.35 0.35 0.35 Type × Number —— Speed r/min Motor output/input power W Air-flows (H/M/L) m³/h Type / Diameter mm Face area m² Temp. scope
External mm Package mm
Drainage pipe material, diameter mm
—— ——
mm
—— Noise level H/M/L dB(A) Weight Net / Shipping kg / kg Refrigerant
Type —— Liquid mm Gas mm
——
——
Cooling Heating Cooling Heating
W 4100 4600 5000 5500
10³×m³/h
1.6 / 2.0 /
——
——
N, V, Hz
A 0.85 0.85 0.85 0.85 Type × Number —— Speed r/min Motor output/input power W Air-flows (H/M/L) m³/h Type / Diameter mm Face area m² Temp. scope
External mm Package mm
Drainage pipe material, diameter mm
—— ——
mm
—— Noise level H/M/L dB(A) Weight Net / Shipping kg / kg Refrigerant
Type —— Liquid mm Gas mm
——
* o.d.=outer diameter; i.d.=inner diameter
Item Model AD092XLERA AD122XLERA
Function Capacity Dehumidifying capacity Power cable
3 × (1.0~1.5mm2 )
Communication cable 2x(0.75~1.25mm
2
), must be shieled
Power source
1, 220~230, 50
Running current
Fan CROSS × 1
550/500/450/400
Dimension (L×W×H)
610×500×220
Controller type
Wired controller YR-E12
Refrigerant control
CROSS × 1
1050/950/850/750 1050/950/850/750
30/75 30/75
550/500/450/400
Heat exchanger 7 7
about 0.12 about 0.12
cooling: 6~7 / heating: 43~60
610×500×220
695/536/265 695/536/265
(o.d./I.d.*) (o.d./I.d.*)
PMV on outdoor unit
Fresh air hole dimension
//
Electricity Heater
//
43/40/38/35 43/40/38/35
14/16 14/16
Piping
R410A R410A
Pipe 6.35 6.35
9.52 9.52
Item Model AD142XLERA AD182XLERA
Connecting method
Flared Flared
Function Capacity Dehumidifying capacity Power cable
3 × 0.75mm
2
Communication cable 2x(0.75~1.25mm
2
), must be shieled
Power source
1, 220~230, 50
Running current
Fan CROSS × 2
780/700/650/600
Dimension (L×W×H)
1090×500×220
Controller type
Wired YR-E12
Refrigerant control
CROSS × 2
1270/1160/1020/900 1270/1160/1020/900
80/200 80/200
780/700/650/600
Heat exchanger 7 7
about 0.23 about 0.23
cooling: 6~7 / heating: 43~60
Fresh air hole dimension
//
1090×500×220
1161/536/269 1161/536/269
(o.d./I.d.*) (o.d./I.d.*)
Flared
25/29 25/29
PMV on outdoor unit
Electricity Heater
//
46/44/40/38 46/44/40/38
Piping
R410A R410A
Pipe 6.35 6.35
12.7 12.7
Connecting method
Flared
-15-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
——
Cooling Heating Cooling Heating
W
4100 4600 5000 5500
10³×m³/h
1.6 / 2 /
—— ——
N, V, Hz
A 0.45 0.45 0.45 0.45 Type × Number —— Speed r/min Motor output/input power W Air-flows (H/M/L) m³/h Type / Diameter mm Face area m² Temp. scope
External mm Package mm
Drainage pipe material, diameter mm
—— ——
mm
—— Noise level H/M/L dB(A) Weight Net / Shipping kg / kg Refrigerant
Type —— Liquid mm Gas mm
——
* o.d.=outer diameter; i.d.=inner diameter
Piping
R410A R410A
Pipe 6.35 6.35
12.7 12.7
Connecting method
Flared
Electricity Heater
//
48/45/41 48/45/41
Flared
28.3/34.3 28.3/34.3
PMV on outdoor unit
Fresh air hole dimension
//
990/655/199
1150/750/300 1150/750/300
PVC, 20/18(o.d./I.d.*) PVC, 20/18(o.d./I.d.*)
700/640/580
Heat exchanger TP2M / 7×0.35
about 0.49 about 0.49
cooling: 6~7 / heating: 43~60
CENTRIFUGAL × 2
1150/1050/850 1150/1050/850
28/80 28/80
Running current
Fan CENTRIFUGAL × 2
700/640/580
Dimension (L×W×H)
990/655/199
Controller type
Infrared YR-H71 or wired YR-E12
Refrigerant control
Communication cable
2x(0.75~1.25mm2 ), must be shieled
Power source
1, 220~230, 50
Capacity Dehumidifying capacity Power cable
3 × 0.75mm
2
Item Model AC142XCERA AC182XCERA
Function
-16-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
——
Cooling Heating Cooling Heating
W
2500 2900 3500 3800
10³×m³/h
1.0 / 1.2 / —— ——
N, V, Hz
A 0.45 0.45 0.45 0.45 Type × Number —— Speed r/min Motor output/input power W Air-flows (H/M/L) m³/h Type / Diameter mm Face area m² Temp. scope
External mm Package mm
Drainage pipe material, diameter mm
—— ——
mm
—— Noise level H/M/L dB(A) Weight Net / Shipping kg / kg Refrigerant
Type —— Liquid mm Gas mm
——
* o.d.=outer diameter; i.d.=inner diameter
Item Model AF092XCERA AF122XCERA
Function Capacity Dehumidifying capacity Power cable
3 × (1.0~1.5mm2 )
Communication cable 2x(0.75~1.25mm
2
), must be shieled
Power source
1, 220~230, 50
Running current
Fan CROSS × 2
480/420/370
Dimension (WxDxH)
720/205/630
Controller type
Infrared YR-H71
Refrigerant control
CROSS × 2
1000/900/800 1050/950/850
50/100 50/100
510/450/400
Heat exchanger TP2M / 7×0.35
about 0.25 about 0.25
cooling: 6~7 / heating: 43~60
Fresh air hole dimension
//
720/205/630
780/280/690 780/280/690
PVC, 16.4/11.4(o.d./I.d.*) PVC, 16.4/11.4(o.d./I.d.*)
Flared
17/20.7 17/20.7
PMV on outdoor unit
Electricity Heater
//
40/38/36 41/39/37
Piping
R410A R410A
Pipe 6.35 6.35
9.52 9.52
Connecting method
Flared
-17-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
AU182XFERA,AU222XFERA
3. Dimension
AU282XHERA:
583
288
113.5
680
319.5
113.5
50
928
810
18
18
950
70
185
380
830
185
340
580
1068
48,.,965743
++.
-..
-*1
/-*
,.
0-*
1/*
20/
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
B9
A9
:;9
HGFI D
><>TT 7KN[^NNU Z\ZWNUZRVU WVSNZ8
MYJRUJPN WRWN
PJZ WRWN
SRX\RM WRWN
>@9TT 7RUMVVY \UR[ MRTNUZRVU8
?>9TT 7LNRSRUP VWNURUP MRTNUZRVU8
@99TT 7WJUNS MRTNUZRVU8
>@9TT 7RUMVVY \UR[ MRTNUZRVU8
?>9TT 7LNRSRUP VWNURUP MRTNUZRVU8
@99TT 7WJUNS MRTNUZRVU8
HGFI D
B>
:=9
:A9
OYNZQ JRY QVSN
Z\ZWNUZRVU QVSMNY
<;9TT
:>9TT
?9TT
V]NYSJWNM MRZ[JULN KN[^NNU [QN LNRSRUP
JUM [QN WJUNSC ;>TT
LNRSRUP
WJUNS
>@
@>
?>
A9
:99
:=>
EJZZN[[N \UR[C
5;:?7<=8697 >:8=4
-/+
,++
3++
33+
100
-++
22+
1-+
1+0 1++
/+ .0 .0 .+
,33
-18-
=MPQBKKBQJNM EJLFMPJNM8+LL,
@MJQ LNEFK
9;/20A><?9 9;/60A><?9
9;/00A><?9
9;.70A><?9
B
/..0
316
C
261-3
261-3
D
/1/
/1/
E
//.3
4/.
F
033
033
G
/.3
/.3
H
66.
2/6
I
75.
3.6
J
00.
00.
T
U
V
W
X
Y
Z
[
\
72.
00.
9;/20A><?9 9;/60A><?9
256
00.
9;.70A><?9
9;/00A><?9
:FJKJMH DNMDFBKFE QSOF RMJQ8
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
- -19
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
Console type unit:
/+*
.,*
+*-
C
B
A
C
model
A B
AS07/09/122XVERA
AS182XVERA
197 265
795
225
305
870
Wall Mounted Type
- -20
G G G
4. Pipe and wiring installation
- 1-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
AU182XFERA combination and the data
COOLING
EER
(W/W)
UnitAUnitBUnitCUnitAUnitBUnit
C
min. data
rated
data
max.
data
min. data
rated
data
max. Data
min.
data
rated
data
max. Data
rated
capacity 7 7 2.0 2.0 1.00 4.00 4.40 0.47 1.60 2.30 2.15 7.80 10.20 2.50 E 7 9 2.0 2.5 1.00 4.50 4.90 0.47 1.75 2.30 2.15 7.80 10.20 2.57 E 7 12 2.0 3.2 1.00 5.20 5.80 0.47 1.75 2.30 2.15 7.80 10.20 2.97 C 7 14 1.73 3.47 1.00 5.20 5.80 0.55 1.85 2.30 2.50 8.30 10.20 2.81 C 7 18 1.48 3.72 1.00 5.20 5.80 0.55 1.85 2.30 2.50 8.30 10.20 2.81 C 9 9 2.5 2.5 1.00 5.00 5.40 0.47 1.75 2.30 2.15 7.80 10.20 2.86 C 9 12 2.3 2.9 1.00 5.20 5.80 0.47 1.75 2.30 2.15 7.80 10.20 2.97 C 9 14 2.0 3.2 1.00 5.20 5.80 0.55 1.85 2.30 2.50 8.30 10.20 2.81 C 9 18 1.73 3.47 1.00 5.20 5.80 0.55 1.85 2.30 2.50 8.30 10.20 2.81 C
12 12 2.6 2.6 1.00 5.20 5.80 0.47 1.75 2.30 2.15 7.80 10.20 2.97 C 12 14
2.42 2.78 1.00 5.20 5.80 0.55 1.85 2.30 2.50 8.30 10.20 2.81 C
12 18
2.18 3.12 1.00 5.30 5.80 0.55 1.85 2.30 2.50 8.30 10.20 2.86 C 7 7 7 1.73 1.73 1.73 1.50 5.20 5.80 0.50 1.70 2.30 2.29 7.62 10.20 3.06 B 7 7 9 1.60 1.60 2.00 1.50 5.20 5.80 0.50 1.70 2.30 2.29 7.62 10.20 3.06 B 7 7 12 1.39 1.39 2.42 1.50 5.20 5.80 0.50 1.70 2.30 2.29 7.62 10.20 3.06 B 7 9 9 1.48 1.86 1.86 1.50 5.20 5.80 0.50 1.70 2.30 2.29 7.62 10.20 3.06 B 7 9 12 1.30 1.63 2.27 1.50 5.20 5.80 0.50 1.65 2.30 2.29 7.62 10.20 3.15 B 9 9 9 1.73 1.73 1.73 1.50 5.20 5.80 0.50 1.65 2.30 2.29 7.62 10.20 3.15 B 9 9 12 1.56 1.56 2.18 1.50 5.30 5.80 0.50 1.65 2.30 2.29 7.40 10.20 3.21 A
HEATING
COP
(W/W)
UnitAUnitBUnitCUnitAUnitBUnit
C
min. data
rated
data
max.
data
min. data
rated
data
max. Data
min.
data
rated
data
max. Data
rated
capacity
7 7 2.30 2.30 1.20 4.60 5.00 0.55 1.85 2.30 2.50 9.10 10.20 2.49 F 7 9 2.30 2.90 1.20 5.20 5.70 0.55 2.05 2.30 2.50 9.10 10.20 2.54 F 7 12 2.30 3.80 1.20 6.10 6.50 0.55 1.90 2.30 2.50 8.43 10.20 3.21 C 7 14 2.30 4.60 1.30 6.90 7.30 0.60 1.95 2.30 2.65 8.65 10.20 3.54 B 7 18 2.10 4.90 1.30 7.00 7.30 0.60 1.95 2.30 2.65 8.65 10.20 3.59 B 9 9 2.90 2.90 1.20 5.80 6.50 0.55 1.90 2.30 2.50 8.43 10.20 3.05 C 9 12 2.80 3.80 1.20 6.60 6.80 0.55 1.90 2.30 2.50 8.43 10.20 3.47 B 9 14 2.70 4.30 1.30 7.00 7.30 0.60 2.00 2.30 2.65 8.65 10.20 3.50 B 9 18 2.40 4.60 1.30 7.00 7.30 0.60 2.00 2.30 2.65 8.65 10.20 3.50 B
12 12 — 3.50 3.50 1.20 7.00 7.30 0.55 1.95 2.30 2.50 8.43 10.20 3.59 B
12 14
3.20 3.80 1.30 7.00 7.30 0.60 2.00 2.30 2.65 8.65 10.20 3.50 B
12 18
2.85 4.15 1.30 7.00 7.30 0.60 2.00 2.30 2.65 8.65 10.20 3.50 B 7 7 7 2.30 2.30 2.30 1.50 6.90 6.90 0.55 2.05 2.30 2.50 8.21 10.20 3.37 C 7 7 9 2.15 2.15 2.70 1.50 7.00 7.30 0.55 2.00 2.30 2.50 8.21 10.20 3.50 B 7 7 12 1.95 1.95 3.10 1.50 7.00 7.30 0.55 1.95 2.30 2.50 8.21 10.20 3.59 B 7 9 9 2.00 2.50 2.50 1.50 7.00 7.30 0.55 1.95 2.30 2.50 8.21 10.20 3.59 B 7 9 12 1.80 2.25 2.95 1.50 7.00 7.30 0.55 1.90 2.30 2.50 8.21 10.20 3.68 A 9 9 9 2.30 2.30 2.30 1.50 6.90 7.30 0.55 1.85 2.30 2.50 8.21 10.20 3.73 A 9 9 12 2.10 2.10 2.80 1.50 7.00 7.30 0.55 1.80 2.30 2.50 7.99 10.20 3.89 A
TRI (1x3)
capacity(kW)
(Nom. heating)
total heating
capacity(kW)
ENERGY
LABEL
BI (1x2)
total current
(A)@230V
total power input
(kW)
Co
mb.
Combinations
ENERGY
LABEL
BI (1x2)TRI (1x3)
capacity(kW)
(Nom. cooling)
total cooling
capacity(kW)
total power input
(kW)
total current
(A)@230V
Combinations
Co
mb.
4.1 Multi combination and the data
2
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
AU222XFERA combination and the data
COOLING
EER
(W/W)
UnitAUnitBUnitCUnitAUnitBUnit
C
min. data
rated
data
max. data
min. data
rated
data
max. Data
min. data
rated
data
max.
Data
rated
capacity 7 9 2.00 2.50 1.00 4.50 4.90 0.47 1.75 2.90 2.20 7.76 12.90 2.57 E 7 12 2.00 3.20 1.00 5.20 5.60 0.47 1.75 2.90 2.20 7.76 12.90 2.97 C 7 14 2.00 4.10 1.00 6.10 6.50 0.47 2.20 2.90 2.20 9.76 12.90 2.77 D 7 18 1.85 4.55 1.20 6.40 6.50 0.55 2.20 2.90 2.50 9.76 12.90 2.91 C 9 9 2.50 2.50 1.00 5.00 5.40 0.55 1.75 2.90 2.50 7.76 12.90 2.86 C 9 12 2.50 3.20 1.00 5.70 6.10 0.47 2.00 2.90 2.20 8.87 12.90 2.85 C 9 14 2.40 4.00 1.00 6.40 6.50 0.47 2.20 2.90 2.20 9.76 12.90 2.91 C 9 18 2.15 4.25 1.20 6.40 6.50 0.55 2.20 2.90 2.50 9.76 12.90 2.91 C
12 12 3.20 3.20 1.00 6.40 6.50 0.47 2.20 2.90 2.20 9.76 12.90 2.91 C 12 14
2.80 3.60 1.20 6.40 6.50 0.55 2.25 2.90 2.50 9.98 12.90 2.84 C
12 18
2.50 3.90 1.20 6.40 6.50 0.55 2.25 2.90 2.50 9.98 12.90 2.84 C 7 7 7 2.00 2.00 2.00 1.50 6.00 6.60 0.50 2.15 2.90 2.30 9.54 12.90 2.79 D 7 7 9 2.00 2.00 2.40 1.50 6.40 6.80 0.50 2.15 2.90 2.30 9.54 12.90 2.98 C 7 7 12 1.80 1.80 2.80 1.50 6.40 6.80 0.50 2.15 2.90 2.30 9.54 12.90 2.98 C 7 7 14 1.60 1.60 3.20 1.50 6.40 6.80 0.55 2.15 2.90 2.50 9.54 12.90 2.98 C 7 7 18 1.45 1.45 3.50 1.50 6.40 6.80 0.55 2.15 2.90 2.50 9.54 12.90 2.98 C 7 9 9 1.70 2.35 2.35 1.50 6.40 6.80 0.50 2.15 2.90 2.30 9.54 12.90 2.98 C 7 9 12 1.65 2.10 2.65 1.50 6.40 6.80 0.50 2.15 2.90 2.30 9.54 12.90 2.98 C 7 9 14 1.50 1.90 3.00 1.50 6.40 6.80 0.60 2.15 2.90 2.65 9.54 12.90 2.98 C 7 12 12 1.60 2.40 2.40 1.50 6.40 6.80 0.60 2.15 2.90 2.65 9.54 12.90 2.98 C 9 9 9 2.10 2.10 2.10 1.50 6.30 6.80 0.50 2.15 2.90 2.30 9.54 12.90 2.93 C 9 9 12 1.95 1.95 2.50 1.50 6.40 6.80 0.50 2.15 2.90 2.30 9.54 12.90 2.98 C 9 9 14 1.75 1.75 2.90 1.50 6.40 6.80 0.60 2.10 2.90 2.65 9.32 12.90 3.05 B 9 12 12 1.80 2.30 2.30 1.50 6.40 6.80 0.50 2.10 2.90 2.30 9.32 12.90 3.05 B
HEATING
EER
(W/W)
UnitAUnitBUnitCUnitAUnitBUnit
C
min. data
rated
data
max. data
min. data
rated
data
max. Data
min. data
rated
data
max.
Data
rated
capacity 7 9 2.30 2.90 1.20 5.20 5.40 0.50 1.90 2.90 2.30 8.65 12.90 2.74 E 7 12 2.30 3.80 1.20 6.10 6.50 0.50 1.95 2.90 2.30 8.43 12.90 3.13 C 7 14 2.30 4.60 1.20 6.90 7.30 0.50 2.20 2.90 2.30 8.65 12.90 3.14 C 7 18 2.15 5.15 1.20 7.30 7.50 0.55 2.20 2.90 2.50 8.65 12.90 3.32 C 9 9 2.90 2.90 1.20 5.80 6.20 0.55 1.95 2.90 2.50 9.09 12.90 2.97 D 9 12 2.90 3.80 1.20 6.70 7.10 0.50 2.00 2.90 2.30 9.09 12.90 3.35 C 9 14 2.80 4.50 1.20 7.30 7.50 0.50 2.25 2.90 2.30 9.32 12.90 3.24 C 9 18 2.50 4.80 1.20 7.30 7.50 0.55 2.25 2.90 2.50 9.32 12.90 3.24 C
12 12 3.65 3.65 1.20 7.30 7.50 0.55 2.20 2.90 2.50 9.09 12.90 3.32 C 12 14
3.30 4.00 1.20 7.30 7.50 0.55 2.15 2.90 2.50 9.54 12.90 3.40 C
12 18
2.95 4.35 1.20 7.30 7.50 0.55 2.15 2.90 2.50 9.76 12.90 3.40 C 7 7 7 2.30 2.30 2.30 1.50 6.90 7.50 0.55 2.05 2.90 2.50 8.21 12.90 3.37 C 7 7 9 2.25 2.25 2.80 1.50 7.30 7.50 0.55 2.10 2.90 2.50 9.32 12.90 3.48 B 7 7 12 2.10 2.10 3.10 1.50 7.30 7.50 0.55 2.10 2.90 2.50 9.32 12.90 3.48 B 7 7 14 1.85 1.85 3.60 1.50 7.30 7.50 0.60 2.15 2.90 2.65 9.54 12.90 3.40 C 7 7 18 1.70 1.70 3.90 1.50 7.30 7.50 0.60 2.15 2.90 2.65 9.54 12.90 3.40 C 7 9 9 2.10 2.60 2.60 1.50 7.30 7.50 0.55 2.10 2.90 2.50 9.32 12.90 3.48 B 7 9 12 1.95 2.30 3.05 1.50 7.30 7.50 0.55 2.10 2.90 2.50 9.32 12.90 3.48 B 7 9 14 1.75 2.15 3.40 1.50 7.30 7.50 0.60 2.10 2.90 2.65 9.32 12.90 3.48 B 7 12 12 1.70 2.80 2.80 1.50 7.30 7.50 0.60 2.10 2.90 2.65 9.32 12.90 3.48 B 9 9 9 2.40 2.40 2.40 1.50 7.20 7.50 0.55 2.10 2.90 2.50 9.32 12.90 3.43 B 9 9 12 2.18 2.18 2.84 1.50 7.20 7.50 0.55 2.05 2.90 2.50 9.09 12.90 3.51 B 9 9 14 2.05 2.05 3.20 1.50 7.30 7.50 0.60 2.10 2.90 2.65 9.54 12.90 3.48 B 9 12 12 2.10 2.60 2.60 1.50 7.30 7.50 0.55 2.00 2.90 2.50 8.87 12.90 3.65 A
BI (1x2)TRI (1x3)
Co
mb.
ENERGY
LABEL
Rated capacity(kW)
(Nom. heating)
total heating
capacity(KW)
total power input
(W)
total current
(A)@230V
ENERGY
LABEL
Rated capacity(Kw)
(Nom. cooling)
BI (1x2)TRI (1x3)
Combinations
Combinations
Co
mb.
total cooling
capacity(kW)
total power input
(kW)
total current
(A)@230V
-22-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
AU252XGERA combination and the data
COOLING
EER
(W/W)
UnitAUnitBUnitCUnitDUnitAUnitBUnitCUnit
D
min. data
rated
data
max.
data
min. data
rated
data
max. Data
min. data
rated
data
max. Data
rated
capacity 7 12 2.00 3.50 1.00 5.50 5.90 0.47 2.06 3.20 2.09 9.76 14.50 2.67 D 7 14 2.00 4.10 1.00 6.10 6.50 0.50 2.37 3.20 2.22 11.22 14.50 2.57 E 7 18 2.00 5.00 1.00 7.00 7.40 0.50 2.34 3.20 2.22 11.09 14.50 2.99 C 9 12 2.50 3.50 1.20 6.00 6.40 0.47 2.16 3.20 2.09 10.20 14.50 2.78 D 9 14 2.50 4.10 1.00 6.60 7.00 0.50 2.34 3.20 2.22 11.09 14.50 2.82 C 9 18 2.43 4.87 1.00 7.3 7.90 0.50 2.44 3.20 2.22 11.54 14.50 2.99 C
12 12 — 3.50 3.50 1.00 7.00 7.40 0.47 2.44 3.20 2.09 11.54 14.50 2.87 C 12 14
3.36 3.94 1.20 7.3 8.00 0.50 2.49 3.20 2.22 11.80 14.50 2.93 C
12 18
3.03 4.27 1.00 7.3 8.00 0.50 2.48 3.20 2.22 11.76 14.50 2.94 C
14 14
3.65 3.65 1.20 7.3 8.00 0.55 2.48 3.20 2.44 11.71 14.50 2.95 C
14 18
3.31 3.99 1.20 7.3 8.00 0.55 2.46 3.20 2.44 11.62 14.50 2.97 C
18 18
3.65 3.65 1.20 7.3 8.00 0.55 2.44 3.20 2.44 11.54 14.50 2.99 C 7 7 7 2.00 2.00 2.00 1.50 6.00 6.60 0.55 2.44 3.20 2.44 11.54 14.50 2.46 E 7 7 9 2.00 2.00 2.50 1.50 6.50 7.10 0.55 2.42 3.20 2.44 11.45 14.50 2.69 D 7 7 12 1.95 1.95 3.41 1.50 7.3 8.10 0.55 2.40 3.20 2.44 11.36 14.50 3.04 B 7 7 14 1.83 1.83 3.65 1.50 7.3 8.20 0.60 2.34 3.20 2.66 11.09 14.50 3.11 B 7 7 18 1.63 1.63 4.03 1.50 7.3 8.20 0.60 2.33 3.20 2.66 11.00 14.50 3.14 B 7 9 9 2.00 2.50 2.50 1.50 7.00 7.60 0.55 2.42 3.20 2.44 11.45 14.50 2.89 C 7 9 12 1.83 2.31 3.17 1.50 7.3 8.20 0.55 2.39 3.20 2.44 11.31 14.50 3.05 B 7 9 14 1.73 2.11 3.46 1.50 7.3 8.20 0.60 2.33 3.20 2.66 11.00 14.50 3.14 B 7 9 18 1.54 1.92 3.84 1.50 7.3 8.20 0.60 2.30 3.20 2.66 10.87 14.50 3.18 B 7 12 12 — 1.63 2.83 2.83 1.50 7.3 8.20 0.55 2.44 3.20 2.44 11.54 14.50 2.99 C 7 12 14 — 1.54 2.59 3.17 1.50 7.3 8.20 0.60 2.39 3.20 2.66 11.31 14.50 3.05 B 7 12 18 — 1.44 2.40 3.46 1.50 7.3 8.20 0.60 2.39 3.20 2.66 11.31 14.50 3.05 B 9 9 9 2.43 2.43 2.43 1.50 7.3 8.20 0.62 2.39 3.20 2.75 11.31 14.50 3.05 B 9 9 12 2.16 2.16 2.98 1.50 7.3 8.20 0.55 2.39 3.20 2.44 11.31 14.50 3.05 B 9 9 14 2.02 2.02 3.27 1.50 7.3 8.20 0.60 2.34 3.20 2.66 11.09 14.50 3.11 B 9 9 18 1.83 1.83 3.65 1.50 7.3 8.20 0.60 2.34 3.20 2.66 11.09 14.50 3.11 B 9 12 12 — 1.92 2.69 2.69 1.50 7.3 8.20 0.55 2.39 3.20 2.44 11.31 14.50 3.05 B 9 12 14 — 1.83 2.50 2.98 1.50 7.3 8.20 0.60 2.34 3.20 2.66 11.09 14.50 3.11 B 9 12 18 — 1.68 2.31 3.31 1.50 7.3 8.20 0.60 2.34 3.20 2.66 11.09 14.50 3.11 B
12 12 12 2.43 2.43 2.43 1.50 7.3 8.20 0.55 2.39 3.20 2.44 11.31 14.50 3.05 B 12 12 14 2.31 2.31 2.69 1.50 7.3 8.20 0.60 2.34 3.20 2.66 11.09 14.50 3.11 B
77771.83 1.83 1.83 1.83 1.80 7.3 8.20 0.60 2.33 3.20 2.66 11.00 14.50 3.14 B
77791.73 1.73 1.73 2.11 1.80 7.3 8.20 0.60 2.33 3.20 2.66 10.87 14.50 3.13 B 7 7 7 12 1.54 1.54 1.54 2.69 1.80 7.3 8.20 0.60 2.33 3.20 2.66 10.78 14.50 3.13 B 7 7 7 14 1.44 1.44 1.44 2.98 1.80 7.3 8.20 0.62 2.35 3.20 2.75 10.65 14.50 3.11 B
77991.63 1.63 2.02 2.02 1.80 7.3 8.20 0.60 2.33 3.20 2.66 10.78 14.50 3.13 B 7 7 9 12 1.44 1.44 1.83 2.59 1.80 7.3 8.20 0.60 2.33 3.20 2.66 10.74 14.50 3.13 B 7 7 9 14 1.39 1.39 1.73 2.79 1.80 7.3 8.20 0.62 2.35 3.20 2.75 10.65 14.50 3.11 B 7 7 12 12 1.34 1.34 2.31 2.31 1.80 7.3 8.20 0.60 2.32 3.20 2.66 10.65 14.50 3.15 B
79991.54 1.92 1.92 1.92 1.80 7.3 8.20 0.60 2.32 3.20 2.66 10.65 14.50 3.15 B 7 9 9 12 1.39 1.73 1.73 2.45 1.80 7.3 8.20 0.60 2.30 3.20 2.66 10.56 14.50 3.17 B
99991.83 1.83 1.83 1.83 1.80 7.3 8.20 0.60 2.28 3.20 2.66 10.65 14.50 3.21 A 9 9 9 12 1.68 1.68 1.68 2.26 1.80 7.3 8.20 0.60 2.25 3.20 2.66 10.56 14.50 3.24 A
Rated capacity(Kw)
(Nom. cooling)
TRI (1x3) BI (1x2)
total cooling
capacity(kW)
total power input
(kW)
total current
(A)@230V
QUADRI(1x4)
Co
mb.
