Haier 3U24GS1ERE, 4U36HS1ERE Installation Manual

4U36HS1ERE
3U24GS1ERE
INSTALLATION MANUAL
MULTI-SPLIT AIR CONDITIONER
Please read this manual carefully before installation.
0150513284
Keep this operation manual for future reference.
Contents
English
Safety Precautions Accessories Procedure for Selecting the Location Installation drawings of indoor and outdoor units Wiring connection Outdoor Unit Installation Guideline Limitations on the installation Refrigerant piping work Pump Down Operation Wiring work Test running Trouble shooting
Your air conditioning product is marked with this symbol.This means that electrical and electronic products shall not be mixed with unsorted household waste.Do not try to dismantle the system yourself:the dismantling of the air conditioning system,treatment of the refrigerant,of oil and of other part must be done by a qualified installer in accordance with relevant local and national legislation.Air conditioners must be treated at a specialized treatment facility for reuse, recycling and recovery.By ensuring this product is disposed of correctly,you will help to prevent potential negative cons­equences for the environment and humen health.Please contact the installer or local authority for more information. Battery must be removed from the remote controller and dis­posed of separately in accordance with relevant local and nationl legislation.
DISPOSAL REQUIREMENTS:
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol.Do not vent into the atmosphere. Refrigerant type:R410A GWP*value:1975 GWP = Global Warming Potential Please fill in with legible ink 1 The factory refrigerant charge of the product 2 The additional refrigerant charge of the product 1+2 the total refrigerant charge on the refrigerant charge label supplied with the product. The filled out label muset be adhered in the proximity of the product charging port(e.g.onto the inside of the stop value cover). A contains fluorinated greenhouse gases covered by the Kyoto Protocol B fatory refrigerant charge of the product:see unit name plate C additional refrigerant amount charged in the field D total refrigerant charge E outdoor unit F refrigerant cylinder and manifold for charging
IMPORTANT INFORMATION REGA­RDING THE REFRIGERANT USED
1356 Broadway, New York, NY 10018
Safety Precautions
WARNING CAUTION
WARNING
CAUTION
Read these Safety Precautions carefully to ensure correct installation. This manual classifies the precautions into WARNING and CAUTION. Be sure to follow all the precautions bellow: they are all important for ensuring safety.
Failure to follow any of WARING is likely to result in such grave consequences as death or serious injury.
Failure to follow any of CAUTION may in some cases result in grave consequences.
The following safety symbols are used throughout this manual:
Be sure to observe this instruction Be sure to establish an earth connection Never attempt
After completing installation, test the unit to check for installation errors. Give the user adequate instructions concerning the use and cleaning of the unit according to the Operation Manual.
Installation should be left to the dealer or another professional.
Improper installation may cause water leakage, electrical shock, or fire.
Install the air conditioner according to the instructions given in this manual.
Incomplete installation may cause water leakage, electrical shock, or fire.
Be sure to use the suplied or specified installation parts.
Use of other parts may cause the unit to come lose, water leakage, electrical shock, or fire.
Install the air conditioner on a solid base that can support the unit's weight.
An inadequate base or incomplete installation may cause injury in the event the unit falls off the base.
Electrical work should be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice.
Insufficient capacity or incomplete electrical work may cause electrical shock or fire.
Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance.
For wiring, use a cable long enough to cover the entire distance with no connection. Do not use an extension cord. Do not put other loads on the power supply, use a dedicated power circuit.
(Failure to do so may cause abnormal heat, electric shock or fire.)
Use the specified types of wires for electrical connections between the indoor and outdoor units.
Firmly clamp the interconnecting wires so their terminals terminals receive no external stresses. Incomplete connections or clamping may cause terminal overheating or fire.
After connectiong interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the electrical covers or panels.
Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, or fire.
If any refrigerant has leaked out during the installation work, ventilate the room.
(The refrigerant produces a toxic gas if exposed to flames.)
After all installation is complete, check to make sure that no refrigerant is leaking out.
