Haier AD282AHERA user guide manual

No. 0010578121
B
DUCT TYPE AIR CONDITIONER
AD282AHEAA AD362AHEAA AD482AHEAA AD602AHEAA
AD282AHERA AD362AHERA AD482AHERA AD602AHERA
Operation & Instruction Manual
Please read this operation manual before using the air conditioner.
1
Table of Contents
Malfunction
7- 8
Care and Maintenance
9
For Preparation of Heating( "Hot Keep")
10
Is The Unit Installed Correctly
11
Installation Manual For Indoor Unit
12-20
Installation Manual For Electric Wiring
21
Safety Precautions
3-5
Parts and Functions
6
Cautions
2
Trouble Shooting
22-23
Cautions
2
All electrical ropairs must be carried out by qualified electricians. Inadequate repairs may result in a major source of danger for the user of the air conditoiner.
Do not damage any parts of the air conditioner that carry refrigerant by piercing or perforating the air conditioner's tubes with sharp or pointed items, crushing or twisting any tubes, or scraping the coatings off the surfaces. If the refrigerant spurts out and gets into eyes, it may result in serious eye injuries.
Do not obstruct or cover the ventilation grille of the air conditioner. Do not put fingers or any other things into the inlet/outlet and swing louver.
Do not allow children to play with the air conditioner. In no case should children be allowed to sit on the outdoor unit.
Disposal of the old air conditioner
Before disposing an old air conditioner that goes out of use, please make sure it's inoperative and safe. Unplug the air conditioner in order to avoid the risk of child entrapment.
It must be noticed that air conditioner system contains refrigerants, which require specialized waste disposal. The valuable materials contained in a air conditioner can be recycled. Contact your local waste disposal center for proper disposal of an old air conditioner and contact your local authority or your dealer if you have any question. Please ensure that the pipework of your air conditioner does not get damaged prior to being picked up by the relevant waste disposal center, and contribute to environmental awareness by insisting on an appropriate, anti-pollution method of disposal.
Disposal of the packaging of your new air conditioner
All the packaging materials employed in the package of your new air conditioner may be disposed without any danger to the environment.
The cardboard box may be broken or cut into smaller pieces and given to a waste paper disposal service. The wrapping bag made of polyethylene and the polyethylene foam pads contain no fluorochloric hydrocarbon.
Consult your local authorities for the name and address of the waste materials collecting centers and waste paper disposal services nearest to your house.
Safety Instructions and Warnings
important observations relating to the assembly, operation and maintenance of the air conditioner.
Installation shall be done by professional people, don't install unit by yourself.
All these valuable materials may be taken to a waste collecting center and used again after adequate recycling.
Damaged air conditioners are not to be put into operation. In case of doubt, consult your supplier.
Use of the air conditioner is to be carried out in strict compliance with the relative instructions set forth in the User's Guide.
For the purpose of safety, the air conditioner must be properly grounded in accordance with specifications.
Always remember to unplug the air conditioner before opening inlet grill. Never unplug your air conditioner by pulling on the power cord. Always grip plug firmly and pull straight out from the outlet.
The manufacturer does not accept responsibility for any damages that may arise due to non-observation of the following instruction.
Before starting the air conditioner, read the information given in the User's Guide carefully. The User's Guide contains very
Safety Precations
Before starting to use the system, read carefully this"SAFETY PRECAUTIONS" to ensure a proper operation of the system.
Safety precautions described here are classified to " WARNING" and " CAUTION". Precautions which are shown in the column of " WANING" means that an improper handing could lead to a grave result like a death, serious injury, etc. However, even if precautions are shown in the column of " CAUTION", a very serious problem could occur depending on situation. Make sure to observe these safety precautions faithfully because they are very important information to ensure the safety.
Symbols which appear frequently in the text have following meanings.
Strictly prohibited.
Observe instructions faithfully.
Provide a positive grounding.
When you have read through the manual, keep it always at hand for read consultation. If the operator is replaced, make sure to hand over this manual to the new operator.
ON
OFF
WARNING
CAUTION
WARNING
CAUTION
CAUTIONS FOR INSTALLATION
The system should be applied to places as office, restaurant, residence and the like.
The system should be installed by your dealer or a professional installer.
When you need some optional devices such as a hu­midifier, electric heater, etc., be sure to use the products which are recommended by us. These devices should be attached by a professional installer.
Application to inferior environment such as an engi neering shop, could cause equipment malfunction and serious injury or death.
Installation by yourself is not encouraged because it could cause such problems as water leakage, electrical shock or fire accident by some improper handing.
Installation by yourself is not encouraged because it could cause such problems as water leakage, electrical shock or fire accident by some improper handing.
Do not install nearby the place where may have leakage of flammable gas.
Depending on the place of installation, a circuit breaker may be necessary.
Drain pipe should be arranged to provide a positive draining.
If the gas leakes and gathers around, it may cause the fire.
Unless the circuit breaker is installed, it could cause elecrical shocks.
Where strong winds may prevail, the system should be fixed securely to prevent a collapse.
