Hach-Lange SI792 D, SI792x D, SI792x D-FF, SI792x D-PA User Manual

Page 1
DOC026.52.00797
si792 D
si792x D
si792x D-FF
si792x D-PA
Dissolved Oxygen
2-Wire Transmitters
USER MANUAL
© HACH Company, 2007. All rights reserved. Printed in Germany
Page 2
2
Page 3

Table of Contents

Section 1 Specifications ......................................................... 5
Section 2 General Information...........................................11
2.1 Safety information ....................................................................11
2.1.1 Use of hazard information ................................................. 11
2.1.2 Precautionary labels.......................................................... 11
2.2 General product information..................................................... 13
2.2.1 Product overview............................................................... 13
2.2.2 FDA 21 CFR part 11 Compliance (HART only)................. 13
2.2.2.1 Electronic signatures for si792(x) D transmitters ....... 14
2.2.2.2 Audit trail for si792(x) D transmitters.......................... 14
Section 3 Installation ..............................................................15
3.1 Hazardous location................................................................... 16
3.2 Unpacking the transmitter ........................................................16
3.3 Mechanical installation ............................................................. 18
3.3.1 Transmitter assembly........................................................ 18
3.3.2 Mounting ........................................................................... 18
3.3.2.1 Wall mount ................................................................. 18
3.3.2.2 Panel or pipe mount (optional) ................................... 18
3.4 Wiring Safety Information......................................................... 20
3.5 Electrical installation................................................................. 21
3.5.1 Wire preparation................................................................ 21
3.5.2 Power and communication connections............................ 23
3.5.2.1 si792(x) D (4–20 mA/HART) wiring............................ 24
3.5.2.2 si792x D-FF and si792x D-PA wiring .........................25
3.5.3 Sensor wire connection..................................................... 25
3.5.3.1 Oxygold G/Oxyferm sensor—si792(x) D (4–20 mA/
HART) ................................................................................. 26
3.5.3.2 Oxygold G/Oxyferm sensor—si792x D-FF or si792x D-
PA .......................................................................................27
3.5.3.3 Oxysens sensor—si792(x) D (4–20 mA/HART)......... 28
3.5.3.4 Oxysens sensor—si792x D-FF and si792x D-PA ......29
3.6 HART communication connection............................................ 30
1
Page 4
Table of Contents
Section 4 Interface and navigation .................................. 31
4.1 si792(x) D (4–20 mA/HART) interface...................................... 31
4.2 si792x D-FF and si792x D-PA interface ................................... 32
4.3 Display...................................................................................... 33
Section 5 Operation—si792(x) D
(4–20 mA/HART) .........................................................................35
5.1 Measure mode .........................................................................35
5.2 Configuration............................................................................ 35
5.2.1 Output configuration.......................................................... 36
5.2.1.1 Output range ..............................................................38
5.2.1.2 Time averaging filter...................................................38
5.2.1.3 Output signal during errors......................................... 38
5.2.1.4 Output signal during HOLD ........................................ 39
5.2.2 Temperature sensor configuration ....................................40
5.2.3 Correction menu configuration ..........................................40
5.2.4 Calibration mode configuration.......................................... 41
5.2.5 Alarm settings configuration .............................................. 41
Section 6 Operation—Foundation Fieldbus................ 43
6.1 Configuration............................................................................ 43
6.1.1 Configuration steps ...........................................................43
6.1.2 Configuration menu........................................................... 44
6.2 Foundation Fieldbus communication........................................ 46
6.2.1 Standard resource block (RB)........................................... 46
6.2.2 Standard analog input block (AI)....................................... 49
6.2.2.1 Operating modes........................................................ 49
6.2.2.2 Set the parameter and units....................................... 49
6.2.2.3 Data processing .........................................................50
6.2.2.4 Alarms ........................................................................ 50
6.2.2.5 Bus parameters for the analog input block.................51
6.2.2.6 Cyclic measured value status..................................... 54
6.2.2.7 Measured value limits—limit bits................................54
6.2.3 Transducer block...............................................................55
6.2.4 Calibration via Foundation Fieldbus.................................. 63
2
Page 5
Table of Contents
Section 7 Operation—Profibus PA...................................65
7.1 Configuration............................................................................ 65
7.1.1 Configuration steps ...........................................................65
7.1.2 Configuration menu........................................................... 66
7.2 Profibus PA communication .....................................................67
Section 8 Calibration .............................................................. 71
8.1 Calibration ................................................................................ 71
8.1.1 Zero calibration ................................................................. 72
8.1.2 DO calibration (default) .....................................................73
8.1.2.1 Calibration in air (recommended)............................... 73
8.1.2.2 Calibration in water .................................................... 74
8.1.3 Gas calibration (volume concentration)............................. 74
8.1.4 Calibration by comparison................................................. 75
8.2 Temperature sensor adjustment ..............................................76
Section 9 Maintenance........................................................... 77
9.1 Cleaning the instrument ...........................................................77
9.2 Sensor maintenance ................................................................77
Section 10 Troubleshooting ................................................79
10.1 Sensoface ..............................................................................79
10.2 Sensocheck............................................................................79
10.3 Error codes.............................................................................80
10.4 Calibration errors....................................................................82
10.5 Diagnostic functions ............................................................... 83
Section 11 Parts and accessories .................................... 85
11.1 si792 D series versions .......................................................... 85
11.2 Accessories............................................................................ 85
Section 12 Contact information......................................... 87
Section 13 Limited warranty ............................................... 90
Appendix A Passcode editor .............................................. 93
3
Page 6
Table of Contents
4
Page 7

