Hach-Lange SI792xE, SI792xT User Manual

Page 1
DOC026.52.00796
si792(x) E—Hach GLI 3700 series
si792(x) T—7MA2200 and 8398 series
Inductive Conductivity
2-Wire Transmitter
USER MANUAL
December 2007, Edition 1
© HACH Company, 2007. All rights reserved. Printed in Germany
Page 2
Page 3

Table of Contents

Section 1 Specifications ......................................................... 5
Section 2 General information...........................................11
2.1 Safety information ....................................................................11
2.1.1 Use of hazard information ................................................. 11
2.1.2 Precautionary labels.......................................................... 11
2.2 General product information..................................................... 13
2.2.1 Product overview............................................................... 13
2.2.2 FDA 21 CFR part 11 compliance (HART only) ................. 14
2.2.2.1 Electronic signatures for si792(x) E/T transmitters ....14
2.2.2.2 Audit trail for si792(x) E/T transmitters....................... 14
Section 3 Installation ..............................................................15
3.1 Hazardous location installation................................................. 16
3.1.1 ATEX safety information ................................................... 16
3.2 Unpacking the transmitter ........................................................17
3.3 Mechanical installation ............................................................. 18
3.3.1 Transmitter assembly........................................................ 18
3.3.2 Mounting ........................................................................... 18
3.3.2.1 Wall mount ................................................................. 18
3.3.2.2 Panel or pipe mount (optional) ................................... 18
3.4 Wiring Safety Information......................................................... 20
3.5 Electrical installation................................................................. 21
3.5.1 Wire preparation................................................................ 21
3.5.2 Power and communication connections............................ 23
3.5.2.1 si792(x) E/T (4-20 mA/HART) wiring.......................... 24
3.5.2.2 si792x E/T-FF and si792x E/T-PA wiring ...................25
3.5.3 Sensor wire connections ................................................... 25
3.5.3.1 Hach GLI 3700 series sensor wiring—si792(x) E ...... 26
3.5.3.2 7MA2200 series sensor wiring—si792(x) T ............... 27
3.5.3.3 8398 series sensor wiring—si792(x) T....................... 28
3.6 HART communication connection............................................ 29
Page 4
Table of Contents
Section 4 Interface and navigation .................................. 31
4.1 si792(x) E/T (4–20 mA/HART) interface................................... 31
4.2 si792x E/T-FF and si792x E/T-PA interface ............................. 32
4.3 Display...................................................................................... 33
Section 5 Operation—4–20 mA/HART............................ 35
5.1 Measure mode .........................................................................35
5.2 Configuration............................................................................ 35
5.2.1 Current output configuration..............................................36
5.2.1.1 Time constant of output filter...................................... 39
5.2.1.2 Output signal during errors......................................... 39
5.2.1.3 Output signal during HOLD ........................................ 40
5.2.2 Temperature compensation configuration.........................41
5.2.3 Alarm settings.................................................................... 42
Section 6 Operation—Foundation Fieldbus................ 43
6.1 Configuration............................................................................ 43
6.1.1 Configuration steps ...........................................................43
6.1.2 Configuration menu........................................................... 44
6.2 Foundation Fieldbus communication........................................ 47
6.2.1 Standard resource block (RB)........................................... 47
6.2.2 Standard analog input block (AI)....................................... 50
6.2.2.1 Operating modes........................................................ 50
6.2.2.2 Set the parameter and units....................................... 50
6.2.2.3 Data processing .........................................................51
6.2.2.4 Alarms ........................................................................ 51
6.2.2.5 Bus parameters for the analog input block.................52
6.2.2.6 Cyclic measured value status..................................... 55
6.2.2.7 Measured value limits—limit bits................................55
6.2.3 Transducer block...............................................................56
6.2.4 Calibration via Foundation Fieldbus.................................. 63
Section 7 Operation—Profibus PA................................... 65
7.1 Configuration............................................................................ 65
7.1.1 Configuration steps ...........................................................65
Page 5
Table of Contents
7.1.2 Configuration menu........................................................... 66
7.2 Profibus PA communication .....................................................67
Section 8 Calibration .............................................................. 71
8.1 Calibration ................................................................................ 71
8.1.1 Enter cell constant............................................................. 72
8.1.2 Calibration with a calibration solution................................ 73
8.1.3 Calibration by comparison/grab sample............................ 74
8.1.4 Zero calibration—air.......................................................... 75
8.1.5 Zero calibration—calibration solution ................................ 75
8.2 Temperature sensor adjustment ..............................................76
Section 9 Maintenance........................................................... 77
9.1 Cleaning the instrument ...........................................................77
9.2 Sensor maintenance ................................................................77
Section 10 Troubleshooting ................................................ 79
10.1 Sensoface ..............................................................................79
10.2 Sensocheck............................................................................79
10.3 Error codes.............................................................................80
10.4 Diagnostic tests...................................................................... 82
Section 11 Replacement parts............................................85
11.1 si792 transmitter versions ......................................................85
11.2 Accessories............................................................................ 85
11.3 Replacement parts .................................................................85
Section 12 Contact information......................................... 87
Section 13 Limited warranty ............................................... 90
Appendix A Calibration solutions .................................... 93
Appendix B Concentration curves................................... 97
B.1 Concentration measurement ranges........................................ 97
B.2 Sodium chloride solution -01- NaCl .........................................99
B.3 Hydrochloric acid -02- HCl..................................................... 100
B.4 Sodium hydroxide solution -03- NaOH ..................................101
B.5 Sulfuric acid -04- H
........................................................ 102
2SO4
Page 6
Table of Contents
B.6 Nitric acid -05- HNO
Appendix C Passcode editor ............................................ 105
Appendix D ATEX safety instructions.......................... 107
Index...............................................................................................111
. ............................................................103
3
Page 7

Section 1 Specifications

Specifications are subject to change without notice.
Transmitter
Composition PBT (polybutylene terephthalate) Display LCD
Fittings
Power requirements—HART 14–30 VDC (30 VDC maximum) Power requirements—FF and Profibus PAFISCO bus supply: 9 to 17.5 VDC
Loop current—HART
Current consumption—FF and Profibus PA
Maximum current in case of fault (FDE)—FF and Profibus PA
Measurement error
2
3 knockouts for M20 x 1.5 strain reliefs 2 knockouts for ½ inch NPT or rigid
metallic conduit
Linear barrier: 9 to 24 VDC 4–20 mA floating;
3.80–22.00 mA specifiable
<13.2mA
<17.6mA
<0.3% of current value + 0.05 mA
Page 8
Specifications
US: si792 E/T
FM Listed for:
Class I, Division 2
si792x E/T; si792x E/T-FF; si792x E/T-PA
FM Listed for:
Class I, Division 1, Groups A, B, C, D Class II, Division 1, Groups E, F Class III, Division 1 Class I, Zone 0, AEx ia, Group IIC T4
Enclosure: Type 2 Canada: si792 E/T
Certification (may not apply to all sensors. Refer to the control drawing or listing for certification information for the sensor that is used).
Output averaging time constant (HART) 0–120 seconds Storage temperature –20 to 70 °C (–4 to 158 °F) Operating temperature –20 to 55 °C (–4 to 131 °F) Weight Approximately 1 kg
CSA Certified to:
Class I, Division 2
si792x E/T CSA Certified and si792x E/T-FF; si792x E/T-PA cFMus Certified to:
Class I, Division 1, Groups A, B, C, D Class I, Division 2, Groups A, B, C, D Sensor: Class I, Zone 0, Group IIC Transmitter: Class I, Zone 1, Group IIC
Enclosure: Type 2 EU: si792x E/T; si792x E/T-FF;
si792x E/T-PA: CE Marked to:
EMC Directive 2004/108/EC ATEX Directive 94/9/EC
ATE X: II 2 (1) G EEx ib (ia) IIC T6 Enclosure: IP65
Page 9
Data retention
Passcodes
Sensocheck
Sensor monitor
Communication
HART communication
Foundation Fieldbus (FF_H1)
Specifications
Parameters and calibration data > 10 years (EEPROM)
Modifiable according to FDA 21 CFR Part 11 “Electronic Signatures” (HART only)
Monitoring of primary coil and its lines for short circuit and of secondary and its lines for open circuit
Direct display of measured values from sensor for validation (resistance/ temperature)
Digital communication by FSK modulation of loop current, reading of device identification, measured values, status and messages, reading and writing of parameters, start of product calibration, signaling of configuration changes according to FDA 21 CFR Part 11.
Bus-powered device with constant current consumption. Cyclic and acyclic data exchange. 1 resource block, 1 transducer block, 3 analog input function blocks (switchable: conductivity, concentration, salinity, temperature, cell constant)
Execution time: 50 ms Certified to ITK 4.6 Physical interface: to IEC 1158-2 Address range: 017 to 246
Page 10
Specifications
Bus-powered device with constant current consumption. Cyclic and acyclic data exchange. Physical block, 2 analog input function blocks, 2 discrete input blocks, logbook block, alarm block.
PNO directive: PROFIBUS-PA,
Profibus-PA (DPV1)
Conductivity input
Electrodeless conductivity sensors, ranges
Range, conductivity
Range, concentration 0.00–100.0% by weight Range, salinity 0.0–45 ‰ (0–35 °C) Measurement error < 1% measured value + 0.02 mS/cm
Temperature input
Sensor
Profile for Process Control Devices, Version 3.0
Physical interface: MBP-IS (Manchester Bus Powered-Intrinsically Safe) to IEC 1158-2 (DIN-EN 61158-2)
Connection: via segment coupler to SPC, PC, PCS
Address range: 1 to 126
7MA2200 series 8398 series Hach 3700 series Conductivity 0.00–1999 mS/cm Concentration 0–100% by weight Salinity 0.0–45 ‰ (0–35 °C)
0.000–9.999 mS/cm
00.00–99.99 mS/cm
000.0–999.9 mS/cm 0–1999 mS/m
0.000–9.999 S/m
00.00–99.99 S/m
Pt100/PT1000/NTC 30 kΩ/NTC 100 kΩ 2-wire connection
Page 11
Specifications
Range, Pt100/Pt1000 –20.0 to 200.0 °C (–4 to 392 °F) Range, NTC 30 kΩ –20.0 to 150.0 °C (–4 to 302 °F) Range, NTC 100 kΩ –20.0 to 130.0 °C (–4 to 266 °F) Adjustment range 10 K Resolution 0.1 °C; 0.1 °F
Measurement error
1
(± 1 count plus sensor error)
2
IEC 746 Part 1, at nominal operating conditions
1,2
< 0.5 K (< 1 K for Pt100;<1 K for NTC >100 °C)
Page 12
Specifications
10
Page 13

Section 2 General information

2.1 Safety information

Please read this entire manual before unpacking, setting up, or operating this equipment. Pay attention to all danger and caution statements. Failure to do so could result in serious injury to the operator or damage to the equipment.
To ensure that the protection provided by this equipment is not impaired, do not use or install this equipment in any manner other than that specified in this manual.

2.1.1 Use of hazard information

DANGER Indicates a potentially or imminently hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION Indicates a potentially hazardous situation that may result in minor or moderate injury.
Important Note: Information that requires special emphasis.
Note: Information that supplements points in the main text.