Install on the place where can endure the weight of air conditioner.
Make sure the system is grounded.
If the pipe is arranged improperly, furniture or the likes may be damaged by leaked water.
Bodily injury could result by a collapse.
Bodily injury could result by a careless installation.
Grounding cable should never be connected to a gas pipe, city water pipe, lightning conductor rod or grounding cable of telephone. If the grounding cable is not set properly, it could cause electric shocks.
CAUTIONS FOR OPERATION
You should refrain from exposing your body directly to cool wind for a long time.
Do not poke the air inlet or outlet with a bar, etc.
When any abnormal condition (scorching smell or oth­ers) is found, stop the operation immediately and turn off the power switch. Then consult your dealer.
It could affect your physical condition or cause some health problems.
Since the internal fan is operating with a high speed, it could cause an injury.
If you continue the operation without removing the cause, it could result in a trouble, electric shock or fire.
The system should never be used for any other purposes than intended such as for preservation of food, flora and fauna, pre­cision deices or work of art.
Do not handle switches with a wet hand.
Combustion apparatus should not be placed allowing a direct exposure to wind of air con­ditioner.
Incomplete combustion could occur on the apparatus.
It could cause electric shocks.
It could cause deterioration of food or other problems.
3
Safety Precautions
4
CAUTION
Do not wash the air conditioner with water.
Do not install the system where the air outlet reaches directly the flora and fauna.
Make sure to use a fuse of proper electric rating.
Do not operate the system while the air outlet grill is removed.
It is strictly prohibited to place a container of combustible gas or liquid near the air condi­tioner or to spray it directly with the gas or liquid.
Neither stand on the air conditioner nor place something on it.
Do not use the power switch to turn on or off the system.
Do not touch the air outlet section while the swing louver is operating.
Do not use such equipment as a water heater, etc. around the indoor unit or the wire controller.
ON
OFF
It could cause electric shocks.
It will not be good for their health.
Use of steel or copper wire in place of a fuse is strictly prohibited because it could result in a trouble or fire accident.
There is a risk of injury.
It could cause a fire accident.
There are risks of falling or injury by collapsed object.
It could cause a fire or water leakage. There is a risk of injury.
If the system is operated at the vicinity of such equip­ment which generates steam, condensed water may drip during cooling operation or it could cause a fault current or short-circuit.
When operating the system simultaneously with a combustion apparatus, indoor air must be ventilated frequently.
Check occasionally the support structure of the unit for any damage
after a use of long
period of time.
Insufficient ventilation could cause an oxygen deficiency accident.
If the structure is not repaired immediately, the unit could topple down to causea personal injury.
When cleaning the system, stop the operation and turn off the power switch.
Do not put water containers on the unit such as a flower vase, etc.
Cleaning should never be done while the internal fans are running with high speed.
If the structure is not repaired immediately, the unit could topple down to cause apersonal injury.
WARNING
CAUTIONS FOR TRANSFER OR REPAIR
Modification of the system is strictly prohibited. When the system needs a repair, consult your dealer.
When the air conditioner is relocated, contact your dealer or a pro­fessional installer.
Improper practice of repair could cause water leakage, electric shock or fire. Improper practice of installation could cause water leakage, electric shock or fire.
Do not place any objects on or climb on the unit.
Do not try to repair or reconstruct by yourself.
5
1. Applicable ambient temperature range:
The machine is adaptive in following situation
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent
or a similar qualified person.
3. If the fuse on PC board is broken please change it with the type of T 3.15A /250VAC.
4. The wiring method should be in line with the local wiring standard.
5. The power cable and connecting cable are self-provided.
The connecting cable should be H05RN-F 4G 0.75mm
2
.
All the cables shall have got the European authentication certificate. During installa-
tion, when the connecting cables break off, it must be assured that the grouding wire is
the last one to be broken off.
6. The breaker of the air conditioner should be all-pole switch; and the distance between its
two contacts should be no less 3mm.
7. The indoor unit installation height is at least 2.5m.
Safety Precautions
outdoor ambient temp.
operation mode
recommended fan speed
> 40¡
< 20¡
< -5¡
> 18¡
cooling
cooling
heating
heating
low
high
low
high
8. In order to obtain the Unit's best performances, the fan speed is recommended according
to the following conditions.
Rated Maximum Minimum 27 32 18 19 23 14 35 43 10 24 26 6 20 27 15
14.5 7 24 7 6 18
Cooling
Heating
Indoor
outdoor
Rated Maximum Minimum 27 32 18 19 23 14 35 43 5 24 26 20 27 15
14.5 7 24 7 6 18
DB C WB C DB C WB C
Indoor
outdoor
DB C WB C
DB C WB C
For *EAA :
For *ERA :
Cooling
Heating
Indoor
outdoor
DB C WB C DB C WB C
Indoor
outdoor
DB C WB C
DB C WB C
6
Indoor Unit
Air outlet
Air inlet
Duct
Duct
Drainpipe
Parts and Functions
please check the following things about your air conditioner before making a servie call.
Unit fails to start
ON
OFF
Is the power source switch adjust cut in?