Section 1 Specifications

Specifications are subject to change without notice.
Transmitter
Composition PBT (polybutylene terephthalate) Display LCD
Fittings
Power Requirements—HART
Power requirements—FF and Profibus PA
Loop current—HART
Current consumption—FF and Profibus PA
Maximum current in case of fault (FDE)—FF and Profibus PA
Measurement error
1
3 knockouts for M20 x 1.5 strain reliefs 2 knockouts for ½ inch NPT or rigid
metallic conduit 12–30 VDC (30 VDC maximum) 100 mA maximum
0.8 W maximum (Ex) FISCO bus supply: 9 to 17.5 VDC
Linear barrier: 9 to 24 VDC 4–20 mA floating;
3.80–22.00 mA specifiable
<13.2mA
<17.6mA
<0.3% current value + 0.05 mA
5
Page 8
Specifications
US: si792 D FM listed for:
Class I, Division 2
si792x D; si792x D-FF; si792x D-PA FM listed for:
Class I, Division 1, Groups A, B, C, D Class II, Division 1, Groups E, F, Class III, Division 1 Class I, Zone 0, AEx ia, Group IIC T4
Enclosure: Type 2
Canada: si792 D CSA certified to:
Certification (may not apply to all sensors. Refer to the control drawing or listing for certification information for the sensor that is used)
Lightning protection EN 61000-4-5 Output averaging time constant (HART) 0–120 seconds
Output span allowed
Storage Temperature –20 to 70 °C (–4 to 158 °F) Operating Temperature –20 to 55 °C (–4 to 131°F)
Class I, Division 2
si792x D CSA certified and si792x C-FF; si792x D-PA cFMus certified to:
Class I, Division 1, Groups A, B, C, D Class I, Division 2, Groups A, B, C, D Sensor: Class I, Zone 0, Group IIC Transmitter: Class I, Zone 1, Group IIC
EU: si792x P; si792x D-FF; si792x D-PA ATEX Certification:
II 2 (1) G EEx ib (ia) IIC T6 Enclosure: Type 2
EU: CE Marked to:
EMC Directive 2004/108/EC ATEX Directive 94/9/EC
Enclosure: IP65
2%–500% 200–9999 µg/L (ppb)
0.5–50 mg/L (ppm)
6
Page 9
Specifications
Weight Approximately 1 kg Dimensions H 144 mm, W 144 mm, D 105 mm
Data retention
Passcodes
Sensocheck
Probe monitor
Communications
HART communication
Foundation Fieldbus (FF_H1)
Parameters and calibration data >10 years (EEPROM)
Modifiable according to FDA 21 CFR Part 11 “Electronic Signatures”
Automatic monitoring for short circuits or open circuits (can be disabled). Delay: 30 seconds.
Direct display of uncorrected sensor signal (sensor current/temperature)
Digital communication by FSK modulation of loop current, reading of device identification, measured values, status and messages, reading and writing of parameters, start of product calibration, signaling of configuration changes according to FDA 21 CFR Part 11.
Bus-powered device with constant current consumption. Cyclic and acyclic data exchange. 1 resource block, 1 transducer block, 3 analog input function blocks (switchable: O
saturation, O temperature, zero, slope, volume
concentration) Execution time: 50 ms Certified to ITK 4.6 Physical interface: to IEC 1158-2 Address range: 017 to 246
concentration,
2
2
7
Page 10
Specifications
Bus-powered device with constant current consumption. Cyclic and acyclic data exchange. Physical block, 2 analog input function blocks, 2 discrete input blocks, logbook block, alarm block.
PNO directive: PROFIBUS-PA,
Profibus-PA (DPV1)
Temperature Input
Probe
Range –20.0 to 150.0 °C (–4 to 302 °F) Adjustment range 10 K Resolution 0.1 °C; 0.1 °F
Measurement error
Dissolved oxygen input
Type A sensor Type B sensor
Measuring current 0–1200 nA; resolution: 20 pA Measurement error
Temperature coefficient 0.005 nA/K Permitted guard current
Polarization voltage
Range, percent saturation 0–199.9%/200–500% (–10 to 80 °C)
1,2
3
3
1,2
Profile for Process Control Devices, Version 3.0
Physical interface: MBP-IS (Manchester Bus Powered-Intrinsically Safe) to IEC 1158-2 (DIN-EN 61158-2)
Connection: via segment coupler to SPC, PC, PCS
Address range: 1 to 126
NTC 30 kΩ/NTC 22 kΩ (selectable), 2-wire connection
<0.5 K (<1 K at T >100 °C)
Oxyferm, Oxysens (Hamilton) Oxygold G (Hamilton)
0.5% measured value + 0.05 nA
20 µA
400–1000 mV; resolution: approximately 3 mV
8
Page 11
Specifications
Range, concentration (–10 to 80 °C)
Range, volume concentration in gas Process pressure 0–9.999 bars (0–999.9 kPa/0–145 PSI) Pressure correction 0–9.999 bars (0–999.9 kPa/0–145 PSI) Salinity correction 0–45 g/kg
Probe calibration
Type A sensor
Range, Type B sensor
Calibration timer 0 to 9999 hours
1
IEC 746 Part 1, at nominal operating conditions
2
(± 1 count plus sensor error)
3
Sensor specifications given in Table 1.
4
si792(x) D and si792x D-FF only
Table 1 Sensor specifications
Sensor type Screw cap
5 meter,
Type A sensor
Type B sensor
Oxysens
Oxyferm VP 40–80 nA 0.01 ppm 22 NTC
Oxygold G VP 180–400 nA 0.001 ppm 22 NTC
fixed cable with stripped ends
0–50.00 mg/L; 0–50.00 ppm 0–9999 µg/L; 0–9999 ppb
4
0–9999 ppm; 0–120.0% (–10 to 80 °C)
Slope 25–130 nA (25 °C, 1013 mbars) Zero point ± 2 nA Slope 200–550 nA (25 °C, 1013 mbars) Zero point ± 2 nA
Sensor current in air (25 °C)
40–80 nA 0.04 ppm 22 NTC
Detection limit
Temperature sensor
9
Page 12
Specifications
10
Page 13

Section 2 General Information

2.1 Safety information

Please read this entire manual before unpacking, setting up, or operating this equipment. Pay attention to all danger and caution statements. Failure to do so could result in serious injury to the operator or damage to the equipment.
To ensure that the protection provided by this equipment is not impaired, do not use or install this equipment in any manner other than that specified in this manual.

2.1.1 Use of hazard information

DANGER Indicates a potentially or imminently hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION Indicates a potentially hazardous situation that may result in minor or moderate injury.
Important Note: Information that requires special emphasis.
Note: Information that supplements points in the main text.

2.1.2 Precautionary labels

Read all labels and tags attached to the instrument. Personal injury or damage to the instrument could occur if not observed. A symbol, if noted on the instrument, will be included with a danger or caution statement in the manual.
This symbol, if noted on the instrument, references the instruction manual for operation and/or safety information.
11
Page 14
General Information
Electrical equipment marked with this symbol may not be disposed of in European public disposal systems after 12 August of 2005. In conformity with European local and national regulations (EU Directive 2002/96/EC), European electrical equipment users must now return old or end-of life equipment to the Producer for disposal at no charge to the user.
Note: For return for recycling, please contact the equipment producer or supplier for instructions on how to return end-of-life equipment, producer-supplied electrical accessories, and all auxiliary items for proper disposal.
This symbol, when noted on a product enclosure or barrier, indicates that a risk of electrical shock and/or electrocution exists.
This symbol, when noted on the product, identifies the location of the connection for Protective Earth (ground).
This symbol, when noted on the product, identifies the location of a fuse or current limiting device.
This symbol, when noted on the product, identifies a risk of chemical harm and indicates that only individuals qualified and trained to work with chemicals should handle chemicals or perform maintenance on chemical delivery systems associated with the equipment.
This symbol, when noted on the product, identifies the presence of a strong corrosive or other hazardous substance and a risk of chemical harm. Only individuals qualified and trained to work with chemicals should handle chemicals or perform maintenance on chemical delivery systems associated with the equipment.
This symbol, when noted on the product, indicated the presence of devices sensitive to Electro-static Discharge (ESD) and indicated that care must be taken to prevent damage with the equipment.
This symbol, when noted on the product, identifies the presence of a strong corrosive or other hazardous substance and a risk of chemical harm. Only individuals qualified and trained to work with chemicals should handle chemicals or perform maintenance on chemical delivery systems associated with the equipment.
12
Page 15
General Information