2.1.2 Precautionary labels

Read all labels and tags attached to the instrument. Personal injury or damage to the instrument could occur if not observed. A symbol, if noted on the instrument, will be included with a danger or caution statement in the manual.
This symbol, if noted on the instrument, references the instruction manual for operation and/or safety information.
11
Page 14
General information
Electrical equipment marked with this symbol may not be disposed of in European public disposal systems after 12 August of 2005. In conformity with European local and national regulations (EU Directive 2002/96/EC), European electrical equipment users must now return old or end-of life equipment to the Producer for disposal at no charge to the user.
Note: For return for recycling, please contact the equipment producer or supplier for instructions on how to return end-of-life equipment, producer-supplied electrical accessories, and all auxiliary items for proper disposal.
This symbol, when noted on a product enclosure or barrier, indicates that a risk of electrical shock and/or electrocution exists.
This symbol, when noted on the product, identifies the location of the connection for Protective Earth (ground).
This symbol, when noted on the product, identifies the location of a fuse or current limiting device.
This symbol, when noted on the product, identifies a risk of chemical harm and indicates that only individuals qualified and trained to work with chemicals should handle chemicals or perform maintenance on chemical delivery systems associated with the equipment.
This symbol, when noted on the product, identifies the presence of a strong corrosive or other hazardous substance and a risk of chemical harm. Only individuals qualified and trained to work with chemicals should handle chemicals or perform maintenance on chemical delivery systems associated with the equipment.
This symbol, when noted on the product, indicated the presence of devices sensitive to Electro-static Discharge (ESD) and indicated that care must be taken to prevent damage with the equipment.
This symbol, when noted on the product, identifies the presence of noxious substances and a risk of chemical harm. Only individuals qualified and trained to work with chemicals should handle chemicals or perform maintenance on chemical delivery systems associated with the equipment.
12
Page 15
General information

2.2 General product information

DANGER Explosion hazard. The Hach GLI 3700 series sensors can only be used with the si792(x) E transmitter.

2.2.1 Product overview

The si792 T, si792x T, si792 E and si792x E transmitters are used for measurement of electrical conductivity and temperature in liquids. Fields of application are: biotechnology, chemical industry, environment, food processing and water/waste-water treatment.
The E and the T models differ only in the types of sensors that can be used with the transmitter. The operation of each version is identical. This user manual refers to both versions as E/T.
The molded transmitter enclosure can be attached to a panel, wall, post or pipe railing. The optional hood (see Accessories on page 85) provides protection against direct weather exposure and mechanical damage.
Three communication options are available for the si792 transmitter:
4–20 mA/HART—si792 E, si792 T, si792x E and si792x T (noted as si792(x) E/T)
Foundation Fieldbus—si792x E-FF and si792x T-FF
Profibus PA—si792x E-PA and si792x T-PA
This user manual includes instructions for all three protocols.
Important Note: An ‘x’ in the model number is an indication of an intrinsically safe (IS) instrument.
The instruments are compatible with different sensor types. See si792
transmitter versions on page 85 for a list of instrument versions.
13
Page 16
General information

2.2.2 FDA 21 CFR part 11 compliance (HART only)

In the directive “Title 21 Code of Federal Regulations, 21 CFR Part 11, Electronic Records; Electronic Signatures“ the US American health agency FDA (Food and Drug Administration) regulates the production and processing of electronic documents for pharmaceutical development and production. The features described in section 2.2.2.1 and section 2.2.2.2 make the transmitter compliant with the requirements of FDA 21 CFR Part 11.
2.2.2.1 Electronic signatures for si792(x) E/T transmitters
Device functions are protected by passcode access, which prevents unauthorized modification of device settings or manipulation of measurement results. Passcodes may be used as electronic signatures. Passcodes can be edited with the passcode editor (Appendix C on page 105).
2.2.2.2 Audit trail for si792(x) E/T transmitters
The si792(x) transmitter can automatically track all changes to the device settings. Each change is tagged with a Configuration Change flag, which is documented using HART communication. Altered device settings or parameters can be retrieved from the transmitter using HART communication.
14
Page 17

Section 3 Installation

DANGER Explosion hazard. Trained personnel only must install or commission the equipment.
DANGER Explosion hazard. Never connect items to the transmitter that are not specified on the control drawing. Do not connect or disconnect any equipment unless power has been switched off or the area is known to be non-hazardous.
DANGER Explosion hazard. The safety of the transmitter may be impaired if any of the following conditions have occurred:
visible damage
storage above 70 °C for prolonged periods
exposure to severe transport stresses
previous installation
failure to operate properly
If any of these conditions have occurred, return the device to the manufacturer for recertification.
The si792 and si792x transmitters differ in hazard classification. The si792 transmitter is designed for non-hazardous or Class I, Division 2, Groups A, B, C, D hazardous locations. The si792x transmitter is designed for Class I, Division 1, Groups A, B, C, D hazardous locations. Refer to the control drawing or listing applicable to the site location.
For outdoor installation, install a protective hood or sunshield (see Accessories on page 85).
Installation of the si792x in an outdoor hazardous location per FM or CSA control drawings requires a suitable enclosure and must follow NEC guidelines. Refer to NEMA 250 to determine enclosure needs.
15
Page 18
Installation

3.1 Hazardous location installation

Before installation, review the applicable Hazardous Location Control Drawings or ATEX EC-Type Examination certificate and safety information included with the instrument and on the provided documentation CD. Follow all regulations specified for the installation location.
Refer to the documentation CD for manuals provided in other languages.

3.1.1 ATEX safety information

Refer to Appendix D for safety information on the use of the electrodeless sensors.
16
Page 19
Installation

3.2 Unpacking the transmitter

Check the shipment for transport damage and make sure all components have been shipped complete. The package includes:
Display module • Bag of hardware and fasteners
• Back enclosure • Test report and user manual
Figure 1 Instrument Components
1 Back enclosure 8 Strain relief (3x) 2 Optional conduit hardware 9 Filler plug (3x) 3 Conduit washer 10 Enclosure screw (4x) 4 Jumper (2x) 11 Display module 5 Cable tie (3x) 12 Hinge pin 6 Sealing insert 13 Hex nuts (5x) 7 Rubber reducer 14 Sealing plug (2x)
17
Page 20
Installation

3.3 Mechanical installation

3.3.1 Transmitter assembly

Refer to Figure 1 and the following instructions to assemble the transmitter.
1. Insert the strain relief fittings in the holes of the back enclosure and secure with the hex nuts (Figure 2).
2. Insert the conduit hardware or plugs in the back enclosure and secure with the hex nuts.
3. Attach the display module to the back enclosure using the hinge pin.

3.3.2 Mounting

Refer to the following sections to mount the transmitter on a wall, panel or pipe.
3.3.2.1 Wall mount
1. Use a punch to open the two wall-mount holes in the back enclosure
(Figure 2).
2. Drill holes in the wall suitable for the user-supplied mounting bolts.
3. Attach the back enclosure to the wall using two customer-supplied
bolts.
4. Insert the clear plastic plugs into the mounting holes.
3.3.2.2 Panel or pipe mount (optional)
Refer to Figure 2 and the instructions supplied with the panel and pipe mounting kits (see Accessories on page 85).
18
Page 21
Installation
Figure 2 Wall attachment dimensions
1 Breakout for wall mounting (2x) 5 Groove for panel mount gasket 2 Hole for pipe mounting (4x) 6 Strain relief opening (3x) 3 Strain relief (3x) 4 Breakout for panel mounting
7 Strain relief or ½ inch conduit opening
(2x) Ø 21.5 mm [0.85 in]
19
Page 22
Installation

3.4 Wiring Safety Information

When making any wiring connections to the instrument, the following warnings and notes must be adhered to, as well as any warnings and notes found throughout the individual installation sections. For more safety information refer to section 2.1 on page 11.
DANGER Always disconnect power to the instrument when making any electrical connections.
Electrostatic Discharge (ESD) Considerations
To minimize hazards and ESD risks, maintenance procedures not requiring power to the analyzer should be performed with power removed.
Delicate internal electronic components can be damaged by static electricity, resulting in degraded instrument performance or eventual failure.
The manufacturer recommends taking the following steps to prevent ESD damage to the instrument:
• Before touching any electronic components (such as printed circuit cards and the components on them) discharge static electricity from the body by touching an earth-grounded metal surface such as the chassis of an instrument or a metal conduit or pipe.
• To reduce static build-up, avoid excessive movement. Transport static-sensitive components in anti-static containers or packaging.
• To discharge static electricity from the body and keep it
discharged, wear a wrist strap connected by a wire to earth ground.
• Handle all static-sensitive components in a static-safe area. If
possible, use anti-static floor pads and work bench pads.
20
Page 23
Installation

3.5 Electrical installation

DANGER Explosion hazard. Do not connect any components that are not specified for the device. Always defer to the Hazardous Location Control Drawing.
Prerequisites:
• Review the applicable control drawing or ATEX EC-Type Examination certificate
• Review the electrical code regulations
• Review the regulations for electrical installations in hazardous locations, if appropriate (e.g. EN 60079-10/EN60079-14; 94/9/EC directive; NEC; CEC; Profibus Technical Guidelines
2.091)
• Remove power or confirm non-hazardous status before making any connections
• Confirm that the intrinsic safety of the device is maintained when connected to other equipment such as a power supply unit.

3.5.1 Wire preparation

To remove the terminal blocks from the transmitter for sensor wiring:
1. Insert a flat screwdriver between the terminal block and the transmitter body.
2. Use the screwdriver as a lever to lift the terminal block off the connectors (see Figure 3).
21
Page 24
Installation
Figure 3 Wire preparation and insertion
1 Stripping lengths for cables 6 Terminals (vary by model number) 2 Stripping lengths for coaxial cables 7 Typical terminal 3 Cable shield connector (not used) 8 Seat insulation against connector 4 ESD shield removed 9 Removing terminal with screwdriver 5 Areas for screwdriver to pry terminal 10 Cable loop position in housing
22
Page 25
Installation

3.5.2 Power and communication connections

DANGER Explosion hazard. The AC power source for the power supply unit cannot exceed 250 VAC. Do not connect the transmitter directly to an AC power source.
DANGER Explosion hazard. The output voltage of the power supply unit cannot exceed 30 VDC. The si792x transmitter must be connected to an appropriately certified explosion-proof power supply unit. Refer to "associated apparatus" in the control drawing or to the EC-Type Examination Certificate for input ratings.
Prerequisites
• Trained personnel only must install or commission the
equipment.
• Follow the instructions in this user manual and the applicable
local and national codes.
• Observe the technical specifications and input ratings during
installation.
• Disconnect all power sources during wiring and installation.
• Use single wires/flexible leads up to 2.5 mm (AWG 14) for
connection to terminals.
• Do not damage the wire when stripping the insulation.
• All parameters must be set by a system administrator (Authority
Having Jurisdiction) before commissioning.
23
Page 26
Installation
3.5.2.1 si792(x) E/T (4-20 mA/HART) wiring
DANGER Explosion hazard. Never connect items to the transmitter that are not specified on the control drawing/ATEX EC-Type certificate.
Refer to Figure 4 and Table 1 to connect the power supply to the si792(x) E/T transmitter.
Figure 4 si792(x) E/T (4–20 mA/HART) wiring
1 HART connection (see warnings in
section 3.6 on page 29)
Table 1 Terminal assignments—si792(x) E/T (4–20 mA/HART)
Terminal No. Assignment
9 Potential equalization—ATEX only (Do not use for FM or CSA)
10 4–20 mA output (–) 11 4–20 mA output (+)
2 Wiring terminals—see Table 1
24
Page 27
Installation
3.5.2.2 si792x E/T-FF and si792x E/T-PA wiring
Refer to Figure 5 and Table 2 to connect power and communications to the si792x E/T-FF or si792x E/T-PA transmitters.
Figure 5 si792x E/T-FF and si792x E/T-PA wiring
1 Wiring terminals—see Table 2
Table 2 Terminal assignments—si792x E/T-FF and si792x E/T-PA
Terminal No. Assignment
9 Potential equalization—ATEX only (Do not use for FM or CSA) 10 Connection from Foundation Fieldbus or Profibus PA (–) 11 Connection from Foundation Fieldbus or Profibus PA (+)