Is city supply power in normal?
Power stoppage?
Isn't the signal receiving section exposed to the direct sunlight or strong illumination?
Isn't the earth leakage breaker in action?
It is dangerous. Turn off the power supply switch immediately and contact the sales dealer.
Power supply switch is not ON.
Cooling or heating is not sufficient
Is the thermostat adjust as required?
Isn't the air filter dirty?
Isn't any doors or windows left open?
Doesn't any obstacle exist at the air inlet or outlet?
Cooling is not sufficient
Isn't sun shine invading direct?
Isn't any unexpected heating load generated?
Isn't the room much crowded?
Isn't the swing louver horizontal? (At HEATING mode)
If swing louver is horizontal, the blow wind does not reach floor.
The wind does not blow during heating operation
Isn't it warming up?
When the air conditioner does not operate properly after you have checked the above mentioned items or when the following phenomenon is observed, stop the operation of the air conditioner and contact your sales dealer.
The fuse or breaker often shuts down. Water drops off during cooling operation. There is a irregularity in operation or abnormal sound is audible. When the CHECK LED1 (red) flickers, an irregularity has occurred in the air conditioner.
Malfunction
7
8
The followings are not malfunction
Shuru
Shuru
When the air conditioner is started, when the compressor starts or stops during operation or when the air conditioner is stopped, it sometimes sounds "shuru shuru" or "gobo gobo". It is the flowing sound of the refrigerant, and it is not a trouble.
Water flowing sound is heard.
This is caused by heat expansion or contraction of plastics.
Cracking sound is heard.
It smells.
Air which blows out from the indoor unit sometimes smells. The smell results from residents of tobacco smoke or cosmetics stuck inside of unit.
When the air conditioner is used at restaurant etc. where dense edible oil fume is always exists, white fog sometimes blows out of air outlet during operation. In this case consult sales dealer for cleaning the heat exchanger.
During operation, white fog comes out of indoor unit.
Unit does not start
Wait for three minutes
It is switched into the FAN mode during cooling.
To prevent frost from being accumulated on the indoor unit heat exchanger, it is sometimes automatically switched to the FAN mode but it will soon return to the cooling mode.
Even if the operation switch is turned on, cooling, dehumidifying or heating is not operable for three minutes after the conditioner is stopped. Because the protecting circuit is activated. (During this time air conditioner operates in fan mode.)
The air conditioner can not be restarted soon after it stops.
Air does not blow or the fan speed can not be changed during dehumidifying
During operation, operation mode has changed over automatically.
Water or steam generates from the outdoor unit during heating.
When it is excessively cooled during dehumidifying, the blower automatically repeats reducing and lowering the fan speed.
Isn't the AUTO mode selected? In the case of AUTO mode, operation mode is changed automati cally from cooling to heating or vise versa according to the room temperature.
This results when frost accumulated on the outdoor unit is removed (during defrosting operation).
Malfunction
9
Points to observe
Turn off the power supply switch. Do not touch with wet hand.
Do not use hot water or volatileliquid.
ON
OFF
Thinner
Do not use!
Benzine
Tooth powder
Cleaning
CAUTION
Do not dry the air filter with fire. Do not run the air conditioner without the air filter.
Do not open the inlet grill until fan stops completely. Fan will continue rotating for a while by the law of inertia after operation is being stopped.
CAUTION
Pre-Season Care
See that there are no obstacles blocking the air inlet and air outlet of both indoor and outdoor units. Make sure that the air filter is not dirty. Cut in the power supply switch 12 hours before starting run.
Post-Season Care
Operate the unit with FAN mode on a fair day for about half a day to dry the inside of the unit well. Stop operation and turn off the power supply switch. Electric power is consumed even the air conditioner is in stop. Clean the air filter and set it in the place.
Care and Cleaning of the unit
Clean with soft and dry cloth. If it is very dirty, dissolve neutral detergent in the lukewarm water and make the cloth wet with the water. After wiping, clean off the detergent using clean water.
Care and Maintenance
10
"HOT KEEP"is operated in the following cases.
When heating is started:
In order to prevent blowing out of cool wind, the indoor unit fan stopped
according to the room temperature which heating operation is started. Wait
for approx. 2 to 3 minute, and the operation will be automatically changed
to the ordinary heating mode.
Defrosting operation (in the heating mode):
When it is liable to frost. the heating operation is stopped automatically
for 5 to 12 minutes once per approx. one hour, and defrosting is operated.
After defrosting is completed, operation mode is automatically changed
to ordinary heating operation.
When the room thermostat is actuated:
When room temperature increases and room temperature controller actu
ates, the fan speed is automatically changed to stop under low temperature
condition of indoor heat exchanger. When room temperature decreases,
air conditioner automatically changes over to ordinary heating operation.
WARMING OPERATION
Heat pump type warming
Defrosting operation
Atmospheric temperature and warming capacity
Period of warm-up
With the heat pump type warming, the mechanism of heat pump that concentrate heat of outdoor
air with the help of refrigerant to warm the indoor space, is utilized.