2.2 General product information

2.2.1 Product overview

The si792 D and si792x D transmitters are used for continuous dissolved oxygen and temperature measurement. Applications include biotechnology, chemical, pharmaceutical and food processing as well as environmental monitoring and sewage treatment. This manual describes the installation, operation and maintenance for standard and EU models of the si792 D series transmitters.
The transmitter accepts various amperometric sensors, for example:
• Hamilton Oxysens, Oxyferm, Oxygold G
The molded transmitter enclosure can be attached to a panel, wall, post or pipe railing. The optional hood (see Accessories on page 87) provides protection against direct weather exposure and mechanical damage.
Three communication options are available for the si792 transmitter:
• 4–20 mA/HART—si792 D and si792x D (si792(x) D)
• Foundation Fieldbus—si792x D-FF
• Profibus PA—si792x PD-PA This user manual includes instructions for all three protocols.
Important Note: An ‘x’ in the model number is an indication of an instrinsically safe (IS) instrument.

2.2.2 FDA 21 CFR part 11 Compliance (HART only)

In the directive “Title 21 Code of Federal Regulations, 21 CFR Part 11, Electronic Records; Electronic Signatures“ the US American health agency FDA (Food and Drug Administration) regulates the production and processing of electronic documents for pharmaceutical development and production. The features described in section 2.2.2.1 and section 2.2.2.2 make the transmitter compliant with the requirements of FDA 21 CFR Part 11.
13
Page 16
General Information
2.2.2.1 Electronic signatures for si792(x) D transmitters
Device functions are protected by passcode access, which prevents unauthorized modification of device settings or manipulation of measurement results. Passcodes may be used as electronic signatures. Passcodes can be edited with the passcode editor (Appendix A on page 93).
2.2.2.2 Audit trail for si792(x) D transmitters
The si792(x) D can automatically track all changes to the device settings. Each change is tagged with a Configuration Change flag, which is documented using HART communication. Altered device settings or parameters can be retrieved from the transmitter using HART communication.
14
Page 17

Section 3 Installation

DANGER Explosion hazard. Trained personnel only must install or commission the equipment.
DANGER Explosion hazard. Never connect items to the transmitter that are not specified on the control drawing. Do not connect or disconnect any equipment unless power has been switched off or the area is known to be non-hazardous.
DANGER Explosion hazard. The safety of the transmitter may be impaired if any of the following conditions have occurred:
• visible damage
• storage above 70 °C for prolonged periods
• exposure to severe transport stresses
• previous installation
• failure to operate properly
If any of these conditions have occurred, return the device to the manufacturer for recertification.
The si792 and si792x transmitters differ in hazard classification. The si792 transmitter is designed for non-hazardous or Class I, Division 2, Groups A, B, C, D hazardous locations. The si792x transmitter is designed for Class I, Division 1, Groups A, B, C, D hazardous locations. Refer to the control drawing or listing applicable to the site location.
For outdoor installation, use of a protective hood or sunshield is recommended (section 11.2 on page 87).
Installation of the si792x in an outdoor hazardous location per FM or CSA control drawings requires a suitable enclosure and must follow NEC guidelines. Refer to NEMA 250 to determine enclosure needs.
15
Page 18
Installation

3.1 Hazardous location

Before installation, review the applicable Hazardous Location Control Drawings or ATEX EC-type Examination certificate included with the instrument and on the provided documentation CD. Follow all regulations specified for the installation location.
Refer to the documentation CD for manuals provided in other languages.

3.2 Unpacking the transmitter

Check the shipment for transport damage and make sure all components have been shipped complete. The package includes:
• Display module • Bag of hardware and fasteners
• Back enclosure • Test report and user manual
16
Page 19
Installation
Figure 1 Instrument Components
1 Back enclosure 8 Strain relief (3x) 2 Optional conduit hardware 9 Filler plug (3x) 3 Conduit washer 10 Enclosure screw (4x) 4 Jumper (2x) 11 Display module 5 Cable tie (3x) 12 Hinge pin 6 Sealing insert 13 Hex nuts (5x) 7 Rubber reducer 14 Sealing plug (2x)
17
Page 20
Installation

3.3 Mechanical installation

3.3.1 Transmitter assembly

Refer to Figure 1 and the following instructions to assemble the transmitter.
1. Insert the strain relief fittings in the holes of the back enclosure and secure with the hex nuts (Figure 2).
2. Insert the conduit hardware or plugs in the back enclosure and secure with the hex nuts.
3. Attach the display module to the back enclosure using the hinge pin.

3.3.2 Mounting

Refer to the following sections to mount the transmitter on a wall, panel or pipe.
3.3.2.1 Wall mount
1. Use a punch to open the two wall-mount holes in the back enclosure
(Figure 2).
2. Drill holes in the wall suitable for the user-supplied mounting bolts.
3. Attach the back enclosure to the wall using two customer-supplied
bolts.
4. Insert the clear plastic plugs into the mounting holes.
3.3.2.2 Panel or pipe mount (optional)
Refer to Figure 2 and the instructions supplied with the panel and pipe mounting kits (see Accessories on page 85).
18
Page 21
Installation
Figure 2 Wall attachment dimensions
1 Breakout for wall mounting (2x) 5 Groove for panel mount gasket 2 Hole for pipe mounting (4x) 6 Strain relief opening (3x) 3 Strain relief (3x) 4 Breakout for panel mounting
7 Strain relief or ½ inch conduit opening
(2x) Ø 21.5 mm [0.85 in]
19
Page 22
Installation