3.5.3 Sensor wire connections

Important Note: Do not connect earth ground to the shield connector in the transmitter. Connect the cable shields to the shield connector.
Refer to the following sections to connect the transmitter to a sensor:
• Hach GLI 3700 series—section 3.5.3.1 on page 26
• 7MA2200 series—section 3.5.3.2 on page 27
25
Page 28
Installation
• 8398 series—section 3.5.3.3 on page 28
3.5.3.1 Hach GLI 3700 series sensor wiring—si792(x) E
1. Install the jumper between terminal 2 and 3 as shown in Figure 6.
2. Use Table 3 to wire the sensor to the transmitter.
Figure 6 si792(x) E wiring for Hach GLI 3700 series sensors
1 Jumper between terminal 2 and 3 2 Wiring terminals—see Table 3
Table 3 Terminal assignments—Hach GLI 3700 series sensors
Terminal No. Assignment Wire color
1 Receive hi white 2 Receive lo blue 3 Send lo yellow 4 Send hi green
Cable shield connection
5
Note:
Do not connect to earth ground.
8 RTD (resistive temperature device) red
shield
26
Page 29
Installation
3.5.3.2 7MA2200 series sensor wiring—si792(x) T
1. Install the jumper between terminal 2 and 3 as shown in Figure 7.
2. Use Table 4 to wire the sensor to the transmitter.
Figure 7 si792(x) T wiring for 7MA2200 series sensors
1 Jumper between terminal 2 and 3 2 Wiring terminals—see Table 4
Table 4 Terminal assignments—7MA2200 series sensors
Terminal No. Assignment Wire color
1 Receive hi green 2 Receive lo yellow 3 Send lo white 4 Send hi brown
Cable shield connection
5
Note:
Do not connect to earth ground.
7 RTD (resistive temperature device) black/grey 8 RTD (resistive temperature device) red/pink
violet/black
27
Page 30
Installation
3.5.3.3 8398 series sensor wiring—si792(x) T
1. Install the jumper between terminal 2 and 3 as shown in Figure 8.
2. Use Table 5 to wire the sensor to the transmitter.
Figure 8 si792(x) T wiring for 8398 series sensors
1 Jumper between terminal 2 and 3 2 Wiring terminals—see Table 5
Table 5 Terminal assignments—8398 series sensor
Terminal No. Assignment Wire color
1 Receive hi brown 2 Receive lo black 3 Send lo shield of brown wire 4 Send hi shield of white wire
Cable shield connection
5
Note:
Do not connect to earth ground.
7 RTD (resistive temperature device) green 8 RTD (resistive temperature device) yellow
white
28
Page 31
Installation

3.6 HART communication connection

DANGER Explosion hazard. Never connect items to the transmitter that are not specified on the control drawing. Do not connect or disconnect any equipment unless power has been switched off or the area is known to be non-hazardous.
DANGER The si792x transmitter must be used with an explosion-proof HART communication device. Refer to the appropriate control drawing for the location of the HART (Rosemount) device.
The handheld HART communication device can only be connected to the transmitter in US Class I, Division 1 classified locations (permitted only by FM). Do not connect the handheld Hart communication device to the transmitter in any Zone or Canadian Class I, Division 1 classified location. Refer to Figure 4 on page 24 for the connector location.
29
Page 32
Installation
30
Page 33

Section 4 Interface and navigation

The si792 transmitter user interface contains a display, indicators and keys for navigation and menu selection.
4.1 si792(x) E/T (4–20 mA/HART) interface
Use the arrow and enter keys to scroll through the menu and change settings. Use the indicators to identify which mode the transmitter is in. Refer to Figure 9 to identify the keys and indicators of the si792(x) E/T transmitter.
Figure 9 User interface—si792(x) E/T transmitter
1 Calibration key 7 Wash mode indicator (not available) 2 Configure key 8 Configuration mode indicator 3 Measure mode indicator 9 Up arrow key 4 Calibration mode indicator 10 Right arrow key 5 Alarm indicator 6 Display
11 Enter key
31
Page 34
Interface and navigation

4.2 si792x E/T-FF and si792x E/T-PA interface

Refer to Figure 10 to identify the keys and indicators of the si792x E/T-FF and si792x E/T-PA transmitter.
Figure 10 User interface—si792x E/T-FF and si792x E/T-PA
1 Measure key 7 Communication indicator
2 Calibration key 8 Configuration mode indicator
3 Measure mode indicator 9 Up arrow key
4 Calibration mode indicator 10 Right arrow key
5 Alarm indicator 11 Enter key
6 Display 12 Configuration mode
32
Page 35
Interface and navigation

4.3 Display

Figure 11 identifies all of the possible icons and symbols that may be
seen in the si792 transmitter display.
Figure 11 Display
1 Passcode 13 Secondary display 2 Temperature 14 Alarm mode 3 4–20 mA output 15 Manual temperature on 4 Limit values (FF and Profibus PA) 16 Calibration mode 5 Alarm 17 Hold mode active 6 Sensocheck—probe error 18 Hourglass (waiting indication) 7 Calibration active 19 Measure mode active 8 Calibration interval 20 Calibration complete 9 Parameter display 21 Calibration—zero or first point 10 Enter prompt 22 Calibration—second point 11 Configuration mode 12 Main display
23 Sensofaces
33
Page 36
Interface and navigation
34
Page 37
Section 5 Operation—4–20 mA/HART
The following section describes how to operate the si792(x) E/T transmitter.

5.1 Measure mode

The display shows the configured process variable (conductivity, concentration, resistivity or salinity) and the temperature value in the measuring mode.
• To return to the measurement mode during calibration press and ENTER.
• To return to the measurement mode during configuration press
CONF and ENTER.
Note: The waiting time for the stabilization of the measured-value is approximately 20 seconds.

5.2 Configuration

Use the configuration mode to specify the sensor, range and other parameters for the system as shown in Table 6.
1. Press CONF and enter 1200 to enter the configuration mode.
2. Use the arrow and enter keys to change the settings. All settings
and options are shown in section 5.2.1, section 5.2.2 and
section 5.2.3.
Table 6 Configuration menu
Code Parameter Passcode
o1 4–20 mA current output
AL. Alarm settings
To exit the configuration mode at any time, press The output current will be held for 20 seconds and the measured value will be displayed.
1200tc Temperature compensation
CONF and ENTER.
CAL
35
Page 38
Operation—4–20 mA/HART
Note: During configuration the transmitter remains in the Hold mode for safety reasons. The loop current is frozen at the value specified in the o1.HoLD menu option. The Sensoface icon is inactive. The configuration mode indicator is displayed (Figure 11 on page 33).

5.2.1 Current output configuration

Select the sensor
2208 SIE (7MA2200 series; default)
si792 T:
o1.SnSR
si792 E:
Enter the cell factor
o1.CELL 0.100–20.000 (3.00 default—si792 T; 4.70 default—si792 E)
Enter the transfer ratio
o1.SFC 1.00–200.00 (68.0 default—si792 T; 25.0 default—si792 E)
Select the temperature sensor
Pt100 (default—si792 T)
o1.rTD
Select the range and units
o1. UnIT
Pt1000 (default—si792 E for GLI/Hach 3700 series sensors) NTC100 NTC30
0.000 mS/cm (si792 T)
00.00 mS/cm
000.0 mS/cm (default) 0000 mS/cm
0.000 S/m
00.00 S/m
000.0 SAL Salinity (SAL)
000.0% Concentration (Conc)
1
1
8398 PM Other 3700 GLI (default) Other
1
Conductivity range and resolution
36
Page 39
Operation—4–20 mA/HART
5.2.1 Current output configuration (continued)
If range is set to 000.0% select solution (Conc)
-01- NaCl (default)
-02- HCI
-03- NaOH
-04- H
2SO4
-05- HNO
o1.ConC
Select characteristic (Linear / Logarithmic curve)
2
o1.CHAR
Specify the value for the 4 and 20 mA signals
o1. 4mA 000.0 mS LIN: Enter current start o1.20mA 000.0 mS LIN: Enter current end o1. 4mA 1 mS (default) LOG: Enter current start o1.20mA 100 mS (default) LOG: Enter current end
Set time averaging filter for reducing noise
o1.FtME 0 SEC (default)
Select a 22 mA signal during errors
o1.FAIL
Signal behavior during HOLD
o1.HOLD
3
-06- H2SO
-07- HCI
-08- HNO
-09- H2SO
-10- NaOH
LIN (default) LOG
ON OFF (default)
LAST (default)
FIX
4
3
4
Solution (Conc) (refer to section B.1 on page 97 for more
information)
Linear/Logarithmic curve
Time constant of output filter (refer to
section 5.2.1.1 for more information)
During HOLD the last measured value is maintained at the output
During HOLD a value (to be entered) is maintained at the output
37
Page 40
Operation—4–20 mA/HART
5.2.1 Current output configuration (continued)
Specify the value to output during HOLD periods
o1.FIX 21.0 mA (default)
1
If “Other” sensor is selected, o1.CELL, o1.SFC and o1.rTD are available
2
If the process variables SAL, % (Conc) or USP are selected the following steps
(Lin/Log) are omitted.
Note: During configuration the instrument/transmitter remains on Hold. Depending on the configuration the loop current is frozen at its last value or at a preset fixed value.
ENTER to access a menu item. Use the ARROW KEYS to edit
Press values. Press
ENTER to save the settings. If a value is outside of the
acceptable range, “Err” will be displayed and the value will not be accepted. To exit the menu and return to the measurement mode, press
CONF and ENTER.
Example: Set the output start point for the 4 mA signal to be 10.0 mS
and the output end point to be 100 mS for the 1.20 mA signal.
1. Press
CONF, enter passcode: 1200. The display will show Conf and
then out.1MNU.
2. Press
3. Press
ENTER to access the output setup menu. The display will
show
CELL.
ENTER, ENTER, ENTER to reach the 4 mA submenu. The
display will show o1.4mA.
4. Use the
UP ARROW and RIGHT ARROW to edit the value to read
10.0 mS value. Press show o1.20mA.
5. Use the
UP ARROW and RIGHT ARROW to edit the value to read
100.0 mS value. Press show o1.FtME.
During HOLD the entered value is maintained at the output (refer to
section 5.2.1.3 for more information)
ENTER to save the value. The display will
ENTER to save the value. The display will
38
Page 41
Operation—4–20 mA/HART
6. Press
5.2.1.1 Time constant of output filter
An averaging filter is available to reduce noise in the output signal. The filter averages readings over a specified time interval. The time interval can be set from 0 to 120 seconds (default: 0 seconds).
When set to 0 seconds, there is no signal averaging for noise reduction. When set to 120 seconds, the current output value will be correspond to the process signal averaged over the last 120 seconds. Increase the time interval to reduce the noise in the output signal.
Note: The filter acts on the output signal but not on the displayed value.
5.2.1.2 Output signal during errors
When an error condition occurs, a 22 mA output signal can be sent as a notification (default: off).
CONF and ENTER to exit the configuration menu.
The transmitter remains in HoLD mode for approximately 20 seconds after calibration and returns to the measurement mode.
39
Page 42
Operation—4–20 mA/HART
5.2.1.3 Output signal during HOLD
The output signal during hold periods can be maintained at the last measured value (Figure 12) or fixed at a specified value (Figure 13). The allowable range for the fixed value is 3.4 to 22 mA.
Figure 12 Output signal during HOLD—last value
1 Output signal during HOLD 2 HOLD mode
Figure 13 Output signal during HOLD—fixed value
1 Output signal during HOLD 2 HOLD mode
40
Page 43
Operation—4–20 mA/HART