When a room is warmed with a heat pump type air conditioner, frost accumulates on the heat ex
changer of outdoor unit along with the drop of indoor temperature. Since the accumulated frost re
duces the effect of warming, it is necessery to automatically switch the operation to the defrosting
mode. During the defrosting operation, heating operation is interrupted.
Warming capacity of heat pump type air conditioner decreases along with the
drop of outdoor temperature.
When the warming capacity is not sufficient, it is recommended to use another
heating implement.
Since the heat pump type air conditioner employs a method to circulate warm
winds to warm the entire space of a room, it takes time before the room tem
perature rises.
It is recommendable to start the operation a little earlier in a very cold morning.
For Preparation of Heating("Hot Keep")
11
For inspection and maintenance
When you change your address or the installation place
Electric work
Confirm the following items for safe and comfortable use of air conditioner. The installation work is to be burden on the sales dealer, and do not conduct it by yourself.
Installation place
Avoid installing the air conditioner near the place where possibility of inflammable gas leakage exists.
Install the unit at well ventilated place.
Install the air conditioner firmly on the foundation that can fully support the weight of the unit.
If not, it may cause vibration or noise.
If some obstacle exist, it may cause capacity reduction or noise increase.
Explosion (Ignition) may occur.
Select the place so as not to annoy neighbor with the hot air or noise.
Snow protection work is necessary where outdoor unit is blocked up by snow.
It is advisable not to install the air con­ditioner at the following special place. It may cause malfunction, consult the sales dealer when you have to install the unit on such a place.
The place where corrosive gas generates (Hot spring area etc.) The place where salt breeze blows (Seaside etc.) The place where dense soot smoke exists The place where humidity is extraordina­rily high The place where near the machine which radiates the electromagnetic wave The place where voltage variation is con­siderably large
For details consult your sales dealer.
The electric work must be burden on the authorized engineer with qualification for electric work and grounding work, and the work must be conducted in accordance with electric equipment technical standard.
The power source for the unit is to be of exclusive use. An earth leakage breaker should be installed.(This is necessary to prevent electric shock.) The unit must be grounded.
Special technology is required for removal or reinstallation of air conditioner, consult the sales dealer. Besides, construction expense is charged for removal or reinstallation.
The capacity of air conditioner will decrease by contamination of inside of unit when it is used for about three years although depending upon the circumstances under which it is used, and so in addition to the usual maintenance service, special inspection/maintenance service is necessary. It is recommended to make a maintenance contract (charged) by consulting your sales dealer.
Is The Unit Installed Correctly
12
1. Safety precautions
WARNING
Please read these "Safety Precautions" first then accurately execute the installation work. Though the precautionary points indicated herein are divided under two headings, and , those points which are related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the section. However, there is also a possibility of serious consequences in relationship to the points listed in the section as well. In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned. After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please explain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner's manual. Moreover, ask the customer to keep this sheet together with the owner's manual.
This system should be applied to places as office, restaurant, residence and the like. Application to inferior environment such as engineering shop could cause equipment malfunction. Please entrust installation to either the company which sold you the equipment or to a professional contractor. Defects from improper installations can be the cause of water leakage, electric shocks and fires. Execute the installation accurately, based on following the installation manual. Again, improper installations can result in water leakage, electric shocks and fires. When a large air-conditioning system is installed to a small room, it is necessary to have a prior planned countermeasure for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration. In regards to preparing this countermeasure, consult with the company from which you perchased the equipment, and make the installation accordingly. In the rare event that a refrigerant leakage and exceeding of threshold concentration does occur, there is the danger of a resultant oxygen deficiency accident. For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient, injury can result from a falling of the unit. Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and hurricanes, etc. Improper installations can result in accidents due to a violent falling over of the unit. For electrical work, please see that a licensed electrician executes the work while following the safety standards related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive use circuits are used. Insufficient power source circuit capacity and defective installation execution can be the cause of electric shocks and fires. Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to the terminal connection part, through properly securing it. Improper connection or securing can result in heat generation or fire. Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper installation can also result in heat generation or fire. When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated refrigerant (R410A) within the refrigeration cycle. Rupture and injury caused by abnormal high pressure can result from such mixing. Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this company can result in water leakage, electric shock, fire and refrigerant leakage.
CAUTION
WARNING
WARNING
CAUTION
CAUTION
Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightning rod or a telephone ground wire. Improper placement of ground wires can result in electric shock. The installation of an earth leakage breaker is necessary depending on the established location of the unit. Not installing an earth leakage breaker may result in electric shock. Do not install the unit where there is a concern about leakage of combustible gas. The rare event of leaked gas collecting around the unit could result in an outbreak of fire. For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
Installation Manual For Indoor Unit
13
1. Before installation [Before finishing installation, do not throw the attached parts installation needs]
NOTICE
All Wiring of this installation must comply with NATIONAL, STATE AND LOCAL REGULATIONS. These instructions do not cover all variations for every kind of installation circumstance. Should further information be desired or should particular problems occur, the matter should be referred to your local distributor.