Combinations
ENERGY
LABEL
-23-
HEATING
COP
(W/W)
UnitAUnitBUnitCUnitDUnitAUnitBUnitCUnit
D
min. data
rated
data
max.
data
min. data
rated data
max. Data
min. data
rated data
max.
Data
rated
capacity 7 12 2.30 3.80 1.00 6.10 6.70 0.47 2.11 3.20 2.09 9.98 14.50 2.89 D 7 14 2.30 4.60 1.00 6.90 7.60 0.50 2.39 3.20 2.22 11.31 14.50 2.89 D 7 18 2.30 5.50 1.00 7.80 8.50 0.50 2.39 3.20 2.22 11.31 14.50 3.26 C 9 12 2.90 3.80 1.20 6.70 7.30 0.47 2.16 3.20 2.09 10.20 14.50 3.11 C 9 14 2.90 4.50 1.00 7.40 8.10 0.50 2.39 3.20 2.22 11.31 14.50 3.10 C 9 18 2.83 5.37 1.00 8.2 9.00 0.50 2.39 3.20 2.22 11.31 14.50 3.43 B
12 12 — 3.80 3.80 1.00 7.60 8.00 0.47 2.34 3.20 2.09 11.09 14.50 3.24 C 12 14
3.71 4.49 1.20 8.2 9.00 0.50 2.39 3.20 2.22 11.31 14.50 3.43 B
12 18
3.38 4.82 1.00 8.2 9.00 0.50 2.39 3.20 2.22 11.31 14.50 3.43 B
14 14
4.10 4.10 1.20 8.2 9.00 0.55 2.48 3.20 2.44 11.76 14.50 3.30 C
14 18
3.76 4.44 1.20 8.2 9.00 0.55 2.47 3.20 2.44 11.67 14.50 3.33 C
18 18
4.10 4.10 1.20 8.2 9.00 0.55 2.47 3.20 2.44 11.67 14.50 3.33 C 7 7 7 2.30 2.30 2.30 1.50 6.90 7.50 0.55 2.44 3.20 2.44 11.54 14.50 2.83 D 7 7 9 2.30 2.30 2.90 1.50 7.50 8.10 0.55 2.42 3.20 2.44 11.45 14.50 3.10 C 7 7 12 2.25 2.25 3.71 1.50 8.2 9.00 0.55 2.40 3.20 2.44 11.36 14.50 3.42 B 7 7 14 2.07 2.07 4.05 1.50 8.2 9.00 0.60 2.34 3.20 2.66 11.09 14.50 3.50 B 7 7 18 1.64 1.64 4.92 1.50 8.2 9.00 0.60 2.33 3.20 2.66 11.00 14.50 3.53 B 7 9 9 2.30 2.90 2.90 1.50 8.10 8.90 0.55 2.42 3.20 2.44 11.45 14.50 3.35 C 7 9 12 2.12 2.60 3.47 1.50 8.2 9.00 0.55 2.39 3.20 2.44 11.31 14.50 3.43 B 7 9 14 1.93 2.41 3.86 1.50 8.2 9.00 0.60 2.33 3.20 2.66 11.00 14.50 3.53 B 7 9 18 1.83 2.22 4.15 1.50 8.2 9.00 0.60 2.30 3.20 2.66 10.87 14.50 3.57 B 7 12 12 — 1.93 3.14 3.14 1.50 8.2 9.00 0.55 2.44 3.20 2.44 11.54 14.50 3.36 C 7 12 14 — 1.78 2.89 3.52 1.50 8.2 9.00 0.60 2.39 3.20 2.66 11.31 14.50 3.43 B 7 12 18 — 1.64 2.60 3.96 1.50 8.2 9.00 0.60 2.39 3.20 2.66 11.31 14.50 3.43 B 9 9 9 2.73 2.73 2.73 1.50 8.2 9.00 0.62 2.39 3.20 2.75 11.31 14.50 3.43 B 9 9 12 2.33 2.33 3.54 1.50 8.2 9.00 0.55 2.39 3.20 2.44 11.31 14.50 3.43 B 9 9 14 2.41 2.41 3.38 1.50 8.2 9.00 0.60 2.34 3.20 2.66 11.09 14.50 3.50 B 9 9 18 2.03 2.03 4.15 1.50 8.2 9.00 0.60 2.34 3.20 2.66 11.09 14.50 3.50 B 9 12 12 — 2.41 2.89 2.89 1.50 8.2 9.00 0.55 2.39 3.20 2.44 11.31 14.50 3.43 B 9 12 14 — 2.12 2.75 3.33 1.50 8.2 9.00 0.60 2.34 3.20 2.66 11.09 14.50 3.50 B 9 12 18 — 1.93 2.56 3.71 1.50 8.2 9.00 0.60 2.34 3.20 2.66 11.09 14.50 3.50 B
12 12 12 2.73 2.73 2.73 1.50 8.2 9.00 0.55 2.39 3.20 2.44 11.31 14.50 3.43 B 12 12 14 2.56 2.56 3.09 1.50 8.2 9.00 0.60 2.34 3.20 2.66 11.09 14.50 3.50 B
77772.05 2.05 2.05 2.05 1.80 8.2 9.00 0.60 2.34 3.20 2.66 11.09 14.50 3.50 B
77791.93 1.93 1.93 2.41 1.80 8.2 9.00 0.60 2.30 3.20 2.66 10.87 14.50 3.57 B 7 7 7 12 1.78 1.78 1.78 2.85 1.80 8.2 9.00 0.60 2.30 3.20 2.66 10.87 14.50 3.57 B 7 7 7 14 1.64 1.64 1.64 3.28 1.80 8.2 9.00 0.62 2.27 3.20 2.75 10.74 14.50 3.61 A
77991.83 1.83 2.27 2.27 1.80 8.2 9.00 0.60 2.30 3.20 2.66 10.87 14.50 3.57 B 7 7 9 12 1.69 1.69 2.12 2.70 1.80 8.2 9.00 0.60 2.30 3.20 2.66 10.87 14.50 3.57 B 7 7 9 14 1.59 1.59 1.93 3.09 1.80 8.2 9.00 0.62 2.27 3.20 2.75 10.74 14.50 3.61 A 7 7 12 12 1.54 1.54 2.56 2.56 1.80 8.2 9.00 0.60 2.27 3.20 2.66 10.74 14.50 3.61 A
79991.83 2.12 2.12 2.12 1.80 8.2 9.00 0.60 2.27 3.20 2.66 10.74 14.50 3.61 A 7 9 9 12 1.59 1.93 1.93 2.75 1.80 8.2 9.00 0.60 2.25 3.20 2.66 10.65 14.50 3.64 A
99992.05 2.05 2.05 2.05 1.80 8.2 9.00 0.60 2.25 3.20 2.66 10.65 14.50 3.64 A 9 9 9 12 1.93 1.93 1.93 2.41 1.80 8.2 9.00 0.60 2.25 3.20 2.66 10.65 14.50 3.64 A
total power input
(W)
total current
(A)@230V
ENERGY
LABEL
BI (1x2)
Co mb
.
Combinations
Rated capacity(kW)
(Nom. heating)
total heating
capacity(KW)
QUADRI(1x4) TRI (1x3)
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
-24-
AU282XHERA combination and the data
COOLING
EER
(W/W)
UnitAUnitBUnitCUnitDUnitAUnitBUnitCUnit
D
min. data
rated
data
max.
data
min. data
rated data
max. Data
min. data
rated
data
max. Data
rated
capacity 7 14 2.00 4.10 1.00 6.10 6.50 0.50 2.20 3.80 2.15 9.76 16.80 2.77 D 7 18 2.00 5.00 1.00 7.00 7.40 0.50 2.45 3.80 2.15 10.87 16.80 2.86 C 9 12 2.50 3.50 1.00 6.00 6.40 0.50 2.35 3.80 2.15 10.43 16.80 2.55 E 9 14 2.50 4.10 1.00 6.60 7.00 0.50 2.20 3.80 2.15 9.76 16.80 3.00 B 9 18 2.50 5.00 1.00 7.50 7.90 0.50 2.50 3.80 2.15 11.09 16.80 3.00 B
12 12 3.50 3.50 1.00 7.00 6.80 0.50 2.25 3.80 2.15 9.98 16.80 3.11 B 12 14
3.50 4.10 1.00 7.60 8.00 0.50 2.60 3.80 2.15 11.54 16.80 2.92 C
12 18
3.05 4.95 1.00 8.00 8.40 0.50 2.60 3.80 2.15 11.54 16.80 3.08 B
14 14
4.00 4.00 1.00 8.00 8.60 0.55 2.70 3.80 2.50 11.98 16.80 2.96 C
14 18
3.50 4.50 1.00 8.00 8.60 0.55 2.70 3.80 2.50 11.98 16.80 2.96 C
18 18
4.00 4.00 1.00 8.00 8.60 0.55 2.70 3.80 2.50 11.98 16.80 2.96 C 7 7 7 2.00 2.00 2.00 1.50 6.00 6.60 0.55 2.70 3.80 2.50 11.98 16.80 2.22 F 7 7 9 2.00 2.00 2.50 1.50 6.50 7.10 0.55 2.70 3.80 2.50 11.98 16.80 2.41 E 7 7 12 2.00 2.00 3.50 1.50 7.50 8.10 0.55 2.70 3.80 2.50 11.98 16.80 2.78 D 7 7 14 2.00 2.00 4.00 1.50 8.00 8.70 0.55 2.70 3.80 2.50 11.98 16.80 2.96 C 7 7 18 1.75 1.75 4.50 1.50 8.00 8.80 0.55 2.70 3.80 2.50 11.98 16.80 2.96 C 7 9 9 2.00 2.00 2.50 1.50 6.50 7.10 0.55 2.70 3.80 2.50 11.98 16.80 2.41 E 7 9 12 2.00 2.50 3.50 1.50 8.00 8.60 0.55 2.70 3.80 2.50 11.98 16.80 2.96 C 7 9 14 1.90 2.30 3.80 1.50 8.00 8.70 0.55 2.70 3.80 2.50 11.98 16.80 2.96 C 7 9 18 1.70 2.10 4.20 1.50 8.00 8.80 0.55 2.65 3.80 2.50 11.76 16.80 3.02 B 7 12 12 1.85 3.05 3.05 1.50 7.95 8.60 0.55 2.70 3.80 2.50 11.98 16.80 2.94 C 7 12 14 1.70 2.90 3.40 1.50 8.00 8.70 0.55 2.70 3.80 2.50 11.98 16.80 2.96 C 7 12 18 1.60 2.60 3.80 1.50 8.00 8.80 0.55 2.65 3.80 2.50 11.76 16.80 3.02 B 7 14 14 1.55 3.20 3.20 1.50 7.95 8.80 0.55 2.65 3.80 2.50 11.76 16.80 3.00 B 71418
1.40 3.00 3.60 1.50 8.00 8.90 0.55 2.65 3.80 2.50 11.76 16.80 3.02 B 9 9 9 2.5 2.5 2.5 1.50 7.50 8.10 0.55 2.65 3.80 2.50 11.76 16.80 2.83 C 9 9 12 2.44 2.44 3.12 1.50 8.00 8.60 0.55 2.65 3.80 2.50 11.76 16.80 3.02 B 9 9 14 2.20 2.20 3.60 1.50 8.00 8.70 0.55 2.65 3.80 2.50 11.76 16.80 3.02 B 9 9 18 2.0 2.0 4.0 1.50 8.00 8.80 0.55 2.65 3.80 2.50 11.76 16.80 3.02 B 9 12 12 2.26 2.87 2.87 1.50 8.00 8.60 0.55 2.65 3.80 2.50 11.76 16.80 3.02 B 9 12 14 2.05 2.60 3.35 1.50 8.00 8.70 0.55 2.65 3.80 2.50 11.76 16.80 3.02 B 9 12 18 1.80 2.50 3.70 1.50 8.00 8.80 0.55 2.65 3.80 2.50 11.76 16.80 3.02 B 9 14 14 1.90 3.05 3.05 1.50 8.00 8.80 0.55 2.65 3.80 2.50 11.76 16.80 3.02 B 9
14 18
1.70 2.90 3.40 1.50 8.00 8.90 0.55 2.65 3.80 2.50 11.76 16.80 3.02 B
12 12 12 2.65 2.65 2.65 1.50 7.95 8.50 0.55 2.65 3.80 2.50 11.76 16.80 3.00 B 12 12 14 2.45 2.45 3.10 1.50 8.00 8.70 0.55 2.65 3.80 2.50 11.76 16.80 3.02 B 12 12 18 2.20 2.20 3.60 1.50 8.00 8.80 0.55 2.65 3.80 2.50 11.76 16.80 3.02 B 12 14 14 2.25 2.85 2.85 1.50 7.95 8.80 0.55 2.65 3.80 2.50 11.76 16.80 3.00 B
77772.02.02.02.01.80 8.00 9.20 0.65 2.60 3.80 2.85 11.54 16.80 3.08 B
77791.90 1.90 1.90 2.30 1.80 8.00 9.20 0.65 2.60 3.80 2.85 11.54 16.80 3.08 B 7 7 7 12 1.75 1.75 1.75 2.75 1.80 8.00 9.20 0.65 2.60 3.80 2.85 11.54 16.80 3.08 B 7 7 7 14 1.60 1.60 1.60 3.20 1.80 8.00 9.30 0.65 2.60 3.80 2.85 11.54 16.80 3.08 B 7 7 7 18 1.45 1.45 1.45 3.65 1.80 8.00 9.50 0.65 2.60 3.80 2.85 11.54 16.80 3.08 B
77991.75 1.75 2.25 2.25 1.80 8.00 9.20 0.65 2.60 3.80 2.85 11.54 16.80 3.08 B 7 7 9 12 1.70 1.70 2.10 2.50 1.80 8.00 9.20 0.65 2.60 3.80 2.85 11.54 16.80 3.08 B 7 7 9 14 1.50 1.50 1.90 3.10 1.80 8.00 9.30 0.65 2.60 3.80 2.85 11.54 16.80 3.08 B 7 7 9 18 1.40 1.40 1.70 3.50 1.80 8.00 9.50 0.65 2.60 3.80 2.85 11.54 16.80 3.08 B 7 7 12 12 1.45 1.45 2.55 2.55 1.80 8.00 9.20 0.65 2.55 3.80 2.85 11.31 16.80 3.14 B 7 7 12 14 1.40 1.40 2.40 2.80 1.80 8.00 9.30 0.65 2.55 3.80 2.85 11.31 16.80 3.14 B
79991.70 2.10 2.10 2.10 1.80 8.00 9.20 0.65 2.60 3.80 2.85 11.54 16.80 3.08 B 7 9 9 12 1.60 2.00 2.00 2.40 1.80 8.00 9.20 0.65 2.55 3.80 2.85 11.31 16.80 3.14 B 7 9 9 14 1.45 1.80 1.80 2.95 1.80 8.00 9.30 0.65 2.55 3.80 2.85 11.31 16.80 3.14 B 7 9 12 12 1.40 1.70 2.45 2.45 1.80 8.00 9.20 0.65 2.50 3.80 2.85 11.09 16.80 3.20 B 7 9 12 14 1.30 1.65 2.30 2.75 1.80 8.00 9.30 0.65 2.50 3.80 2.85 11.09 16.80 3.20 B
99992.00 2.00 2.00 2.00 1.80 8.00 9.20 0.65 2.55 3.80 2.85 11.31 16.80 3.14 B 9 9 9 12 1.90 1.90 1.90 2.30 1.80 8.00 9.20 0.65 2.50 3.80 2.85 11.09 16.80 3.20 B 9 9 9 14 1.70 1.70 1.70 2.90 1.80 8.00 9.30 0.65 2.50 3.80 2.85 11.09 16.80 3.20 B 9 9 12 12 1.65 1.65 2.05 2.65 1.80 8.00 9.40 0.65 2.50 3.80 2.85 11.09 16.80 3.20 B
Co
mb.
ENERGY
LABEL
Rated capacity Output/kW
(Nom. cooling)
total cooling
capacity(kW)
total power input
(kW)
BI (1x2)TRI (1x3)QUADRI(1x4)
Combinations
total current
(A)@230V
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
-25-
HEATING
EER
(W/W)
UnitAUnitBUnitCUnitDUnitAUnitBUnitCUnit
D
min. data
rated
data
max. data
min. data
rated
data
max. Data
min. data
rated
data
max. Data
rated
capacity 7 14 2.30 4.60 1.20 6.90 7.50 0.50 2.80 3.80 2.15 12.42 16.80 2.46 F 7 18 2.30 5.50 1.20 7.80 8.40 0.50 2.90 3.80 2.15 12.87 16.80 2.69 E 9 12 2.90 3.80 1.20 6.70 7.30 0.50 2.90 3.80 2.15 12.87 16.80 2.31 G 9 14 2.90 4.60 1.20 7.50 8.20 0.50 3.00 3.80 2.15 13.31 16.80 2.50 F 9 18 2.90 5.50 1.20 8.40 9.20 0.50 3.00 3.80 2.15 13.31 16.80 2.80 D
12 12 3.80 3.80 1.20 7.60 8.20 0.50 2.95 3.80 2.15 13.09 16.80 2.58 F 12 14
3.80 4.60 1.20 8.40 9.10 0.50 2.90 3.80 2.15 12.87 16.80 2.90 D
12 18
3.80 5.50 1.20 9.30 10.20 0.50 3.10 3.80 2.15 13.75 16.80 3.00 C
14 14
4.60 4.60 1.20 9.20 10.20 0.55 3.00 3.80 2.50 13.31 16.80 3.07 C
14 18
4.60 5.40 1.20 10.00 10.50 0.55 3.00 3.80 2.50 13.31 16.80 3.33 C
18 18
5.00 5.00 1.20 10.00 11.00 0.55 3.00 3.80 2.50 13.31 16.80 3.33 C 7 7 7 2.30 2.30 2.30 1.50 6.90 7.80 0.55 2.85 3.80 2.50 12.64 16.80 2.42 F 7 7 9 2.30 2.30 2.90 1.50 7.50 8.40 0.55 2.85 3.80 2.50 12.64 16.80 2.63 E 7 7 12 2.30 2.30 3.80 1.50 8.40 9.30 0.55 2.85 3.80 2.50 12.64 16.80 2.95 D 7 7 14 2.30 2.30 4.60 1.50 9.20 10.20 0.55 2.80 3.80 2.50 12.42 16.80 3.29 C 7 7 18 2.30 2.30 5.40 1.50 10.00 10.50 0.55 2.80 3.80 2.50 12.42 16.80 3.57 B 7 9 9 2.30 2.90 2.90 1.50 8.10 10.50 0.55 2.90 3.80 2.50 12.87 16.80 2.79 E 7 9 12 2.30 2.90 3.80 1.50 9.00 10.50 0.55 2.90 3.80 2.50 12.87 16.80 3.10 C 7 9 14 2.30 2.90 4.60 1.50 9.80 10.50 0.55 2.80 3.80 2.50 12.42 16.80 3.50 B 7 9 18 2.15 2.70 5.15 1.50 10.00 11.00 0.55 2.85 3.80 2.50 12.64 16.80 3.51 B 7 12 12 2.30 3.80 3.80 1.50 9.90 10.80 0.55 2.90 3.80 2.50 12.87 16.80 3.41 B 7 12 14 2.15 3.55 4.30 1.50 10.00 11.00 0.55 2.90 3.80 2.50 12.87 16.80 3.45 B 7 12 18 2.00 3.25 4.75 1.50 10.00 11.00 0.55 2.90 3.80 2.50 12.87 16.80 3.45 B 7 14 14 2.00 4.00 4.00 1.50 10.00 11.00 0.55 2.85 3.80 2.50 12.64 16.80 3.51 B 71418
1.90 3.70 4.40 1.50 10.00 11.00 0.55 2.85 3.80 2.50 12.64 16.80 3.51 B 9 9 9 2.90 2.90 2.90 1.50 8.70 10.50 0.55 2.90 3.80 2.50 12.87 16.80 3.00 C 9 9 12 2.90 2.90 3.80 1.50 9.60 10.50 0.55 2.90 3.80 2.50 12.87 16.80 3.31 C 9 9 14 2.75 2.75 4.50 1.50 10.00 10.50 0.55 2.85 3.80 2.50 12.64 16.80 3.51 B 9 9 18 2.50 2.50 5.00 1.50 10.00 11.50 0.55 2.80 3.80 2.50 12.42 16.80 3.57 B 9 12 12 2.80 3.60 3.60 1.50 10.00 11.50 0.55 2.80 3.80 2.50 12.42 16.80 3.57 B 9 12 14 2.55 3.35 4.10 1.50 10.00 11.50 0.55 2.80 3.80 2.50 12.42 16.80 3.57 B 9 12 18 2.40 3.10 4.50 1.50 10.00 11.50 0.55 2.85 3.80 2.50 12.64 16.80 3.51 B 9 14 14 2.40 3.80 3.80 1.50 10.00 11.50 0.55 2.90 3.80 2.50 12.87 16.80 3.45 B 9
14 18
2.25 3.55 4.20 1.50 10.00 11.50 0.55 2.90 3.80 2.50 12.87 16.80 3.45 B
12 12 12 3.35 3.35 3.35 1.50 10.05 11.50 0.55 2.95 3.80 2.50 13.09 16.80 3.41 B 12 12 14 3.10 3.10 3.80 1.50 10.00 11.50 0.55 2.90 3.80 2.50 12.87 16.80 3.45 B 12 12 18 2.90 2.90 4.20 1.50 10.00 11.50 0.55 2.90 3.80 2.50 12.87 16.80 3.45 B 12 14 14 2.90 3.55 3.55 1.50 10.00 11.50 0.55 2.90 3.80 2.50 12.87 16.80 3.45 B
77772.30 2.30 2.30 2.30 1.80 9.20 10.50 0.65 2.90 3.80 2.85 12.87 16.80 3.17 C
77792.30 2.30 2.30 2.90 1.80 9.80 10.50 0.65 2.90 3.80 2.85 12.87 16.80 3.38 C 7 7 7 12 2.15 2.15 2.15 3.55 1.80 10.00 11.50 0.65 2.85 3.80 2.85 12.64 16.80 3.51 B 7 7 7 14 2.00 2.00 2.00 4.00 1.80 10.00 11.50 0.65 2.85 3.80 2.85 12.64 16.80 3.51 B 7 7 7 18 1.85 1.85 1.85 4.45 1.80 10.00 11.50 0.65 2.85 3.80 2.85 12.64 16.80 3.51 B
77992.20 2.20 2.80 2.80 1.80 10.00 11.50 0.65 2.90 3.80 2.85 12.87 16.80 3.45 B 7 7 9 12 2.05 2.05 2.55 3.35 1.80 10.00 11.50 0.65 2.90 3.80 2.85 12.87 16.80 3.45 B 7 7 9 14 1.90 1.90 2.40 3.80 1.80 10.00 11.50 0.65 2.85 3.80 2.85 12.64 16.80 3.51 B 7 7 9 18 1.75 1.75 2.20 4.30 1.80 10.00 11.50 0.65 2.85 3.80 2.85 12.64 16.80 3.51 B 7 7 12 12 1.90 1.90 3.10 3.10 1.80 10.00 11.50 0.65 2.90 3.80 2.85 12.87 16.80 3.45 B 7 7 12 14 1.75 1.75 2.90 3.60 1.80 10.00 11.50 0.65 2.85 3.80 2.85 12.64 16.80 3.51 B
79992.10 2.65 2.65 2.65 1.80 10.05 11.50 0.65 2.90 3.80 2.85 12.87 16.80 3.47 B 7 9 9 12 1.95 2.45 2.45 3.15 1.80 10.00 11.50 0.65 2.90 3.80 2.85 12.87 16.80 3.45 B 7 9 9 14 1.80 2.25 2.25 3.70 1.80 10.00 11.50 0.65 2.85 3.80 2.85 12.64 16.80 3.51 B 7 9 12 12 1.95 2.25 2.90 2.90 1.80 10.00 11.50 0.65 2.80 3.80 2.85 12.42 16.80 3.57 B 7 9 12 14 1.70 2.15 2.80 3.35 1.80 10.00 11.50 0.65 2.80 3.80 2.85 12.42 16.80 3.57 B
99992.50 2.50 2.50 2.50 1.80 10.00 11.50 0.65 2.75 3.80 2.85 12.20 16.80 3.64 A 9 9 9 12 2.30 2.30 2.30 3.10 1.80 10.00 11.50 0.65 2.75 3.80 2.85 12.20 16.80 3.64 A 9 9 9 14 2.20 2.20 2.20 3.40 1.80 10.00 11.50 0.65 2.75 3.80 2.85 12.20 16.80 3.64 A 9 9 12 12
2.15 2.15 2.85 2.85
1.80 10.00 11.50 0.65 2.70 3.80 2.85 11.98 16.80 3.70 A
ENERGY
LABEL
Rated capacity Output/kW
(Nom. heating)
total heating
capacity(KW)
total power input
(W)
total current
(A)@230V
BI (1x2)TRI (1x3)QUADRI(1x4)
Combinations
Co
mb.