5.2.2 Temperature compensation configuration

Select temperature unit
tc.UnIT
Select temperature compensation
tc. LIN
1
If SAL or USP is selected, the following steps are omitted.
Note: Calibrate a temperature sensor adjustment for a correct temperature measurement. Use a separate temperature sensor with fast response for measuring processes with rapid temperature changes.
Press values. Press acceptable range, “Err” will be displayed and the value will not be accepted. To exit the menu and return to the measurement mode, press
CONF and ENTER.
°C (default) °F
1
Linear temperature compensation with entry of temperature coefficient. Reference
Lin (default)
nLF
OFF Temperature compensation turned off
temperature = 25 °C Enter temperature coefficient
02.00%/K (default) (xx.xx%/K) Temperature compensation for naturals
waters to EN 27888
ENTER to access a menu item. Use the ARROW KEYS to edit
ENTER to save the settings. If a value is outside of the
41
Page 44
Operation—4–20 mA/HART

5.2.3 Alarm settings

Select Sensocheck
AL.SnSO
Enter alarm delay
AL.dLY 0010 sec (default) Range: 0–600 sec
LED in Hold mode
AL.LED
CHECK ON CHECK OFF (default)
HOLD ON LED blinks during hold HOLD OFF LED off during hold
Continuous Sensocheck evaluation of sensor function
42
Page 45
Section 6 Operation—Foundation Fieldbus
The following section describes how to navigate and operate the si792x E/T-FF transmitter. The transmitter can be operated as follows:
• Direct interface with the transmitter (section 6.1)
• Foundation Fieldbus communication (section 6.2 on page 47)

6.1 Configuration

Use the configuration mode to specify the sensor, range and other parameters for the system.

6.1.1 Configuration steps

Complete the following steps to configure the si792 transmitter.
1. Press MEAS + CAL and then enter 1200 to enter the configuration
mode.
2. Use the arrow and enter keys to change the settings. All settings
and options are shown in section 6.1.2.
To exit the configuration mode at any time, press MEAS + CAL and
ENTER. The Hold mode will be active for 20 seconds and then the
then measured value will be displayed.
Note: During configuration the transmitter remains in the Hold mode for safety reasons. The Sensoface icon is inactive. The configuration mode indicator is displayed (Figure 11 on page 33).
43
Page 46
Operation—Foundation Fieldbus

6.1.2 Configuration menu

Select the sensor
2208 SIE (7MA2200 series; default)
In.SnSR
Select nominal cell factor (other sensor)
ln.CELL 00.100 – 20.000 (default: 1.980)
Select the transfer ratio (other sensor)
ln.SFC 0010.00 – 2000.00 (default: 120.00)
Select temperature probe (other sensor)
ln.rTD
si792 T:
si792 E:
100 PT (default) 1000 PT 100 NTC 30 NTC
8398 PM Other 3700 GLI (default) Other
44
Page 47
Operation—Foundation Fieldbus
6.1.2 Configuration menu (continued)
Select the variable/unit
0.000 mS/cm
00.00 mS/cm
000.0 mS/cm (default)
0.000 S/m
00.00 S/m
00.00 SAL
ln.UnIT
000.0% ln.CoNC
Select temperature unit
tc.UnIT
Select temperature compensation
tc.
Select Sensocheck
AL.SnSO
°C (default) °F
OFF Temperature compensation turned off
LIN (default)
nLF Natural waters (to EN 27888)
CHECK ON CHECK OFF (default)
Linear temperature compensation Enter temperature coefficient:
Range: 0–19.99%/K (default: 2.00%/K) Reference temperature = 25 °C
Continuous Sensocheck evaluation of sensor function
-01- NaCl (default)
-02- HCl
-03- NaOH
-04- H
-05- HNO
-06- H2SO
-07- HCl
-08- HNO
-09- H2SO
-10- NaOH
2SO4
3
4
3
4
45
Page 48
Operation—Foundation Fieldbus
6.1.2 Configuration menu (continued)
LED in Hold mode
AL.LED
Enter Fieldbus address (optional)
FF.ADR 0017 – 0031 BUS (default: 0026 BUS)
1
Use only when there is no bus connection. The transmitter will restart and set all
parameters to default values. Individual settings must be entered once more.
HOLD ON LED blinks during hold HOLD OFF (default) LED off during hold
1
46
Page 49
Operation—Foundation Fieldbus

6.2 Foundation Fieldbus communication

Use the Foundation Fieldbus specification to set up and configure the si792 transmitter. The communication parameters are listed in the following sections. The sensor can be calibrated as described in
section 6.2.4 on page 63.

6.2.1 Standard resource block (RB)

The standard resource block describes the transmitter characteristics (manufacturer, device name, operating status, global status). The resource block must be in automatic mode for any of the other blocks to operate. The bus parameters for the standard resource block (RB) are shown in Table 7.
Table 7 Bus parameters—resource block (RB)
Parameter Description Default R/W
ST_REV Static revision 0 R TAG_DESC TAG description R/W STRATEGY Strategy 0 R/W ALERT_KEY Alert key 0 R/W
Target OOS R/W
MODE_BLK
BLOCK_ERR Block error R RS_STATE Resource state 1 R TEST_RW Test R/W DD_RESOURCE DD resource R MANUFAC_ID Manufacturer ID 0x001D6D for Hach R
DEV_TYPE Device type
DEV_REV Device revision 1 R DD_REV DD revision 1 R
Actual Permitted OOS, Auto Normal Auto
si792 T: 0068 si792 E: 0066
R
47
Page 50
Operation—Foundation Fieldbus
Table 7 Bus parameters—resource block (RB) (continued)
Parameter Description Default R/W
GRANT_DENY
HARD_TYPES Hardware type 1 R RESTART Restart R/W FEATURES Feature supported Reports/ Soft W Lock R FEATURES Feature selected Reports/ Soft W Lock R/W
CYCLE_TYPE Cycle type
CYCLES_SEL Cycle selected
MIN_CYCLE_T Min cycle time MEMORY_SIZE Memory size R NV_CYCLE_T Non-volatile cycle time R FREE_SPACE Free space R FREE_TIME Free time R SHED_RCAS R/W SHED_ROUT R/W FAULT_STATE Fault state R SET_FSTATE Set fault state 1 R/W CLR_FSTATE Clear fault state 1 R/W MAX_NOTIFY Max notifications 20 R LIM_NOTIFY Limit of notification 8 R/W CONFIRM_TIME Confirmation time WRITE_LOCK Write locking 1 (unlocked) R/W
UPDATE_EVT
Grant 0 R/W Deny 0 R/W
Scheduled/ Block Execution
Scheduled/ Block Execution
1
1600
/32 ms (50 ms)
1
/32 ms
640000
Unacknowledged 0 R/W Update state 0 R Time stamp 0 R Static revision 0 R Relative index 0 R/W
R
R/W
R
R/W
48
Page 51
Operation—Foundation Fieldbus
Table 7 Bus parameters—resource block (RB) (continued)
Parameter Description Default R/W
Unacknowledged R/W
BLOCK_ALM
ALARM_SUM
ACK_OPTION
WRITE_PRI Write priority 0 R/W
WRITE_ALM
ITK_VER ITK_version 4 R
DEVICE_LOCK
Alarm state R Time stamp R Sub-code R Value R Current R Unacknowledged R Unreported R Disabled R/W Automatic acknowledge
option
Unacknowledged R/W Alarm state R Time stamp R Sub-code R Value R
Locks the device for local access.
1 byte Data type = uns8 Range:
0 (unlocked) 1 (locked)
0 (disabled) R/W
0 (unlocked) R/W
49
Page 52
Operation—Foundation Fieldbus