3.4 Wiring Safety Information

When making any wiring connections to the instrument, the following warnings and notes must be adhered to, as well as any warnings and notes found throughout the individual installation sections. For more safety information refer to section 2.1 on page 11.
DANGER Always disconnect power to the instrument when making any electrical connections.
Electrostatic Discharge (ESD) Considerations
To minimize hazards and ESD risks, maintenance procedures not requiring power to the analyzer should be performed with power removed.
Delicate internal electronic components can be damaged by static electricity, resulting in degraded instrument performance or eventual failure.
The manufacturer recommends taking the following steps to prevent ESD damage to the instrument:
• Before touching any electronic components (such as printed circuit cards
and the components on them) discharge static electricity from the body by touching an earth-grounded metal surface such as the chassis of an instrument or a metal conduit or pipe.
• To reduce static build-up, avoid excessive movement. Transport static-
sensitive components in anti-static containers or packaging.
• To discharge static electricity from the body and keep it
discharged, wear a wrist strap connected by a wire to earth ground.
• Handle all static-sensitive components in a static-safe area. If
possible, use anti-static floor pads and work bench pads.
20
Page 23
Installation

3.5 Electrical installation

DANGER Explosion hazard. Do not connect any components that are not specified for the device. Always defer to the Hazardous Location Control Drawing.
DANGER Hamilton dissolved oxygen sensors are ATEX certified. The combination of Hamilton dissolved oxygen sensors and the si792 D transmitter are FM C1D1 certified. The Hamilton sensors are not certified by CSA for use in Canadian hazardous locations. See CSA control drawings for approved sensor options
Prerequisites:
• Review the applicable control drawing or ATEX certificate
• Review the electrical code regulations
• Review the regulations for electrical installations in hazardous locations as needed (e.g. EN 60079-10/EN60079-14; 94/9/EC directive; NEC; CEC; Profibus Technical Guidelines 2.091).
• Remove power or confirm non-hazardous status before making any connections
• Confirm that the intrinsic safety of the device is maintained when connected to other equipment such as a power supply unit.

3.5.1 Wire preparation

To remove the terminal blocks from the transmitter for sensor wiring:
1. Insert a flat screwdriver between the terminal block and the transmitter body.
2. Use the screwdriver as a lever to lift the terminal block off the connectors (see Figure 3 on page 22).
21
Page 24
Installation
Figure 3 Wire preparation and insertion
1 Stripping lengths for cables 6 Terminals (vary by model number) 2 Stripping lengths for coaxial cables 7 Typical terminal 3 Cable shield connector 4 ESD shield removed 9 Removing terminal with screwdriver 5 Areas for screwdriver to pry terminal 10 Cable loop position in housing
1
Not used for si792x D-ff and si792x D-PA transmitters.
1
8 Seat insulation against connector
22
Page 25
Installation

3.5.2 Power and communication connections

DANGER Explosion hazard. The AC power source for the power supply unit cannot exceed 250 VAC. Do not connect the transmitter directly to an AC power source.
DANGER Explosion hazard. The output voltage of the power supply unit cannot exceed 30 VDC. The si792x transmitter must be connected to an appropriately certified explosion-proof power supply unit. Refer to "associated apparatus" in the control drawing or to the EC-Type Examination Certificate for input ratings.
Prerequisites
• Trained personnel only must install or commission the
equipment.
• Follow the instructions in this user manual and the applicable
local and national codes.
• Observe the technical specifications and input ratings during
installation.
• Disconnect all power sources during wiring and installation.
• Use single wires/flexible leads up to 2.5 mm (AWG 14) for
connection to terminals.
• Do not damage the wire when stripping the insulation.
• All parameters must be set by a system administrator (Authority
Having Jurisdiction) before commissioning.
23
Page 26
Installation
3.5.2.1 si792(x) D (4–20 mA/HART) wiring
DANGER Explosion hazard. Never connect items to the transmitter that are not specified on the control drawing/ATEX EC-Type certificate.
Refer to Figure 6 and Table 2 and the following steps to connect the power supply to the si792(x) D transmitter.
Figure 4 si792(x) D (4–20 mA/HART) wiring
1 HART connection (see warnings in
section 3.6 on page 30)
Table 2 Terminal assignments—si792(x) D
Terminal No. Assignment
9 Equipotential bonding for ATEX. Do not connect for FM and CSA.
10 4–20 mA output (–) 11 4–20 mA output (+)
2 Wiring terminals—see Table 4
24
Page 27
Installation
3.5.2.2 si792x D-FF and si792x D-PA wiring
Refer to Figure 5 and Table 3 to connect power and communications to the si792x D-FF or si792x D-PA transmitters.
Figure 5 si792x D-FF and si792x D-PA wiring
1 Wiring terminals—see Table 3
Table 3 Terminal assignments—si792x D-FF and si792x D-PA
Terminal No. Assignment
9 Equipotential bonding for ATEX. Do not connect for FM and CSA. 10 Connection from FF or Profibus PA (–) 11 Connection from FF or Profibus PA (+)

3.5.3 Sensor wire connection

Important Note: Do not connect earth ground to the shield connector in the transmitter. Connect the cable shields to the shield connector.
Refer to the following sections to connect the transmitter to a sensor:
• Oxygold G/Oxyferm sensor (si792(x) D, section 3.5.3.1)
• Oxygold G/Oxyferm sensor (si792x D-FF/si792x D-PA, section 3.5.3.2)
• Oxysens sensor (si792(x) D, section 3.5.3.3)
• Oxysens sensor (si792x D-FF/si792x D-PA, section 3.5.3.4)
25
Page 28
Installation
3.5.3.1 Oxygold G/Oxyferm sensor—si792(x) D (4–20 mA/HART)
Use Figure 6 and Table 4 to wire the sensor to the transmitter.
Figure 6 Oxygold G/Oxyferm sensor (VP connector)—si792(x) D
1 Wiring terminals—see Table 4
Table 4 Terminal assignments—Oxygold G or Oxyferm sensor
Ter min al No.
1
With VP cable LZY079, LZY353 and LZY354. Blue and gray are not used.
Assignment
1 Cathode (coaxial center wire) clear 5 Anode (coaxial shield) shield/red
Cable shield connection
6
Note:
Do not connect to earth ground.
7 RTD (resistive temperature device) green 8 RTD (resistive temperature device) white
Wire color
shield/yellow-
green
1
26
Page 29
Installation
3.5.3.2 Oxygold G/Oxyferm sensor—si792x D-FF or si792x D-PA
Use Figure 7 and Table 5 to wire the sensor to the transmitter.
Figure 7 si792x D-FF and si792x D-PA wiring for Oxygold G/Oxyferm
1 Wiring terminals—see Table 5
Table 5 Terminal assignments—Oxygold G or Oxyferm sensor
Ter min al No.
1
With VP cable LZY079, LZY353 and LZY354. Blue and gray are not used.
Assignment
2 Cathode receive high clear
4 Anode shield/red
Cable shield connection
5
Note:
Do not connect to earth ground.
7 RTD (resistive temperature device) green
8 RTD (resistive temperature device) white
Wire color
shield/yellow-
green
1
27
Page 30
Installation
3.5.3.3 Oxysens sensor—si792(x) D (4–20 mA/HART)
Use Figure 8 and Table 6 to wire the sensor to the transmitter.
Figure 8 si792(x) D wiring example for Oxysens sensor (fixed cable)
1 Wiring terminals—see Table 6
Table 6 Terminal assignments—Oxysens sensor
Ter min al No.
Assignment Wire color
1 Cathode (coaxial center wire) clear 5 Anode brown
Cable shield connection
6
Note:
Do not connect to earth ground.
7 RTD (resistive temperature device) yellow 8 RTD (resistive temperature device) blue
shield
28
Page 31
Installation
3.5.3.4 Oxysens sensor—si792x D-FF and si792x D-PA
Use Figure 9 and Table 7 to wire the sensor to the transmitter.
Figure 9 si792x D-FF and si792x D-PA wiring example for Oxysens
(fixed cable)
1 Wiring terminals—see Table 7
Table 7 Terminal assignments—Oxysens sensor
Ter min al No.
Assignment Wire color
2 Cathode receive high clear
4 Anode brown
Cable shield connection
5
Note:
Do not connect to earth ground.
7 RTD (resistive temperature device) yellow
8 RTD (resistive temperature device) blue
shield
29
Page 32
Installation