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
-26-
AU342XHERA combination and the data
COOLING
EER
(W/W)
UnitAUnitBUnitCUnitDUnitAUnitBUnitCUnit
D
min. data
rated
data
max.
data
min. data
rated
data
max. Data
min.
data
rated
data
max. Data
rated
capacity 7 18 2.00 5.00 1.00 7.00 7.50 0.50 2.85 4.00 2.15 12.64 18.10 2.46 E 9 18 2.50 5.00 1.00 7.50 8.00 0.50 2.90 4.00 2.15 12.87 18.10 2.59 E
12 14
3.50 4.10 1.00 7.60 8.10 0.50 2.90 4.00 2.15 12.87 18.10 2.62 D
12 18
3.50 5.00 1.00 8.50 9.00 0.50 3.30 4.00 2.15 14.64 18.10 2.58 E
14 14
4.10 4.10 1.00 8.20 8.80 0.50 3.30 4.00 2.15 14.64 18.10 2.48 E
14 18
4.10 5.00 1.00 9.10 9.70 0.50 3.50 4.00 2.15 15.53 18.10 2.60 D
18 18
5.00 5.00 1.00 10.00 10.50 0.50 3.50 4.00 2.15 15.53 18.10 2.86 C 7 7 12 2.00 2.00 3.50 1.50 7.50 8.10 0.55 3.10 4.00 2.50 13.75 18.10 2.42 E 7 7 14 2.00 2.00 4.10 1.50 8.10 8.80 0.55 3.20 4.00 2.50 14.20 18.10 2.53 E 7 7 18 2.00 2.00 5.00 1.50 9.00 9.80 0.55 3.25 4.00 2.50 14.42 18.10 2.77 D 7 9 9 2.00 2.50 2.50 1.50 7.00 7.60 0.55 3.10 4.00 2.50 13.75 18.10 2.26 F 7 9 12 2.00 2.50 3.50 1.50 8.00 8.60 0.55 3.10 4.00 2.50 13.75 18.10 2.58 E 7 9 14 2.00 2.50 4.10 1.50 8.60 9.30 0.55 3.15 4.00 2.50 13.98 18.10 2.73 D 7 9 18 2.00 2.50 5.00 1.50 9.50 10.20 0.55 3.40 4.00 2.50 15.08 18.10 2.79 D 7 12 12 2.00 3.50 3.50 1.50 9.00 9.60 0.55 3.40 4.00 2.50 15.08 18.10 2.65 D 7 12 14 2.00 3.50 4.10 1.50 9.60 10.20 0.55 3.40 4.00 2.50 15.08 18.10 2.82 C 7 12 18 1.90 3.30 4.80 1.50 10.00 10.50 0.55 3.40 4.00 2.50 15.08 18.10 2.94 C 9 9 9 2.50 2.50 2.50 1.50 7.50 8.10 0.55 3.40 4.00 2.50 15.08 18.10 2.21 F 9 9 12 2.50 2.50 3.50 1.50 8.50 9.10 0.55 3.40 4.00 2.50 15.08 18.10 2.50 E 9 9 14 2.50 2.50 4.10 1.50 9.10 9.80 0.55 3.35 4.00 2.50 14.86 18.10 2.72 D 9 9 18 2.50 2.50 5.00 1.50 10.00 10.50 0.55 3.35 4.00 2.50 14.86 18.10 2.99 C 9 12 12 2.50 3.50 3.50 1.50 9.50 10.20 0.55 3.40 4.00 2.50 15.08 18.10 2.79 D 9 12 14 2.45 3.45 4.10 1.50 10.00 10.50 0.55 3.38 4.00 2.50 15.00 18.10 2.96 C 9 12 18 2.30 3.20 4.50 1.50 10.00 10.50 0.55 3.38 4.00 2.50 15.00 18.10 2.96 C
12 12 12 3.33 3.33 3.33 1.50 10.00 10.50 0.55 3.40 4.00 2.50 15.08 18.10 2.94 C 12 12 14 3.15 3.15 3.70 1.50 10.00 10.50 0.55 3.38 4.00 2.50 15.00 18.10 2.96 C 12 12 18 2.90 2.90 4.20 1.50 10.00 10.50 0.55 3.38 4.00 2.50 15.00 18.10 2.96 C
77772.00 2.00 2.00 2.00 1.80 8.00 8.80 0.65 3.25 4.00 2.85 14.42 18.10 2.46 E
77792.00 2.00 2.00 2.50 1.80 8.50 9.30 0.65 3.25 4.00 2.85 14.42 18.10 2.62 D 7 7 7 12 2.00 2.00 2.00 3.50 1.80 9.50 10.30 0.65 3.25 4.00 2.85 14.42 18.10 2.92 C 7 7 7 14 1.95 1.95 1.95 4.10 1.80 9.95 10.80 0.65 3.30 4.00 2.85 14.64 18.10 3.02 B 7 7 7 18 1.85 1.85 1.85 4.45 1.80 10.00 11.00 0.65 3.30 4.00 2.85 14.64 18.10 3.03 B
77992.00 2.00 2.50 2.50 1.80 9.00 9.80 0.65 3.25 4.00 2.85 14.42 18.10 2.77 D 7 7 9 12 2.00 2.00 2.50 3.50 1.80 10.00 10.50 0.65 3.25 4.00 2.85 14.42 18.10 3.08 B 7 7 9 14 1.85 1.85 2.35 3.95 1.80 10.00 10.80 0.65 3.30 4.00 2.85 14.64 18.10 3.03 B 7 7 9 18 1.75 1.75 2.15 4.35 1.80 10.00 11.00 0.65 3.30 4.00 2.85 14.64 18.10 3.03 B 7 7 12 12 1.80 1.80 3.20 3.20 1.80 10.00 10.80 0.65 3.25 4.00 2.85 14.42 18.10 3.08 B 7 7 12 14 1.70 1.70 3.00 3.60 1.80 10.00 10.90 0.65 3.30 4.00 2.85 14.64 18.10 3.03 B 7 7 12 18 1.60 1.60 2.80 4.00 1.80 10.00 11.00 0.65 3.30 4.00 2.85 14.64 18.10 3.03 B
79992.00 2.50 2.50 2.50 1.80 9.50 10.30 0.65 3.25 4.00 2.85 14.42 18.10 2.92 C 7 9 9 12 1.90 2.40 2.40 3.30 1.80 10.00 10.80 0.65 3.28 4.00 2.85 14.55 18.10 3.05 B 7 9 9 14 1.80 2.25 2.25 3.70 1.80 10.00 10.90 0.65 3.25 4.00 2.85 14.42 18.10 3.08 B 7 9 9 18 1.70 2.10 2.10 4.10 1.80 10.00 11.00 0.65 3.25 4.00 2.85 14.42 18.10 3.08 B 7 9 12 12 1.75 2.15 3.05 3.05 1.80 10.00 10.80 0.65 3.25 4.00 2.85 14.42 18.10 3.08 B 7 9 12 14 1.65 2.05 2.90 3.40 1.80 10.00 10.90 0.65 3.22 4.00 2.85 14.29 18.10 3.11 B 7 9 12 18 1.55 1.95 2.70 3.80 1.80 10.00 11.00 0.65 3.20 4.00 2.85 14.20 18.10 3.13 B 7 12 12 12 1.60 2.80 2.80 2.80 1.80 10.00 11.00 0.65 3.22 4.00 2.85 14.29 18.10 3.11 B 7 12 12 14 1.55 2.70 2.70 3.05 1.80 10.00 11.00 0.65 3.22 4.00 2.85 14.29 18.10 3.11 B
99992.50 2.50 2.50 2.50 1.80 10.00 11.00 0.65 3.30 4.00 2.85 14.64 18.10 3.03 B 9 9 9 12 2.30 2.30 2.30 3.10 1.80 10.00 11.00 0.65 3.25 4.00 2.85 14.42 18.10 3.08 B 9 9 9 14 2.15 2.15 2.15 3.55 1.80 10.00 11.00 0.65 3.24 4.00 2.85 14.37 18.10 3.09 B 9 9 9 18 2.00 2.00 2.00 4.00 1.80 10.00 11.00 0.65 3.23 4.00 2.85 14.33 18.10 3.10 B 9 9 12 12 2.10 2.10 2.90 2.90 1.80 10.00 11.00 0.65 3.20 4.00 2.85 14.20 18.10 3.13 B 9 9 12 14 2.00 2.00 2.75 3.25 1.80 10.00 11.00 0.65 3.17 4.00 2.85 14.06 18.10 3.15 B 9 9 12 18 1.85 1.85 2.60 3.70 1.80 10.00 11.00 0.65 3.15 4.00 2.85 13.98 18.10 3.17 B 9 12 12 12 1.90 2.70 2.70 2.70 1.80 10.00 11.00 0.65 3.17 4.00 2.85 14.06 18.10 3.15 B 9 12 12 14 1.85 2.50 2.50 3.15 1.80 10.00 11.00 0.65 3.17 4.00 2.85 14.06 18.10 3.15 B
12 12 12 12 2.50 2.50 2.50 2.50 1.80 10.00 11.00 0.65 3.17 4.00 2.85 14.06 18.10 3.15 B
TRI (1x3)QUADRI(1x4)
total power input
(kW)
total current
(A)@230V
ENERGY
LABEL
BI (1x2)
Co
mb
.
Combinations
Rated capacity Output/kW
(Nom. cooling)
total cooling
capacity(kW)
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
-27-
HEATING
EER
(W/W)
UnitAUnitBUnitCUnitDUnitAUnitBUnitCUnit
D
min. data
rated
data
max.
data
min.
data
rated
data
max.
Data
min. data
rated
data
max. Data
rated
capacity 7 18 2.30 5.50 1.20 7.80 7.50 0.50 2.95 4.00 2.15 12.64 18.10 2.64 E 9 18 2.90 5.50 1.20 8.40 8.40 0.50 3.00 4.00 2.15 12.87 18.10 2.80 D
12 14
3.80 4.60 1.20 8.40 7.30 0.50 3.00 4.00 2.15 12.87 18.10 2.80 D
12 18
3.80 5.50 1.20 9.30 8.20 0.50 3.30 4.00 2.15 14.64 18.10 2.82 D
14 14
4.60 4.60 1.20 9.20 9.20 0.50 3.30 4.00 2.15 14.64 18.10 2.79 E
14 18
4.60 5.50 1.20 10.10 8.20 0.50 3.45 4.00 2.15 15.53 18.10 2.93 D
18 18
5.50 5.50 1.20 11.00 9.10 0.50 3.45 4.00 2.15 15.53 18.10 3.19 C 7 7 12 2.30 2.30 3.80 1.20 8.40 10.20 0.55 2.95 4.00 2.50 13.75 18.10 2.85 D 7 7 14 2.30 2.30 4.60 1.20 9.20 10.20 0.55 2.90 4.00 2.50 14.20 18.10 3.17 C 7 7 18 2.30 2.30 5.50 1.20 10.10 10.50 0.55 2.95 4.00 2.50 14.42 18.10 3.42 B 7 9 9 2.30 2.90 2.90 1.20 8.10 11.00 0.55 2.95 4.00 2.50 13.75 18.10 2.75 E 7 9 12 2.30 2.90 3.80 1.50 9.00 7.80 0.55 2.95 4.00 2.50 13.75 18.10 3.05 C 7 9 14 2.30 2.90 4.60 1.50 9.80 8.40 0.55 3.00 4.00 2.50 13.98 18.10 3.27 C 7 9 18 2.30 2.90 5.50 1.50 10.70 9.30 0.55 3.05 4.00 2.50 15.08 18.10 3.51 B 7 12 12 2.30 3.80 3.80 1.50 9.90 10.20 0.55 2.95 4.00 2.50 15.08 18.10 3.36 C 7 12 14 2.30 3.80 4.60 1.50 10.70 10.50 0.55 3.00 4.00 2.50 15.08 18.10 3.57 B 7 12 18 2.10 3.60 5.30 1.50 11.00 10.50 0.55 3.05 4.00 2.50 15.08 18.10 3.61 A 9 9 9 2.90 2.90 2.90 1.50 8.70 10.80 0.55 3.00 4.00 2.50 15.08 18.10 2.90 D 9 9 12 2.90 2.90 3.80 1.50 9.60 11.00 0.55 3.05 4.00 2.50 15.08 18.10 3.15 C 9 9 14 2.90 2.90 4.60 1.50 10.40 11.00 0.55 3.10 4.00 2.50 14.86 18.10 3.35 C 9 9 18 2.80 2.80 5.40 1.50 11.00 11.00 0.55 3.10 4.00 2.50 14.86 18.10 3.55 B 9 12 12 2.90 3.80 3.80 1.50 10.50 11.00 0.55 3.05 4.00 2.50 15.08 18.10 3.44 B 9 12 14 2.70 3.80 4.50 1.50 11.00 11.00 0.55 3.10 4.00 2.50 15.00 18.10 3.55 B 9 12 18 2.55 3.55 4.90 1.50 11.00 10.50 0.55 3.15 4.00 2.50 15.00 18.10 3.49 B
12 12 12 3.66 3.66 3.66 1.50 11.00 11.50 0.55 3.45 4.00 2.50 15.08 18.10 3.19 C 12 12 14 3.45 3.45 4.10 1.50 11.00 11.50 0.55 3.40 4.00 2.50 15.00 18.10 3.24 C 12 12 18 3.20 3.20 4.60 1.50 11.00 11.50 0.55 3.40 4.00 2.50 15.00 18.10 3.24 C
77772.30 2.30 2.30 2.30 1.50 9.20 11.50 0.65 3.25 4.00 2.85 14.42 18.10 2.83 D
77792.30 2.30 2.30 2.90 1.50 9.80 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.02 C 7 7 7 12 2.30 2.30 2.30 3.80 1.80 10.70 10.50 0.65 3.25 4.00 2.85 14.42 18.10 3.29 C 7 7 7 14 2.20 2.20 2.20 4.40 1.80 11.00 10.50 0.65 3.30 4.00 2.85 14.64 18.10 3.33 C 7 7 7 18 2.05 2.05 2.05 4.85 1.80 11.00 11.50 0.65 3.30 4.00 2.85 14.64 18.10 3.33 C
77992.30 2.30 2.90 2.90 1.80 10.40 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.20 C 7 7 9 12 2.25 2.25 2.85 3.65 1.80 11.00 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.38 C 7 7 9 14 2.10 2.10 2.65 4.15 1.80 11.00 11.50 0.65 3.30 4.00 2.85 14.64 18.10 3.33 C 7 7 9 18 1.95 1.95 2.35 4.75 1.80 11.00 11.50 0.65 3.30 4.00 2.85 14.64 18.10 3.33 C 7 7 12 12 2.00 2.00 3.50 3.50 1.80 11.00 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.38 C 7 7 12 14 1.90 1.90 3.30 3.90 1.80 11.00 11.50 0.65 3.30 4.00 2.85 14.64 18.10 3.33 C 7 7 12 18 1.75 1.75 3.10 4.40 1.80 11.00 11.50 0.65 3.30 4.00 2.85 14.64 18.10 3.33 C
79992.30 2.90 2.90 2.90 1.80 11.00 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.38 C 7 9 9 12 2.10 2.65 2.65 3.60 1.80 11.00 11.50 0.65 3.28 4.00 2.85 14.55 18.10 3.35 C 7 9 9 14 2.00 2.50 2.50 4.00 1.80 11.00 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.38 C 7 9 9 18 1.85 2.30 2.30 4.55 1.80 11.00 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.38 C 7 9 12 12 2.00 2.30 3.35 3.35 1.80 11.00 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.38 C 7 9 12 14 1.80 2.25 3.20 3.75 1.80 11.00 11.50 0.65 3.22 4.00 2.85 14.29 18.10 3.42 B 7 9 12 18 1.70 2.15 2.95 4.20 1.80 11.00 11.50 0.65 3.20 4.00 2.85 14.20 18.10 3.44 B 7 12 12 12 1.70 3.10 3.10 3.10 1.80 11.00 11.50 0.65 3.22 4.00 2.85 14.29 18.10 3.42 B 7 12 12 14 1.70 3.00 3.00 3.30 1.80 11.00 11.50 0.65 3.22 4.00 2.85 14.29 18.10 3.42 B
99992.75 2.75 2.75 2.75 1.80 11.00 11.50 0.65 3.30 4.00 2.85 14.64 18.10 3.33 C 9 9 9 12 2.55 2.55 2.55 3.35 1.80 11.00 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.38 C 9 9 9 14 2.35 2.35 2.35 3.95 1.80 11.00 11.50 0.65 3.24 4.00 2.85 14.37 18.10 3.40 C 9 9 9 18 2.20 2.20 2.20 4.40 1.80 11.00 11.50 0.65 3.23 4.00 2.85 14.33 18.10 3.41 B 9 9 12 12 2.30 2.30 3.20 3.20 1.80 11.00 11.50 0.65 3.20 4.00 2.85 14.20 18.10 3.44 B 9 9 12 14 2.20 2.20 3.00 3.60 1.80 11.00 11.50 0.65 3.17 4.00 2.85 14.06 18.10 3.47 B 9 9 12 18 2.05 2.05 2.85 4.05 1.80 11.00 11.50 0.65 3.15 4.00 2.85 13.98 18.10 3.49 B 9 121212
2.00 3.00 3.00 3.00
1.80 11.00 11.50 0.65 3.15 4.00 2.85 13.98 18.10 3.49 B
9 121214
2.00 2.75 2.75 3.50
1.80 11.00 11.50 0.65 3.15 4.00 2.85 13.98 18.10 3.49 B
12 12 12 12
2.75 2.75 2.75 2.75
1.80 11.00 11.50 0.65 3.15 4.00 2.85 13.98 18.10 3.49 B
Co
mb.