WARNING
BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION. FAI­LURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH, EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE.
Confirm the way to move the unit to the installation place. Before moving the unit to the installation place, do not remove their packages. When have to remove the package, use a soft material or protection board with rope to lift the unit
assembly to avoid unit damage or bumping a scrape.
2. Choose installation place
(1) The chosen installation place should meet the following requirements and get the users consent.
Place ensures ideal airflow distribution. The passage of airflow has no obstacles. When importing outside air, it should be imported directly from outdoors. (if the pipe can not be
extended, it also can not be imported from top)
Place ensures enough space for maintenance. The pipe length between indoor and outdoor unit is in the permitted limit (referring to outdoor unit
installation part).
The indoor unit, outdoor unit, electric wire and connection wire is at least 1m away from television and radio. This is to avoid the image disturbance and noise caused by the above mentioned home appliance. (Even if 1m away, if the electromagnetic wave is too strong, it can also cause noise.)
(2) The height of ceiling
The indoor unit can install on the ceiling, which height is no more than 3m.
(3) Install and use the hoisting screw. Check if the installation place can bear the weight of unit assembly.
If not certain, strengthen it before install the unit.
(600x600)
Over 100
Over 900
Air out
Air in
Checking meatus
Ceiling
Over 300
Over 200
Installation Manual For Indoor Unit
14
(1) The position relation among hoisting screw (unit: mm)
(3) Hanger bolts installation
Use care of the piping direction when the unit is installed.
Hanging bolt M10
Hole-in anchor Hole-in plug
Insert
Concrete
360
890
250
794
600
750
Down side
Up side
360
1270
250
794
853853
1103
Down side
Up side
(2) If necessary, cut the opening installation and checking needed on the ceiling. (If has ceiling)
Before installation, finish the preparation work of all the pipes (refrigerant, drainage) and wire (wire controller connection wire, indoor and outdoor unit connection wire) of indoor unit, so that after installation, they can be immediately connected with outdoor unit.
Cut the opening on the ceiling. Maybe it needs to strengthen the ceiling to keep the ceiling even and flat and prevent the ceiling from vibration. For details, please consult to the builder.
(Use M10 screw bolt)
In order to bear the weight of the unit, for existed ceiling, using foundation screw bolt, for new ceiling, using burying embedded screw bolt, burying screw bolt or spot supplied other parts.
Before going on installation, adjust the gaps with ceiling.
3. Preparation before installation
AD282AHEAA AD282AHERA AD362AHEAA
AD362AHERA AD482AHEAA AD482AHERA AD602AHEAA AD602AHERA
Installation Manual For Indoor Unit
15
4. Installation of indoor unit
Fix the indoor unit to the hanger bolts. If required, it is possible to suspend the unit to the beam, etc. Directly by use of the bolts without using the hanger bolts.
When the dimensions of main unit and ceiling holes does not match, it can be adjusted with the slot holes of hanging bracket.
Note
Adjusting to the levelness
(a) Adjust the out of levelness using a level or by the following method.
Make adjustment so that the relation between the lower surface of the unit proper and water level in the hose becomes as given below.
(b) Unless the adjustment to the levelness is made properly, malfunctioning or failure of the float switch may occur.
PVC hose
Piping side
Supply water
Water level
0~5 mm
(0~0.2")
Bring the piping side slightly lower.
Hanging bolt
M10 nut
Main unit
M10 washer
M10 spring washer
Drain hose
Stage difference part
Drain socket
Drain socket
Main unit
VP 25 joint (field purchased)
Pipe cover(large) [for insulation] (accessory)
VP 25 (field purchased)
Pipe cover [for insulation] (field purchased)
Drain hose (accessory)
Pipe cover(small) [for insulation] (accessory)
Clamp (accessory)
Adhesion
For drain pipe, use hard PVC general purpose pipe VP 25(I.D.1") which can be purchased locally. When connecting, insert a PVC pipe end securely into the drain socket before tightening securely using the attached drain hose and clamp. Adhesive must not be used connection of the drain socket and drain hose (accessory).
(c)
5. Drain Piping
(a) Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding across an elevation or making traps.
When connecting the drain pipe to unit, pay suffcient attention not to apply excess force to the piping on the unit side. Also, fix the piping at a point as close as possible to the unit.
Do not pipe under water
Keep free from traps
Avoid riding across an elevation
Air vent
Improper piping
Good piping
1.5m ~ 2m
Suspension bolts
Heat insulation
A downhill grade of 1/100 or more
(b)
Installation Manual For Indoor Unit
16
Drainage Test
Conduct a drainage test after completion of the electrical work. During the trial, make sure that drain flows properly through the piping and that no water leaks from connections. In case of a new building, conduct the test before it is furnished with the ceiling. Be sure to conduct this test even when the unit is installed in the heating season.
Procedures
Supply about 1000 cc of water to the unit through the air outlet using a feed water pump. Check the drain while cooling operation.