3.6 HART communication connection

DANGER Explosion hazard. Never connect items to the transmitter that are not specified on the control drawing. Do not connect or disconnect any equipment unless power has been switched off or the area is known to be non-hazardous.
DANGER The si792x transmitter must be used with an explosion-proof HART communication device. Refer to the appropriate control drawing for the location of the HART (Rosemount) device.
The handheld HART communication device can only be connected to the transmitter in US Class I, Division 1 classified locations (permitted only by FM). Do not connect the handheld Hart communication device to the transmitter in any Zone or Canadian Class I, Division 1 classified location. Refer to Figure 4 on page 24 for the connector location.
30
Page 33

Section 4 Interface and navigation

The si792 transmitter user interface contains a display, indicators and keys for navigation and menu selection.
4.1 si792(x) D (4–20 mA/HART) interface
Use the arrow and enter keys to scroll through the menu and change settings. Use the indicators to identify which mode the transmitter is in. Refer to Figure 10 to identify the keys and indicators of the si792(x) D.
Figure 10 User interface—si792(x) D
1 Calibration key 7 Wash mode indicator (not available) 2 Configure key 8 Configuration mode indicator 3 Measure mode indicator 9 Up arrow key 4 Calibration mode indicator 10 Right arrow key 5 Alarm indicator 6 Display
11 Enter key
31
Page 34
Interface and navigation

4.2 si792x D-FF and si792x D-PA interface

Refer to Figure 11 to identify the keys and indicators of the si792x D-FF and the si792x D-PA.
Figure 11 User interface—si792x D-FF and si792x D-PA
1 Measure key 7 Communication indicator
2 Calibration key 8 Configuration mode indicator
3 Measure mode indicator 9 Up arrow key
4 Calibration mode indicator 10 Right arrow key
5 Alarm indicator 11 Enter key
6 Display 12 Configuration mode
32
Page 35
Interface and navigation

4.3 Display

Figure 12 identifies all of the possible icons and symbols that may be
seen in the si792 transmitter display.
Figure 12 Display
1 Passcode 13 Secondary display 2 Temperature 14 Alarm mode 3 4–20 mA output (HART) 15 Manual temperature on 4 Limit values (FF and Profibus PA) 16 Calibration mode 5 Alarm 17 Hold mode active 6 Sensocheck—sensor error 18 Hourglass 7 Calibration active 19 Measure mode active 8 Calibration interval 20 Calibration complete 9 Parameter display 21 Calibration—zero or first point 10 Enter prompt 22 Calibration—second point 11 Configuration mode 12 Main display
23 Sensofaces
33
Page 36
Interface and navigation
34
Page 37
Section 5 Operation—si792(x) D (4–20 mA/HART)
The following section describes how to navigate and operate the si792(x) D transmitters.

5.1 Measure mode

In the measure mode the display shows the dissolved oxygen value and the temperature. The status bar is shown above the measure mode indicator.
• To return to the measure mode from the configure menu, press
CONF and then ENTER.
• To return to the measure mode from the calibration menu, press
CAL and then ENTER.
Note: The waiting time for the stabilization of the measured value is approximately 20 seconds.

5.2 Configuration

Use the configuration mode to specify the sensor, range and other parameters for the system as shown in Table 8.
1. Press CONF and enter 1200 to enter the configuration mode.
2. Use the arrow and enter keys to change the settings. All settings and options are shown in section 5.2.1, section 5.2.2, section 5.2.3,
section 5.2.4 and section 5.2.5.
Table 8 Configuration menu
Code Setting Passcode
35
Page 38
Operation—si792(x) D (4–20 mA/HART)
Table 8 Configuration menu
o1 4–20 mA current output tc Temperature sensor
Corr
CAL Calibration setup AL Alarm settings
To exit the configuration mode at any time, press
ENTER. The output current will be held for 20 seconds and the
measured value will be displayed.
Note: During configuration the transmitter remains in the Hold mode for safety reasons. The loop current is frozen at the value specified in the o1.HoLD menu option. The Sensoface icon is inactive. The configuration mode indicator is displayed (Figure 12 on page 33).