6.2.2 Standard analog input block (AI)

Three Analog Input Function Blocks provide for cyclic transmission of measured values (currently measured value with status, alarm limits, freely selectable process parameter).
6.2.2.1 Operating modes
Use the MODE_BLK parameter to set the following operating modes:
• OOS—out of service. If not write-protected, access to all parameters is allowed.
• MAN—manual
• Auto—online, normal state
6.2.2.2 Set the parameter and units
Use CHANNEL to set the measured parameter and units (Table 8). The corresponding measurement unit is selected in the UNITS subparameter of XD_SCALE (Table 9 on page 52).
Table 8 Measurement parameters and units
Channel Parameter Unit Unit value
µS/cm 1586
1 Conductivity
2 Concentration % (percent) 1342
3 Temperature
4 Salinity ‰ (parts per thousand) 2003 5Resistance MΩ/cm 1587 6 Cell constant
mS/cm 1302 S/cm 1299
°C 1001 °F 1002
cm
-1
2004
50
Page 53
Operation—Foundation Fieldbus
6.2.2.3 Data processing
Use the L_TYPE parameter to apply a linearization function to the data.
• Direct—data is sent directly from the TB to the AI without processing. The units for the XD_SCALE and OUT_SCALE parameters must be identical.
• Indirect—data from the TB is linearly scaled from the input scale (XD_SCALE) to the output scale (OUT_SCALE).
• Indirect square root—data is rescaled from the input scale (XD_SCALE) and recalculated using a root function. Then the value is linearly scaled to the output scale (OUT_SCALE).
6.2.2.4 Alarms
The AI block can generate block alarms and limit alarms. Use the ACK_OPTION parameter to specify if an alarm must be acknowledged. When the measured value status is “bad”, the AI block BLOCK_ERR parameter indicates an Input Failure.
Block alarms—a block error will be reported via the BLOCK_ERR parameter (simulate active, input failure, block configuration error, out of service (OOS)). The BLOCK_ALM parameter sends the alarm status to the control system.
Limit alarms—the measured value OUT falls outside of the limit values (HI_HI_LIM, HI_LIM, LO_LIM, LO_LO_LIM).
If an alarm occurs, evaluate the following bus parameters:
• OUT parameter (currently measured value) in the Al block
• LAST_ERROR parameter in the transducer block
• SENSOFACE_STATUS parameter in the transducer block
51
Page 54
Operation—Foundation Fieldbus
6.2.2.5 Bus parameters for the analog input block
The bus parameters for the analog input function block (AI) are shown in Table 9.
Table 9 Bus parameters/analog input blocks (AI)
Parameter Description Default R/W
ST_REV Static Revision 0 R TAG_DESC TAG Description R/W STRATEGY Strategy 0 R/W ALERT_KEY Alert Key 0 R/W
Targe t O O S
MODE_BLK
BLOCK_ERR Block Error R
PV
OUT
SIMULATE
XD_SCALE
OUT_SCALE
Actual — Permitted OOS, Auto Normal Auto
Process Value R Status R Measured Value R Status R Simulate Status R/W Simulate Value R/W Transducer Status R Transducer Value R Simulate Enable / Disable R/W High Range 100 R/W Low Range 0 R/W Units Index 0 R/W Decimal Point 0 R/W High Range 100 R/W Low Range 0 R/W Units Index 0 R/W Decimal Point 0 R/W
R/W
52
Page 55
Operation—Foundation Fieldbus
Table 9 Bus parameters/analog input blocks (AI) (continued)
Parameter Description Default R/W
GRANT_DENY
IO_OPTS IO Block Options 0 R/W STATUS_OPTS Status Options CHANNEL Channel 1 R/W L_TYPE Linearization Type 0 R/W LOW_CUT Low Cut Off 0 R/W PV_TIME Filter Time 0 R/W
FIELD_VAL
UPDATE_EVT
BLOCK_ALM
ALARM_SUM
ACK_OPTION
AlARM_HYS Alarm Hysteresis 0.50% R/W HI_HI_PRI High High Priority 0 R/W HI_HI_LIM High High Limit INF R/W HI_PRI High Priority 0 R/W HI_LIM High Limit INF R/W LO_PRI Low Priority 0 R/W
Grant 0 R/W Deny 0 R/W
Percent Value R Status R Unacknowledged 0 R/W Update State 0 R Time Stamp 0 R Static Revision 0 R Relative Index 0 R Unacknowledged 0 R/W Alarm State 0 R Time Stamp 0 R Sub-code 0 R Current 0 R Unacknowledged 0 R Unreported 0 R Disabled 0 R/W Automatic Acknowledge
Option
0R/W
53
Page 56
Operation—Foundation Fieldbus
Table 9 Bus parameters/analog input blocks (AI) (continued)
Parameter Description Default R/W
LO_LIM Low Limit –INF R/W LO_LO_PRI Low Low Priority 0 R/W LO_LO_LIM Low Low Limit –INF R/W
Unacknowledged 0 R/W
HI_HI_ALM
HI_ALM
LO_ALM
LO_LO_ALM
Alarm State 0 R Time Stamp 0 R Sub-code 0 R Val ue 0 R Unacknowledged 0 R/W Alarm State 0 R Time Stamp 0 R Sub-code 0 R Val ue 0 R Unacknowledged 0 R/W Alarm State 0 R Time Stamp 0 R Sub-code 0 R Val ue 0 R Unacknowledged 0 R/W Alarm State 0 R Time Stamp 0 R Sub-code 0 R Val ue 0 R
54
Page 57
Operation—Foundation Fieldbus
6.2.2.6 Cyclic measured value status
The cyclic measured value status is shown in Table 10.
Table 10 Cyclic measured value status
Priority Quality Sub-status
Low
Good
Uncertain
Bad
High Out of Service 00 01 11 xx 0 x 1C
Good Non-Specific 10 00 00 00 0 x 80 Good Active Advisory Alarm 10 00 10 xx 0 x 88 Good Active Critical Alarm 10 00 11 xx 0 x 8C Uncertain Non-Specific 01 00 00 xx 0 x 40 Last Usable Value (LUV) 01 00 01 xx 0 x 44 Substitute-Set 01 00 10 xx 0 x 48 Initial Value 01 00 11 xx 0 x 4C Sensor Conversion Not Accurate 01 01 00 xx 0 x 50 Engineering Unit Violation 01 01 01 xx 0 x 54 Sub-Normal 01 01 10 xx 0 x 58 Non-Specific 00 00 00 xx 0 x 00 Sensor Failure 00 01 00 xx 0 x 10 Device Value 00 00 11 xx 0 x 0C
Bin-coding (no limit bits)
6.2.2.7 Measured value limits—limit bits
The respective status bit is set when a condition occurs (Table 11). The status bit is reset when the condition no longer exists.
Table 11 Limit bit description
Bin coding of limit bits Description
00 OK 01 Low-limited 10 High-limited 11 Constant
Hex­coding
55
Page 58
Operation—Foundation Fieldbus
Range
The revision value is
incremented every
time a static parame-
ter in the block is
changed.
Data
type

6.2.3 Transducer block

56
The transducer block provides for acyclic data transmission. Calibration, configuration, and
maintenance commands coming from the control station are processed in the Transducer
Block. The bus parameters for the transducer block (TB) are shown in Table 12 (default values
Table 12 Transducer block parameters
are in bold type).
Parameter Description R/W Bytes
The revision of the static data
associated with the function
R2
block. Used by the host to
determine when to re-read the
static data.
The user description of the
ST_REV
R/W 32 Default: Text
intended application of the
TAG -DE SC
R/W 2 Default: 0
block.
The strategy field can be used
to identify a grouping of blocks.
STRATEGY
Can be used for any purpose
by the user.
R/W 1 Default: 0
Identification number that may
be used by the host system to
ALERT_KEY
sort alarms and other device
information.
Page 59
Range
Data
type
Operation—Foundation Fieldbus
Available modes:
Automatic, Out Of
Service
(OOS), Manual
Default: 0
Default: 0
Table 12 Transducer block parameters (continued)
Parameter Description R/W Bytes
111
R/WRR/W
Allows the user to set the Tar-
get, Permitted, and Normal
device mode. Displays the
1
R/W
Actual mode.
Ta rg e t
Actual
Permitted
Normal
Reflects the error status associ-
ated with the hardware or soft-
MODE_BLK
11822
R2
ware of the block. It is a bit
string so multiple errors may be
shown.
BLOCK_ERR
Unacknowledged Update State
R
Time Stamp Static Rev Relative
Index
UPDATE_EVENT
11821
R
Unacknowledged Alarm State
Time Stamp Subcode Value
BLOCK_ALM
57
Page 60
Operation—Foundation Fieldbus
Default: 65535 =
Range
Data
type
other
0 = 2208 SIE
1 = 8398 PM
2 = Other
0 = 3700 GLI
1 = Other
58
Table 12 Transducer block parameters (continued)
Directory that specifies the
Parameter Description R/W Bytes
R4
number and the starting indices
of the transducers in the trans-
ducer block.
A transducer block sub-code.
TRANSDUCER_
DIRECTORY
TRANSDUCER_TYPE Identifies the transducer type. R 2
R1 Default: 0
XD_ERROR contains the high-
est priority alarm that has been
activated in the
TB_DETAILED_STATUS
parameter.
XD_ERROR
A directory that specifies the
R36
number, starting indices, and
DD item of IDs of the data col-
lection in each transducer
within a transducer block. Used
by the host for efficient transfer
COLLECTION_
DIRECTORY
R/W 1 uns8
R/W 1 uns8
of information.
Selects the connection of the
sensor
Selects the connection of the
sensor
Output
SENSOR_CONNECTION
(si792x T)
SENSOR_CONNECTION
(si792x E)
Page 61
Range
Data
type
Operation—Foundation Fieldbus
4
4
SO
SO
2
2
1 = 0.000 mS/cm
2 = 00.00 mS/cm
3 = 000.0 mS/cm
4 = 0.000 S/m
5 = 00.00 S/m
6 = SAL
7 = 000.0% (Conc)
1 = -01- NaCl
2 = -02- HCl
DS_65
4
1
5 = -05- HNO36 = -06- H
3 = -03- NaOH
4 = -04- H
7 = -07- HCl
8 = -08- HNO39 = -09- H
4
SO
2
10 = -10- NaOH
Table 12 Transducer block parameters (continued)
R
Shows the primary value and
status
Val ue
Status
PRIMARY_VALUE
Parameter Description R/W Bytes
R/W 1 uns16
Selects the displayed primary
value
PRIMARY_VALUE_TYPE
R/W 2 uns8
Selects the solution used for
CONCENTRATION
concentration measurement.
59
Page 62
Operation—Foundation Fieldbus
60
Table 12 Transducer block parameters (continued)
Range
Data
type
Parameter Description R/W Bytes
1001 = °C
1002 = °F
128 = Pt100
200 = Pt1000
1000 = NTC30
1003 = NTC100
0 = TC OFF
1 = TC LIN
2 = TC nLF
00.00 to 19.99%/ K
Default: 2.00%/ K
DS_65
4
1
R
R
R/W 2 uns16
Process temperature value and
status
Val ue
Status
Degree C or degree F. Changes
the unit of temperature being
Temperature
SECONDARY_VALUE_2
SECONDARY_VALUE_
displayed and transmitted.
UNIT_2
Type of temperature sensor.
The value entered must corre-
R/W 2 uns16
TEMP_SENSOR_TYPE
spond to the temp. sensor
being used.
Selects the temperature com-
R/W 1 uns8
R/W 4 float
pensation
Sets the temperature coefficient
if the TEMP_COMPENSATION
TEMP_COMPENSATION
TEMP_COEFFICIENT
is set to Lin
Sets the wire impedance of the
R/W 4 float Default: 0 Ω
temp. sensor. Typically 0 unless
the wire of the sensor gets too
TEMP_WIRE_IMPEDANCE
long
Page 63
Range
Data
type
Operation—Foundation Fieldbus
-10 to +10K
Default: 0
0 to 20.0
Default: 1.98
-0.5 to +0.5 mS
Default: 1.0
1.0 to 200.0
Default: 120.0
0 = Nop
1 = Sample
Default: 0 if step 1 of
product calibration
was not started
0 = Off
1 = On
0 = Off
1 = On
Table 12 Transducer block parameters (continued)
R/W 4 float
Desired temperature reading,
used for temperature measure-
ment calibration.
TEMP_SENSOR_CAL
Calibration
CELL_FACTOR Sets the cell factor. R/W 4 float
Parameter Description R/W Bytes
ZERO Sets the zero value. R/W 4 float
R/W 1 uns8
R4 float
R/W 4 float Default: 0.0
Starts the 1st part of conductiv-
ity product calibration.
Shows the stored value of the
first step of conductivity product
calibration
Sets the value for the 2nd part
of conductivity product calibra-
tion.
TRANSFER_RATIO Sets the transfer ratio. R/W 4 float
CAL_SAMPLE_PRD
CAL_SAMPLE_PRD_
STORED_VAL
CAL_PRODUCT
Alert
HOLD Sets the device to HOLD mode. R/W 1 uns16
R/W 1 uns8
Enables or disables Sensoch-
eck.
SENSOCHECK
61
Page 64
Operation—Foundation Fieldbus
0 = Off
1 = On
0...100
Default: 0 = None
0 = Good
1 = Neutral
R1 uns8
Shows the current status of the
2 = Bad
Sensoface.
Table 12 Transducer block parameters (continued)
Range
Data
type
62
ALARM_LED_MODE Sets the LED to HOLD mode. R/W 1 uns8
LAST_ERROR Shows the last error. R 2 uns16
SENSOFACE_STATUS
Identification and local parameter setting
SW_REV_LEVEL Software revision number R 2 uns16
Parameter Description R/W Bytes
HW_REV_LEVEL Hardware revision number R 1 uns8
Page 65
Operation—Foundation Fieldbus

6.2.4 Calibration via Foundation Fieldbus

The transmitter can be calibrated via Foundation Fieldbus using the comparison or grab sample method.
1. Make sure the system is configured for conductivity (PRIMARY_VALUE_TYPE = mS/cm or S/m).
2. Collect a grab sample and set CAL_SAMPLE_PRD to sample. The conductivity value of the sample is stored. After writing, the parameter is automatically reset to NOP (no operation).
3. Read the parameter CAL_SAMPLE_PRD_STORED_VAL. It contains the stored value.
4. Measure the grab sample and write the lab value in CAL_PRODUCT. The device is now calibrated. CAL_SAMPLE_PRD_STORED_VAL is reset to zero.
63
Page 66
Operation—Foundation Fieldbus
64
Page 67
Section 7 Operation—Profibus PA
The following section describes how to navigate and operate the si792x Profibus-PA transmitter. The transmitter can be operated as follows:
• direct interface with the transmitter (section 7.1)
• remote operation from the control station (section 7.2 on
page 67)
Note: Calibration must be completed by direct interface with the transmitter.