(g)
1
2
3
4
1
2
VP 30
Secure the elevation as high as possible (approx. 100 mm)
A downhill grade of 1/100 or more
When constructing drain piping for several units, position the common pipe about 100 mm below the drain outlet of each unit as shown in the sketch. Use VP 30(11/4") or thicker pipe for this purpose.
(d)
(e)
The stiff PVC pipe put indoor side should be heat insulated.
(f)
Avoid putting the outlet of drain hose in the places with irritant gas generated. Do not insert the drain hose directly into drainage, where the gas with sulfur may be generated.
Backwater bend Because
the drain spout is at the position, which negative pressure may occur. So with the rise of water level in the drain pan, water leakage may occur. In order to prevent water leakage, we designed a backwater bend.
The structure of backwater bend should be able to be cleaned. As the below figure shown, use T type joint. The backwater bend is set near the air conditioner.
As figure shown, set a backwater bend in the middle of drain hose.
H
1
H
2
H1=100mm or the static pressure of air sending motor H2=1/2H1 (or between 50~100mm)
6. Installation of air suction and discharging duct
A
Insulation
muffler cavity (air sending)
Sacking joint
Air volume adjuster
Air outlet
Enlarging chart of profile chart A
Vibration resistance hook
Checking meatus
Air conditioner main unit
Ceiling
Air suction grille with air filter
Please consult the after sales service worker of Haier Air Conditioner for the choosing and installation of suction inlet, suction duct, discharging outlet and discharging duct. Calculating the design drawing and outer static pressure, and choose the discharging duct with proper length and shape.
Installation Manual For Indoor Unit
17
The calculation of duct resistance (the simple calculation is as follow table)
Straight part
Bend part
Air out part
Static pressure box
Air inlet grille (with air filter)
Calculate as per 1m length 1Pa, 1Pa/m
Each bend takes as a3~4m long straight duct
Calculate as 25Pa
Calculate as 50Pa/each
Calculate as 40Pa/each
Good exampleBad exampleBad example
The length difference among every duct is limited below 2:1. Reduce the length of duct as possible as can. Reduce the amount of bend as possible as can.
Use heat insulation material to bind and seal the part connecting main unit and the flare part of air discharging duct. Perform duct installation work, before the fitment of ceiling.
7. Calculation method of the dimension of the simple quadrate air duct
Presuming the unit length friction impedance of the duct is 1Pa/m, when the dimension of one side of the air duct is fixed as 250mm, as shown below:
Note:1Pa/m=0.1mmAg/m
The chosen chart of simple duct
m3/h(m3/n)
100 200 300 400 500 600(10)
800 1,000 1,200(20)
250 x 60
(mmxmm)
250 x 90 250 x 120 250 x 140
250 x 170 250 x 190 250 x 230 250 x 270 250 x 310
Shape
Item
Air volume
Square duct
Dimension
m3/h(m3/n)
1,400 1,600
1,800(30) 2000 2400 3,000(50) 3,500 4,000 4,500 5,000 5,500 6,000(100)
(mmxmm)
250 x 350 250 x 390
250 x 430 250 x 470 250 x 560 250 x 650 250 x 740 250 x 830 250 x 920 250 x 1000 250 x 1090 250 x 1180
Shape
Item
Air volume
Square duct
Dimension
Static pressure box
Air conditioner
Equipped with air filter (bought)
B
A
A
A
Installation Manual For Indoor Unit
600m3/h (10m
3
/min)
Duct
(mmxmm)
2400m3/h (40m3/min)
250x560
250x190
Air volume
B
A
AD362AHERA AD482AHEAA AD482AHERA AD602AHEAA AD602AHERA
Duct
(mmxmm)
Air volume
300m3/h (5m3/min)
1200m
3
/h
(20m3/min)
250x310
250x120
AD282AHEAA AD282AHERA AD362AHEAA
18
8. The attentive matters in installation of air suction and discharging duct
Recommend to use anti frost and sound absorbing duct. (locally bought) The duct installation work should be finished before the fitment of ceiling.
The duct must be heat insulated.
The specific air discharging outlet should be installed at the place where the airflow can be reasonably distributed.
The surface should leave a checking meatus for checking and maintenance.
9. The examples of improper installation
Do not use air in duct and take the ceiling inner side instead. The result is because of the irregular outer air mass, strong wind and sunshine, the humidity is increased.
There may be water drop on the outside of duct. For cement and other new constructions, even if not taking ceiling inner side as duct, the humidity will also be so high. At this time, use glass fiber to perform heat preservation to the whole. (use iron net to bind the glass fiber)
Affected by the capacity of air discharging fan, the strong wind in the outer duct and wind direction, when unit air sending volume exceeds the limit, the discharged water of heat exchanger will overflow, leading to water leakage.
Air
Air
Duct
Special air discharging outlet
Use screw bolt to fix
Air discharging fan
Improper example
Installation Manual For Indoor Unit
19
10. The operation method of fan controller
Through the fan controller switch in the electric box, the air volume of this unit can be continuously adjusted. It is unnecessary to adjust air volume through the duct side wind level (unit outside static adjustment). The air volume set should be in the operation air volume range.