5.2.1 Output configuration

Select the parameter
o1. FCT
Select the sensor type
o1.SnSR
Select the units
o1.UniT
Correction for pressure, salinity, polarization voltage.
1200
CONF and then
Table 9 Output setup menu—out.1MNU
DO (concentration by weight; default) GAS (concentration by volume)
Type A (standard; default) examples: Oxysens, Oxyferm Type B (trace measurements) example: Oxygold G
SAt % (percent saturation; default) Conc µg/L
DO (default)
GAS
Conc mg/L Conc ppb Conc ppm GAS % (default) GAS ppm
36
Page 39
Operation—si792(x) D (4–20 mA/HART)
Table 9 Output setup menu—out.1MNU (Continued)
Specify the value for the 4 mA signal (section 5.2.1.1)
o1. 4mA Enter the minimum DO or GAS value (default: 0%)
Specify the value for the 20 mA signal (section 5.2.1.1)
o1.20mA Enter the maximum DO or GAS value (default: 500%)
Set time averaging filter for reducing noise (section 5.2.1.2)
o1.Ftme Enter the time in seconds (0 to 120 seconds; default: 0 seconds)
Send a 22 mA signal during errors (section 5.2.1.3)
o1.FAil
Specify the value to send during HOLD periods (section 5.2.1.4)
o1.HoLD
Press values. Press acceptable range, “Err” will be displayed and the value will not be accepted. To exit the menu and return to the measurement mode, press
CONF and then ENTER.
Example: Set the 4 mA current output signal to 2 mg/L O
1. Press Conf and then out.1MNU.
2. Press show o1.UniT.
3. Press show o1.4mA.
4. Use the
03.00 mg/L. Press
o1.20mA.
5. Press
On Off (default)
LAST measured value (default) FIXed Enter the value in mA (0 to 22 mA; default: 21 mA)
ENTER to access a menu item. Use the ARROW KEYS to edit
ENTER to save the settings. If a value is outside of the
.
2
CONF, enter passcode: 1200, ENTER. The display will show
ENTER to access the output setup menu. The display will
ENTER, ENTER to show the 4 mA submenu. The display will
UP ARROW and RIGHT ARROW to edit the value to
ENTER to save the value. The display will show
CONF and then ENTER to exit the configuration menu.
37
Page 40
Operation—si792(x) D (4–20 mA/HART)
5.2.1.1 Output range
The upper and lower end of the dissolved oxygen range should correspond to the 4 mA and 20 mA signals. For example, to set a range of 3–10 mg/L O 20 mA signal to a value of 10 mg/L O
5.2.1.2 Time averaging filter
An averaging filter is available to reduce noise in the output signal. The filter averages readings over a specified time interval. The time interval can be set from 0 to 120 seconds (default: 0 seconds).
When set to 0 seconds, there is no noise reduction and the signal is the same before and after the filter. When set to 120 seconds, the signal after the filter will be averaged over 120 seconds. Increase the time interval to reduce the noise in the output signal.
Note: The filter acts on the output signal but not on the displayed value.
5.2.1.3 Output signal during errors
When an error condition occurs, a 22 mA output signal can be sent as a notification (default: off).
, set the 4 mA signal to a value of 3 mg/L and the
2
.
2
38
Page 41
Operation—si792(x) D (4–20 mA/HART)
5.2.1.4 Output signal during HOLD
The output signal during hold periods can be maintained at the last measured value (Figure 13) or fixed at a specified value (Figure 14). The allowable range for the fixed value is 3.8 to 22 mA.
Figure 13 Output signal during HOLD—last value
1 Output signal during HOLD 2 HOLD mode
Figure 14 Output signal during HOLD—fixed value
1 Output signal during HOLD 2 HOLD mode
39
Page 42
Operation—si792(x) D (4–20 mA/HART)

5.2.2 Temperature sensor configuration

An overview of the temperature compensation setup menu is shown in
Table 10.
Table 10 Temperature sensor setup menu—tc
Select temperature unit
tc.UnIT
Select temperature sensor
tc.rTD
Press values. Press
°C (default) °F
22NTC (default) 30NTC
ENTER to access a menu item. Use the ARROW KEYS to edit
ENTER to save the settings. If a value is outside of the
acceptable range, “Err” will be displayed and the value will not be accepted. To exit the menu and return to the measurement mode, press
CONF and then ENTER.

5.2.3 Correction menu configuration

An overview of the corrections menu is shown in Table 11.
Table 11 Corrections setup menu—Corr MNU
Specify the polarization voltage
Co.UPoL Enter the polarization voltage (400–1000 mV; default: 675 mV)
Select pressure units
Bar (default)
Co.UniT
Specify the correction for process pressure (for % saturation only)
Co.PrES Enter the process pressure (default: 1.013 Bar)
Specify the correction for salinity
Co. SAL
1
ppt—parts per thousand (corresponds to g/kg)
KPa PSI
Enter the salinity value of the sample (0–45.00 ppt
MNU
1
; default: 0 ppt)
40
Page 43
Operation—si792(x) D (4–20 mA/HART)

5.2.4 Calibration mode configuration

An overview of the calibration setup menu is shown in Table 12. Refer to Appendix A on page 95 for buffer tables.
Table 12 Calibration mode setup menu—CAL
Select calibration units
CA. MOD
Enter calibration timer interval
CA.tiME Enter the time interval for calibration (0 to 9999 hours; default: 0 h)
SAt (default) Conc

5.2.5 Alarm settings configuration

An overview of the alarm setup menu is shown in Table 13.
Table 13 Output setup menu for alarm settings—ALrt MNU
Select Sensocheck on or off
AL.SnSO
Enter alarm delay
AL.dLY 0010 sec (default) Range: 0000–0600 sec
LED in Hold mode
AL.LED
CHECK ON CHECK OFF (default)
HOLD ON LED blinks during hold HOLD OFF LED off during hold
Continuous evaluation of sensor function
MNU
41
Page 44
Operation—si792(x) D (4–20 mA/HART)
42
Page 45
Section 6 Operation—Foundation Fieldbus
The following section describes how to navigate and operate the si792x D-FF. The transmitter can be operated as follows:
• Direct interface with the transmitter (section 6.1)
• Foundation Fieldbus communication (section 6.2 on page 46)

6.1 Configuration

Use the configuration mode to specify the sensor, range and other parameters for the system.

6.1.1 Configuration steps

Complete the following steps to configure the si792 transmitter.
1. Press MEAS + CAL and enter 1200 to enter the configuration mode.
2. Use the arrow and enter keys to change the settings. All settings and options are shown in section 6.1.2.
To exit the configuration mode at any time, press MEAS + CAL and
ENTER. The Hold mode will be active for 20 seconds and then the
then measured value will be displayed.
Note: During configuration the transmitter remains in the Hold mode for safety reasons. The Sensoface icon is inactive. The configuration mode indicator is displayed (Figure 10 on page 31).
43
Page 46
Operation—Foundation Fieldbus