Combinations
QUADRI(1x4)
ENERGY
LABEL
Rated capacity Output/kW
(Nom. heating)
total heating
capacity(KW)
total power input
(W)
total current
(A)@230V
BI (1x2)TRI (1x3)
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
-28-
AU362XHERA combination and the data
COOLING
EER
(W/W)
UnitAUnitBUnitCUnitDUnitEUnitAUnitBUnitCUnitDUnit
E
min. data
rated
data
max. data
min. data
rated
data
max. Data
min. data
rated
data
max. Data
rated
capacity
7 18 — — 2.00 5.00 1.00 7.00 7.50 0.50 2.85 4.00 2.15 12.64 18.10 2.46 E 9 18 — — 2.50 5.00 1.00 7.50 8.00 0.50 2.90 4.00 2.15 12.87 18.10 2.59 E
12 14
— 3.50 4.10 1.00 7.60 8.10 0.50 2.90 4.00 2.15 12.87 18.10 2.62 D
12 18
— 3.50 5.00 1.00 8.50 9.00 0.50 3.30 4.00 2.15 14.64 18.10 2.58 E
14 14
— 4.10 4.10 1.00 8.20 8.80 0.50 3.30 4.00 2.15 14.64 18.10 2.48 E
14 18
— 4.10 5.00 1.00 9.10 9.70 0.50 3.50 4.00 2.15 15.53 18.10 2.60 E
18 18
— 5.00 5.00 1.00 10.00 10.50 0.50 3.50 4.00 2.15 15.53 18.10 2.86 C 7 7 12 — 2.00 2.00 3.50 1.50 7.50 8.10 0.55 3.10 4.00 2.50 13.75 18.10 2.42 E 7 7 14 — 2.00 2.00 4.10 1.50 8.10 8.80 0.55 3.20 4.00 2.50 14.20 18.10 2.53 E 7 7 18 — 2.00 2.00 5.00 1.50 9.00 9.80 0.55 3.25 4.00 2.50 14.42 18.10 2.77 D 7 9 9 2.00 2.50 2.50 1.50 7.00 7.60 0.55 3.10 4.00 2.50 13.75 18.10 2.26 F 7 9 12 — 2.00 2.50 3.50 1.50 8.00 8.60 0.55 3.10 4.00 2.50 13.75 18.10 2.58 E 7 9 14 — 2.00 2.50 4.10 1.50 8.60 9.30 0.55 3.15 4.00 2.50 13.98 18.10 2.73 D 7 9 18 — 2.00 2.50 5.00 1.50 9.50 10.20 0.55 3.40 4.00 2.50 15.08 18.10 2.79 D 7 12 12 — 2.00 3.50 3.50 1.50 9.00 9.60 0.55 3.40 4.00 2.50 15.08 18.10 2.65 D 7 12 14 — 2.00 3.50 4.10 1.50 9.60 10.20 0.55 3.40 4.00 2.50 15.08 18.10 2.82 C 7 12 18 — 1.90 3.30 4.80 1.50 10.00 10.50 0.55 3.40 4.00 2.50 15.08 18.10 2.94 C 9 9 9 2.50 2.50 2.50 1.50 7.50 8.10 0.55 3.40 4.00 2.50 15.08 18.10 2.21 F 9 9 12 — 2.50 2.50 3.50 1.50 8.50 9.10 0.55 3.40 4.00 2.50 15.08 18.10 2.50 E 9 9 14 — 2.50 2.50 4.10 1.50 9.10 9.80 0.55 3.35 4.00 2.50 14.86 18.10 2.72 D 9 9 18 — 2.50 2.50 5.00 1.50 10.00 10.50 0.55 3.35 4.00 2.50 14.86 18.10 2.99 C 9 12 12 — 2.50 3.50 3.50 1.50 9.50 10.20 0.55 3.40 4.00 2.50 15.08 18.10 2.79 D 9 12 14 — 2.45 3.45 4.10 1.50 10.00 10.50 0.55 3.38 4.00 2.50 15.00 18.10 2.96 C 9 12 18 — 2.30 3.20 4.50 1.50 10.00 10.50 0.55 3.38 4.00 2.50 15.00 18.10 2.96 C
12 12 12 — — 3.33 3.33 3.33 1.50 10.00 10.50 0.55 3.40 4.00 2.50 15.08 18.10 2.94 C 12 12 14 — — 3.15 3.15 3.70 1.50 10.00 10.50 0.55 3.38 4.00 2.50 15.00 18.10 2.96 C 12 12 18 — — 2.90 2.90 4.20 1.50 10.00 10.50 0.55 3.38 4.00 2.50 15.00 18.10 2.96 C
7777—2.00 2.00 2.00 2.00 1.80 8.00 8.80 0.65 3.25 4.00 2.85 14.42 18.10 2.46 E 7779—2.00 2.00 2.00 2.50 1.80 8.50 9.30 0.65 3.25 4.00 2.85 14.42 18.10 2.62 D 7 7 7 12 — 2.00 2.00 2.00 3.50 1.80 9.50 10.30 0.65 3.25 4.00 2.85 14.42 18.10 2.92 C 7 7 7 14 — 1.95 1.95 1.95 4.10 1.80 9.95 10.80 0.65 3.30 4.00 2.85 14.64 18.10 3.02 B 7 7 7 18 — 1.85 1.85 1.85 4.45 1.80 10.00 11.00 0.65 3.30 4.00 2.85 14.64 18.10 3.03 B 7799—2.00 2.00 2.50 2.50 1.80 9.00 9.80 0.65 3.25 4.00 2.85 14.42 18.10 2.77 D 7 7 9 12 — 2.00 2.00 2.50 3.50 1.80 10.00 10.50 0.65 3.25 4.00 2.85 14.42 18.10 3.08 B 7 7 9 14 — 1.85 1.85 2.35 3.95 1.80 10.00 10.80 0.65 3.30 4.00 2.85 14.64 18.10 3.03 B 7 7 9 18 — 1.75 1.75 2.15 4.35 1.80 10.00 11.00 0.65 3.30 4.00 2.85 14.64 18.10 3.03 B 7 7 12 12 — 1.80 1.80 3.20 3.20 1.80 10.00 10.80 0.65 3.25 4.00 2.85 14.42 18.10 3.08 B 7 7 12 14 — 1.70 1.70 3.00 3.60 1.80 10.00 10.90 0.65 3.30 4.00 2.85 14.64 18.10 3.03 B 7 7 12 18 — 1.60 1.60 2.80 4.00 1.80 10.00 11.00 0.65 3.30 4.00 2.85 14.64 18.10 3.03 B 7999—2.00 2.50 2.50 2.50 1.80 9.50 10.30 0.65 3.25 4.00 2.85 14.42 18.10 2.92 C 7 9 9 12 — 1.90 2.40 2.40 3.30 1.80 10.00 10.80 0.65 3.28 4.00 2.85 14.55 18.10 3.05 B 7 9 9 14 — 1.80 2.25 2.25 3.70 1.80 10.00 10.90 0.65 3.25 4.00 2.85 14.42 18.10 3.08 B 7 9 9 18 — 1.70 2.10 2.10 4.10 1.80 10.00 11.00 0.65 3.25 4.00 2.85 14.42 18.10 3.08 B 7 9 12 12 — 1.75 2.15 3.05 3.05 1.80 10.00 10.80 0.65 3.25 4.00 2.85 14.42 18.10 3.08 B 7 9 12 14 — 1.65 2.05 2.90 3.40 1.80 10.00 10.90 0.65 3.22 4.00 2.85 14.29 18.10 3.11 B 7 9 12 18 — 1.55 1.95 2.70 3.80 1.80 10.00 11.00 0.65 3.20 4.00 2.85 14.20 18.10 3.13 B 7 12 12 12 — 1.60 2.80 2.80 2.80 1.80 10.00 11.00 0.65 3.22 4.00 2.85 14.29 18.10 3.11 B 7 12 12 14 — 1.55 2.70 2.70 3.05 1.80 10.00 11.00 0.65 3.22 4.00 2.85 14.29 18.10 3.11 B 9999—2.50 2.50 2.50 2.50 1.80 10.00 11.00 0.65 3.30 4.00 2.85 14.64 18.10 3.03 B 9 9 9 12 — 2.30 2.30 2.30 3.10 1.80 10.00 11.00 0.65 3.25 4.00 2.85 14.42 18.10 3.08 B 9 9 9 14 — 2.15 2.15 2.15 3.55 1.80 10.00 11.00 0.65 3.24 4.00 2.85 14.37 18.10 3.09 B 9 9 9 18 — 2.00 2.00 2.00 4.00 1.80 10.00 11.00 0.65 3.23 4.00 2.85 14.33 18.10 3.10 B 9 9 12 12 — 2.10 2.10 2.90 2.90 1.80 10.00 11.00 0.65 3.20 4.00 2.85 14.20 18.10 3.13 B 9 9 12 14 — 2.00 2.00 2.75 3.25 1.80 10.00 11.00 0.65 3.17 4.00 2.85 14.06 18.10 3.15 B 9 9 12 18 — 1.85 1.85 2.60 3.70 1.80 10.00 11.00 0.65 3.15 4.00 2.85 13.98 18.10 3.17 B 9 12 12 12 — 1.90 2.70 2.70 2.70 1.80 10.00 11.00 0.65 3.17 4.00 2.85 14.06 18.10 3.15 B 9 12 12 14 — 1.85 2.50 2.50 3.15 1.80 10.00 11.00 0.65 3.17 4.00 2.85 14.06 18.10 3.15 B
12 12 12 12 — 2.50 2.50 2.50 2.50 1.80 10.00 11.00 0.65 3.17 4.00 2.85 14.06 18.10 3.15 B
7
77772.00 2.00 2.00 2.00 2.00 2.00 10.00 11.00 0.70 3.30 4.00 2.85 13.98 18.10 3.03 B
7
77791.90 1.90 1.90 1.90 2.38 2.00 10.00 11.00 0.70 3.28 4.00 2.85 13.98 18.10 3.05 B
7
7 7 7 12 1.74 1.74 1.74 1.74 3.04 2.00 10.00 11.00 0.70 3.26 4.00 2.85 13.98 18.10 3.07 B
7
7 7 7 14 1.65 1.65 1.65 1.65 3.39 2.00 10.00 11.00 0.70 3.30 4.00 2.85 13.98 18.10 3.03 B
7
7 7 7 18 1.54 1.54 1.54 1.54 3.85 2.00 10.00 11.00 0.70 3.30 4.00 2.85 13.98 18.10 3.03 B
7
77991.82 1.82 1.82 2.27 2.27 2.00 10.00 11.00 0.70 3.25 4.00 2.85 13.98 18.10 3.08 B
7
7 7 9 12 1.67 1.67 1.67 2.08 2.92 2.00 10.00 11.00 0.70 3.26 4.00 2.85 13.98 18.10 3.07 B
7
7 7 9 14 1.59 1.59 1.59 1.98 3.25 2.00 10.00 11.00 0.70 3.28 4.00 2.85 13.98 18.10 3.05 B
7
7 7 9 18 1.48 1.48 1.48 1.85 3.70 2.00 10.00 11.00 0.70 3.26 4.00 2.85 13.98 18.10 3.07 B
7
7 7 12 12 1.54 1.54 1.54 2.69 2.69 2.00 10.00 11.00 0.70 3.30 4.00 2.85 13.98 18.10 3.03 B
7
7 7 12 14 1.47 1.47 1.47 2.57 3.01 2.00 10.00 11.00 0.70 3.33 4.00 2.85 13.98 18.10 3.00 B
7
79991.74 1.74 2.17 2.17 2.17 2.00 10.00 11.00 0.70 3.35 4.00 2.85 13.98 18.10 2.99 C
7
7 9 9 12 1.60 1.60 2.00 2.00 2.80 2.00 10.00 11.00 0.70 3.35 4.00 2.85 13.98 18.10 2.99 C
7
7 9 9 14 1.53 1.53 1.91 1.91 3.13 2.00 10.00 11.00 0.70 3.33 4.00 2.85 13.98 18.10 3.00 B
7
7 9 12 12 1.48 1.48 1.85 2.59 2.59 2.00 10.00 11.00 0.70 3.34 4.00 2.85 13.98 18.10 2.99 C
7
99991.67 2.08 2.08 2.08 2.08 2.00 10.00 11.00 0.70 3.38 4.00 2.85 13.98 18.10 2.96 C
7
9 9 9 12 1.54 1.92 1.92 1.92 2.69 2.00 10.00 11.00 0.70 3.37 4.00 2.85 13.98 18.10 2.97 C
7
9 9 9 14 1.47 1.84 1.84 1.84 3.01 2.00 10.00 11.00 0.70 3.35 4.00 2.85 13.98 18.10 2.99 C
9
99992.00 2.00 2.00 2.00 2.00 2.00 10.00 11.00 0.70 3.35 4.00 2.85 13.98 18.10 2.99 C
9
9 9 9 12 1.85 1.85 1.85 1.85 2.59 2.00 10.00 11.00 0.70 3.28 4.00 2.85 13.98 18.10 3.05 B
Com
b.
Combinations
total cooling
capacity(kW)
TRI (1x3)QUADRI(1x4)Quintuple(1×5)
total power input
(kW)
total current
(A)@230V
ENERGY
LABEL
BI (1x2)
Rated capacity Output/kW
(Nom. cooling)
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
-29-
HEATING
EER
(W/W)
UnitAUnitBUnitCUnitDUnitEUnitAUnitBUnitCUnitDUnit
E
min. data
rated
data
max. data
min. data
rated
data
max. Data
min. data
rated
data
max.
Data
rated
capacity
7 18 — — 2.30 5.50 — 1.20 7.80 7.50 0.50 2.95 4.00 2.15 12.64 18.10 2.64 E 9 18 — — 2.90 5.50 — 1.20 8.40 8.40 0.50 3.00 4.00 2.15 12.87 18.10 2.80 E
12 14
— — 3.80 4.60 — 1.20 8.40 7.30 0.50 3.00 4.00 2.15 12.87 18.10 2.80 E
12 18
— — 3.80 5.50 — 1.20 9.30 8.20 0.50 3.30 4.00 2.15 14.64 18.10 2.82 D
14 14
— — 4.60 4.60 — 1.20 9.20 9.20 0.50 3.30 4.00 2.15 14.64 18.10 2.79 E
14 18
— — 4.60 5.50 — 1.20 10.10 8.20 0.50 3.45 4.00 2.15 15.53 18.10 2.93 D
18 18
— — 5.50 5.50 — 1.20 11.00 9.10 0.50 3.45 4.00 2.15 15.53 18.10 3.19 C 7 7 12 — 2.30 2.30 3.80 1.20 8.40 10.20 0.55 2.95 4.00 2.50 13.75 18.10 2.85 D 7 7 14 — 2.30 2.30 4.60 1.20 9.20 10.20 0.55 2.90 4.00 2.50 14.20 18.10 3.17 C 7 7 18 — 2.30 2.30 5.50 1.20 10.10 10.50 0.55 2.95 4.00 2.50 14.42 18.10 3.42 B 7 9 9 — 2.30 2.90 2.90 1.20 8.10 11.00 0.55 2.95 4.00 2.50 13.75 18.10 2.75 E 7 9 12 — 2.30 2.90 3.80 1.50 9.00 7.80 0.55 2.95 4.00 2.50 13.75 18.10 3.05 C 7 9 14 — 2.30 2.90 4.60 1.50 9.80 8.40 0.55 3.00 4.00 2.50 13.98 18.10 3.27 C 7 9 18 — 2.30 2.90 5.50 1.50 10.70 9.30 0.55 3.05 4.00 2.50 15.08 18.10 3.51 B 7 12 12 — — 2.30 3.80 3.80 1.50 9.90 10.20 0.55 2.95 4.00 2.50 15.08 18.10 3.36 C 7 12 14 — — 2.30 3.80 4.60 1.50 10.70 10.50 0.55 3.00 4.00 2.50 15.08 18.10 3.57 B 7 12 18 — — 2.10 3.60 5.30 1.50 11.00 10.50 0.55 3.05 4.00 2.50 15.08 18.10 3.61 A 9 9 9 — 2.90 2.90 2.90 1.50 8.70 10.80 0.55 3.00 4.00 2.50 15.08 18.10 2.90 D 9 9 12 — 2.90 2.90 3.80 1.50 9.60 11.00 0.55 3.05 4.00 2.50 15.08 18.10 3.15 C 9 9 14 — 2.90 2.90 4.60 1.50 10.40 11.00 0.55 3.10 4.00 2.50 14.86 18.10 3.35 C 9 9 18 — 2.80 2.80 5.40 1.50 11.00 11.00 0.55 3.10 4.00 2.50 14.86 18.10 3.55 B 9 12 12 — — 2.90 3.80 3.80 1.50 10.50 11.00 0.55 3.05 4.00 2.50 15.08 18.10 3.44 B 9 12 14 — — 2.70 3.80 4.50 1.50 11.00 11.00 0.55 3.10 4.00 2.50 15.00 18.10 3.55 B 9 12 18 — — 2.55 3.55 4.90 1.50 11.00 10.50 0.55 3.15 4.00 2.50 15.00 18.10 3.49 B
12 12 12 — 3.66 3.66 3.66 1.50 11.00 11.50 0.55 3.45 4.00 2.50 15.08 18.10 3.19 C 12 12 14 — 3.45 3.45 4.10 1.50 11.00 11.50 0.55 3.40 4.00 2.50 15.00 18.10 3.24 C 12 12 18 — 3.20 3.20 4.60 1.50 11.00 11.50 0.55 3.40 4.00 2.50 15.00 18.10 3.24 C
7777—2.30 2.30 2.30 2.30 1.50 9.20 11.50 0.65 3.25 4.00 2.85 14.42 18.10 2.83 D 7779—2.30 2.30 2.30 2.90 1.50 9.80 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.02 C 7 7 7 12 — 2.30 2.30 2.30 3.80 — 1.80 10.70 10.50 0.65 3.25 4.00 2.85 14.42 18.10 3.29 C 7 7 7 14 — 2.20 2.20 2.20 4.40 — 1.80 11.00 10.50 0.65 3.30 4.00 2.85 14.64 18.10 3.33 C 7 7 7 18 — 2.05 2.05 2.05 4.85 — 1.80 11.00 11.50 0.65 3.30 4.00 2.85 14.64 18.10 3.33 C 7799—2.30 2.30 2.90 2.90 1.80 10.40 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.20 C 7 7 9 12 — 2.25 2.25 2.85 3.65 — 1.80 11.00 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.38 C 7 7 9 14 — 2.10 2.10 2.65 4.15 — 1.80 11.00 11.50 0.65 3.30 4.00 2.85 14.64 18.10 3.33 C 7 7 9 18 — 1.95 1.95 2.35 4.75 — 1.80 11.00 11.50 0.65 3.30 4.00 2.85 14.64 18.10 3.33 C 7 7 12 12 — 2.00 2.00 3.50 3.50 — 1.80 11.00 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.38 C 7 7 12 14 — 1.90 1.90 3.30 3.90 — 1.80 11.00 11.50 0.65 3.30 4.00 2.85 14.64 18.10 3.33 C 7 7 12 18 — 1.75 1.75 3.10 4.40 — 1.80 11.00 11.50 0.65 3.30 4.00 2.85 14.64 18.10 3.33 C 7999—2.30 2.90 2.90 2.90 1.80 11.00 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.38 C 7 9 9 12 — 2.10 2.65 2.65 3.60 — 1.80 11.00 11.50 0.65 3.28 4.00 2.85 14.55 18.10 3.35 C 7 9 9 14 — 2.00 2.50 2.50 4.00 — 1.80 11.00 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.38 C 7 9 9 18 — 1.85 2.30 2.30 4.55 — 1.80 11.00 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.38 C 7 9 12 12 — 2.00 2.30 3.35 3.35 — 1.80 11.00 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.38 C 7 9 12 14 — 1.80 2.25 3.20 3.75 — 1.80 11.00 11.50 0.65 3.22 4.00 2.85 14.29 18.10 3.42 B 7 9 12 18 — 1.70 2.15 2.95 4.20 — 1.80 11.00 11.50 0.65 3.20 4.00 2.85 14.20 18.10 3.44 B 7 12 12 12 — 1.70 3.10 3.10 3.10 1.80 11.00 11.50 0.65 3.22 4.00 2.85 14.29 18.10 3.42 B 7 12 12 14 — 1.70 3.00 3.00 3.30 1.80 11.00 11.50 0.65 3.22 4.00 2.85 14.29 18.10 3.42 B 9999—2.75 2.75 2.75 2.75 1.80 11.00 11.50 0.65 3.30 4.00 2.85 14.64 18.10 3.33 C 9 9 9 12 — 2.55 2.55 2.55 3.35 — 1.80 11.00 11.50 0.65 3.25 4.00 2.85 14.42 18.10 3.38 C 9 9 9 14 — 2.35 2.35 2.35 3.95 — 1.80 11.00 11.50 0.65 3.24 4.00 2.85 14.37 18.10 3.40 C 9 9 9 18 — 2.20 2.20 2.20 4.40 — 1.80 11.00 11.50 0.65 3.23 4.00 2.85 14.33 18.10 3.41 B 9 9 12 12 — 2.30 2.30 3.20 3.20 — 1.80 11.00 11.50 0.65 3.20 4.00 2.85 14.20 18.10 3.44 B 9 9 12 14 — 2.20 2.20 3.00 3.60 — 1.80 11.00 11.50 0.65 3.17 4.00 2.85 14.06 18.10 3.47 B 9 9 12 18 — 2.05 2.05 2.85 4.05 — 1.80 11.00 11.50 0.65 3.15 4.00 2.85 13.98 18.10 3.49 B 9 121212—
2.00 3.00 3.00 3.00
1.80 11.00 11.50 0.65 3.15 4.00 2.85 13.98 18.10 3.49 B
9 121214—
2.00 2.75 2.75 3.50
1.80 11.00 11.50 0.65 3.15 4.00 2.85 13.98 18.10 3.49 B
12 12 12 12 —
2.75 2.75 2.75 2.75
1.80 11.00 11.50 0.65 3.15 4.00 2.85 13.98 18.10 3.49 B
7
7777
2.20 2.20 2.20 2.20 2.20 2.10
11.00 11.50
0.70 3.30
4.00 2.85 13.98 18.10
3.33 C
7
7779
2.09 2.09 2.09 2.09 2.64 2.10
11.00 11.50
0.70 3.29
4.00 2.85 13.98 18.10 3.34 C
7
77712
1.95 1.95 1.95 1.95 3.22 2.10
11.00 11.50
0.70 3.28
4.00 2.85 13.98 18.10 3.35 C
7
77714
1.83 1.83 1.83 1.83 3.67 2.10
11.00 11.50
0.70 3.26
4.00 2.85 13.98 18.10 3.37 C
7
77718
1.72 1.72 1.72 1.72 4.12 2.10
11.00 11.50
0.70 3.24
4.00 2.85 13.98 18.10 3.40 C
7
7799
1.99 1.99 1.99 2.51 2.51 2.10
11.00 11.50
0.70 3.28
4.00 2.85 13.98 18.10
3.35 C
7
77912
1.86 1.86 1.86 2.35 3.07 2.10
11.00 11.50
0.70 3.27
4.00 2.85 13.98 18.10 3.36 C
7
77914
1.76 1.76 1.76 2.22 3.51 2.10
11.00 11.50
0.70 3.26
4.00 2.85 13.98 18.10 3.37 C
7
77918
1.65 1.65 1.65 2.08 3.95 2.10
11.00 11.50
0.70 3.24
4.00 2.85 13.98 18.10 3.40 C
7
7 7 12 12
1.74 1.74 1.74 2.88 2.88 2.10
11.00 11.50
0.70 3.28
4.00 2.85 13.98 18.10 3.35 C
7
7 7 12 14
1.65 1.65 1.65 2.73 3.31 2.10
11.00 11.50
0.70 3.26
4.00 2.85 13.98 18.10
3.37 C
7
7999
1.90 1.90 2.40 2.40 2.40 2.10
11.00 11.50
0.70 3.25
4.00 2.85 13.98 18.10 3.38 C
7
79912
1.78 1.78 2.25 2.25 2.94 2.10
11.00 11.50
0.70 3.29
4.00 2.85 13.98 18.10 3.34 C
7
79914
1.69 1.69 2.13 2.13 3.37 2.10
11.00 11.50
0.70 3.27
4.00 2.85 13.98 18.10 3.36 C
7
7 9 12 12
1.68 1.68 2.11 2.77 2.77 2.10
11.00 11.50
0.70 3.30
4.00 2.85 13.98 18.10 3.33 C
7
9999
1.82 2.29 2.29 2.29 2.29 2.10
11.00 11.50
0.70 3.30
4.00 2.85 13.98 18.10 3.33 C
7
99912
1.71 2.16 2.16 2.16 2.82 2.10
11.00 11.50
0.70 3.28
4.00 2.85 13.98 18.10
3.35 C
7
99914
1.62 2.04 2.04 2.04 3.24 2.10
11.00 11.50
0.70 3.26
4.00 2.85 13.98 18.10 3.37 C
9
9999
2.20 2.20 2.20 2.20 2.20 2.10
11.00 11.50
0.70 3.25
4.00 2.85 13.98 18.10 3.38 C
9
99912
2.07 2.07 2.07 2.07 2.71 2.10
11.00 11.50
0.70 3.25
4.00 2.85 13.98 18.10
3.38 C
QUADRI(1x4)
Rated capacity Output/kW
(Nom. heating)
total heating
capacity(KW)
Combinations
TRI (1x3)
ENERGY
LABEL
BI (1x2)
total power input
(W)
total current
(A)@230V
Quintuple(1×5)
Com
b.
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
-30-
4.2. Wiring connection
_xoyy| *xt~ Y _xoyy| *xt~ X _xoyy| *xt~ W
Md^I NNLJNOLi0I QL^/
c*~oyy| *xt~
dy,p| }*zzv. nlmvpV ^LQebJ\ O] PKLww
N
Yyww*xtnl~tyx nlmvp Efstpvo ,t|pFV ^LQebJ\ NkMKQww
N
Yyxxpn~txr nlmvp V ^LQebJ\ O] NKQww
N
`b b`
YM YN
NLW
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
AU18-222XFERA
31-
AU25-342X*ERA
[-lwzvp,t|txrotlr|lwK
dvpl}p |pqp| ~y ~sp txoyy| *xt~ tx}~lvvl~tyx wlx*lv ~y qtxo op~ltvv. sy, ~y }p~ lxo nspnu ~sp nyww*xtnl~tyx
loo|p}}K
_xny||pn~ loo|p}} }p~~txr ,tvv nl*}p lmxy|wlv ~y ~sp }.}~pwK
`]`\]WdX\WbX
\WbX ]WdX
^
_
b
d
`]`\
\WbX ]WdX `\ `]
_
^
]WdX\WbX
_xoyy| *xt~ Y
_xoyy| *xt~ X
_xoyy| *xt~ W
_xoyy| *xt~ Z
Md^I NNLJNOLi0I QL^/
c*~oyy| *xt~
dy,p| }*zzv. nlmvpV
^LQebJ\ O] EQKL0TKLF
ww
N
Yyww*xtnl~tyx nlmvp
Efstpvo ,t|pFV ^LQebJ
\N- ELKSQ0MKQFww
N
Yyxxpn~txr nlmvpV
^LQebJ\ O] EMKQ0NKQF
ww
N
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
32-
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
AU362XHERA:
3
21
7
6
-+4, .+5,
3
21
7
6
.+5,-+4,
+6,
0
/
+7,
+6,
0
/
+7,
+7,
-+4, .+5,
+6,
-+4, .+5,
0
/
.+5,-+4,
4
5
3.
3-
P_YUeY dYZYd fb f\Y ]aXbbd ga]f ]aefU__Uf]ba `UagU_ fb Z]aX XYfU]__i \bh fb eYf UaX W\YW^ f\Y Wb``ga]WUf]ba
UXXdYee=
MaWbddYWf UXXdYee eYff]a[ h]__ WUgeY UVabd`U_ fb f\Y eiefY`=
MaXbbd ga]f H
MaXbbd ga]f G
MaXbbd ga]f F
OgfXbbd ga]f
PbhYd egcc_i WUV_YD
L>BQN<J AK 9B=>kC=>:``
@
Gb``ga]WUf]ba WUV_Y 9R\]Y_X h]dY:D
L>BQN<J @ T ?=B``
@
GbaaYWf]a[ WUV_YD
L>BQN<J AK @=B``
@
?PL; @@><@A>Sk; B>Lj
A>E
+6, +7,
MaXbbd ga]f I
MaXbbd ga]f E
33-
4.3 /7,.-8436/+/7---8436/ limitations on the installation
b\
b]
b^
h
aY
/
0
1
aZ
gsp ztztxr vpxr~s txqy|wl~tyxI zvpl}p |pqp| ~sp qyvvy,txr ~lmvpK
Zp}n|tz~tyx}
emfkgflg
WI XI Yvt{*to ztzp
WI XI Y ]l} ztzp
ww
_~pw
cfoijnj
hxt~
`M Eyxp ,l.F
`N Eyxp ,l.F
`O Eyxp ,l.F
s
^H
^J
ww
w
w
w
w
w
w
ft/p yq ~sp vt{*to }top nyxxpn~tyx ztzp
dtzp vpxr~s ,spx ~sp nywz|p}}y| nyxxpn~} ,t~s ~,y txoyy| *xt~}
Z|yz mp~,ppx p+p|. ~,y txoyy| *xt~}
Z|yz mp~,ppx ~sp y*~oyy| *xt~ lxo ~sp txoyy| *xt~
wML
wq
wu
wu
[
[
ft/p yq ~sp rl} }top nyxxpn~tyx ztzp
dtzp vpxr~s ,spx ~sp nywz|p}}y| nyxxpn~} ,t~s ~,y txoyy| *xt~}
dtzp vpxr~s ,spx ~sp nywz|p}}y| nyxxpn~} yxv. yxp txoyy| *xt~
Z|yz mp~,ppx ~sp y*~oyy| *xt~ lxo ~sp txoyy| *xt~
RKOQ
UKQN
wqp
wqp
w25
wu
wqu
wqp
w25
w25
`MH`NH`O w gy~lv vt{*to ztztxr vpxr~s
wsp wtu
`twt~l~tyx}+lv*p}yx~spztztxr,y|uK
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
-34-
gsp ztztxr vpxr~s txqy|wl~tyxI zvpl}p |pqp| ~sp qyvvy,txr ~lmvpK
Zp}n|tz~tyx}
f~lxol|o
WI XI YIZ vt{*to ztzp
WI XI YIZ ]l} ztzp
ww
_~pw
al-tw*w
hxt~
`M Eyxp ,l.F
`N Eyxp ,l.F
`O Eyxp ,l.F
s
^H
^J
ww
w
w
w
w
w
w
ft/p yq ~sp vt{*to }top nyxxpn~tyx ztzp
dtzp vpxr~s ,spx ~sp nywz|p}}y| nyxxpn~} ,t~s ~,y txoyy| *xt~}
Z|yz mp~,ppx p+p|. ~,y txoyy| *xt~}
Z|yz mp~,ppx ~sp y*~oyy| *xt~ lxo ~sp txoyy| *xt~
[
[
ft/p yq ~sp rl} }top nyxxpn~tyx ztzp
dtzp vpxr~s ,spx ~sp nywz|p}}y| nyxxpn~} ,t~s ~,y txoyy| *xt~}
dtzp vpxr~s ,spx ~sp nywz|p}}y| nyxxpn~} yxv. yxp txoyy| *xt~
Z|yz mp~,ppx ~sp y*~oyy| *xt~ lxo ~sp txoyy| *xt~
RKOQ
UKQN
`MH`NH`OH`P w
gy~lv vt{*to ztztxr vpxr~sE_~ t} xy xppo ~y nsl|rp loot~tyxlv |pq|trp|lx~ ,t~stx ~st} +lv*pF
`P Eyxp ,l.F w dtzp vpxr~s ,spx ~sp nywz|p}}y| nyxxpn~} yxv. yxp txoyy| *xt~
b\
b]
b_
h
aY
/
0
2
1
b^
q
u
u
qp
qp
tp
qp
ru
u
qu
qp
ru
ru
vp
ru
aZ
ML
`twt~l~tyx} +lv*p} yx ~sp ztztxr ,y|u K
AU28-342XHERA
- -
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
35
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
The piping length information, please refer the following table.