Figure I shows the position of fan controller in the electric box and operation method.
After finishing the electric work, perform test run. According to the main points in Figure II making the chosen switch No. accordant. And confirm if it reaches the needed air volume.
Note:
1) When operating the fan controller, it is possible to touch the electric charging part, so do cut off the power supply.
2) Do not set the dial at the position less than 1.
3) The figure circled in Figure 2 indicate the capacity number of fan controller( for AD482AHEAA). The
non listed capacity number may exceed the permitted operation capacity range, so it is impossible to
operate.
4) When delivering from factory, the capacity number of fan controller is set at No.5.
Rotate this switch
(capacity number setting: No. 1 ~ No. 8)
Once the fan controller has trouble, this linker can perform emergency assistant control. When this linker is connected to the linker from the PCB, it can operate with total load.
When this linker is connected to the linker from the PCB, through the fan speed adjustment panel to adjust speed.
High
Condition of standard air volume
Low
(air volume 100Pa)
Outer static pressure Pa
Example of duct
Lower limit
Upper limit
Standard air volume
(m3/min)
The example of the method of choosing capacity number:
1) If the unit is in high-speed operation, needing take outer static pressure is 180Pa in capacity air volume 34m3/min as working condition point, according to Figure II The characteristic chart of air volume, the capacity number of fan controller is No. 2.
2) If the unit is in low speed operation, needing take outer static pressure is 60Pa in capacity air volume 32m
3
/min as working condition point, according to Figure II The characteristic chart of air volume, the capacity number of fan controller is No. 4.
Installation Manual For Indoor Unit
200
150
100
50
0
26 30 34 35 40 43
*
*
*
*
*
*
*
*
*
*
*
*
*
*
Figure 1
Figure 2
20
11. Refrigerant pipe
[The air side pipe, liquid side pipe must be faithfully heat insulated, if no heat insulation, it may cause water leakage.]
The outdoor unit has been charged with refrigerant. When connect the pipe to the unit or dismantling the pipe from the unit, please follow the figure shown,
use spanner and torque spanner together. When connect cone nut, the inner side and outside of cone nut should paste with refrigerant oil. Use
hand to twist 3 4 rings, then fasten with spanner.
Referring to Table I to confirm the fasten torque. (too tight may damage nut leading to leakage) Check if the connection pipe leaks, then do heat insulation treatment, as below figure shown. Only use seal cushion to bind the joint part of air pipe and heat insulation parts.
Paste the refrigerant oil here
Torque spanner
Spanner
Pipe joint
Cone nut
Middle size seal cushion (accessory)
(Use seal cushion to bind the pipe joint)
Clamp
Heat insulation (accessory)
(for liquid pipe)
(for gas pipe)
Heat insulation (accessory)
Gas pipe
Liquid pipe
Liquid pipe
Gas pipe
Electric box
Upper
Air inlet
Air outlet
Down side
Drain hose connection mouth VP25 PVC pipe
9.52
12.0~12.4
18.6~19.0
3270~3990 N.cm (333~407 kgf.cm)
6180~7540 N.cm (630~770 kgf.cm)
(mm)
Specification of pipe
15.88
Tighten torque
Cone
Cone dimension A (mm)
R0.4~0.8
A
90 0.5
45 2
Installation Manual For Indoor Unit
22.9~23.3
9720~11860 N.cm (990~1210 kgf.cm)
19.05
310
30
530
80 510
21
5. Electric wiring
WARNING
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
(1) Selection of size of power supply and interconnecting wires.
Precautions for Electric wiring
Electric wiring work should be conducted only by authorized personnel. Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated grip on the ends of the wires. Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.)
(2) Wiring connection
Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by terminals.