6.1.2 Configuration menu

Select signal level
ln.rnGE
Select the sensor
ln.SnSR
Select process medium (O2 dissolved (DO) / gas (GAS)
ln.FCT
Select filter time
ln.FtME 0000–0120 SEC (default: 0000 SEC)
Select temperature unit
tc.UnIT
Select temperature sensor
tc.rTD
Select polarization voltage
Co.UPOL –1000–0 mV (default: –0675 mV)
Select pressure unit
Co.UnIT
Select pressure correction
Hi level (default) Lo level
Type A (default). See Table 1 on page 9. Type B. See Table 1 on page 9.
DO (default) ln.UnIT
GAS ln.UnIT
°C (default) °F
22 NTC (default) 30 NTC
BAR (default) kPa PSI
% (default) mg/L µg/L ppm ppb ppm (default) %
44
Page 47
Operation—Foundation Fieldbus
6.1.2 Configuration menu (continued)
Co.PrES
Select salinity correction
Co.SAL 0.00–45.00 mg/L (default: 0.00 mg/L)
Select calibration mode
Ca.MOD
Select calibration interval
CA.tiME 0000–9999 h (default 0000 h)
Select Sensocheck
AL.SnSO
LED in Hold mode
AL.LED
Select Fieldbus address (optional)
FF.ADR 0017–0031 BUS (default: 0026 BUS)
1
Use only when there is no bus connection. The transmitter will restart and set all
parameters to default values. Individual settings must be entered once more.
0.000–9.999 BAR (default: 1.013 BAR)
999.9 kPa / 145.0 PSI (not in sensor)
SAt (default) Conc
CHECK ON CHECK OFF (default)
HOLD ON LED blinks during hold HOLD OFF (default) LED off during hold
Continuous Sensocheck evaluation of sensor function
1
45
Page 48
Operation—Foundation Fieldbus

6.2 Foundation Fieldbus communication

Use the Foundation Fieldbus specification to set up and configure the si792 transmitter. The communication parameters are listed in the following sections. The sensor can be calibrated as described in
section 6.2.4 on page 63.

6.2.1 Standard resource block (RB)

The standard resource block describes the transmitter characteristics (manufacturer, device name, operating status, global status). The resource block must be in automatic mode for any of the other blocks to operate. The bus parameters for the standard resource block (RB) are shown in Table 14.
Table 14 Bus parameters—resource block (RB)
Parameter Description Default R/W
ST_REV Static revision 0 R TAG_DESC TAG description ‘ R/W STRATEGY Strategy 0 R/W ALERT_KEY Alert key 0 R/W
Ta rg e t
MODE_BLK
BLOCK_ERR Block error R RS_STATE Resource state 1 R TEST_RW Test R/W DD_RESOURCE DD resource R MANUFAC_ID Manufacturer ID 0x001D6D for Hach R DEV_TYPE Device type 0x0064 R DEV_REV Device revision 1 R DD_REV DD revision 1 R
Actual — Permitted OOS, Auto Normal Auto
(out of service)
OOS
R/W
46
Page 49
Operation—Foundation Fieldbus
Table 14 Bus parameters—resource block (RB) (continued)
Parameter Description Default R/W
GRANT_DENY
HARD_TYPES Hardware type 1 R RESTART Restart R/W FEATURES Feature supported Reports/ Soft W Lock R FEATURES Feature selected Reports/ Soft W Lock R/W
CYCLE_TYPE Cycle type
CYCLES_SEL Cycle selected
MIN_CYCLE_T Min cycle time MEMORY_SIZE Memory size R NV_CYCLE_T Non-volatile cycle time R FREE_SPACE Free space R FREE_TIME Free time R SHED_RCAS R/W SHED_ROUT R/W FAULT_STATE Fault state R SET_FSTATE Set fault state 1 R/W CLR_FSTATE Clear fault state 1 R/W MAX_NOTIFY Max notifications 20 R LIM_NOTIFY Limit of notification 8 R/W CONFIRM_TIME Confirmation time WRITE_LOCK Write locking 1 (Unlocked) R/W
UPDATE_EVT
Grant 0 R/W Deny 0 R/W
Scheduled/ Block Execution
Scheduled/ Block Execution
1
1600
/32 ms (50ms)
1
/32 ms
640000
Unacknowledged 0 R/W Update state 0 R Time stamp 0 R Static revision 0 R Relative index 0 R/W
R
R/W
R
R/W
47
Page 50
Operation—Foundation Fieldbus
Table 14 Bus parameters—resource block (RB) (continued)
Parameter Description Default R/W
Unacknowledged R/W
BLOCK_ALM
ALARM_SUM
ACK_OPTION
WRITE_PRI Write priority 0 R/W
WRITE_ALM
ITK_VER ITK_version 4 R
DEVICE_LOCK
Alarm state R Time stamp R Sub-code R Val ue R Current R Unacknowledged R Unreported R Disabled R/W Automatic acknowledge
option
Unacknowledged R/W Alarm state R Time stamp R Sub-code R Val ue R
Locks the device for local access.
1 byte Data type = uns8 Range:
0 (Unlocked) 1 (Locked)
0 (Disabled) R/W
0 (Unlocked) R/W
48
Page 51
Operation—Foundation Fieldbus