7.1 Configuration

Use the configuration mode to specify the sensor, range and other parameters for the system.

7.1.1 Configuration steps

Complete the following steps to configure the si792 transmitter.
1. Press MEAS + CAL and then enter 1200 to enter the configuration mode.
2. Use the arrow and enter keys to change the settings. All settings and options are shown in section 7.1.2.
To exit the configuration mode at any time, press MEAS + CAL and then
ENTER. The Hold mode will be active for 20 seconds and then the
measured value will be displayed.
Note: During configuration the transmitter remains in the Hold mode for safety reasons. The Sensoface icon is inactive. The configuration mode indicator is displayed (Figure 11 on page 33).
65
Page 68
Operation—Profibus PA

7.1.2 Configuration menu

Select the range and units
0.000 mS
00.00 mS
000.0 mS (default) 0000 mS
-01- NaCl (default)
-02- HCl
000.0%
000.0 SAL
Select temperature unit
°C (default) °F
Select temperature sensor
100 PT (default) 1000 PT 30 NTC 100 NTC busEXT (external temp during measurement; manual temp during
calibration, °C)
Select temperature compensation
OFF Temperature compensation turned off
tc
LIN (default)
nLF
-03- NaOH
-04- H
-05- HNO
-06- H2SO4 (95 – 99% by weight)
1
Linear temperature compensation with entry of temperature coefficient (00.00–19.99%/ K). Reference temperature = 25 °C.
Enter temperature coefficient
02.00%/K (default) (xx.xx%/K) Temperature compensation for naturals
waters to EN 27888
(0 – 35% by weight)
2SO4
3
66
Page 69
Operation—Profibus PA
7.1.2 Configuration menu (continued)
Select Sensocheck
CHECK ON CHECK OFF (default)
Enter Profibus address
Edit 0001–0126 BUS (default: 0126)
1
Temperature compensation is not available for salinity.
2
Use only when there is no bus connection. The transmitter will restart and set all
parameters to default values. Individual settings must be entered once more.
2
Continuous Sensocheck evaluation of sensor function

7.2 Profibus PA communication

Profibus uses a master/slave data exchange technique. The master (typically a PLC) generates queries to individual slaves. The slaves, in turn, reply back with a response to the master. A Profibus message contains the information required to send a query or request, including the slave address, function code, data, and a checksum. See Table 13
on page 68 for Profibus communication parameters in case of errors.
67
Page 70
Operation—Profibus PA
Logbook
(default)
68
Table 13 PROFIBUS communication
Text of binary message
Physical Block
No. of
(default)
(PB)
Analog input
status
binary
message
Cause
CHK SLOPE Yes
Global status
1 0000 11xx Failure ERR SYSTEM Yes
2 0000 11xx Failure ERR PARAMETERS Yes
3 0000 11xx Failure ERR MEMORY Yes
Factory settings
defective
Configuration data
defective, Gaincheck
Memory error
(RAM, ROM,
EPROM)
Failure ERR COND VALUE Yes
Failure ERR TEMP VALUE Yes
Failure CHK SENSOR Yes
Maintenance
req.
Function check CAL RUNNING Yes
0100 0111
01 00 1111
0100 0111
01 00 1111
0100 0111
01 00 1111
0100 0111
01 00 1111
4 0101 01xx Failure ERR MEAS VALUE Yes
5
6
Cond, sal range
violation
Conductance range
violation
Temp range violation
Temperature probe
Sensocheck 7
Cell constant 8 1010 01xx
Calibration 9
Configuration 10 1010 00xx Function check CONF RUNNING Yes
Page 71
Table 13 PROFIBUS communication (continued)
Logbook
Text of binary message
Physical Block
Analog input
No. of
(default)
(default)
(PB)
Global status
status
binary
message
Operation—Profibus PA
LO_LIMIT SAL
LO_LO_LIMIT COND
LO_LO_LIMIT MOcm
LO_LO_LIMIT SAL
HI_HI_LIMIT TEMP
HI_LIMIT TEMP
Limit 2
17 1000 1010
Bit 2
Limit 2
LO_LIMIT TEMP
Bit 3
18 1000 1001
HI_HI_LIMIT COND
HI_HI_LIMIT MOcm
HI_HI_LIMIT SAL
HI_LIMIT COND
HI_LIMIT MΩ cm
HI_LIMIT SAL
LO_LIMIT COND
LO_LIMIT MΩ cm
Limit 1
Bit 4
Limit 2
Function check HOLD X
Limit 1
Bit 1
Limit 1
Bit 2
Limit 1
Bit 3
0100 0111
01 00 1111
11
12 1000 1110
13 1000 1010
14 1000 1001
15 1000 1101
Bit 1
16 1000 1110
Cause
HOLD
(Device state =
Maintenance)
HI_HI_LIM
FB analysis
Cond/MO/SAL
HI_LIM
FB analysis
Cond/MO/SAL
LO_LIM
FB analysis
Cond/MO/SAL
LO_LO_LIM
FB analysis
Cond/MO/SAL
HI_HI_LIM
FB temperature
HI_LIM
FB temperature
LO_LIM
FB temperature
69
Page 72
Operation—Profibus PA
Logbook
(default)
LO_LO_LIMIT TEMP
Text of binary message
(default)
Limit 2
(PB)
Global status
status
binary
message
Bit 4
19 1000 1101
Table 13 PROFIBUS communication (continued)
Physical Block
Analog input
No. of
70
Cause
LO_LO_LIM
FB temperature
Logbook empty 20 Function check EMPTY LOGBOOK
Page 73

Section 8 Calibration

8.1 Calibration

Important Note: Use a thermometer to make sure that the displayed temperature is accurate.
Important Note: Enter the sensor data in the configuration menu before calibration.
Important Note: The transmitter must be calibrated each time a new sensor is connected.
Important Note: If measurements are taken in an area with a cross­section < 110 mm, use a calibration beaker with the same size and material (metal/plastic).
Note: Only qualified personnel should conduct the tasks described in this section of the manual.
The transmitter is adjusted to the sensor through the calibration. Use the following methods and passcodes for calibration as described in
Table 14.
Table 14 Methods and passcodes for calibration
Method Passcode
Display calibration information 0000 Enter cell constant 1100 Calibration with a known calibration solution Calibration by product comparison/grab sample Zero calibration in air Zero calibration with calibration solution Temperature sensor calibration 1015
1 Not available for Profibus PA and Foundation Fieldbus versions.
During calibration the transmitter remains in the Hold mode for safety reasons. The loop current is frozen at the value specified in the
0110 110 5
1001
1
1
71
Page 74
Calibration
o1.HoLD menu option. The Sensoface icon is inactive. The calibration mode indicator is displayed (Figure 11 on page 33).
To exit the calibration mode at any time, press The output current will be held for 20 seconds and the measured value will be displayed.

8.1.1 Enter cell constant

1. Press CAL, enter passcode: 1100, ENTER. CAL CELL will be
displayed for 3 seconds.
2. Use the cell constant of the connected sensor. The conductivity value will be displayed also.
Note: A cell constant change will change the conductivity value.
Note: If the entry of the cell constant takes longer than 6 seconds,
the display will alternate between showing the conductivity and temperature value.
3. Press
4. The transmitter displays the cell constant value and CELL. Press
ENTER.
5. The transmitter remains in HoLD mode. Press ENTER again.
Note: Repeat the calibration when “Err” is displayed.
UP ARROW and RIGHT ARROW to enter the value of the
ENTER to save the value.
The transmitter remains in HoLD mode for approximately 20 seconds after calibration and returns to the measure mode.
CAL and then ENTER.
72
Page 75
Calibration

8.1.2 Calibration with a calibration solution

Use a calibration solution with a known conductivity value to adjust the transmitter to show the same value as the solution.
Note: Stabilize the temperature during calibration.
1. Press
2. Remove and clean the sensor.
3. Immerse the sensor in the calibration solution.
4. Use the
5. Press
6. The display will show the new cell constant. Press
7. The transmitter remains in HoLD mode. Press
Note: Repeat the calibration when “Err” is displayed.
CAL, enter passcode: 0110, ENTER. CAL SOL will be
displayed for 3 seconds. The transmitter is ready for calibration.
UP ARROW and RIGHT ARROW to enter the known value of
the calibration solution.
Note: If the entry of the calibration solution value takes longer than 6 seconds, the display will alternate between showing the cell constant and the temperature value.
ENTER to save the value.
ENTER.
ENTER again.
The transmitter remains in HoLD mode for approximately 20 seconds after calibration and returns to the measure mode.
The display will show the temperature-corrected value of the calibration solution (unless temperature compensation is set to off in the configuration menu).
73
Page 76
Calibration