Descriptions
Standard
A, B, C, D, E liquid pipe
A, B, C, D,E Gas pipe
mm
Item
Maximum
Unit
L1 (one way)
L2 (one way)
L3 (one way)
h
H +
H -
mm
m
m
m
m
m
m
Size of the liquid side connection pipe
Drop between every two indoor units
Drop between the outdoor unit and the indoor unit
/
/
Size of the gas side connection pipe
Drop between the outdoor unit and the indoor unit
6.35
9.52
L1+L2+L3+L4+L5 m
Total liquid piping length(It is no need to charge additional refrigerant within this value)
L4 (one way) m
L1
L2
L5
h
H +
A
B
E
C
L3
1
5
5
10
10
40
10
25
5
15
10
25
25
60
25
Conneting pipe length
Conneting pipe length
Conneting pipe length
Conneting pipe length
L4
D
L5 (one way) m
10 25
Conneting pipe length
H -
10
`twt~l~tyx} +lv*p} yx ~sp ztztxr ,y|u K
AU362XHERA
- -36
1. Do not connected the embedded branch piping and the outdoor unit when only carrying out piping work without connecting the indoor unit in ordor to add another indoor unit later. Make sure no dirt or mositure gets into eigher side of the embedded branch piping.
2.It is impossible to connect the indoor unit for one room only. Be sure to connect at least 2 rooms.
Installation drawings of indoor and outdoor units
Wrap the insulation pipe with the finishing tape from bottom to top.
Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no gap is left in the insulation pipe's cut line.
Arrangement of piping directions
If there is the danger of the unit falling or overturning, fix the unit with foundation bolts, or with wire or other means. If the location does not have good drainage, place the unit on a level mounting base(or a plastic pedestal). Install the outdoor unit in a level position. Failure to do so may result in water leakage or accumulation.
Rear left
Rear right
Right
Below
Left
Attenti on must be paid to the rising up of drain hose
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
4.4 Outdoor units installation
37-
Refrigerant piping work
Forced fastening without careful centering may damage the threads and cause a leakage of gas.
Pipe Diameter (
) Fastening Torque
Liquid Side 6.35mm (1/4'')
18N.m
Gas Side 9.52mm (3/8'') 50N.m
3. Attaching Drain-Elbow If the drain-elbow is used, please attach it as figure.
Flare nut
Half union
Torque wrench
Spanner
Liquid pipe
Gas pipe
6.35mm ( 1/4'' ) x 0.8mm
9.52mm ( 3/8'' ) x 0.8mm
2. Connection of pipe Apply refrigerant oil on half union and flare nut.
To bend a pipe, give the roundness as large as possible not to crush the pipe. Connecting the pipe of gas side firstly makes working easier.
1. Selection of pipe To this unit, both liquid and gas pipes shall be insulated as they become low temperature in operation.
Use optional parts for piping set or pipes covered with equivalent insulation material.
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
38-
4.Cutting and Flaring work of piping Pipe cutting is carried out with a pipe cutter and burs must be removed.
After inserting the flare nut, flaring work is carried out.
Less than 5cm
It becomes high midway. The end is immersed in
water
It waves. It gap with the ground
ts too small.
There is the bad smell from a ditch.
Please pour water in the drain pan of the indoor unit, and confirm that drainage is carried out serely to outdoor. In case that the attached drain hose is in a room, please apply heat insulation to it without fail.
5.On drainage
Please install the drain hose so as to be downward slope without fail. Please don't do the drainage as shown below.
Correct
Incorrect
Lean Damage of flare Crack Partial Too outside
Pipe diameter
Size A (mm) Liquid side Gas side
6.35mm(1/4")
9.52mm(3/8")
0.8~1.5
1.0~1.5
A
Flare tooling die
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
39-
In case of gas leakage, tighten parts of pipe connection. If leakage stops, then proceed 6 steps.
Purging method: to use vacuum pump
2 way valve
3 way valve
90
0
Service port
90
0
for 6 sec.
6 .Detach the charge hose from the service port, open 2­way valve and 3-way. Turn the valve rod anticlockwise until hitting lightly.
Liquid stop valve
2 way valve
3 way valve
Gas stop valve
Gauge maifold(R410A)
Vacuum pump(R410A)
Open
Close
2 way valve
3 way valve
6
6
2 way valve
3 way valve
Valve rod cap Valve rod cap
Service port cap
1 .Detach the service portis cap of 3-way valve, the valve rod's cap for 2-way valve and 3-way valves, connect the service port into the projection of charge hose (low) for gaugemanifold. Then connect the projection of charge hose (center) for gaugemanifold into vacuum pump.
2 .Open the handle at low in gaugemanifold, operate vacuum pump. If the scale-moves of gause (low) reach vacuum condition in a moment, check 1 again.
3 .Vacuumize for over 15min. And check the level gauge which should read -0.1MPa (-76 cm Hg) at low pressure side. After the completion of vacuumizing, close the handle 'Lo' in the vacuum pump. Check the condition of the scale and hold it for 1-2min. If the scale-moves back in spite of tightening, make flaring work again, then return to the beginning of 3 .
4 .Open the valve rod for the 2-way valve to and an angle of anticlockwise 90 degree. After 6 seconds, close the 2­way valve and make the inspection of gas leakge.
5 .No gas leakage?
If it does not stop gas leakage, discharge whole refrigerants from the service port. After flaring work again and vacuumize, fill up prescribed refrigerant from the gas cylinder.
7 .To prevent the gas leakage, turn the service ports cap, the valve rodis cap for 2-way valve and 3-way's a little more than the point where the torque increases suddenly.
CAUTION: If the refrigerant of the air conditioner leaks, it is necessary to make all the refrigerant out. Vacuumize first, then charge the liquid refrigerant into air conditioner according to the amount marked on the name plate.
90
o
10s
6.35mm
(1/4")
2 way valve
3 way valve
2 way valve
3 way valve
9.52mm
(3/8")
6.35mm (1/4")
9.52mm
(3/8")
To indoor unit C
To indoor unit D
2 way valve
3 way valve
6.35mm (1/4")
To indoor unit B
9.52mm
(3/8")
2 way valve
3 way valve
To indoor unit A
6.35mm (1/4")
9.52mm
(3/8")
8 .Take the same steps from 1 to 7 for each ways to ensure a completely vacuum for the whole system.
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
40-
1. Electric wiring Note:
The air conditioner must use special circuit , and wiring by the qualified electrician according to the wiring rules specified in national standard. The grounding wire and the neutral wire shall be strictly separated. Connect the neutral wire with grounding wire is incorrect. The electric leakage breaker must be installed. All the electric wire must be copper wire.When wiring,there shall keep a proper distance between the power line and communication wire to avoid twist together. Otherwise,signal disturbance will occur,and the air conditioner can not operate normally. Power supply: 1PH, 220-230V~, 50Hz. The wiring method of power line is Y connection. If the power line is damaged, in order to avoid risk of electric shock, it must be replaced by the manufacturer or its repair center or other similar qualified person.The connecting cable must be shielded. Fuse: T3.15A 250VAC T25A 250VAC (Please check with the outdoor unit wiring diagram.) Please check the circuit diagram about the fuse replaced.
Wiring work
2. Wiring method Wiring method of orbicular terminals For the connection wire with orbicular terminals, its wiring method is as shown in the right figure: remove the connecting screw, put the screw through the ring on the end of the wire, then connect to the terminal block and fasten screw. Wiring method of straight terminals For the connection wire without orbicular terminals, its wiring method is: loosen the connection screw, and insert the end of the connection wire completely into the Terminal block, then fasten the screw. Slightly pull the wire outwards to confirm it is firmly held.
Crimp connection method for wires without terminals
Wiring Method for
Ring Terminal Block
Correct Pressing
Wrong Pressing
Terminal
block
Pressing
Clamps
Do not connect the wire with same diameter to the same side
Connect the wire with same diameter to the two sides of the terminal
Do not connect the wire with different diameters
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
41-
3. Wiring method of outdoor unit:
Loosen wire cover and connect the power line and communication wire of indoor unit to the terminal correspondingly. Note: When connecting power line to power supply terminal, please pay attention to the following items:
Do not connect the power line with different dimensions to the same connection wire end. Improper contact will cause heat generation. Do not connect the power line with different dimensions to the same grounding wire end. Improper contact will affect protection.
Keep a proper distance between the communication wire and the power line. Otherwise, abnormal communication will occur because of disturbance. And also, the communication wires should be shielded wire, and the shield cover should be grounded on the outdoor unit. Do not connect the power line to the connecting end of communication wire. Incorrect connection will cause damage to the connected unit.
4. Wiring method of indoor unit
Crimp connection method for connection wire After connection,the wire must be fastened by wire cover. The wire cover shall press on the protection coat of the connection wire,as shown in right top figure. Note:When connecting the wiring,confirm the terminal number of indoor and outdoor units carefully. Incorrect wiring will damage the controller of air conditioner or the unit can not operate.
Terminal block Cord anchorage A Cord anchorage B
Valve cover
Wiring work
Power line Remove the repair board of the outdoor unit and loosen the wire cover A,then put the live wire, neutral wire and grounding wire through the wire cover ,and connect them to terminal block correspon dingly. After connection, fasten wire cover to its previous state. Communication wire of indoor unit. Loosen wire cover , put the communication wire through the wire cover B, and connect them to terminal block correspondingly. After connection, fasten wire cover B to its previous state. Note: Power line and communication wire are provided by consumers themselves.
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
42-
Items to confirm
Test running
Before starting the test running, please confirm the following works have been done successfully.
1) Correct piping work;
2) Correct wiring work;
3) Correct match of indoor and outdoor unit;
4) Proper recharge of refrigerant if needed;
5) Correct indoor unit addresses setting. Make sure that all the stop valves are fully open. Check the voltage supplied to the outdoor and indoor units, please cinfirm that is 230V.
Test running.
1) If the temperature is lower than 16 OC, it is impossible to test cooling with remote controller, and also when the temperature is higher than 30 OC, it is impossible to test heating.
2) To test cooling, set the lowest temperature at 16 OC. To test heating,set the highest temperature, at 30OC.
3) Please check both cooling and heating operation of each unit individually and then also check the simultaneous operation of all indoor units.
4) After ruuning the unit for about 20 minutes, check the indoor unit outlet temperature.
5) After the unit is stopped, or working mode changed, the system will not start again for about 3 minutes.
6) During cooling operation, frost may ocur on the indoor unit or pipes, this is normal.
7) Operate the unit according to the operation manual. Please kindly explain to our customers how to operate through the instruction manual.
Gas leakage from pipe connection? Heat insulation treatment of pipe connection? Are the connection wiring of indoor and outdoor unit firmly inserted into the terminal block? Is the connection wiring of indoor and outdoor firmly fixed? Is drainage securely arranged? Is the ground wire securely and firmly connected? Is power supply voltage abided by electric code? Is there any noise? Does cooling perform normally? Does room temperature regulator operate normally?
Check items for test run, put mark " in ".
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
43-
30Taha_pekj kb Jjop]hh]pekj Qh]_a
,3- Qh]_a ]^kra pda _aehejc sdana d]ra ajkqcd ol]_a pk ]nn]jca pda qjep0 ,4- Qh]_a sdana pda `n]ej]ca lela _]j ^a ]nn]jca` sahh0 ,5- Qh]_a sdana ejhap ]j` kqphap ]en kb ej`kkn ]j` kqp`kkn qjep sehh jkp ^a ^hk_ga`0 ,6- Ek jkp atlkoa pda qjep pk pda lh]_a sepd da]ru keh kn ikeopqna ,a0c0gep_daj ]j` skngodkl-0 ,7- Ek jkp oap pda qjep ej pda lh]_a sdana `aopnq_pera c]o ,oq_d ]o oqhbqne_ ]_e` c]o- kn lqjcajp c]o ,pdejjan ]j` c]okheja­_kj_ajpn]pao ]j` nap]ejo0
,8- Qh]_a opnkjc ajkqcd pk oqllknp pda qjep saecdp0
,9- Ok atlajoera ]npe_hao oq_d ]o pahareoekj ]j` le]jk ^ahks ej`kkn qjep0
,:- Fjkqcd ol]_a bkn i]ejpaj]j_a0 ,;- Qh]_a ikna pd]j 3i ]s]u bnki pahareoekj ]j` n]`ek pk ]rke`
`eopqn^ejc pahareoekj ]j` n]`ek0 ,32- F]ou bkn i]ejpaj]j_a0
40Jjop]hh]pekj Qnal]n]pekj
,3- Qkoepekj kb _aehejc klajejc ^apsaaj qjep ]j` oqolaj`ejc ^khp ,bnkjp reas kb qjep-0
,4- Qnal]na ]hh lelejc ,nabnecan]jp.s]pan `n]ej]ca -]j` senao ,_kjja_pekj sena kb naikpa _kjpnkhhan. ej`kkn qjep _kjja_pekj senao- pk pda ej`kkn qjep ^abkna ejop]hh]pekj ej kn`an pk _kjja_p ej`kkn qjep eiia`e]pahu ]bpan ejop]hh]pekj0
,5- Jjop]hh ] oqolaj`ejc ^khp
Uk oqllknp pda qjep saecdp .]j_dkn ^khp odkqh` ^a qoa` ej pda _]oa kb ]hna]`u ateopo _aehejc0 Gks jas _aehejc. qoa bhqod/ej pula ^khp. ^qehp/ej pula ^khp kn l]npo lnap]na` ej pda beah`0 Cabkna ckejc kj ejop]hhejc. ]`fqop ol]_a pk _aehejc0
30Jjop]hh]pekj pkkho
30 T_nas `neran
40 I]_go]s
50 Enehh sepd ] `e]iapan kb 82ii
60 Jjjan dat]ckj ol]jjan.odebpejc
ol]jjan
70 Tl]jjan ,36. 39. 3;.46.49ii-
80 Qela _qppan
90 Qela atl]j`an
:0 Ljeba
;0 Qej_ano
320 Ma]g]ca `apa_pkn kn ok]lu s]pan
330 C]j` p]la
340 T_n]lan
350 Sabnecan]jp keh
Uda ejop]hh]pekj pkkho heopa` ej pda bkhhksejc odaap _]j ^a qoa` ]o namqena`0
40B__aookneao , b]_pknu lnkre`a` -
Ben kqphap
Ben kqphap
Ben ejhap
407i Pran
307i
307i
2053i
I
Eeop]j_a ^apsaaj
oqolaj`ejc ^khpo 757ii
Jj`kkn qjep 792ii
Daehejc klajejc 872ii
Pnj]iajp l]jah 922ii
Jj`kkn qjep 792ii
Daehejc klajejc 872ii
Pnj]iajp l]jah 922ii
Pranh]l ^apsaaj _aehejc ]j` knj]iajp l]jah od]hh ^a 47ii
Tqolaj`ejc ^khpo
Daehejc
Pnj]iajp l]jah
372ii
542ii
82ii
B
C
D
E
F
G
Tui^kh Q]npo O]ia
B`daoera p]la
Qela _h]il
Dkjja_pejc dkoa
En]ej]ca dkoa
Okj/du`nko_kle_ da]p ejoqh]pejc i]pane]h
Huloqi lks`an
Vilmaggamfji ^jjgl
Vilmaggamfji [kjbdcnkdl
Vilmaggamfji [kjbdcnkdl
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
4.5. Cassette type AB***XCERA
44-
50 Jjop]hh]pekj kb ej`kkn qjep
Jj _]oa kb jk _aehejc
Jjop]hh qjep pailkn]nehu
Qqp oqolaj`ejc ^n]_gap kj pda oqolaj`ejc ^khp pk d]jc pda qjep ql0 Ca oqna pk qoa jqp ]j` s]odan ]p ^kpd aj` kb pda ^na]gap pk oa_qna benihu0
Bbpan ejop]hh]pekj kj pda _aehejc
,3- B`fqop qjep pk epo necdp lkoepekj ,Saban pk lnal]n]pekj bkn ejop]hh]pekj/,3--
,4-Dda_g pd]p qjep eo dknevkjp]h0
Qqp oqolaj`ejc ^n]_gap kj pda oqolaj`ejc ^khp pk d]jc pda qjep ql0Ca oqna pk qoa jqp ]j` s]odan ]p ^kpd aj` kb pda ^n]_gap pk oa_qna ep benihu0
X]pan lqil ]j` bhk]pejc osep_d eo ejop]hha` ejoe`a ej`kkn qjep._da_g bkqn _knjano kb pda qjep bkn epo haran qoejc dknevkjp]h _kil]n]pkn kn QWD pq^a sepd s]pan0,Jb qjep eo pehpejc ]c]ejop pda `ena_pekj kb s]pan `n]ej]ca. lnk^hai i]u k__qn kj bhk]pejc s]pan ha]g]ca0-
Jj pda _]oa kb _aehejc ]hna]`u ateopo
,3-Jjop]hh qjep pailkn]nehu
,4-B`fqop pda daecdp ]j` lkoepekj kb pda qjep0 ,5-Qnk_aa` sepd lnk_a`qna ,6- kb + Jj pda _]oa kb jk _aehejc +
60 Jjop]hh]pekj kb s]pan `n]ej]ca lela
,3- Jjop]hh s]pan `n]ej]ca lela
Qela `e]iapan od]hh ^a amq]h kn h]ncan pd]j pd]p kb _kjja_pejc lela ,Qela kb lkhupdaja= oeva<47ii= P0E0< 54ii -
En]ejlela odkqh` ^a odknp. sepd ] `ksjs]n` ohkla ]p ha]op 31322 pk lnarajp ]en ^]c bnki bkniejc0
Jb `ksjs]n` ohkla kb `n]ejlela _]jjkp ^a i]`a.hebpejc lela od]hh ^a ejop]hha`0
Laal ] `eop]j_a kb 3/307i ^apsaaj oqolaj`ejc ^khpo. pk i]ga s]pan dkoa opn]ecdp0
Oqp ,Qnal]na ej baeh`-
X]odan ,Qnal]na` ej baeh`-
Tqolaj`ejc ^khpo
G]opaj ,`kq^ha jqpo-
Jjoanp
X]odan betejc l]`
,lnal]na` ej baeh`-
[ oa_qna pda s]odan benihu\
harahan
Qkhupdaja lela
Okpa< Bhh pda ]^kra iajpekja` l]npo od]hh ^a lnal]na` ej baeh`. pda `e]iapan kb oqolaj`ejc ^khp eo N32
>Jjop]hh]pekj Ft]ilha@
ohkla kran 31322
{y{z|}
Daehejc
Skkb
Bj_dkn ^khp
Mkjc jqp kn pdna]`
Tqolaj`ejc ^ehp N32
72 w372ii
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
45-
Voa pda `n]ej]ca dkoa ]j` _hel lnkre`a` sepd qjep0 Jjoanp s]pan lela ejpk s]pan lhqc qjpeh ep na]_dao pda sdepa p]la0
Uecdpaj pda _hel qjpeh da]` kb pda o_nas eo haoo pd]j 6ii bnki dkoa0
Xej` pda `n]ej]ca dkoa pk pda _hel qoejc oa]h l]` bkn da]p ejoqh]pekj0
Jjoqh]pa `n]ej]ca dkoa ej pda nkki0
70 D]qpekjo bkn pda s]pan `n]ej]ca hebpejc lela
Jjop]hh]pekj daecdp kb s]pan `n]ej]ca hebpejc lela od]hh ^a haoo pd]j 4:2ii
Udana odkqh` ^a ] necdp ]jcha sepd qjep .522ii bnki qjep0
> Okpa @
Uda ohkla kb s]pan `n]ej]ca dkoa od]hh ^a sepdej 97ii . i]ga pda `n]ej]ca lhqc jkp pk ^a]n at_aooera bkn_a0
Jb oaran]h s]pan dkoao fkej pkcapdan. kb ]o lan bkhhksejc lnk_a`qnao0
Tla_ebe_]pekjo kb pda oaha_pa` `n]ej]ca dkoao od]hh iaap pda namqenaiajpo bkn pda qjep nqjjejc
80 Jjop]hh]pekj kb Pnj]iajp Q]jah
Jjop]hh knj]iajp l]jah kj ej`kkn qjep
,3- Dda_g sdapdan ej`kkn qjep eo dknevkjp]h sepd harahan kn lkhupdaja lela behha` sepd s]pan . ]j` _da_g pd]p pda `eiajoekj kb pda _aehejc klajejc eo _knna_p0 U]ga kbb pda haran c]qca ^abkna ejop]hhejc pda knj]iajp l]jah0
,4- G]opaj pda o_naso pk i]ga pda daecdp `ebbanaj_a ^apsaaj pda psk oe`ao kb ej`kkn qjep haoo pd]j 7ii0
,5- Genop bet ep sepd o_naso pailkn]hhu0 ,6- G]opaj pda psk pailkn]hhu betejc o_naso ]j` kpdan psk. ]j` pecdpaj pda bkqn o_naso0
,7- Dkjja_p pda senao kb ouj_dnk/ikpkn0
,8- Dkjja_p pda sena kb oecj]h0
,9- Jb jk naolkjoa kb naikpa _kjpnkhhan._da_g sdapdan pda senejc eo _knna_p.naop]np naikpa _kjpnkhhan 32 oa_kj`o ]bpan odqp kbb lksan oqllhu0
Thkla ^ahks 31322
Dkjja_pekj `n]ej]ca dkoa sepd ] U/fkejp
322ii xkran
Dhel
U]la,sdepa-
En]ej]ca dkoa
M]nca oeva oa]h l]`
6ii ^ahks
,]__aooknu-
Dhel
Dhel
X]pan `n]ej]ca hebpejc lela
Tqolaj`ejc ^n]_gap
En]ej]ca dkoa
4:2ii qjpan
722ii ^ahks
442ii
522ii ^ahks
3/307i
442
En]ej]ca dkoa
97ii ^ahks
722ii ^ahks
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
46-
Meiepo kb l]jah ^k]n` ejop]hh]pekj
,3-Jjop]hh pda l]jah ^k]n` ej pda `ena_pekj odksj ej pda becqna0 ,4-Uda ej_knna_p `ena_pekj sehh naoqhp ej s]pan ha]g]ca. ia]jsdeha osejc ]j` oecj]h na_aerejc ]na jkp ^a _kjja_pa` oq__aoobqhhu0
Dkjpnkh ^kt
90 Qelejc Dkjja_pekj
,3- Eeiajoekj kb _kjja_pejc lela
Gh]na _kjja_pekj
H]o lela
5/s]u r]hra
Jj`kkn Vjep
Pqp`kkn qjep
Memqe` lela
4/s]u r]hra
Gh]na _kjja_pekj
BC2;4YDFSB BC344YDFSB
BC364YDFSB BC3:4YDFSB
Gh]na _kjja_pekj
H]o lela
5/s]u r]hra
Jj`kkn Vjep
Pqp`kkn qjep
Memqe` lela
4/s]u r]hra
Gh]na _kjja_pekj
,
B
,]`]lpkn. bnki ;074 pk 3409-
Uk kqp`kkn qjep
Uk c]o lela
H]o lela
Memqe` lela
H]o lela
BC2;4YDFSB BC344YDFSB
Memqe` lela
;074ii
8057ii
3409ii
8057ii
BC364YDFSB BC3:4YDFSB
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
47-
D]qpekjo bkn lelejc _kjja_pekj
Ek jkp pseop kn `abkni pda _kjja_pejc lela0
Ek jkp iet `qopo0
Uda ^aj`ejc n]`eqo od]hh ^a ]o h]nca ]o lkooe^ha0 Ckpd c]o lela ]j` hemqe` lela od]hh ^a da]p ejoqh]pekj0
Ok ha]g]ca ej pda bh]na0
,5- Qelejc _kjja_pekj
Dkjja_pejc iapdk`
Tia]n nabnecan]jp keh kj pda fkejpo kb lelejc ]j` bh]na0
Uda ^aj`ejc n]`eqo od]hh ^a ]o h]nca ]o lkooe^ha0
Bhecj pda lela _ajpan sdaj b]opajejc. ]j` pecdpaj pda
jqp. ]o odksj ej pda becqna0
Q]u ]ppajpekj pk jkp iet bknaecj i]ppano oq_d ]o o]j`o
ej0
Ee]iapan kb Qela
Memqe` Qela 8057ii
H]o Qela ;074ii
Uecdpaj Uknmqa
,O0 i-
330:
72
Jb jkp ]hecja` .pecdpaj pda jqp ^u bkn_a sehh `]i]ca pda jqp pd]p naoqhp ej c]o ha]g]ca
:0Fha_pne_]h Xenejc
Xenejc iapdk`o< :03 Xenejc iapdk` kb nejc paniej]h
Gkn _kjja_pejc heja sdkoa aj` eo ] nejc.epo senejc iapdk`
]o odksj ej pda necdp becqna< naikra senejc o_nas ]j` l]oo
ep pdnkqcd pda aj` nejc kb _kjja_pejc heja.pdaj _kjja_p ep pk
pda paniej]h ^hk_g ]j` pecdpaj o_nas0
Xenejc iapdk` kb nejc paniej]h
-.