(The refrigerant produces a toxic gas if exposed to flames.)
When installing or relocating the system, be sure to keep the refrigerant circuit free from substances other than the specified refrigerant(R410A), such as air.
(Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture, resulting in injury.)
During pump-down, stop the compressor before removing the refrigerant piping.
If the compressor is still running and the stop valve is open during pump-down, air will be sucked in while the compressor is running, causing abnormal pressure and no condense-able added to the system.
Be sure to establish a ground. Do not ground the unit to a utility pipe, arrester, or telephone earth.
In complete earth may cause electrical shock, or fire. A high surge current from lightning or other sources may cause damage to the air conditioner.
Do not install the air conditioner in a place where there is danger of exposure to inflammable gas leakage.
If the gas leaks and builds up around the unit, it may catch fire.
Establish drain piping according to the instructions of this manual.
Inadequate piping may cause flooding.
Tighten the flare nut according to the specified method such as with a torque wrench.
If the flare nut is tightened too hard, the flare nut may crack after a long time and cause refrigerant leakage.
Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.
Accessories
Procedure for Selecting the Location
NOTE:
No.
1
2
3
Quantity
1
4
Name of parts
Drainage elbow
Rubber cushion
Clap
Drawing
1
1
Note
3
Adaptor(3/8 1/2)
Adaptor(1/2 3/8)
1
3
Accessories supplied with the outdoor unit:
1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified.
2) Choose a location where the hot air discharged from the unit or the operation noise, will not cause a nuisance to the neighbors of the user.
3) Avoid places near a bedroom and the like, so that the operation noise will cause no trouble.
4) There must be sufficient space for carrying the unit into and out of the site.
5) There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.
6) The site must be free from the possibility of flammable gas leakage in a nearby place. Locate the unit so that the noise and the discharged hot air will not annoy the neighbors.
7) Install units, power cords and inter-unit cables at least 10ft away from television and radio sets. This is to prevent interference to images and sounds. (Noises may be heard even if they are more than 10ft away depending on radio wave conditions.)
8) In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the air conditioner.
9)Since drain flows out of the outdoor unit, do not place under the unit anything which must be kept away from moisture.
Cannot be installed hanging from ceiling or stacked.
3U24GS1ERE
4U36HS1ERE
3U24GS1ERE
4U36HS1ERE
3U24GS1ERE 4U36HS1ERE
3U24GS1ERE 4U36HS1ERE
4U36HS1ERE
Installation figure please refers to 4U36HS1ERE.
1. Connect indoor and outdoor piping when installing unit. Do not leave piping connected to only one unit
2.You must connect 2 units, minimum
Installation drawings of indoor and outdoor units
If there is the danger of the unit falling or overturning, fix the unit with foundation bolts, or with wire or other means. If the location does not have good drainage, place the unit on a level mounting base(or a plastic pedestal). Install the outdoor unit in a level position. Failure to do so may result in water leakage or accumulation.
Arrangement of piping directions
Rear left
Rear right
Right
Below
Left
Wrap the insulation pipe with the finishing tape from bottom to top.
Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no gap is left in the insulation pipe's cut line.
more than 10cm
more than10cm
more than 60cm
more than 25 cm
(4 in)
(4 in)
(24 in)
(10 in)
More than 15cm
More than 10cm
Attention must be paid to the rising up of drain hose
More than
10cm
(6 in)
(4 in)
(4 in)
Installation drawings of indoor and outdoor units
*MUST CONNECT (2) INDOOR UNITS
Connection cautions
model 3U24GS1ERE 4U36HS1ERE
connection priority between indoor and stop valve higher from down to up
when there is 1 indoor,the prior stop valve is
when there are 2 indoors,the prior stop valves are
when there are 3 indoors,the prior stop valves are
when there are 4 indoors,the prior stop valves are
Note: For better oil return and more reliable system, please execute as the above when connecting indoor unit.
C
C B
C B A
D
D C
D C B
D C B A