8.1.3 Calibration by comparison/grab sample

The sensor can be calibrated by measuring the process water with a portable instrument or taking a grab sample and measuring its value in the lab (one-point calibration). The sensor does not need to be removed from the process during calibration. The sample temperature should correspond to the measured process temperature for accurate results.
Note: The calibration by comparison option is not available when the selected range and units is set to 000.0%.
1. Press
2. Measure the process water with a portable instrument or collect a
3. Measure the grab sample with a laboratory or portable meter.
4. Press
5. Edit the displayed value to match the value measured by the
6. Press
Press in the hold mode for approximately 20 seconds.
Note: For comparison calibration via Foundation Fieldbus, see
section 6.2.4 on page 63.
CAL, enter passcode: 1105, ENTER. The display will briefly
show CAL PRD and then StorE.
grab sample for measurement in the lab. Press
The cal mode indicator will flash to indicate that calibration has not been completed. The transmitter will continue to measure and display the current sample values.
CAL, enter passcode: 1105, ENTER to access the product
calibration once more. The display will briefly show CAL PRD and then CALC.
laboratory or portable meter and press show the new cell constant.
ENTER to end the calibration. The display will show the
measured value alternating with Hold.
ENTER to return to the measuring mode. The outputs will remain
ENTER to proceed.
ENTER. The display will
74
Page 77
Calibration
8.1.4 Zero calibration—air
1. Press CAL, enter passcode: 1001, ENTER. CAL ZRO will be
displayed for 3 seconds.
2. Remove and clean the sensor.
Note: Make sure that the sensor is dry.
3. Use the zero is displayed as the conductivity value.
Note: If the entry of the zero point value takes longer than 6 seconds, the display will alternate between showing the conductivity value and the temperature value.
4. Press
5. The display will show the new cell constant value and the zero point.
Press ENTER to confirm.
6. Immerse the sensor in the process water.
7. The transmitter remains in HoLD mode. Press
Note: Repeat the calibration when “Err” is displayed.
8.1.5 Zero calibration—calibration solution
Use a calibration solution with low conductivity for calibration.
1. Press CAL, enter passcode: 1001, ENTER. CAL ZRO will be displayed for 3 seconds.
2. Remove and clean the sensor.
3. Immerse the sensor in the calibration solution.
4. Use the the conductivity value of the calibration solution is displayed.
UP ARROW and RIGHT ARROW to change the value until
ENTER to confirm.
ENTER again.
The transmitter remains in HoLD mode for approximately 20 seconds after calibration and returns to the measure mode.
UP ARROW and RIGHT ARROW to change the value until
75
Page 78
Calibration
Note: If the entry of the zero point value takes longer than 6 seconds, the display will alternate between showing the conductivity value and the temperature value.
5. Press
6. The display will show the new cell constant value and the zero point.
7. Remove and clean the sensor from the calibration solution.
8. Immerse the sensor in the process water.
9. The transmitter remains in HoLD mode. Press
Note: Repeat the calibration when “Err” is displayed.
ENTER to confirm.
Press ENTER to confirm.
ENTER again.
The transmitter remains in HoLD mode for approximately 20 seconds after calibration and returns to the measure mode.

8.2 Temperature sensor adjustment

1. Press CAL, enter passcode: 1015, ENTER. CALTMP will be
displayed for 3 seconds. The transmitter is ready for calibration.
2. Measure the process temperature with a thermometer.
3. Use the
measured temperature from the external thermometer.
4. Press
5. The transmitter remains in HoLD mode. Press
Note: Repeat the calibration when “Err” is displayed.
UP ARROW and RIGHT ARROW to enter the value of the
ENTER to save the value.
ENTER again.
The transmitter remains in HoLD mode for approximately 20 seconds after calibration and returns to the measure mode.
76
Page 79

Section 9 Maintenance

DANGER
Explosion hazard. Only qualified personnel should conduct the tasks described in this section of the manual.
DANGER Electrostatic hazard. Follow the instructions in Electrostatic
Discharge (ESD) Considerations on page 20 before conducting
any maintenance tasks.

9.1 Cleaning the instrument

Use only a moistened antistatic, lint-free cloth to remove dust, dirt and spots from the external surfaces of the transmitter. Use a mild household cleaner if necessary.

9.2 Sensor maintenance

Refer to the user manual supplied with each sensor for specific cleaning requirements.
77
Page 80
Maintenance
78
Page 81

Section 10 Troubleshooting

10.1 Sensoface

The Sensoface feature is active whenever Sensocheck is active. This feature monitors the sensor for defects in the sensor or cable, and indicates the maintenance status of the sensor (see Table 15).
Table 15 Sensoface description
Sensoface Description
The sensor is operating properly.
The operation of the sensor is acceptable, but will require replacement soon.
The sensor is no longer usable. Replace the sensor.

10.2 Sensocheck

The Sensocheck feature monitors the primary and secondary coil for short and open circuits. When problems are detected, the error message “Err 33” (“Err 34”) is displayed, along with an icon corresponding to the type of problem (see Table 16).
Sensocheck can be switched off during configuration and Sensoface is also disabled.
Note: For confirmation a sensoface is displayed after a calibration setting.
79
Page 82
Troubleshooting
Table 16 Error descriptions
Display Problem Description
Sensor is defective
Temperature
error
Test the primary (send) coil Test the secondary (receive) coil Refer also to Err 33 and Err 34 (Table 17). Make sure that the measured temperature is within
the range of the temperature compensation table (temperature compensation, concentration, salinity)

10.3 Error codes

Table 17 describes transmitter errors and parameter-specific errors.
Table 17 Error codes
Code Description Corrective action
Make sure that the entered cell constant is correct.
Make sure that the range
ERR 01 measured value flashes
ERR 02 measured value flashes
setting is correct. Make sure that the SAL
value is < 45‰ Test the sensor connection or
replace cables. Make sure that the
conductance range is <3000mS
80
Page 83
Troubleshooting
Table 17 Error codes (continued)
Code Description Corrective action
Test the temperature sensor wiring.
Make sure that the correct temperature sensor was selected in the configuration menu (GLI/Hach 3700 series sensors use Pt1000).
Measure the resistance of the temperature sensor in the sensor to make sure of a correct reading. For GLI/ Hach 3700 series sensors, the resistance between red and yellow wires should be between 1090–1105 ohms at 23–27 °C.
Check the loop power supply voltage to the transmitter.
Measure the loop power supply voltage to the transmitter.
Make sure that the 4–20 mA output range settings cover a wide enough range and are correct (see section 5.2.1
on page 36)
Test the primary (send) coil
Make sure that the temperature is within the range of the temperature compensation table (temperature compensation, concentration, salinity)
ERR 03
ERR 11
ERR 12
ERR 13
ERR 33
Temperature sensor icon flashes; open or short circuit; temperature range exceeded
Current output icon flashes; current is below 3.8 mA
Current output icon flashes; current is above 20.5 mA
Current output icon flashes; reading range value set too large or too small
Sensocheck icon flashes; Sensoface icon active (see
section 10.2)
Temperature icon flashes; independent of Sensoface icon (see section 10.2)
81
Page 84
Troubleshooting
Table 17 Error codes (continued)
Code Description Corrective action
ERR 34 Sensocheck icon flashes;
ERR 98
ERR 99
Sensoface icon active (see
section 10.2)
CONF flashes; configuration or calibration data is defective. Memory error in the program.
FAIL flashes; EEPROM or RAM defective
Test the secondary (receive) coil
Reconfigure and calibrate the device.
Return to the factory for repair and calibration.

10.4 Diagnostic tests

Function Description
View the output current
View calibration data
View sensor monitor for validation
View the last error message
From the measuring mode, press current will show in the main display for five seconds, then return to measuring mode.
From the measuring mode, press passcode ‘0000’. The cell constant will show in the main display. After 20 seconds, the transmitter will return to the measuring mode, or press the measuring mode.
From the measuring mode press ‘2222’ for the validation of the sensor and a complete measured-value processing. The measured resistance is shown in the main display and the measuring temperature is shown in the lower display. Press immediately to the measuring mode.
Press CONF and enter passcode "0000". The last error message is displayed for approximately 20 seconds.
CAUTION The transmitter does not go automatically to Hold mode.
ENTER. The output
CAL and then enter
ENTER to return immediately to
CONF and enter passcode
ENTER to return
82
Page 85
Troubleshooting
10.4 Diagnostic tests (continued)
Function Description
CONF and enter passcode
RIGHT ARROW key.
UP ARROW key.
CONF, then ENTER to return to
Specify output current
From the measuring mode, press ‘5555’. The measured current will show in the secondary display. The output current in the main display can be modified.
To change the output current:
1. Select the current value with the
2. Edit the number using the
3. Press
ENTER to confirm. The entered value will show in
the secondary display. The transmitter will remain in Hold mode.
4. To exit Hold mode, press measuring mode.
83
Page 86
Troubleshooting
84
Page 87

Section 11 Replacement parts

11.1 si792 transmitter versions

Description Catalog number
si792(x) E versions (for Hach GLI 3700 series)
si792 E, inductive conductivity, CID2 LXV503.99.70002 si792x E, inductive conductivity, CID1; ATEX Zone 1 LXV503.99.70102 si792x E-PA, inductive conductivity, CID1; ATEX Zone 1 LXV503.99.76102 si792x E-FF, inductive conductivity, CID1; ATEX Zone 1 LXV503.99.77102
si792(x) T versions (e.g. for 7MA2200 and 8398 series)
si792 T, inductive conductivity, CID2 LXV502.99.70002 si792x T, inductive conductivity, CID1; ATEX Zone 1 LXV502.99.70102 si792x T-PA, inductive conductivity, CID1; ATEX Zone 1 LXV502.99.76102 si792x T-FF, inductive conductivity, CID1; ATEX Zone 1 LXV502.99.77102

11.2 Accessories

Description Catalog number
Complete Documentation CD, si792 series Panel-Mount Installation Kit, si792 LZY484 Pipe-Mount Installation Kit, si792 LZY483 Protective Hood, si792 LZY485 User Manual, si792 E and si792 T, ind. conductivity, English DOC026.52.00796

11.3 Replacement parts

Description Catalog number
Installation Kit, si792, LZY486 Rear Housing, si792, LZY487
85
Page 88
Replacement parts
86
Page 89

