Haier AB072FDBHA, AB122FDAHA, AB092FDAHA, AB092FDBHA, AB122FDBHA Installation Manual

...
MRV Intelligent Network Cassette Type
Air Conditioner Indoor Unit
INSTALLATION MANUAL
No.0010570459 B
Please read this manual carefully before using.
Please keep this manual carefully and safely.
AB072FDBHA AB092FDBHA AB122FDBHA AB162FDBHA AB182FDBHA AB242FDBHA AB282FDBHA
Contents
Safety cautions-----------------------------------------------------------------------------------------------------1
Indoor unit installation----------------------------------------------------------------------------------------- 2-7
Refrigerant piping------------------------------------------------------------------------------------------------8-9
Electrical wiring & Application control--------------------------------------------------------------------10-14
Trial operation-----------------------------------------------------------------------------------------------------15
Troubleshooting-----------------------------------------------------------------------------------------------16-17
Panel installation----------------------------------------------------------------------------------------------18-21
Caution
Auto Restart function for C-MRV models
Haier Auto Restart function: when the unit power drops down suddenly, the unit microprocessor will store the previous working condition and when the power is on again, the unit will run as this memory.
Auto Restart function is designed basically on the MRV whole system, but it is suitable for each indoor unit individually.
If some of indoor units power cut down, but the outdoor unit and the other indoor units still work, maybe problems will happen such as freezing at cooling mode and overload protection at heating mode on those indoor units without power.
Reason
When one or some indoor units power drops down and the other indoor units are still work, the indoor units without the power, will keep the previous working condition before the power is off. And expansion valve keeps open at a kind of opening rate condition as the previous requirement, so there is refrigerant flowing in the exchanger, but the indoor fan stops working. If the units work at cooling mode, the indoor units without the power will maybe make freezing. If the unit works at heating mode, maybe the outdoor unit compressor will stop because of the pressure or temperature protection. This is our design basically on Auto Restart function currently. Haier, Herewith, solemnly informs our customers, installers, distributors, etc. when making
installation, please make sure when the power is shut down whether artificially or accidentally, the whole system including outdoor unit and all the indoor units must be off. If you do not make the installation as our indication, Haier will not be responsible for any problem resulting from this.
21
20
Safety Cautions
1
The following safety measures must be strictly followed.
Keep these safety measures close at hand for timely references.
After installation, trial run must be made to ensure normal operation. Familiarize the user with the use
and maintenance through this manual.
If the air conditioner is transferred to a new user, this manual should also be transferred.
Please pay attention to the following:
Warning: Inappropriate use may lead to fatal or serious injuries.
Caution: Inappropriate use may lead to bodily harm or mechanical damage; it may lead to serious
consequences in some cases.
Any instructions with the sign of ì NOî shall be strictly followed, otherwise, it may cause me-
chanical damage or endanger the safety of the user.
Any instructions with the sign of ì STOPî shall be strictly followed, otherwise, it may cause me-
chanical damage or endanger the safety of the user.
Entrusted installation Installation should be entrusted with after-sale servicemen. Self-installation is likely to cause water leakage, shock and fire, etc.
Installation should be done according to this install­ation manual. Inappropriate installation may lead to water leakage, shock and fire, etc.
Connection of the earth wire The earth wire should not be connected to gas pipes, water pipes, lightning rods or telephone wires. Poor earth may lead to shocks
After-sale servicemen should take measures to avoid refrigerant leakage. Refrigerant leak may cause anoxia when a certain density is reached. If the room is small, make sure to have sound safety measures to avoid anoxia accidents.
The installation of the electric part should be con­ducted by qualified professionals and done accord­ing to the installation manual. Special return circuit must be used. Insufficient capacity return circuit and inappropriate installation may lead to fire accidents.
Installation site The site must be firm enough to withstand the weight of the air conditioner to prevent falling. During installation, if refrigerant leakage occurs, ventilation measures must be taken. When refrig­erant meets with fire, hazardous gas will be produced.
After installation, make sure that there is no refriger­ant leakage. Refrigerant, if meeting with heaters and stoves, etc in the room, may produce hazardous gas.
Specific cables should be used for the wiring. To avoid external tension of the cables, the terminals should be firmly fixed. Inappropriate connection and fixture may lead to fire accidents.
In order to discharge the condensed water, the installation of the drainpipe should be done in accordance with the manual instructions. The drainpipe should be treated for heat isolation. Inappropriate treatment may lead to water leak­age in the room.
Electric leak breaker should be installed. Without it, shock accidents may occur.
Do not install at places where inflammable gas leak may occur.
Gas leakage may lead to fire accident.