Sejc Uaniej]h
U
C
Cn]va` oa]i
`
Gep pda jqp kj ]j` b]opaj
,4- Uda i]teiqi hajcpd ]j` `nkl daecdp kb _kjja_pejc lela
Uda i]teiqi hajcpd eo 42i
Uda i]teiqi `nkl daecdp eo 32i0
Uk ajoqna pda abbe_eaj_u .Qelao od]hh ^a ]o odknp ]o lkooe^ha0
Tl]jjan
Tl]jjan
Kkejp
Oqp
C?:02/;02,ii­`?605/705,ii­U?302/402,ii­,Gkn ukqn nabanaj_a-
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
48-
30Udana ]na psk iapdk`o pk oap pda _kiiqje_]pekj ]``naoo B0 Voa pda naikpa _kjpnkhhan,`ab]qhp op]pqo ej benop ejop]hh]pekj-0 C0 Voa `el osep_dao kj pda ej`kkn qjep QDC0 40 B``naoo oappejc lnk_a`qna sdaj qoejc pda naikpa _kjpnkhhan0 B0 Tap pda ]``naooao kjhu ]bpan pda oq__aoobqh ejop]hh]pekj kb pda nabnecan]jp lelao ]j` _kjja_pejc _]^hao. ]j` klaj ]hh pda opkl r]hrao= C0 Qha]oa _kjbeni pd]p pda ej`kkn qjepo ]j` pda kqp`kkn qjep ej pda o]ia ouopai qoa pda o]ia lksan okqn_a= D0 Qksan kj pda qjepo. ^qp lqp ]hh pda ej`kkn qjepo ej pda op]pqo kb TUBOECZ= E0 Qha]oa jkpa pd]p pda ]``naoo iqop ^a oap ]o bkhhksejc<
:D>EEF IDAH H@;H =EDD?=H HE J;BJ? 60 H@? ;>>F?GG CIGH <? 15 :D>EEF IDAH H@;H =EDD?=H HE J;BJ? 70 H@? ;>>F?GG CIGH <? 25 :D>EEF IDAH H@;H =EDD?=H HE J;BJ? 80 H@? ;>>F?GG CIGH <? 35 :D>EEF IDAH H@;H =EDD?=H HE J;BJ? 90 H@? ;>>F?GG CIGH <? 45
pda MFE ^k]n` eo ^h]jg0
ON Vicjjk nifm bjhhnifbamfji acckdlldl ldmmfie
QP_^VZYL TPVX ^Z RZ ^UV]M ^US _YV^ `VXX YZ^ `Z\WN
F0 Ft]ilha< oap qjep B pk ]``naoo 30 Dkjpejqkqohu lnaoo pda aiancaj_u osep_d bkn ]^kqp 37 oa_kj`o. pda ^qvvan sehh okqj` 6 peiao,QJ QJ QJ QJ­]j` pdaj ha]ra ck kb pda osep_d0 Bp pdeo peia. pda ej`kkn qjep d]o ajpana` pda ]``naoo oappejc lnk_a`qna0 Cqp G0 Voa pda _kjpnkhhan pk pqnj kj pda ej`kkn qjep0 Bp pdeo peia. pda _kjpnkhhan odkqh` ^a _d]jca` bnki PGG pk PO. ]j` pdaj pdaUJNFS MFE bhodao kj_a0 Ud]p eo pk o]u. pda ]``naoo oappejc eo aj]^ha`0 H0 Qnaoo pda ^qppkj+TMFFQ + kj pda _kjpnkhhan. pda peiao ukq lnaoo ep op]j`o bkn pda ]``naoo ukq s]jp pk oap. `ap]eha` ]o bkhhksejc< Qnaoo ^qppkj + TMFFQ + kj_a. pda ]``naoo eo +3 +. ]j` pda UJNFS MFE bh]odao kj_a= Qnaoo ^qppkj + TMFFQ + pse_a. pda ]``naoo eo+4+.]j`pdaUJNFS MFE bh]odao pse_a=
:04 Xenejc kb ej`kkn qjep
Uda `eop]j_a ^apsaaj pda oecj]h senao ]j` pda lksan _]^ao odkqh` ^a ]p ha]op 72ii0
D
CB
R
Q
3,M- 4,O- 4,O-3,M-
Q
R
BC
D
MO
D3 D4
,Jj _]oa kb qoejc sena` _kjpnkhhan-
Uk kpdan ej`kkn qjep
Uk sena` _kjpnkhhan
Uk kqp`kkn qjep
Dkiiqje_]pekj _]^ha ,Tdeah` sena-<
I27SO/G 4Y ,2097/307-ii
4
Qksan _]^ha < I27SO/G 5H ,3/407-ii
4
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
49-
50 B``naoo oappejc lnk_a`qna sdaj qoejc pda EJQ osep_dao TX23 ]j` TX250 B0 Uda EJQ osep_dao TX23 ]j` TX25 ]na kj pda ej`kkn qjep QDC0 C0 Cabkna _]nnuejc kqp pda ]``naoo oappejc skng. pda ouopai iqop ^a lksana` kbb0 D0 U]ga kbb pda bnkjp l]j]h ]j` pda behpano. pdaj p]ga kbb pda bh]lo ]j` ]hok pda bnkjp _kran.`eo_kjja_p pda osejc ikpkn _kjja_pkno bnki pda QDC ]j` pdaj p]ga kqp pda hksan l]np kb pda QDC0 E0 Dd]jca pda lkoepekj kb EJQ 9 kb TX23 bnki PGG pk PO. eb b]eh pk `k pdeo. pda ]``naooao oap ^u TX25 sehh jkp skng0 F0 Voa TX25 pk oap pda ]``naooao ]o bkhhksejc ,EP OPU DIBOHF PUIFS EJQ TXJUDIFT-<
60 Iks pk _da_g pda ]``naooaoA Xdaj bejeod ]hh pda ]^kra skngo. lha]oa lksan kbb ]j` lksan kj ]c]ej pk pda sdkha ouopai ^qp oap ]hh pda ej`kkn qjepo ej TUBOECZ0 Udaj _kjpejkqohu lnaoo pda aiancaj_u osep_d qjpeh ukq da]n pda ^qvvan okqj` 7 peiao,Qe Qe Qe Qe Qe-. ]j` pdaj pda UJNFS MFE ^k]n` sehh odks pda ]``naoo kb pdeo ej`kkn qjep0 Qnaoo ]ju gau kj pda naikpa _kjpnkhhan. ep sehh atep pda ]``naoo _da_gejc lna_a`qna0
Qnaoo ^qppkj + TMFFQ + pdnaa peiao. pda ]``naoo eo+5+.]j`pdaUJNFS MFE bh]odao pdnaa peiao= Qnaoo ^qppkj + TMFFQ + bkqn peiao. pda ]``naoo eo+6+.]j`pdaUJNFS MFE bh]odao bkqn peiao= I0 Voa pda naikpa _kjpnkhhan pk pqnj kbb pda qjep. Bp pdeo peia. pda _kjpnkhhan odkqh` ^a _d]jca` bnki PO pk PGG. ]j` pda qjep sehh atep pda ]``naoo oappejc lnk_a`qna. pda ]``naoo sehh ^a iaikneva`0 Uda MFE ^k]n` sehh ]hs]uo `eolh]u pda ]``naoo kb pdeo ej`kkn qjep qjpeh pda ouopai ^a lksana` kbb0 J0 Jb ukq s]jp pk _d]jca pda ]``naoo. lha]oa nala]p pda ]^kra opalo bnki F pk H0
K0 Bbpan oappejc ]hh pda ]``naooao. lha]oa lksan kbb pda ouopai ]j` pdaj lksan kj ]c]ej0 Ppdanseoa pda ouopai sehh jkp op]np pk skng0 L0 Pj_a pda ]``naooao ]na oq__aoobqhhu oap. lha]oa `k jkp _d]jca ep ]ju ikna pk ]rke` _kjbqoekj0
3456789:
PO
PGG
TX23
TX25
3456789:
PO
PGG
PO
PGG
PO
PGG
JOEPPS VOJU BEESFTT
3
4
5
3456789:
3456789:
3456789:
PO
PGG
6
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
50-
SELECTING THE MOUNTING POSITION
(1)Do not install where there is the danger of com-
bustible gas leakage.
(2) Do not install near heat sources. (3) If children under 10 years old may approach
the unit, take preventive measures so that they cannot reach the unit.
Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not topple or fall
WARNING
CAUTION
Decide the mounting position with the customer as follows:
INDOOR UNIT
(1) Install the indoor unit level on a strong wall, floor,
ceiling which is not subject to vibration.
(2) The inlet and outlet ports should not be obstructed:
the air should be able to blow all over the room.
(3) Install the unit near an electric outlet or special
branch circuit.
(4) Do not install the unit where it will be exposed to
direct sunlight.
(5) Install the unit where connection to the outdoor
unit is easy.
(6) Install the unit where the drain pipe can be easily
installed.
(7) Take servicing, etc. into consideration and leave the
spaces shown in Fig.A. Also install the unit where the filter can be removed.
Under ceiling
2 cm or more
Ceiling
Indoor unit
30 cm or more
Left
Right
1.5m
Floor console
30 cm or more
30 cm or more
1.5m
1.5m
Left
Right
may be difference
Fig.A
Indoor unit
4.6. Convertible type AC*** X CERA
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
51-
Open the intake grill and remove the three or four or six screws.(Fig. 1)
Remark: The main unit can be wired before the indoor
unit is installed. Select the most appropriate installation order.
A. FLOOR CONSOLE TYPE
1. DRILLING FOR PIPING Select piping and drain directions.(Fig.2) The piping and drain can be made in three directions as shown below.
(Fig.2)
rear
right
down
REMOVE THE INTAKE GRILL
PREPARING INDOOR UNIT INSTALLATION
When installing set to wall, install the accessory wall bracket at the position shown in Fig.5,and mount the set to it.
Fig. 1
Intake grill
(Fig. 5)
Wall bracket
Side of set
99cm
50cm
24.5cm
6.5cm
12.5cm 10cm
7cm hole
3.5cm hole
The drain hose can be connected to either the left or right side.(Fig.3)
(Fig. 3)
Drain hose (Left side) Drain hose (Right side)
Wall
7cm
6mm
Indoor unit outdoor unit
(Fig.4)
When the directions are selected, drill a 7 cm dia. hole on the wall so that the hole is tilted downward toward the outdoor for smooth water flow. When the pipe is led out from the rear, make a hole in Fig.4, at the position shown.
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
52-
Select whether the drain hose will be connected to the left or right side.(Fig.3) Insert the drain hose into the drain pan, then secure the drain hose with a nylon fastener. (Fig.6)
2. INSTALLING DRAIN HOSE
(Fig. 6)
Wrap the insulation (drain hose) around the drain hose connection. (Fig.7)
(Fig. 7)
CAUTION
Do not install the unit drain hose side is too high. Height A should be less than 5 mm.(Fig.9)
Fig. 8
Be sure to arrange the drain hose correctly so that it is leveled lower than the drain hose connecting port of the indoor unit.
Drain pan
Drain hose
Nylon fastener
Drain pan
Drain hose
Insulation (Drain hose)
OK NO NO
Arrange the drain hose lower than this portion.
Drain hose
Fig. 9
A A
Drain hose
B. UNDER CEILING TYPE
Using the installation template, drill holes for piping and anchor bolts(for holes).(Fig.10)
Installation template
Wall
Ceilling
Drilling position for piping
Drilling position for anchor bolt
200mm
900mm
Fig. 10
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
53-
3. INSTALLING BRACKETS Install the brackets with nuts, washers and spring
washers.(Fig. 15)
4. INSTALLING INDOOR UNIT
Bracket (Right)
Bracket (Left)
Select piping and drain directions. (Fig.11)
1. DRILLING FOR PIPING
Insert the anchor bolts into the drilled holes, and drive the pins completely into the anchor bolts with a hammer. (Fig. 14)
2. DRILLING HOLES FOR ANCHOR BOLTS AND INSTALLING THE ANCHOR BOLTS
When the directions are selected, drill 80mm and 50mm or 150mm dia. hole on the wall so that the hole is tilted downward toward the outdoor for smooth water flow.
With a concrete drill, drill four 12.7 mm dia. Holes. (Fig.13)
Wall
6mm
Install the drain hose at the rear; it should not be installed on the top or right side.
Fig. 11
Rear (Install the drain hose in the direction.)
Right
CAUTION
Fig. 12
Now, securely tighten the hex bolts in both sides.
Fig. 17
Reset the hex bolts as shown in Fig.16.
Hex bolt
8 to 13mm
Indoor unit
Fig. 16
Apply the indoor unit to the brackets.(Fig.17)
Bolt
Bracket
Indoor unit
Fig. 13
12.7mm
Fig. 14
Fig. 15
Spring washer
Special nut
Bracket
- -
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
54
Select whether the drain hose will be connected to the left or right side.(Fig.3) Insert the drain hose into the drain pan, then secure the drain hose with a nylon fastener.(Fig.6) Wrap the insulation (drain hose)around the drain hose connection.(Fig.7) Be sure to arrange the drain hose correctly so that it is leveled lower than the drain hose connecting port of the indoor unit.(Fig.18)
5. INSTALL THE DRAIN HOSE
Fig. 18
Pass the drain hose through here
CONNECTING THE PIPING
OUTDOOR UNIT INSTALLATION
1. FLARE PROCESSING (1) Cut the connection pipe with pipe cutters so
that the pipe is not deformed.
(2) Holding the pipe downward so that cuttings
cannot enter the pipe, remove the burrs.
(3) Remove the flare nut from the indoor unit pipe
and outdoor unit and insert the flare nut onto the pipe, and flare with a flaring tool.
2. BENDING PIPES The pipes are shaped by your hands. Be careful
not to collapse them.
NO
Remove the hole cover.
OK
Arrange the drain hose lower than this portion
Drain hose
VT wire
Drain hose
Fig. 19
Piping hole
Base (Bottom)
Intake grill
VT wire hole
Cut the grill
Fig. 21
OK
NO
Extend the pipe by unwinding it
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
55-
(1) Dimension of connecting pipe
(2) The maximum length and drop height of connecting pipe
Cautions for piping connection
Smear refrigerant oil on the joints of piping and flare. The bending radius shall be as large as possible. Align the pipe center when fastening, and tighten the nut, as shown in the figure. Pay attention to not mix foreign matters such as sands in.
Do not twist or deform the connecting pipe. Do not mix dusts.
The bending radius shall be as large as possible. Both gas pipe and liquid pipe shall be heat insulation.
No leakage in the flare.
(3) Piping connection
Connecting method
Spanner
Spanner
Joint
Nut
If not aligned ,tighten the nut by force will damage the nut that result in gas leakage
Please refer to the installation manual of outdoor unit To ensure the efficiency , Pipes shall be as short as possible.
Fit the nut on and fasten
AC142XCERA AC182XCERA
Flare connection
Gas pipe
3-way valve
Indoor Unit
Outdoor unit
Liquid pipe
2-way valve
Flare connection
A
Diameter of Pipe Liquid Pipe 6.35mm
Gas Pipe 12.7mm
Tighten Torque
(N. m)
11.8
49.0
A
(adaptor, from 9.52 to 12.7)
To outdoor unit
To gas pipe
90
0.5
O
Gas pipe Liquid pipe
12.7mm
6.35mm
AC142XCERA AC182XCERA
3. PIPING CONNECTION
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
56-
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)(Fig.24A)
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 25mm of the
exposed solid wire. (2) Using a screwdriver, remove the terminal screw(s) on the terminal board. (3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw. (4) Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal
screw using a screw driver.
B. For strand wiring(Fig.24B)
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 10mm of the
exposed strand wiring. (2) Using a screwdriver, remove the terminal screw(s)on the terminal board. (3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end. (4) Position the round terminal wire, and replace and tighten the terminal screw using a screw driver.
After passing the connection cord and power cable through the insulation tube, fasten it with the cord clamp, as shown in Fig.25
HOW TO FIXED CONNECTION CORD AND POWER CABLE AT THE CORD CLAMP
Fig. 25
Insulation tube
Cord clamp
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
Fig. 24
Insulation
Loop
A. Solid wire
Terminal board
Screw with special washer
Round terminal
Wire
Screw with special washer
Round terminal
Wire
Round terminal
B. Strand wire
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
57-
ELECTRICAL WIRING
1. INDOOR UNIT SIDE
(1) Remove the electric component box.
(2) Pull out the electric component box.
(3) Remove the electric component box cover.
Remove the three tapping screws.
(1) Remove the cord clamp. (2) Process the end of the connection cords to the
dimensions shown in Fig.34.
(3) Connect the end of the connection cord fully into the
terminal block.
(4) Wiring
(4) Fasten the connection cord with a cord clamp. (5) Fasten the end of the connection cord with the
screw.
Be careful not to pinch the lead wires between the electric component box and base.
CAUTION
(1) Match the terminal block numbers and connection
cord colors with those of the outdoor unit. Erroneous wiring may cause burning of the electric parts.
(2) Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
(3) Always fasten the outside covering of the connection
cord with the cord clamp.(If the insulator is chafed, electric leakage may occur.)
(4) Always connect the ground wire.
Do not remove the screws. If the screws are removed, the electric component box will fall.
Fig. 26
Remove the four tapping screws.
Fig. 27
Electric component box
CAUTION
Fig.28
Fig. 29
Base
Electric component box cover
CAUTION
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
58-
(5). Wiring of indoor unit
The distance between the signal wires and the power cabes should be at least 50mm.
C
BA
Q
P
1(L) 2(N)
2(N)1(L)
P
Q
A B
C
L N
C1 C2
(In case of using wired controller)
To other indoor unit
To wired controller
To outdoor unit
(P) (Q)
1.Incorrect address setting will cause abnormal to the system.
2.Communication cable must be use sheilded type.
3.Communication cable and power cable must be use ring terminal type.
Communication cable (Shield wire): H05RN-F 2X (0.75-1.5)mm
2
Power cable : H05RN-F 3G (1-2.5)mm
2
WARNING
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
59-
1.There are two methods to set the communication address A. Use the remote controller(default status in first installation). B. Use dip switches on the indoor unit PCB.
2. Address setting procedure when using the remote controller. A. Set the addresses only after the successful installation of the refrigerant pipes and connecting cables, and open all the stop valves; B. Please confirm that the indoor units and the outdoor unit in the same system use the same power source; C. Power on the units, but put all the indoor units in the status of STANDBY; D. Please note that the address must be set as following:
Indoor unit that connect to valve A, the address must be 1; Indoor unit that connect to valve B, the address must be 2; Indoor unit that connect to valve C, the address must be 3; Indoor unit that connect to valve D, the address must be 4;
the LED board is blank.
(6). Indoor unit communication addresses setting
CAUTION! FAIL TO DO THIS, THE UNIT WILL NOT WORK.
E. Example: set unit A to address 1. Continuously press the emergency switch for about 15 seconds, the buzzer will sound 4 times(PI PI PI PI) and then leave go of the switch. At this time, the indoor unit has entered the address setting procedure. But F. Use the controller to turn on the indoor unit. At this time, the controller should be changed from OFF to ON, and then theTIMER LED flshes once. That is to say, the address setting is enabled. G. Press the button"SLEEP " on the controller, the times you press it stands for the address you want to set, detailed as following: Press button " SLEEP " once, the address is "1 ", and the TIMER LED flashes once; Press button " SLEEP " twice, the address is " 2 ", and theTIMER LED flashes twice; Press button " SLEEP " three times, the address is " 3 ", and the TIMER LED flashes three times; Press button " SLEEP " four times, the address is " 4 ", and the TIMER LED flashes four times; H. Use the remote controller to turn off the unit, At this time, the controller should be changed from ON to OFF, and the unit will exit the address setting procedure, the address will be memorized. The LED board will always display the address of this indoor unit until the system be powered off. I. If you want to change the address, please repeat the above steps from E to G. J. After setting all the addresses, please power off the system and then power on again. Otherwise the system will not start to work. K. Once the addresses are successfully set, please do not change it any more to avoid confusion.
3. Address setting procedure when using the DIP switches SW01 and SW03. A. The DIP switches SW01 and SW03 are on the indoor unit PCB. B. Before carrying out the address setting work, the system must be powered off. C. Take off the front panal and the filters, then take off the flaps and also the front cover,disconnect the swing motor connectors from the PCB and then take out the lower part of the PCB. D. Change the position of DIP 7 of SW01 from OFF to ON, if fail to do this, the addresses set by SW03 will not work. E. Use SW03 to set the addresses as following (DO NOT CHANGE OTHER DIP SWITCHES):
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
60-
4. How to check the addresses? When finish all the above works, please power off and power on again to the whole system but set all the indoor units in STANDBY. Then continously press the emergency switch until you hear the buzzer sound 5 times(Pi Pi Pi Pi Pi), and then the TIMER LED board will show the address of this indoor unit. Press any key on the remote controller, it will exit the address checking precedure.
1 2 3 4 5 6 7 8
ON OFF
SW01
SW03 INDOOR
UNIT ADDRESS
1
2
3
4
(7).Setting method of temperature compensation (For heating function only)
In 24 oC heating mode,press sleep 7 times continuously.Indoor buzzer sounds 2 times,that show temp.compensatoin works.Swith on the unit in heating mode by the remote controller,press the time button to set the set temp.compensatoin.so the set temp. compensation=the current set temp.-24 oC.For example,if the set temp. is 24 oC,the temp.compensation is 0 oC;if the set temp.is 25 oC,the temp. compensation is 1 oC;if the set temp.is 30 oC,the temp. compensation is 6 oC;if the settemp.is 23 oC,the temp. compensation is -1 oC;if the set temp.is 16 oC,the temp. compensation is -8 oC;If setting is finished, press ON/OFF button, then the unit quits the temp. compensation.
Set method of temperature compensation(-8 oC~6 oC) in heating mode with the remote controller.
1 2 3 4 5 6 7 8
ON OFF
ON OFF
1 2 3 4 5 6 7 8
ON OFF
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON OFF
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
61-
ELECTRICAL WIRING
(1) The power source capacity must be the sum of the
room air conditioner current and the current of other electrical appliances. When the current contracted
capacity is insufficient, change the contracted
capacity.
(2) When the voltage is too low and the air conditioner
is difficult to start, contact the power company the
voltage raised.
CAUTION
TEST RUNNING
1. CHECK ITEMS
(1) INDOOR UNIT
(1) Is operation of each button on the remote control
unit normal? (2) Does each lamp light normally? (3) Do not air flow direction louvers operate normally? (4) Is the drain normal?
(2) Air filter removal and cleaning, and how to use
air louvers.
(3) Give the operating and installation manuals to
the customer.
(1) Always use a special branch circuit and install a special
receptacle to supply power to the room air conditioner.
(2) Use a circuit breaker and receptacle matched to the capacity of the room air conditioner.
(3) The circuit breaker is installed in the permanent wiring.
Always use a circuit that can trip all the poles of the
wiring and has an isolation distance of at least 3mm between the contacts of each pole.
(4) Perform wiring work in accordance with standards so
that the room air conditioner can be operated safely and positively.
(5) Install a leakage circuit breaker in accordance with the
related laws and regulations and electric company standards.
WARNING
MOUNT THE COVER PLATE AND
THE INTAKE GRILL
(2) OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during
operation?
(2) Will noise, wind, or drain water from the unit disturb
the neighbors?
(3) Is there any gas leakage?
CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operating manual:
(1) Starting and stopping method, operation switching,
temperature adjustment, timer, air flow switching, and other remote control unit operations.
1.Mount the cover plate. (Right)
(1) Cut a pipe exit hole in the right plate. This is
only when the pipe exits from the right side.
(This operation is not required when the
protrusion is on the top or rear.)
Fig. 31
Cover plate (Right)
(2) Join the cover plates (right) and mount with screws.
Fig. 32
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
62-
(2) Insert the hinges on the bottom of the intake grill into the holes in the base assembly. Then mount the arms to the three areas on the top of the intake grill.
Fig. 35
Fig. 34
(1) Cut the right side of the intake grill. This is only when the pipe exits from the right side
3. Mount the intake grill.
(1) Join the cover plate (left) and mount with screws.
Fig. 33
2. Mount the cover plate.(Left)
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
63-
Self-contained accessories
3. Accessories for installation
Name of Parts
No. A B
C D E F
Non-adhesive Tape
Adhesive tape
Connecting Hose
Gypsum powder
Drain hoseHeat insulation
material
4. Choose the installation place
Install the indoor unit where the weight of the unit can be supported. Install the indoor unit where the heat source and steam source are not close and the unit inlet and outlet are not blocked. Install the indoor unit where the drainage is easy and the outdoor unit can be easily connected. Install the indoor unit where its cold air and hot air can be easily sent to all the corners of the room. Install the indoor unit where the power socket is near and there is sufficient space around the indoor unit. Install the indoor unit where there is no T.V set, radio set, and wireless appliance underneath, and the sunlight lamp is over one meter away. If the remote controller is installed on the wall, the indoor unit shall be ensured to receive the signal while the sunlight lamp is on.
2. Preparation for installation
Installation tools
7 Pipe Cutter
14 Refrigeration Oil
6 Spanner
13 Scraper or File
5 Shifting Spanner
12 Measuring Tape
4 Inner Hexagon Spanner
11 Leakage Checker or Soap Liquid
3 60mm Drill
10 Clippers
2 Steel Saw
9 Knives
1 Screw Driver (flat head, wabbler, triangle)
8 Pipe Expander
4.7 Duct type AD***XLERA
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
64-
1. Drill a hole in the wall and insert the connecting pipe and wire through a PVC wall-through tube purchased locally. The wall hole shall be with a outward down slope of at least 1/100. (See Figure 1)
2. Before drilling check that there is no pipe or reinforcing bar just behind the drilling position. Drilling shall avoid at positions with electric wire or pipe.
3. Mount the unit on a strong and horizontal building roof. If the base is not firm, it will cause noise, vibration or pipe broken and refrigerant leakage (see Figure 6).
4. Support the unit firmly.
5. Change the form of the connection pipe, connection wire and drain pipe so that they can go
through the wall hole easily.
5. Installation procedure
When installing the ceiling concealed type indoor unit, a specially designed return air bellows shall be installed, as shown in Figure 3, Figure 4.
Figure 3
Figure 4
A
Installing building roof
Ceiling
Air supply
Air outlet duct
Unit
Return air
Return air bellows
Air outlet grille
Air supply
No obstacles within 1 m(0Pa)
Unit
Return air
Return air bellows
0.5m(0Pa)or 5m(50Pa)
Each air return and supply duct should fix to the floor precast slab by using an iron stand. Use glue to seal the interface closely. Recommend the distance between the air return duct and the wall is more than 150mm.