Section 12 Contact information

HACH Company World Headquarters
P.O. Box 389 Loveland, Colorado 80539-0389 U.S.A. Tel (800) 227-HACH (800) 227-4224 (U.S.A. only) Fax (970) 669-2932 orders@hach.com www.hach.com
Repair Service in Latin America, the Caribbean, the Far East, Indian Subcontinent, Africa, Europe, or the Middle East:
Hach Company World Headquarters, P.O. Box 389 Loveland, Colorado, 80539-0389 U.S.A. Tel +001 (970) 669-3050 Fax +001 (970) 669-2932 intl@hach.com
HACH LANGE LTD
Unit 1, Chestnut Road Western Industrial Estate IRL-Dublin 12 Tel. +353(0)1 46 02 5 22 Fax +353(0)1 4 50 93 37 info@hach-lange.ie www.hach-lange.ie
Repair Service in the United States:
HACH Company Ames Service 100 Dayton Avenue Ames, Iowa 50010 Tel (800) 227-4224 (U.S.A. only) Fax (515) 232-3835
HACH LANGE GMBH
Willstätterstraße 11 D-40549 Düsseldorf Tel. +49 (0)2 11 52 88-320 Fax +49 (0)2 11 52 88-210 info@hach-lange.de www.hach-lange.de
DR. BRUNO LANGE GES. MBH
Industriestraße 12 A-3200 Obergrafendorf Tel. +43 (0)27 47 74 12 Fax +43 (0)27 47 42 18 info@hach-lange.at www.hach-lange.at
Repair Service in Canada:
Hach Sales & Service Canada Ltd. 1313 Border Street, Unit 34 Winnipeg, Manitoba R3H 0X4 Tel (800) 665-7635 (Canada only) Tel (204) 632-5598 Fax (204) 694-5134 canada@hach.com
HACH LANGE LTD
Pacific Way Salford GB-Manchester, M50 1DL Tel. +44 (0)161 872 14 87 Fax +44 (0)161 848 73 24 info@hach-lange.co.uk www.hach-lange.co.uk
DR. BRUNO LANGE AG
Juchstrasse 1 CH-8604 Hegnau Tel. +41(0)44 9 45 66 10 Fax +41(0)44 9 45 66 76 info@hach-lange.ch www.hach-lange.ch
87
Page 90
Contact information
HACH LANGE FRANCE S.A.S.
33, Rue du Ballon F-93165 Noisy Le Grand Tél. +33 (0)1 48 15 68 70 Fax +33 (0)1 48 15 80 00 info@hach-lange.fr www.hach-lange.fr
HACH LANGE APS
Åkandevej 21 DK-2700 Brønshøj Tel. +45 36 77 29 11 Fax +45 36 77 49 11 info@hach-lange.dk www.hach-lange.dk
HACH LANGE S.L.U.
Edif. Arteaga Centrum C/Larrauri, 1C- 2ª Pl. E-48160 Derio/Vizcaya Tel. +34 94 657 33 88 Fax +34 94 657 33 97 info@hach-lange.es www.hach-lange.es
HACH LANGE S.R.O.
Lešanská 2a/1176 CZ-141 00 Praha 4 Tel. +420 272 12 45 45 Fax +420 272 12 45 46 info@hach-lange.cz www.hach-lange.cz
HACH LANGE SA
Motstraat 54 B-2800 Mechelen Tél. +32 (0)15 42 35 00 Fax +32 (0)15 41 61 20 info@hach-lange.be www.hach-lange.be
HACH LANGE AB
Vinthundsvägen 159A SE-128 62 Sköndal Tel. +46 (0)8 7 98 05 00 Fax +46 (0)8 7 98 05 30 info@hach-lange.se www.hach-lange.se
HACH LANGE LDA
Av. do Forte nº8 Fracção M P-2790-072 Carnaxide Tel. +351 214 253 420 Fax +351 214 253 429 info@hach-lange.pt www.hach-lange.pt
HACH LANGE KFT.
Hegyalja út 7-13. H-1016 Budapest Tel. +36 (06)1 225 7783 Fax +36 (06)1 225 7784 info@hach-lange.hu www.hach-lange.hu
DR. LANGE NEDERLAND B.V.
Laan van Westroijen 2a NL-4003 AZ Tiel Tel. +31(0)344 63 11 30 Fax +31(0)344 63 11 50 info@hach-lange.nl www.hach-lange.nl
HACH LANGE S.R.L.
Via Riccione, 14 I-20156 Milano Tel. +39 02 39 23 14-1 Fax +39 02 39 23 14-39 info@hach-lange.it www.hach-lange.it
HACH LANGE SP.ZO.O.
ul. Opolska 143 a PL-52-013 Wrocław Tel. +48 (0)71 342 10-83 Fax +48 (0)71 342 10-79 info@hach-lange.pl www.hach-lange.pl
HACH LANGE S.R.L.
Str. Leonida, nr. 13 Sector 2 RO-020555 Bucuresti Tel. +40 (0) 21 201 92 43 Fax +40 (0) 21 201 92 43 info@hach-lange.ro www.hach-lange.ro
88
Page 91
HACH LANGE
8, Kr. Sarafov str. BG-1164 Sofia Tel. +359 (0)2 963 44 54 Fax +359 (0)2 866 04 47 info@hach-lange.bg www.hach-lange.bg
ΗΑCH LANGE E.Π.Ε.
Αυλίδος 27 GR-115 27 Αθήνα Τηλ . +30 210 7777038 Fax +30 210 7777976 info@hach-lange.gr www.hach-lange.gr
Contact information
HACH LANGE SU ANALİZ SİSTEMLERİ LTD .ŞTİ.
Hilal Mah. 75. Sokak Arman Plaza No: 9/A TR-06550 Çankaya/ ANKARA Tel. +90 (0)312 440 98 98 Fax +90 (0)312 442 11 01 bilgi@hach-lange.com.tr www.hach-lange.com.tr
HACH LANGE E.P.E.
27, Avlidos str GR-115 27 Athens Tel. +30 210 7777038 Fax +30 210 7777976 info@hach-lange.gr www.hach-lange.gr
HACH LANGE D.O.O.
Fajfarjeva 15 SI-1230 Domžale Tel. +386 (0)59 051 000 Fax +386 (0)59 051 010 info@hach-lange.si www.hach-lange.si
89
Page 92

Section 13 Warranty, liability and complaints

The manufacturer warrants that the product supplied is free of material and manufacturing defects and undertakes the obligation to repair or replace any defective parts at zero cost.
The warranty period for instruments is 24 months. If a service contract is taken out within 6 months of purchase, the warranty period is extended to 60 months.
With the exclusion of the further claims, the supplier is liable for defects including the lack of assured properties as follows: all those parts that can be demonstrated to have become unusable or that can only be used with significant limitations due to a situation present prior to the transfer of risk, in particular due to incorrect design, poor materials or inadequate finish will be improved or replaced, at the supplier's discretion. The identification of such defects must be notified to the supplier in writing without delay, however at the latest 7 days after the identification of the fault. If the customer fails to notify the supplier, the product is considered approved despite the defect. Further liability for any direct or indirect damages is not accepted.
If instrument-specific maintenance and servicing work defined by the supplier is to be performed within the warranty period by the customer (maintenance) or by the supplier (servicing) and these requirements are not met, claims for damages due to the failure to comply with the requirements are rendered void.
Any further claims, in particular claims for consequential damages cannot be made.
Consumables and damage caused by improper handling, poor installation or incorrect use are excluded from this clause.
The manufacturer process instruments are of proven reliability in many applications and are therefore often used in automatic control loops to provide the most economical possible operation of the related process.
90
Page 93
Warranty, liability and complaints
To avoid or limit consequential damage, it is therefore recommended to design the control loop such that a malfunction in an instrument results in an automatic change over to the backup control system; this is the safest operating state for the environment and the process.
91
Page 94
Warranty, liability and complaints
92
Page 95

Appendix A Calibration solutions

Note: Use the tables in this section to calibrate the transmitter when automatic temperature compensation is set to off.
Table 18 Potassium Chloride solutions (Conductivity in mS/cm)
Temperature
°C °F 0.01 mol/L 0.1 mol/L 1 mol/L
0 32 0.776 7.15 65.41
5 41 0.896 8.22 74.14 10 50 1.02 9.33 83.19 15 59 1.147 10.48 92.52 16 60.8 1.173 10.72 94.41 17 62.6 1.199 10.95 96.31 18 64.4 1.225 11.19 98.22 19 66.2 1.251 11.43 100.14 20 68 1.278 11.67 102.07 21 69.8 1.305 11.91 104 22 71.6 1.332 12.15 105.94 23 73.4 1.359 12.39 107.89 24 75.2 1.386 12.64 109.84 25 77 1.413 12.88 111.8 26 78.8 1.441 13.13 113.77 27 80.6 1.468 13.37 115.74 28 82.4 1.496 13.62 29 84.2 1.524 13.87 30 86 1.552 14.12 31 87.8 1.581 14.37 32 89.6 1.609 14.62 33 91.4 1.638 14.88 34 93.2 1.667 15.13 35 95 1.696 15.39 36 96.8 15.64
Concentration
1
93
Page 96
Calibration solutions
1Data source: K. H. Hellwege (Editor), H. Landolt, R. Börnstein: Zahlenwerte und Funktionen ..., volume 2, part. volume 6
Table 19 Sodium Chloride solutions (Conductivity in mS/cm)
Temperature Concentration
°C °F
0 32 0.631 5.786 134.5 1 33.8 0.651 5.965 138.6 2 35.6 0.671 6.145 142.7 3 37.4 0.692 6.327 146.9 4 39.2 0.712 6.51 151.2 5 41 0.733 6.695 155.5 6 42.8 0.754 6.881 159.9 7 44.6 0.775 7.068 164.3 8 46.4 0.796 7.257 168.8
9 48.2 0.818 7.447 173.4 10 50 0.839 7.638 177.9 11 51.8 0.861 7.831 182.6 12 53.6 0.883 8.025 187.2 13 55.4 0.905 8.221 191.9 14 57.2 0.927 8.418 196.7 15 59 0.95 8.617 201.5 16 60.8 0.972 8.816 206.3 17 62.6 0.995 9.018 211.2 18 64.4 1.018 9.221 216.1 19 66.2 1.041 9.425 221 20 68 1.064 9.631 226 21 69.8 1.087 9.838 231 22 71.6 1.111 10.047 236.1 23 73.4 1.135 10.258 241.1 24 75.2 1.159 10.469 246.2 25 77 1.183 10.683 251.3
0.01 mol/L
1
0.1 mol/L1Saturated
2
94
Page 97
Calibration solutions
Table 19 Sodium Chloride solutions (Conductivity in mS/cm)
Temperature Concentration
°C °F
26 78.8 1.207 10.898 256.5 27 80.6 1.232 11.114 261.6 28 82.4 1.256 11.332 266.9 29 84.2 1.281 11.552 272.1 30 86 1.306 11.773 277.4 31 87.8 1.331 11.995 282.7 32 89.6 1.357 12.22 288 33 91.4 1.382 12.445 293.3 34 93.2 1.408 12.673 298.7 35 95 1.434 12.902 304.1 36 96.8 1.46 13.132 309.5
1Data source: Test solutions calculated according to DIN IEC 746-3 2Data source: K. H. Hellwege (Editor), H. Landolt, R. Börnstein: Zahlenwerte und Funktionen ..., volume 2, part. volume 6
0.01 mol/L
1
0.1 mol/L1Saturated
2
95
Page 98
Calibration solutions
96
Page 99

Appendix B Concentration curves

B.1 Concentration measurement ranges

For the solutions listed in Table 20, the transmitter determines the concentration from the measured conductivity and temperature values in % by weight.
The measurement error is made up of the sum of measurement and the stored accuracy of the concentration curves.
Note: The transmitter must be calibrated each time a new sensor is connected.
Note: Calibrate a temperature sensor adjustment for a correct temperature measurement.
Note: Use a separate temperature sensor with fast response for measuring processes with rapid temperature changes.
97
Page 100
Concentration curves
Table 20 Concentration ranges
Substance Solution Range (% by weight) Temperature
NaCl -01-
-02-
HCl
-07-
-03-
NaOH
-10-
-04-
H
2SO4
HNO
3
-09-
-06-
-05-
-08-
0–26% 0 °C 0–28% 100 °C (212 °F) 0–18% –20 °C (–4 °F) 0–18% 50 °C (122 °F) 22–39% –20 °C (–4 °F) 22–39% 50 °C (122 °F) 0–13% 0 °C (32 °F) 0–24% 100 °C (212 °F) 15–50% 0 °C (32 °F) 35–50% 100 °C (212 °F) 0–26% –17 °C (1.4 °F) 0–37% 110 °C (230 °F) 28–88% –17 °C (1.4 °F) 39–88% 115 °C (239 °F) 94–99% –17 °C (1.4 °F) 89–99% 115 °C (239 °F) 0–30% –17 °C (1.4 °F) 0–30% 50 °C (122 °F) 35–96% –20 °C (–4 °F) 35–96% 50 °C (122 °F)
98
Loading...