Item
Model
Phase
3
Switch breaker
(A)
Circuit breaker
Overcurrent protector
rated capacity (A)
Power source
wire size
(minimum)
(mm2)
30 20 2.5
Switch
breaker(A)
Earth leakage breaker
Leak
current(mA)
30 30
AD482AHEAA AD482AHERA AD602AHEAA AD602AHERA
AD282AHEAA AD362AHEAA AD362AHERA AD482AHEAA AD482AHERA AD602AHEAA AD602AHERA
AD282AHEAA AD282AHERA AD362AHEAA AD362AHERA AD482AHERA AD602AHERA
Installation Manual For Electric Wiring
301 40 30 6.0 40
AD282AHEAA AD362AHEAA AD362AHERA
3 30 20 4.0 30 30
AD282AHEAA AD282AHERA AD362AHEAA AD362AHERA AD482AHERA AD602AHERA
POWER SUPPLY:
1PH,220-230V~,50Hz
INDOOR UNIT TERMINAL BLOCK
L N
1 2 3
1 2 3
OUTDOOR UNIT TERMINAL BLOCK
Y/G
Y/G
OUTDOOR UNIT TERMINAL BLOCK
INDOOR UNIT TERMINAL BLOCK
POWER SUPPLY:
380-400V, 3N~,50Hz
R S T
N 1 2 3
1 2 3
Y/G
Y/G
Y/G
22
For remote
type, flash
times
1
2
3
4
5
6
8
9
10
11
12
13
15
17
18
19
20
Failure description
Indoor ambient temp. sensor failure
Indoor coil temp. sensor failure
Outdoor ambient temp. sensor failure
Outdoor coil temp. sensor failure/Compressor
discharging temp. sensor abnormal
Over-current protection /
Power supply abnormal
High/Low pressure abnormal
Communication between wired
controller and indoor abnormal
Communication between indoor and outdoor abnormal
Drainage system abnormal
Outside alarm signal input
Gas pipe temp. sensor abnormal
Temperature protection malfunction
EEPROM abnormal
Compressor overheat
Abnormal mode
Outdoor coil B(suction temp sensor-for MRV II)
Outdoor discharging B(oil temp sensor-for MRV II)
Reason
Sensor broken down or short circuit for more than 2m continuously
Sensor broken down or short circuit for more than 2m continuously
Sensor broken down or short circuit for more than 2m continuously
Sensor broken down or short circuit for more than 2m continuously
CT check abnormal 3 times in 30m
/Fault phase, short of phase, out of balance greatly
High pressure switch acts 3 times in 30m/Low pressure switch acts
in normal running
Communication abnormal for more than 4m continuously
Communication abnormal for more than 4m continuously
Float switch broken down for more than 25m continuously
Outside signal broken down for more than 10s
Sensor broken down or short circuit for more than 2m continuously
Solenoid valve act incorrectly 3 times continuously
EEPROM data missing
The discharging temperature is higher than 120degree
Indoor operation mode is different with the running indoor unit.
Sensor broken down or short circuit for more than 2m continuously
Sensor broken down or short circuit for more than 2m continuously
Remarks
Failure code
on wired
controller
01(01H)
02(02H)
74(4AH)
73(49H)
72(48H)
83(53H)
07(07H)
06(06H)
08(08H)
11(0BH)
03(03H)
13(0DH)
05(05H)
80(50H)
12(0CH)
75(4BH)
77(4DH)
For central
control,
failure code
01D
02D
11D
12D
10D
14D
06D
05D
21D
30D
20D
31D
17D
15D
23D
18D
15D
shows resumable fault,
shows it is not resumable fault.
Resumable if
lower than
100 degree
Error display (For *EAA series)
Trouble Shooting
23
Trouble Shooting
Resumable if
lower than 100
degree
For remote
type, flash
times1234
567
8
9
10111213141516
17
181920
21
Failure description
Indoor ambient temp. sensor failure
Indoor coil temp. sensor failure
Outdoor ambient temp. sensor failure
Outdoor coil temp. sensor failure
Over-current protection
High pressure abnormal
Power supply abnormal
Communication between wired
controller and indoor abnormal
Communication between indoor and outdoor abnormal
Drainage system abnormal
Outside alarm signal input
Gas pipe temp. sensor abnormal
Temperature protection malfunction
Discharging temp. sensor abnormal
EEPROM abnormal
Pressure abnormal(low pressure)
Compressor overheat
Abnormal mode
Outdoor coil B(suction temp sensor-for MRV II)
Outdoor discharging B(oil temp sensor-for MRV II)
SPDU module temperature protection
Reason
Sensor broken down or short circuit for more than 2m continuously
Sensor broken down or short circuit for more than 2m continuously
Sensor broken down or short circuit for more than 2m continuously
Sensor broken down or short circuit for more than 2m continuously
CT check abnormal 3 times in 30m
High pressure switch acts 3 times in 30m
Fault phase, short of phase, out of balance greatly
Communication abnormal for more than 4m continuously
Communication abnormal for more than 4m continuously
Float switch broken down for more than 25m continuously
Outside signal broken down for more than 10s
Sensor broken down or short circuit for more than 2m continuously
Solenoid valve act incorrectly 3 times continuously
Sensor broken down or short circuit for more than 2m continuously
EEPROM data missing
Low pressure switch acts in normal running
The discharging temperature is higher than 120degree
Indoor operation mode is different with the running indoor unit.
Sensor broken down or short circuit for more than 2m continuously
Sensor broken down or short circuit for more than 2m continuously
Spdu module temperature is too high
Remarks
Failure code
on wired
controller
01(01H)
02(02H)
74(4AH)
73(49H)
72(48H)
83(53H)
71(47H)
07(07H)
06(06H)
08(08H)
11(0BH)
03(03H)
13(0DH)
76(4CH)
05(05H)
84(54H)
80(50H)
12(0CH)
75(4BH)
77(4DH)
20(32D)
For central
control,
failure code
01D
02D
11D
12D
10D
14D
22D
06D
05D
21D
30D
20D
31D
15D
17D
26D
15D
23D
18D
15D
07D
shows resumable fault, shows it is not resumable fault.
Error display ( For *ERA series )
HAIER GROUP Qingdao Haier Air Conditioner Electric Co., Ltd. Address: Haier Garden, Qianwangang Road, Economic Development Zone, Qingdao, Shandong 266555, P.R.China Web Site: http://www.haier.com