Fig 1
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
65-
The distance between air duct outlet and air conditioner outlet is according to the length of actually installed air duct and in service behavior of the static pressure terminal: Installation sketch map for long and short air duct is showed below, when connect to short air duct, using low static terminal (terminal color is white), the distance between air duct outlet and air conditioner outlet is no more than 0.5m; when connect to long air duct, using middle static terminal (terminal color is red), the distance between air duct outlet and air conditioner outlet could be within 5m at this point.
As figure shown, suspend and install the unit.
Drain piping of condensed water should keep a downhill grade of 1% or more. Use insulating pipe to cover the drain piping of condensed water to keep warmth.
Figure 5
Figure 6
air return shutter
air return duct
sling dog
drain piping
transition air duct
air outlet duct
air diffuser
joint of air diffuser
M8 broad foundation bolt
M8 suspension screw
M8 broad lock ring
M8 nut
Unit
Installation for air duct of indoor unit
This type of unit uses circular air duct with its caliber of 180mm. An additional transitive air duct is necessary for the circular air duct to connect to the air supply inlet. It should be also connected to its respective air diffuser separately. See Fig.1. Adjust the wind speed of each air diffuser outlet to keep in line on the whole, so as to meet a demand of the air conditioner in the room.
1. Installation of air discharge duct
Indoor unit
flexible joint or static pressure box
transitive air duct
circular air duct
joint of air diffuser
air diffuser
Fig1: Duct connected
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
66-
2. Installation of air return duct
3. Air duct insulation
Use M8 or M10 suspension screws (4, prepared in the field) (when the suspension screw height exceeds 0.9 m, M10 size is the only choice). These screws shall be installed as follows with space adapting to air conditioner overall dimensions according to the original building structures.
Use rivets to connect the air return duct to the air return inlet of the indoor unit. The other end connects to the air return shutter. as shown in Fig.2.
indoor unit
air return shutter
rivet
air return duct
Fig2: Duct return connected
Insulation layer is needed for air supply and return duct. First, paste a glue nail to the air duct, and then attach the insulation cotton that has a tinfoil layer and use the glue nail cover to fix. Finally, seal the air duct interface with tinfoil adhesive tape closely. as shown in Fig3.
galvanized board
glue nail
insulating fabric
tinfoil
adhesive tape
glue nail cover
Fig3
Installing the suspension screw
Wooden structure
A square wood shall be supported by the beams and then set the suspension screws.
Square wood
Suspension screw
Beam
New concrete slab
To set with embedded parts, foundation bolts etc.
Iron reinforcement
Knife embedded part
Foundation bolt
Guide plate embedded part Pipe suspension foundation bolt
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
67-
Original concrete slab
Use hole hinge, hole plunger or hole bolt.
Steel reinforcement structure
Use steel angle or new support steel angle directly.
Hanging of the indoor unit
Fasten the nut on the suspension screw and then hang the suspension screw in the Tslot of the suspension part of the unit. Aided with a level meter, adjust level of the unit within 5 mm.
Hanging bolt
Suspension screw
Support steel angle
In order to drain water normally, the drain pipe shall be processed as specified in the installation manual and shall be thermal insulated to avoid dew generation. Improper hose connection may cause indoor water leakage.
CAUTION
Requirements
The indoor drain pipe shall be thermal insulated. The connection part between the drain pipe and the indoor unit shall be insulated so as to prevent dew generation. The drain pipe shall be slant downwards (greater than 1/100). The middle part shall not be of Stype elbow, otherwise abnormal sound will be produced. The horizontal length of the drain pipe shall be less than 20 m. In case of long pipe, supports shall be provided every 1.5
2m to prevent wavy form. Central piping shall be laid out according to the following figure. Take care not to apply external force onto the drain pipe connection part.
Wall
Outside
Slant
Drain pipe (supplied by the user)
VP30
To the largest (app. 10cm)
Down slope above 1/100
S type elbow
1.5m~2m Support
Insulation (supplied by the user)
Down slope above 1/100
-6
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
8-
Supplementary refrigerant
The refrigerant supplementation shall be as specified in the installation instructions attached with the outdoor unit. The added refrigerant shall be R22. The adding procedure shall be aided with a measuring meter for a specified amount of supplemented refrigerant
Pipe cutting and expanding
If the pipe is too long or the flare is damaged, it needs to be cut or expanded.
Allowable pipe length and drop
These parameters differ according to the outdoor unit. See the instruction manual attached with the outdoor unit for details.
Pipe and insulation material
Hose
Drain pipe size: ?19.05mm2 (3/4") PVC pipe. The hose is used for adjusting the off-center and angle of the rigid PVC pipe.
Drain confirmation
During trial run, check that there is no leakage at the pipe connection part during water draining even in winter.
Rigid PVC pipe VP31.5mm (internal diameter)Pipe
Foamed PE with thickness above 7mm
Insulation
Wrap the hose and its clamp until to the indoor unit without any clearance with insulating material, as shown in the figure.
Insulation treatment:
Directly stretch the hose to install without making any deformation. The soft end of the hose must be fastened with a hose clamp. Please apply the hose on horizontal part
Hose Hose clamp
Subsidiary insulation
Insulation
Rigid PVC pipe
Requirement
Overfilling or underfilling of refrigerant will cause compressor fault. The amount of the added refrigerant shall be as specified in the instructions.
1. Pipe cutting 2. Removing burrs 3.Insertion nut 4. Pipe expansion
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
69-
The connection of indoor unit pipes must use double spanners. The installing torque shall be as given in the following table.
Double-spanner operation
Pipe expansion dimensions as follows:
Pipe expander
A
Piping Connection
Flare connection
Gas pipe
3-way valve
Indoor Unit
Outdoor unit
Liquid pipe
2-way valve
Flare connection
AD092XLERA AD122XLERA
AD142XLERA AD182XLERA
Flare connection
Gas pipe
3-way valve
Indoor Unit
Outdoor unit
Liquid pipe
2-way valve
Flare connection
A
To outdoor unit
To gas pipe
A
(adaptor, from 9.52 to 12.7)
6.35 mm (1/4") 0.8 ~ 1.5
9.52 mm (3/8") 1.0 ~ 1.8
12.7 mm (1/2") 1.2 ~ 2.0
Pipe diameter
?
Size A (mm)
Connecting pipe
O.D.(mm)
? 6.35 ? 9.52
? 12.70
Installing torque
(N-m)
11.8 (1.2kgf-m)
24.5 (2.5kgf-m)
49.0 (5.0 kgf-m)
Increased installing
torque (N-m)
13.7 (1.4 kgf-m)
29.4 (3.0 kgf-m)
53.9 (5.5 kgf-m)
Slope Damage Bur Partial Overlong
Correct
Incorrect
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
70-
1. Indoor unit communication addresses setting
CAUTION! FAIL TO DO THIS, THE UNIT WILL NOT WORK.
(2). Address setting procedure when using the DIP switches SW01 and SW03. A. The DIP switches SW01 and SW03 are on the indoor unit PCB. B. Change the position of DIP 7 of SW01 from OFF to ON, if fail to do this, the addresses set by SW03 will not work. C. Use SW03 to set the addresses as following (DO NOT CHANGE OTHER DIP SWITCHES):
(1).Please note that the address must be set as following:
1 2 3 4 5 6 7 8
ON OFF
SW01 SW03
1 2 3 4 5 6 7 8
ON OFF
ON OFF
1 2 3 4 5 6 7 8
ON OFF
1 2 3 4 5 6 7 8
ON OFF
1 2 3 4 5 6 7 8
INDOOR UNIT ADDRESS
1
2
3
4
OUTDOOR VALVE
A
B
C
D
This kind of indoor units can only set the address by using the Dip Switches.
Indoor unit that connect to valve A, the address must be 1; Indoor unit that connect to valve B, the address must be 2; Indoor unit that connect to valve C, the address must be 3; Indoor unit that connect to valve D, the address must be 4;
2.Installation check and trial operation
Check the Layout of the Drain Pipe and Connection Wires, and also the piping and address setting. The drain pipe should be placed underneath, and the connection wires should be placed upside; and the drain pipe especially the section inside the machine and indoors must be wound up with insulating material to preserve heat. The drain pipe shall be sloped and no concave and convex shall occur along the whole pipe. And the cases as the right figure indicates shall not occur.
3.Installation check
Is power supply voltage required? Is water completely drained to outdoors? Are power wire and connection wires between indoor and outdoor units correctly connected? Is any gas leaked from the pipe connectors? Are series numbers of the terminals on the indoor and outdoor units corresponding to each other? Is the connection section of the auxiliary pipe insulated? Is the indoor unit fixed firmly? Is noise big?
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
71-
4.Trial operation
The person who has completed this installation shall be requested to conduct a test operation for check: Is the temperature adjuster working normally? Does the location for installation conform to requirements? Winding up with Protective Plastic Tape.The connection pipes,drain pipe, and the connection wires shall be wound up with PVC tape.
The connection pipes shall also be wound up with insulating material to preserve the temperature. The airing direction shall be from bottom to top.
NOTE!
1 Wiring method of ring terminal For connecting line which end is a ring,its wiring method as shown in the right figure: remove
wiring screw and pass it through the end ring of connecting line,then connect it to the terminal block and tighten screw.
Wiring methods:
Ring Terminal
Brazed seam
B=8.0-9.0(mm) d=4.3-5.3(mm) T=1.0-2.0(mm) (For your referrence)
Wiring method of ring terminal
2 Wiring method of straight terminal
For connecting line which end is not a ring, its wiring method as follows: loosen wiring screw ans insert the end of connecting line totally into the terminal block,then tighten the screw and pull the connecting line slightly to confirm that it is clamped firmly.
Correct crimp connection of wire
Terminal block
Incorrect crimp connection of wire
Crimp connection clamp
3 Crimp connection method of connecting line
After finishing wiring.connecting line must be fastened by wire clamp,which pressed on the external sheath of the connecting line, as shown in the right figure:
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
72-
4 Wiring of indoor unit
The distance between the signal wires and the power cabes should be at least 50mm.
C
BA
Q
P
1(L) 2(N)
2(N)1(L)
P
Q
A B
C
L N
C1 C2
To other indoor unit
To wired controller(A,B,C)
To outdoor unit
(P Q)
Waring:
1.Incorrect address setting will cause abnormal to the system.
2.Communication cable must be use sheilded type.
Communication cable (Shield wire): H05RN-F 2X1.5 mm
2
Power cable : H05RN-F 3G 2.5 mm
2
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
73-
Installation of indoor unit
selection of installation place
Fig1
330
Fig2
Fig3
Tool necessary
4.8. Console type AF***XCERA
Place where it is easy to route drainage pipe and outdoor piping. Place ,away from heat source and with less direct sunlight. Place where cool and warm air could be delivered evently to every corner of the room. Place near power supply socket.Leave enough space around the unit. Place ,robust not causing vibration,where the body can be supported sufficiently. To prevent interference, place it at least 1m away from other electric machines, such as TV set, radio. Installing According to the dimension of the figure 2 shown, nail two cement steel nails on the wall,Keep 2~3mm out.then hang the back of the unit on them. There must be no gap between the indoor unit and wall. Remove the front panel,then use two expansible screws to fix the unit on the floor. As figure 3 shown. Once refrigerant piping and drain piping connections are complete,fill the gap of the throght hole with putty. Attach the front panel and front grille in their orginal positions once all connections are complete.
1. Screw driver
2. Hacksaw
3. 70mm dia.hole core drill
4. Spanner(dia. 17,27mm)
5. Spanner(14,17,27mm)
6. Pipe cutter
7. Flaring tool
8. Knife
9. Nipper
10. Gas leakage detector or soap water
11. Measuring tape
12. Reamer
13. Refrigerant oil
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
74-
Fixing of the unit
1. Position of the wall hole
Wall hole should be decided according to installation place and piping direction.(refer to installation drawings).
2. Making a wall hole Drill a hole of 120X70mm dia. with a little slope towards outside.
3. Piping connection
Threads on the pipes may be damaged when tightening if the pipes are not well aligned.
(1)Schematic diagram for unit connection
(4) Pipe connection process
Torque
11.8 N.m
Pipe Value
6.35mm
Liquid
40 N.m
(2)Connection pipe dimensions:
9.52mm
Gas
Outdoor uint
3-way Valve
2-way Valve
Indoor unit
Indoor unit
Apply and tighten the nut.
(3)Cautions for pipe connection
Pipes free from twists, deformation, water, dust. Dedicated tools for each R407C and R410A should be used and stored separately. Optimized radii of bends Insulation to be applied on all gaseous pipes Flared section free from cracks
Joint
Spanner
Spanner
Nut
Apply refrigeration oil on the end of the pipe to be connected and on the flared section. Align the pipes to be connected and tighten the nut. (See the figure) Ensure that no foreign articles enter into the pipes.
Flared pipe connection
Indoor side
Outdoor side
Thickness of wall
Wall hole
70mm
(Cross section of wall hole)
Double-spanner operation
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
75-
1. Arrangement of piping and drainage pipe After opening inlet grill,you will see a control box.
Remove the cover before working.
Cut away, with a hammer or a saw, the lid for piping according to piping direction.
According to the piping method, connect the piping on indoor unit with union of connection pipe. Arrange the piping as per the wall hole and bind drain hose connecting electric cable and piping together with polyethylene tape. Insert the bound piping connecting electric cable and drain hoes through wall hole to connect with outdoor unit.
2. Arrangement drain hose
Drain hose shall be placed in under place. There should be a slope when arrange drain hose. Avoid up and down waves in drain hose. If humidity is high, drain pipe(especially in room and indoor unit) must be covered with installation material.
Insulation material
Copper tube
Drain hose
Connecting electric cable for indoor and outdoor unit
Electric wiring :
Piping connection of the indoor unit
Process of wire connections
1. Loop terminal After removing the screw, fix the wire ring on the screw, reinsert the screw into the block terminal and then tighten the screw.
2. Straight terminal After loosening the screw, inset the wire end into the block terminal and then tighten
the screw. Slightly pull the wire to see if it is tightly fixed.
3. Wire capping
After completion of connection, capping clips must be
applied on the external sleeve of the wires.
- -
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
76
Others
The power plug should be connected as follows: L for live line, N for neutral line and
for grounding.
The signal wire must be shielded wire.
2. Piping cutting and flaring
Be sure to carry out deburring after cutting with a pipe cutter. Insert flaring tool to make a flare.
Installation inspection and test run: Please operate unit according to this Manual. Items to be checked during test run. Please made a '' '' in '' ''
Are there any gas leakage? How is insulation at piping connection carried out? Are electric wires of indoor and outdoor unit firmly inserted into terminal block? Is electric wiring of indoor and outdoor securely fixed? Is drainage securely carried out? Is earth line(grounding) securely connected? Is power supply voltage abided by the code? Is there any noise? Is control display normal? Is cooling operation normal? Is room temp. regulator normal?
Liquid pipe
Pipe diameter
Size A (mm)
0.8 ~1.5
1.0 ~1.5
6.35mm(1/4")
9.52mm(3/8")
Gas pipe
A
Correct Incorrect
Lean
Damage of flare Crack Partial Too outside
Flare tooling die
Voltage: single-phase1PH,220-230V~,50Hz
The power source must be grounded.
Connection parameters: H05RN-F 3G(1.0-1.5)mm
Signal parameters:
1. Power supply requirements:
Cables for power supply, connection and signals are prepared by the owner.
Electrical cables should be connected by
Y
method. Damaged or wornelectrical
cable must be replaced by authorized after sales agents.
A circuit breaker must be installed
Dedicated electrical cable should be installed by a qualified technician in accordance with the state regulation for electrical engineering.
H05RN-F 2x(0.75-1.5)mm
(Shieded wire)
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
77-
Remove air intake screen and take out the front wires. Connect the wires as specified in the above methods and diagrams for indoor unit and wire con- nections. Properly apply capping clips on the wires. Replace the air intake screen.
Do not link the connecting and signal wire with the
same cable, a snug space must be maintained between connecting and signal wires.
Shield of the signal wire should be spot grounded.
Incorrect address setting will cause abnormal to the system. Communication cable must be use sheilded type. Incorrect address setting will cause abnormal to the system.and then put it down perpendicularly. Signal connecting cable must be sheilded type. The distance between the signal wires and the power cabes should be at least 50mm.
WARNING
Correct crimp connection of wire
Incorrect crimp connection of wire
1(L) 2(N)
P
Q
1(L) 2(N)
P
Q
1(L) 2(N)
P
Q
TO OUTDOOR UNIT
L N
C1 C2 (P) (Q)
Communication cable (Shield wire): H05RN-F 2X1.5mm
2
Power cable : H05RN-F 3G 2.5mm
2
Wiring connection:
Wiring of indoor unit
Block terminal
Capping clip
Wiring diagram of loop terminals
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
78-
Indoor unit communication addresses setting
CAUTION! FAIL TO DO THIS, THE UNIT WILL NOT WORK.
3. Address setting procedure when using the DIP switches SW01 and SW02. A. The DIP switches SW01 and SW02 are on the indoor unit PCB. B. Before carrying out the address setting work, the system must be powered off. C. Take off the front panal and the filters, then take off the flaps and also the front cover,disconnect the swing motor connectors from the PCB and then take out the lower part of the PCB. D. Change the position of DIP 1 of SW01 from OFF to ON, if fail to do this, the addresses set by SW02 will not work. E. Use SW02 to set the addresses as following (DO NOT CHANGE OTHER DIP SWITCHES):
1.There are two methods to set the communication address A. Use the remote controller(default status in first installation). B. Use dip switches on the indoor unit PCB.
2. Address setting procedure when using the remote controller. A. Set the addresses only after the successful installation of the refrigerant pipes and connecting cables, and open all the stop valves; B. Please confirm that the indoor units and the outdoor unit in the same system use the same power source; C. Power on the units, but put all the indoor units in the status of STANDBY; D. Please note that the address must be set as following:
Indoor unit that connect to valve A, the address must be 1; Indoor unit that connect to valve B, the address must be 2; Indoor unit that connect to valve C, the address must be 3; Indoor unit that connect to valve D, the address must be 4;
E. Example: set unit A to address 1. Continuously press the emergency switch for about 15 seconds, the buzzer will sound 4 times(PI PI PI PI) and then leave go of the switch. At this time, the indoor unit has entered the address setting procedure. But the LED board is blank. F. Use the controller to turn on the indoor unit. At this time, the controller should be changed from OFF to ON, and then theTIMER LED flshes once. That is to say, the address setting is enabled. G. Press the button
SLEEP
on the controller, the times you press it stands for the address you want to set, detailed as following: Press button
SLEEP
once, the address is
1
, and the TIMER LED flashes once;
Press button
SLEEP
twice, the address is
2
, and theTIMER LED flashes twice;
Press button
SLEEP
three times, the address is
3
, and the TIMER LED flashes three times;
Press button
SLEEP
four times, the address is
4
, and the TIMER LED flashes four times; H. Use the remote controller to turn off the unit, At this time, the controller should be changed from ON to OFF, and the unit will exit the address setting procedure, the address will be memorized. The LED board will always display the address of this indoor unit until the system be powered off. I. If you want to change the address, please repeat the above steps from E to G.
J. After setting all the addresses, please power off the system and then power on again. Otherwise the system will not start to work. K. Once the addresses are successfully set, please do not change it any more to avoid confusion.
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
79-
When finish all the above works, please power off and power on again to the whole system but set all the indoor units in STANDBY. Then continously press the emergency switch until you hear the buzzer sound 5 times(Pi Pi Pi Pi Pi), and then the LCD display board will show the address of this indoor unit. Press any key on the remote controller, it will exit the address checking precedure.
How to check the addresses?
1 2 3 4 5 6 7 8
ON OFF
SW01
SW02
INDOOR UNIT ADDRESS
1
2 3
4
1 2 3 4 5 6 7 8
ON OFF
ON OFF
1 2 3 4 5 6 7 8
ON OFF
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON OFF
-8
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
0-
PRECAUTION
Self-contained accessories
3. Accessories for installation
Name of Parts
No. A B
C D E F
Non-adhesive Tape
Adhesive tape
Connecting Hose
Gypsum powder
Drain hose
Heat insulation material
2. Preparation for installation
Installation tools
7 Pipe Cutter
14 Refrigeration Oil
6 Spanner
13 Scraper or File
5 Shifting Spanner
12 Measuring Tape
4 Inner Hexagon Spanner
11 Leakage Checker or Soap Liquid
3 60mm Drill
10 Clippers
2 Steel Saw
9 Knives
1 Screw Driver (flat head, wabbler, triangle)
8 Pipe Expander
4. Choose the installation place
Install the indoor unit where the weight of the unit can be supported.
Install the indoor unit where the heat source and steam source are not close and the unit inlet and outlet are not blocked.
Install the indoor unit where the drainage is easy and the outdoor unit can be easily connected.
Install the indoor unit where its cold air and hot air can be easily sent to all the comers of the room.
Install the indoor unit where the power socket is near and there is sufficient space around the indoor unit.
Install the indoor unit where there is no T.V set, radio set, and wireless applian ce underneath, and the sunlight lamp is over one meter away.
If the remote controller is installed on the wall, the indoor unit shall be ensured to receive the signal while the sunlight lamp is on.
An electric leakage breaker must be installed, otherwise electric shock or other accidents would occur.
After completion of the installation, the air conditioner shall be electrified to check for electric leakage.
Execute proper grounding. Do not connect the earth wire to a gas pipe, water pipe, lightening rod, or a telephone ground wire. Improper placement of earth wires can result in electric shock.
4.9. Wall mounted type AS***XVERA
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
81-
5. Method for Cutting and Expanding Pipes.
Make a hole of 60mm in diameter, slightly descending to outside the wall. Install piping hole cover and seal it off with putty after installation.
4. Drawing of pipe Rear piping Draw pipes and the drain hose, then fasten them with the adhesive tape. Left Left-rear, piping. In case of left side piping, cut away, with a nipper, the lid for left piping. In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for left-rear piping which is marked on heat insulation materials. (1) Insert the drain hose into the dent of heat insulation materials of indoor unit. (2) Insert the indoor/outdoor electric cord from backside of indoorunit, and pull it out on the front side, then connect them. (3) Coat the flaring seal face with refrigerant oil and connect pipes. Cover the connection part with heat insulation materials closely, and make sure fixing with adhesive tape.
Correct Not Correct
cracks on expanded mouth burr incomplete too longTilting
6. When the mounting plate is first fixed
1. Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the wall, then temporarily fasten the plate with one steel nail.
2. Make sure once more the proper level of the plate, by hanging a thread with a weight from the central top of the plate, then fasten securely the plate with the attachment steel nail.
3. Making a Hole on the wall and Fitting the piping Hole cover.
A=80mm
Indoor side Outdoor side
Wall hole
Thickness
of wall
70mm
(Section of wall hole) Piping hole pipe
60mm
2-5mm
When the pipe is too long or the mouth is damaged, the pipe needs to cut or expanded.
1.cutting hose 2.Removing burr 3.Put on nut 4.Expand Hose
Hose Expander
A
Expansion Size
Hose dia.
Size (mm)A
0.8-1.5
1.0-1.5
6.35 mm(1/4)
9.52 mm(3/8)
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
82-
Heat insulation material
Drain hose
Piping
Indoor/outdoor electric cable
signal wire
Change-for-fresh-air tube
Indoor/outdoor electric cord and drain hose must be bound with refrigerant piping by protecting tape
8. Indoor unit communication addresses setting
1.There are two methods to set the communication address A. Use the remote controller(default status in first installation). B. Use dip switches on the indoor unit PCB.
2. Address setting procedure when using the remote controller. A. Set the addresses only after the successful installation of the refrigerant pipes and connecting cables, and open all the stop valves; B. Please confirm that the indoor units and the outdoor unit in the same system use the same power source; C. Power on the units, but put all the indoor units in the status of STANDBY; D. Please note that the address must be set as following: Indoor unit that connect to valve A, the address must be 1; Indoor unit that connect to valve B, the address must be 2; Indoor unit that connect to valve C, the address must be 3; E. Example: set unit A to address 1. Continuously press the emergency switch for about 15 seconds, the buzzer will sound 4 times(PI PI PI PI) and then leave go of the switch. At this time, the indoor unit has entered the address setting procedure. But the LCD display board is blank. F. Use the controller to turn on the indoor unit. At this time, the controller should be changed from OFF to ON, and then the LCD display board will display number
1
. That is to say, the address setting is enabled.
G. Press the button
SLEEP
on the controller, the times you press it stands for the address you want to set, detailed as following: Press button
SLEEP
one time, the address is
1
, and the LCD display board shows
1
;
Press button
SLEEP
two times, the address is
2
, and the LCD display board shows
2
;
Press button
SLEEP
three times, the address is
3
, and the LCD display board shows
3
; H. Use the remote controller to turn off the unit, At this time, the controller should be changed from ON to OFF, and the unit will exit the address setting procedure, the address will be memorized. The LCD display board will always display the address of this indoor unit until the system be powered off.
Lid for right piping
Lid for under piping
Lid for left piping
Fix with adhesive tape
7. Other direction piping
Cut away, with a nipper, the lid for piping according to the piping direction and then bend the pipe according to the position of wall hole. When bending, be careful not to crash pipes. Connect beforehand the indoor/outdoor electric cable, and then pull out the connected to the heat insulation of connecting part specially. Hang surely the unit body onto the upper notches of the mounting plate. Move the body from side to verify its secure fixing. In order to fix the body onto the mounting plate, hold up the body aslant from the underside and then put it down perpendicularly.
CAUTION! FAIL TO DO THIS, THE UNIT WILL NOT WORK.
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
83-
I. If you want to change the address, please repeat the above steps from E to G. J. After setting all the addresses, please power off the system and then power on again. Otherwise the system will not start to work. K. Once the addresses are successfully set, please do not change it any more to avoid confusion.
3. Address setting procedure when using the DIP switches SW01 and SW02. A. The DIP switches SW01 and SW02 are on the indoor unit PCB. B. Before carrying out the address setting work, the system must be powered off. C. Take off the front panal and the filters, then take off the flaps and also the front cover,disconnect the swing motor connectors from the PCB and then take out the lower part of the PCB. D. Change the position of DIP 1 of SW01 from OFF to ON, if fail to do this, the addresses set by SW02 will not work. E. Use SW02 to set the addresses as following(DO NOT CHANGE OTHER DIP SWITCHES):
8.Installation check and trial operation
Check the Layout of the Drain Pipe and Connection Wires, and also the piping and address setting. The drain pipe should be placed underneath, and the connection wires should be placed upside; and the drain pipe especially the section inside the machine and indoors must be wound up with insulating material to preserve heat. The drain pipe shall be sloped and no concave and convex shall occur along the whole pipe. And the cases as the right figure indicates shall not occur.
9.Installation check
10.Trial operation
4. How to check the addresses? When finish all the above works, please power off and power on again to the whole system but set all the indoor units in STANDBY. Then continously press the emergency switch until you hear the buzzer sound 5 times(Pi Pi Pi Pi Pi), and then the LCD display board will show the address of this indoor unit. Press any key on the remote controller, it will exit the address checking precedure.
The person who has completed this installation shall be requested to conduct a test operation for check:
Is the temperature adjuster working normally? Does the location for installation conform to requirements?
Winding up with Protective Plastic Tape.The connection pipes,drain pipe, and the connection wires shall be wound up with PVC tape.
Notes: The connection pipes shall also be wound up with insulating material to preserve the temperature. The airing direction shall be from bottom to top.
Is power supply voltage required? Is water completely drained to outdoors? Are power wire and connection wires between indoor and outdoor units correctly connected? Is any gas leaked from the pipe connectors? Are series numbers of the terminals on the indoor and outdoor units corresponding to each other? Is the connection section of the auxiliary pipe insulated? Is the indoor unit fixed firmly? Is noise big?
1 2 3 4 5 6 7 8
ON OFF
SW01
SW02
1 2 3 4 5 6 7 8
ON OFF
ON OFF
ON OFF
INDOOR UNIT ADDRESS
1
2
3
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
84-
5.1. 1.
CN7 CN6 CN5 CN4 CN3 CN2 CN1 CN8
CN9
CN15 CN16CN14 CN13
CN12
CN11
CN10
CN17 CN18 CN19 CN20
CN21
CN22
CN23
SW5
SW1
SW2
SW3
SW4
Lamp1
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
5. PCB photo,Wiring diagram and function description
SW05 is used for factory quality control engineers, the default position is : OFF OFF OFF OFF
LED5
LED1
LED2
LED3
LED4
SW05
0010452047
Outdoor PCB photo
5.1 Outdoor unit
85-
5.1.2. Wiring diagram
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
N
L
M
CN17
TD
TE
TS
TA
TC
CN16 CN15
LED2
LED1
CN12
CN11
CRANKCASE
HEATER
CN10
CN9
Y/G
4-WAY
VALVEAC FAN MOTOR
W
U
COMPRESSOR
R
V
B
W
CN2
220VAC-N
Q
P
T25A 250VAC
FUSE
LED5
LED3
LED4
LED1
LED2
M
R R
To Indoor Units
CN21
250VAC T3.15A
SW5
TD: COMPRESSOR VENT SENSOR
SW5
To Power Supply
CN26
FUSE1
TS: COMPRESSOR INHALE SENSOR
TC CONDENSING TEMPERATURE SENSOR
TE DEFROSTING TEMPERATURE SENSOR
TA AMBIENT TEMPERATURE SENSOR
0010576926
TOCI
TOCI PIPING TEMPERATURE SENSOR
M M
CN4
N L M
CN22
CN18
PMV_B
PMV_C
PMV_D
PMV_A
SV2
CN6
ON
1 23 4 5 6 7 8
PTC
BUS
L
CN8
N
ON
4321
SW3 SW4
SW2SW1
start/up stop/down
B : BLACK
R : RED
OR : ORANGE
W : WHITE
Y/G : YELLOW/GREEN
CN19
LPHP
CN20
CN23
H
CN3
CN5
CN14 CN13
CN1 CN2
CN7
LED
DEBUG_LED
4WV
TO SPDU
CN1
N L
CN5
CONTROL
CIRCUIT
BOARD
CN4
CN3
220VAC-L
CN8
CN7
CIRCUIT
BOARD
POWER
RL1
U V W
ACN
RI
ACL
RO
N(-)
P(+)
+-
SPDU
W B
Y/G
Y/G
WB
ORBL
BL : BLUE
capacitor
capacitor
reactor
SW5-5 SW5-6
SW5-5 SW5-6
ON
ON
18000
BTU
22000
BTU
CN25
AU182\222XFERA
86-
- -
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
N L
W
U
COMPRESSOR
R
V
B
W
CN2
220VAC-N
Q P
T25A 250VAC
FUSE
LED5
LED3
LED4
LED1
LED2
R R
To Indoor Units
TD: COMPRESSOR VENT SENSOR
SW5
To Power Supply
CN26
TS: COMPRESSOR INHALE SENSOR
TC CONDENSING TEMPERATURE SENSOR
TE DEFROSTING TEMPERATURE SENSOR
TA AMBIENT TEMPERATURE SENSOR
TOCI PIPING TEMPERATURE SENSOR
ON
4321
B : BLACK
R : RED
OR : ORANGE
W : WHITE
Y/G : YELLOW/GREEN
CN1
N L
CN5
CN4
CN3
220VAC-L
CN8
CN7
CIRCUIT
BOARD
POWER
RL1
U V W
ACN
RI
ACL
RO
N(-)
P(+)
+-
SPDU
W B
Y/G
Y/G
WB
ORBL
BL : BLUE
capacitor
reactor
CN25
CN18
TD
TE
TS
TA
TC
CN17 CN15
LED1
LED2
CN12
CN11
CRANKCASE
HEATER
CN10
CN9
4-WAY
VALVE
M
CN22
250VAC T3.15A
SW5
FUSE1
TOCI
CN4
N L M
CN23
CN19
PMV_B
PMV_C
PMV_E
PMV_A
SV2
CN6
ON
1 23 4 5 6 7 8
PTC
BUS
L
CN8
N
SW3 SW4
SW2SW1
CN20
LPHP
CN21
CN24
H
CN3
CN5
CN14
CN13
CN1
CN2
CN7
LED
DEBUG_LED
4WV
CONTROL
CIRCUIT
BOARD
TO ISPM
VALVE
UNLOAD
capacitor
M
AC FAN MOTOR
M M M
CN16
PMV_D
AU252XGERA:
87
AU282XHERA,AU342XHERA Wiring Diagram
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
-
N L
CN17
TD
TE
TS
TA
TC
CN16 CN15
LED2
LED1
CN12
CN11
CRANKCASE
HEATER
CN10
CN9
4-WAY
VALVE
W
U
COMPRESSOR
V
CN1
Q P
T25A 250VAC
FUSE
LED5
LED3
LED4
LED1
LED2
M
CN21
250VAC T3.15A
SW5
TD: COMPRESSOR VENT SENSOR
SW5
To Power Supply
CN26
FUSE1
TS: COMPRESSOR INHALE SENSOR
TC CONDENSING TEMPERATURE SENSOR
TE DEFROSTING TEMPERATURE SENSOR
TA AMBIENT TEMPERATURE SENSOR
TOCI
TOCI PIPING TEMPERATURE SEN SOR
M
M
CN4
N L M
CN22
CN18
PMV_B
PMV_C
PMV_D
PMV_A
SV2
CN6
ON
1 23 4 5 6 7 8
PTC
BUS
L
CN8
N
ON
4321
SW3 SW4
SW2SW1
start/up stop/down
B : BLACK
R : RED
OR : ORANGE
W : WHITE
Y/G : YELLOW/GREEN
CN19
LPHP
CN20
CN23
H
CN3
CN5
CN14
CN13
CN1
CN2
CN7
LED
DEBUG_LED
4WV
CN2
CN5
CONTROL
CIRCUIT
BOARD
CN4
CN3
CN8
CN7
CIRCUIT
BOARD
POWER
U V W
R
T/RB
S
P1
N(-)
P(+)
+-
ISPM
ORBL
BL : BLUE
capacitor
reactor
M
TO ISPM
communication terminal
VALVE
UNLOAD
BR R
B
W
0010577425
CN206
BR:BROWN
SW5-6SW5-5
SW5-6
34000
BTU
28000
BTU
on
on
SW5-5
capacitor
M
AC FAN MOTOR
B
W
R W B
B
W
Y/G
88-
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
N
L
CN18
TD
TE
TS
TA
TC
CN17 CN15
LED1
LED2
CN12
CN11
CRANKCASE
HEATER
CN10
CN9
4-WAY
VALVE
W
U
COMPRESSOR
V
CN1
Q P
T25A 250VAC
FUSE
LED5
LED3
LED4
LED1
LED2
M
CN22
250VAC T3.15A
SW5
TD: COMPRESSOR VENT SENSOR
SW5
To Power Supply
CN26
FUSE1
TS: COMPRESSOR INHALE SENSOR
TC CONDENSING TEMPERATURE SENSOR
TE DEFROSTING TEMPERATURE SENSOR
TA AMBIENT TEMPERATURE SENSOR
TOCI
TOCI PIPING TEMPERATURE SEN SOR
CN4
N L M
CN23
CN19
PMV_B
PMV_C
PMV_E
PMV_A
SV2
CN6
ON
1 23 4 5 6 7 8
PTC
BUS
L
CN8
N
ON
4321
SW3 SW4
SW2SW1
B : BLACK
R : RED
OR : ORANGE
W : WHITE
Y/G : YELLOW/GREEN
CN20
LPHP
CN21
CN24
H
CN3
CN5
CN14
CN13
CN1
CN2
CN7
LED
DEBUG_LED
4WV
CN2
CN5
CONTROL
CIRCUIT
BOARD
CN4
CN3
CN8
CN7
CIRCUIT
BOARD
POWER
U V W
R
T/RB
S
P1
N(-)
P(+)
+-
ISPM
Y/G
ORBL
BL : BLUE
capacitor
reactor
TO ISPM
communication terminal
VALVE
UNLOAD
BR R
B
W
CN206
BR:BROWN
capacitor
M
AC FAN MOTOR
B
W
R W B
B
W
M M M
CN16
PMV_D
M
AU362XHERA
89-
5.1.3. Switch setting and functions:
No Item
A8
Set in factory
Switch function: SW5-1---outdoor fan motor selection, ON: DC fan motor; OFF: AC fan
motor
C1
Switch function: SW5-2---defrosting data setting, ON=6degree, OFF8degree (set
when out of factory).
For the place where is easy to frost, it is 6 degree; for the place hard to frost, it is 8
degree.
C2
Switch function: SW5-3SW5-4---piping length selection, the set data is M when out of
factory. SSW5-3=OFF SW4=ON L(SW5-3=ON SW4=OFF)
- SW5-3=ON SW4=ON M(SW5-3=OFF SW4=OFF)
C3
Switch function: SW5-5SW5-6---outdoor horse power selection (for different outdoor,
the current limitation is different too. The corresponding selection must be taken, or
the module protection will occur. )
2HPSW5-5=OFF SW5-6=ON 2.5HPSW5-5=ON SW5-6=OFF 3HP SW5-5=ON SW5-6=ON) 3.5HP(SW5-5=OFF SW5-6=OFF)
C4
Switch function: SW5-7,SW5-8:
SW5-7pre-set, set as OFF when out of factory. SW5-8silent operation function, ON---available, OFF---not available (set when
out of factory)
When it is ON, the max. fan speed is Class-6, and the max. running frequency is 10Hz.
C8
Set in factory
2. Defination of 4-bit dip switch SW5 on failure indicator board:
1 2 3 4 Defination
OFF OFF OFF OFF State when out of factory (normal state)
OFF ON OFF OFF
Compulsory cooling: frequency 60HZ, outdoor fan motor Class-7, fixed open angle
300, the others are in normal state
ON OFF OFF OFF
Compulsory heating: frequency 50HZ, outdoor fan motor Class-5, fixed open angle
300, the others are in normal state
OFF OFF ON OFF
Rated operation: auto changeover for cool/heat, max. frequency 53HZ(E) in cooling,
and max. frequency 72HZ(E) in heating, the frequency is set automatically in other
states.
3. Main control functions
3.1 Refrigerant diagram
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
-90-
T
d
Ts
Tao
Tc
Te
TmC
TinC
TaiC
Toci
TouC
TinB
TmB
TaiB
TouB
TinA
TmA
TaiA
TouA
HPSW
L P S W
Pipe system for AU182XFERA and AU222XFERA
Pipe system for AU282XHERA
3.2 Outdoor frequency control
3.2.1 Compressor running frequency range: 20~90RPS
3.2.2 Defination of high-efficiency operation and its frequency control
In order to meet the cooling request at high ambient temperature and the heating request at low ambient
temperature, we set the high-efficiency operation. Entering condition: cooling mode, Tao≥33℃(E), heating mode, Tao≤5℃(E).
3.3 Electronic expansion valve (EEV) control
3.3.1 Electronic characteristic
Max. open angle 500 pulse
Driving speed PPS
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
91-
3.3.2 Initialization of EEV
EEV driving speed: open direction: 32MS; close direction: 32MS
3.3.3 Open angle limitation of EEV
Unit stop Adjustable upper
limitation
Thermostat ON Thermostat
OFF
Adjustable lower
limitation
Cool/dry
5E 450E
standard open
angle+tolerance
5E 80E
heat
60(E) 450(E)
standard open
angle+tolerance
60(E) 80(E)
3.3.4 Standard open angle control In Cool/Dry mode, standard open angle: outdoor ambient temp.≥20℃, 250 pulse(E);
Outdoor ambient temp.<20℃, 210 pulse(E);
In Heat mode, standard open angle: outdoor ambient temp.≥10℃, pulse (E);
outdoor ambient temp.<10℃, 210 pulse (E).
3.3.5 When discharging temp. Td is too high, modify the EEV angle.
In order to cooperate the compressor discharging temp. over high protection, the system will enlarge the
EEV open angle. Within 5 minutes after compressor starts up, it will not modify. The detecting period is 30
seconds.
Cooling mode Indoor modification angle
100<discharging temp.
+50degree/30seconds, it will stop until up to the max. permitted
opening angle
90< discharging temp.<=100
Keep the angle
<=90
-5degree/30seconds, and reduce to 0 degree gradually
Heating mode Indoor modification angle
100< discharging temp.
+50degree/30seconds, it will stop until up to the max. permitted
opening angle
90< discharging temp.<=100
Keep the angle
<=90
-5degree/30seconds, and reduce to 0 degree gradually
3.4 4-way valve control in heating
Protection when 4-way valve can not reverse in heating:
10 minutes later after compressor startup, if indoor coil average temp. is below 15degree and keeps for 1
minute, the unit will stop and occur the 4-way valve protection.
compressor ON
OFF
4-way valve ON
OFF 15s(E) 2minutes and 55s
3.5 Electric heater control
If compressor has not run for a long time, the refrigerant will deposit on the bottom of compressor and mix
with the refrigeranr oil. When re-startup, because low pressure reduces, refrigerant will be segregated
from the refrigerant oil and cause soam in the oil, which will make compressor exhaust a lot of oil.
Therefore please stop heating the compressor bottom to ensure the low pressure in startup period should
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
92-
not go down greatly.
Ambient temp. TA27degree, when compressor stops, the electric heater will be electrified. When TA32degree, or compressor running, the electric heater will be off.
Heater ON OFF Ambient temp. TA(℃) 27 32
3.6 Control of liquid spray valve SV2:
According to the compressor discharging temp., open or close the SV2. Control condition: A. In every mode (including defrosting and oil return operation), the control can work.
B. In 3 minutes after compressor startup, ignore the abnormal compressor suction and discharging value. 3 minutes later after compressor startup, according to the discharging temp., the following procedure
will be taken:
Td90, SV2 close; Td110, SV2 open. In 150 seconds when compressor stops, in order to keep the system in balanc, please open the liquid
spray valve SV2. 150 seconds later after compressor stops, SV2 close.
3.7 Control of defrosting in heating
In heating mode, defrosting temp. sensor will check the frosting condition of outdoor heat exchanger and
make defrosting control.
3.7.1 Enter condition: In heating mode, if the compressor has run for 10 minutes continously and run for 45 minutes in all, the
system will measure the defrosting temperature sensor Te and outdoor ambient temp. sensor TA, if the
below condition can be met for continous 5 minutes, the unit will enter defrosting operation:
Te ≤C×TA-α
Herein: C:TA<0℃,C=0.8 TA≥0℃,C=0.6
According to SW2, the setting is as follow: in the place easy to frost, it is H; when out of factory, it is M.
Jumper
selection
M(out of factory) H
α()
8(E) 6(E)
Defrosting entering condition: -15℃≤C×TA-α≤-2℃ ③Stop and Pause condition of compressor running accumulative time in heating mode:
Checking Stop: running operation changes from heating to cooling.
Checking Pause: thermostat OFF, or the unit stops.
3.7.2 Cancel condition:
It will take the max. 10 minutes from beginning defrosting to quit it. Te sensor will measure the condition of outdoor heat exchanger, if the temp. is over 7 for 60 seconds in all or is up to 12 for 30 seconds in all,
the defrosting will be over.
3.7.3 Compulsory defrosting control
Enter condition: in heating mode, after receiving the compulsory defrosting signal from indoor unit, the unit
will perform the compulsory defrosting operation. Cancel condition: Te≥12℃ and keep for 1 minute or the defrosting time is over 10 minutes.
The manual defrosting signal of indoor unit will remain until the outdoor enters defrosting mode.
Note: When outdoor compressor not running, the unti still can enter manual defrosting, but it will comply
with the 3-minute protection of compressor.
-9
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
3-
3.8 Frequency control when Td is too high
Purpose: make compressor frequency control if the discharging temp. is too high, to lower the discharging
temp. efficiently and ensure the system can run normally.
beginning end
fixed frequency indicated FQY 60s defrosting FQY 80 Hz(E) 60s soft startup
compressor
0HZ 0HZ
5s
outdoor motor ON send defrosting signal to indoor Auto
OFF
4-way valve ON
OFF 15s
ON
Spray valve SV2 OFF
450-pulse 450-pulse
350-pulse(E)
all EEVs auto open angle auto open angle
all indoor motors ON
OFF anti-cold air function
Dischar
g
in
g
tem
p
. TD
If keeping for 10s, the unit stops, 3 minutes later, the unit can
re-startup. If in 60 minutesthe unit occurs alarm for 3 times, the
failure can be eliminated.
Reduce FQY rapidly 2HZ/S
Reduce FQY rapidly 1HZ/S
Reduce FQY slowly 1HZ/10S
Remain FQY
Increase FQY slowly 1HZ/10S
120
115
110
105
100
95
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
3.7.4 Defrosting operation flow chart
94-
3.9 Frequency control when there is CT over current protection
3.10 High pressure protection
When the input signal of pressure switch is high level:1, that shows there is no protection.
When the input signal of pressure switch is low level: 0 for 1 minute, that shows high pressure protection
works. At this time, compressor stops, outdoor will send the alarm signal. The alarm can be resumable. If
in 60 minutes, the failure occurs 3 times, the failure can be confirmed and send failure code to indoor.
Meanwhile, by controling the max. condensate temp. Tc (cooling) or TmAVE (heating), please confirm as
follow:
In nominal cooling/dry/heating mode, high pressure can be controlled by limiting the max. frequency.
3.11 Low pressure protection
(1) When compressor is running, if output signal of low pressure switch is low level: 0 for 1 minute
continously, compressor will stop,outdoor alarms. The alarm can be resumable. If in 60 minutes, the
failure occurs 3 times, the failure can be confirmed and send failure code to indoor.
(2) When compressor no running, if output signal of low pressure switch is low level: 0 for 30 seconds
continously, alarm will occur.
Co
n
de
n
s
in
g
t
e
m
p
.
Keep for 5 seconds, stop to alarm, after 3-minute standby, the
unit can restartup. In 3 minutes it occurs 3 times continously,
unit will stop to alarm and the failure can be resumed after being
electrified again.
Reduce FQY rapidly 2HZ/S
Reduce FQY rapidly 1HZ/S
Reduce FQY slowly 1HZ/10S
Remain FQY
Increase FQY slowly 1HZ/10S
1.0 I
0.95I
0.93I
0.90I
0.88I
0.85I
Stop immediately, if abnormal stop 3 times in 1 hour, the
unit will stop and alarm.
Reduce FQY rapidly 2HZ/S
Reduce FQY rapidly 1HZ/S
Reduce FQY slowly 1HZ/10S
Remain FQY
Increase FQY slowly 1HZ/10S
70
68
66
64
62
60
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
-95-
·When unit stops, the reason that system still checks the low pressure : in a long time stop, make
protection for the compressor on the condition of great refrigerant leakage.
·The reason that low pressure switch action time is 30 seconds: when compressor stops, low pressure
does not change, so it will be shorter than the set time in operation.
(3) When compressor starts up, in 8 minutes, low pressure switch signal will be shielded.
(4) In defrosting, low pressure switch will be shielded.
(5) In oil return procedure, low pressure switch will be shielded.
(6) In the refrigerant discharging procedure after the oil return in cooling is over, low pressure switch will
be shielded.
In addition, the system will control low pressure through the evaporator temp. TE to realize the low
pressure protection function.
In cooling, confirm through Tc2AVE:
In heating, confirm through defrosting temp. Te:
If the failure is not confirmed as the permanent protection, outdoor will not send failure code to indoor, and
indoor will not alarm.
TinAVE
-25
-30
-35
-40
-45
Normal operation
Min. running FQY 20HZ
SV2 OFF & 20HZ
SV2 ON & 20HZ
Keep for 5 seconds, unit stops and alarm
occurs. 3 minutes later, restart up. If i
t
occurs 3 times in 1 hour, it will always
alarm and stop, electrify again and failure
will be cleared.
Te
-30
-35
-40
-45
-50
Normal operation
Min. running FQY 20HZ
SV2 OFF & 20HZ
SV2 ON & 20HZ
Keep for 5 seconds, unit stops and
alarm occurs. 3 minutes later, restart
up. If it occurs 3 times in 1 hour, it will
always alarm and stop, electrify again
and failure will be cleared.
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
96-
CN19 CN4
CN3
CN2
CN20
CN21
CN1
CN22
CN11
SW1
SW2
SW3
CN16
Lamps 3,4
CN8
CN7
CN14 CN26CN24 CN13 CN12 CN10 CN15 CN9Lam
p
s 1
,
2
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
5.2 Indoor unit
5.2.1 AB,AD PCB photo
97-
5.2.2. Wiring Diagram
- -
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
CN3
CN2
CN21
CN1
FUSE1
T3.15A
250VAC
M
AC FAN
MOTOR
capacitor
2uF 450V
Y/G
L
N
Y/G
TO OUTDOOR
UNIT
CN20
CN4
W
CN19
W
M
DRAINING
PUMP MOTOR
CN22
G
CN24
R
CN14
W
CN13
B
CN12
W
CN10
W
float
switch
PIPING
TEMPERATURE
SENSOR
AMBIENT
TEMPERATURE
SENSOR
Tc1 Tc2 Tm
LED
CN15
Y
M
SWING
MOTOR
CN11
W
SW01 SW02 SW03
CN26
CN16
R
P
Q
BA
C
TO
OUTDOOR
UNIT
TRANSFORMER
B: BLACK BR: BROWN
R: RED W : WHITE
Y/G : YELLOW/GREEN
BL:BLUE Y:YELLOW
WIRED
CONTROLLER
please pull out the short-connector from
CN16 (default set from factory).The short
-connector is in the accessories.
CN7
W
CN8
BL
CN9
BL
ON
1
2
34567
8 8
7
6
543
2
1 1
2
345
6
7
8
WIRED
CONTROLLER
INFRARED
CONTROLLER
SW03-4
ON
ON/OFF
CARD
ON
SW03-4
9000
BTU
12000
BTU
18000
BTU
14000
BTU
ON
SW03-1 SW03-2 SW03-3
SW03-1
ON
SW03-3SW03-2
SW03-2 SW03-3
ON
SW03-1
SW03-1
ON
SW03-3SW03-2
please plug in the short-connector to CN16
CN18
BR BL
A
B
C
ON ON
BL Y
BR R
0R
OR: ORANGE
AB*XCERA:
AB, AD
98
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
AD***XLERA
CN3
CN2
CN21
CN1
FUSE1
T3.15A
250VAC
M
AC FAN
MOTOR
Y/G
L
N
Y/G
TO OUTDOOR
UNIT
CN20
CN4
CN19
W
W
G
CN22
R
CN24
W
CN14 CN13
B W
CN12 CN10
W
Tm
PIPING
TEMPERATURE
SENSOR
AMBIENT
TEMPERATURE
SENSOR
TC2TC1
CN15
Y
CN11
SW01 SW02 SW03
W
CN26
R
CN16
W
P
Q
BA
C
TO
OUTDOOR
UNIT
TRANSFORMER
B: BLACK BR: BROWN
R: RED W : WHITE
Y/G : YELLOW/GREEN
BL:BLUE Y:YELLOW
OR
ORANGE
WIRED
CONTROLLER
alternative)
CN7
W
BL
CN8
CN9
BL
ON
1
2
34567
8 8
7
6
543
2
1 1
2
34567
8
ON/OFF
CARD
9000
BTU
12000
BTU
18000
BTU
14000
BTU
ON
SW03-1 SW03-2 SW03-3
SW03-1
ON
SW03-3SW03-2
SW03-2 SW03-3
ON
SW03-1
SW03-1
ON
SW03-3SW03-2
CN18
BR BL
A
B
C
ON ON
BR
R
BL
Y
OR
WIRED
CONTROLLER
(default set
from factory)
99-
5.2.3. AC142-182XCERA PCB Photo
CN20
Lamp 3,4
CN1
CN3
CN21
CN6
CN5
CN4
CN12
SW2
CN7
SW3
CN15
CN26
Lamp 1,2
CN22
SW1
CN8
CN24CN10 CN14 CN13
CN2
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
100-
Loading...