6.2.2 Standard analog input block (AI)

Three Analog Input Function Blocks provide for cyclic transmission of measured values (currently measured value with status, alarm limits, freely selectable process parameter).
6.2.2.1 Operating modes
Use the MODE_BLK parameter to set the following operating modes:
• OOS—out of service. If not write-protected, access to all
parameters is allowed.
• MAN—manual
• Auto—online, normal state
6.2.2.2 Set the parameter and units
Use CHANNEL to set the measured parameter and units (Table 15). The corresponding measurement unit is selected in the UNITS subparameter of XD_SCALE (Table 16 on page 51).
Table 15 Measurement parameters and units
Channel Parameter Unit Unit value
1 Saturation % (percent) 1342
mg/l 2001
2 Concentration
3 Temperature
4 Zero A 2003 5 Slope A 1587
Volume
6
concentration
μg/l 2002 ppm 1423 ppb 1424 °C 1001 °F 1002
% percent 1342 ppm 1423
49
Page 52
Operation—Foundation Fieldbus
6.2.2.3 Data processing
Use the L_TYPE parameter to apply a linearization function to the data.
• Direct—data is sent directly from the TB to the AI without processing. The units for the XD_SCALE and OUT_SCALE parameters must be identical.
• Indirect—data from the TB is linearly scaled from the input scale (XD_SCALE) to the output scale (OUT_SCALE).
• Indirect square root—data is rescaled from the input scale (XD_SCALE) and recalculated using a root function. Then the value is linearly scaled to the output scale (OUT_SCALE).
6.2.2.4 Alarms
The AI block can generate block alarms and limit alarms. Use the ACK_OPTION parameter to specify if an alarm must be acknowledged. When the measured value status is “bad”, the AI block BLOCK_ERR parameter indicates an Input Failure.
Block alarms—a block error will be reported via the BLOCK_ERR parameter (simulate active, input failure, block configuration error, out of service (OOS)). The BLOCK_ALM parameter sends the alarm status to the control system.
Limit alarms—the measured value OUT falls outside of the limit values (HI_HI_LIM, HI_LIM, LO_LIM, LO_LO_LIM).
If an alarm occurs, evaluate the following bus parameters:
• OUT parameter (currently measured value) in the Al block
• LAST_ERROR parameter in the transducer block
• SENSOFACE_STATUS parameter in the transducer block
50
Page 53
Operation—Foundation Fieldbus
6.2.2.5 Bus parameters for the analog input block
The bus parameters for the analog input function block (AI) are shown in Table 16.
Table 16 Bus parameters/analog input blocks (AI)
Parameter Description Default R/W
ST_REV Static Revision 0 R TAG_DESC TAG Description R/W STRATEGY Strategy 0 R/W ALERT_KEY Alert Key 0 R/W
Target OOS
MODE_BLK
BLOCK_ERR Block Error R
PV
OUT
SIMULATE
XD_SCALE
OUT_SCALE
Actual — Permitted OOS, Auto Normal Auto
Process Value R Status R Measured Value R Status R Simulate Status R/W Simulate Value R/W Transducer Status R Transducer Value R Simulate Enable / Disable R/W High Range 100 R/W Low Range 0 R/W Units Index 0 R/W Decimal Point 0 R/W High Range 100 R/W Low Range 0 R/W Units Index 0 R/W Decimal Point 0 R/W
R/W
51
Page 54
Operation—Foundation Fieldbus
Table 16 Bus parameters/analog input blocks (AI) (continued)
Parameter Description Default R/W
GRANT_DENY
IO_OPTS IO Block Options 0 R/W STATUS_OPTS Status Options CHANNEL Channel 1 R/W L_TYPE Linearization Type 0 R/W LOW_CUT Low Cut Off 0 R/W PV_TIME Filter Time 0 R/W
FIELD_VAL
UPDATE_EVT
BLOCK_ALM
ALARM_SUM
ACK_OPTION
AlARM_HYS Alarm Hysteresis 0.50% R/W HI_HI_PRI High High Priority 0 R/W HI_HI_LIM High High Limit INF R/W HI_PRI High Priority 0 R/W HI_LIM High Limit INF R/W LO_PRI Low Priority 0 R/W
Grant 0 R/W Deny 0 R/W
Percent Value R Status R Unacknowledged 0 R/W Update State 0 R Time Stamp 0 R Static Revision 0 R Relative Index 0 R Unacknowledged 0 R/W Alarm State 0 R Time Stamp 0 R Sub-code 0 R Current 0 R Unacknowledged 0 R Unreported 0 R Disabled 0 R/W Automatic Acknowledge
Option
0R/W
52
Page 55
Operation—Foundation Fieldbus
Table 16 Bus parameters/analog input blocks (AI) (continued)
Parameter Description Default R/W
LO_LIM Low Limit –INF R/W LO_LO_PRI Low Low Priority 0 R/W LO_LO_LIM Low Low Limit –INF R/W
Unacknowledged 0 R/W
HI_HI_ALM
HI_ALM
LO_ALM
LO_LO_ALM
Alarm State 0 R Time Stamp 0 R Sub-code 0 R Value 0 R Unacknowledged 0 R/W Alarm State 0 R Time Stamp 0 R Sub-code 0 R Value 0 R Unacknowledged 0 R/W Alarm State 0 R Time Stamp 0 R Sub-code 0 R Value 0 R Unacknowledged 0 R/W Alarm State 0 R Time Stamp 0 R Sub-code 0 R Value 0 R
53
Page 56
Operation—Foundation Fieldbus
6.2.2.6 Cyclic measured value status
The cyclic measured value status is shown in Table 17.
Table 17 Cyclic measured value status
Priority Quality Sub-status
Low
Good
Uncertain
Bad
High Out of Service 00 01 11 xx 0 x 1C
Good Non-Specific 10 00 00 00 0 x 80 Good Active Advisory Alarm 10 00 10 xx 0 x 88 Good Active Critical Alarm 10 00 11 xx 0 x 8C Uncertain Non-Specific 01 00 00 xx 0 x 40 Last Usable Value (LUV) 01 00 01 xx 0 x 44 Substitute-Set 01 00 10 xx 0 x 48 Initial Value 01 00 11 xx 0 x 4C Sensor Conversion Not Accurate 01 01 00 xx 0 x 50 Engineering Unit Violation 01 01 01 xx 0 x 54 Sub-Normal 01 01 10 xx 0 x 58 Non-Specific 00 00 00 xx 0 x 00 Sensor Failure 00 01 00 xx 0 x 10 Device Value 00 00 11 xx 0 x 0C
Bin-coding (no limit bits)
6.2.2.7 Measured value limits—limit bits
The respective status bit is set when a condition occurs (Table 18). The status bit is reset when the condition no longer exists.
Table 18 Limit bit description
Bin coding of limit bits Description
00 OK 01 Low-limited 10 High-limited 11 Constant
Hex­coding
54
Page 57
Operation—Foundation Fieldbus
Range
The revision value is
incremented every
time a static
parameter in the
block is changed.
Data
type

6.2.3 Transducer block

The transducer block provides for acyclic data transmission. Calibration, configuration, and
maintenance commands coming from the control station are processed in the Transducer
Table 19 Transducer block bus parameters
Block. The bus parameters for the transducer block (TB) are shown in Table 19 (default values
are in bold type).
R2
The revision of the static data
associated with the function
block. Used by the host to
Parameter Description R/W Bytes
ST_REV
determine when to re-read the
R/W 32 Default: Text
static data.
The user description of the
intended application of the
TAG -DE SC
block.
R/W 2 Default: 0
The strategy field can be used
to identify a grouping of blocks.
STRATEGY
Can be used for any purpose
by the user.
Identification number that may
R/W 1 Default: 0
be used by the host system to
sort alarms and other device
information.
ALERT_KEY
55
Page 58
Operation—Foundation Fieldbus
Available modes:
Automatic, Out Of
Service
Range
Data
type
(OOS), Manual
Default: 0
Default: 0
56
Allows the user to set the
Target, Permitted, and Normal
111
R/WRR/W
device mode. Displays the
1
R/W
Actual mode.
Target
Actual
Permitted
Normal
Reflects the error status
associated with the hardware or
11822
R2
software of the block. It is a bit
string so multiple errors may be
shown.
Unacknowledged Update State
R
Time Stamp Static Rev Relative
Index
11821
R
Unacknowledged Alarm State
Time Stamp Subcode Value
Table 19 Transducer block bus parameters (continued)
Parameter Description R/W Bytes
MODE_BLK
BLOCK_ERR
UPDATE_EVENT
BLOCK_ALM
Page 59
Range
Data
type
Operation—Foundation Fieldbus
Default: 65535 =
other
0 = LO_LEVEL
1 = HI_LEVEL
0 = Standard
1 = Traces
R4
Directory that specifies the
number and the starting indices
of the transducers in the
transducer block.
R1 Default: 0
A transducer block sub-code.
XD_ERROR contains the
highest priority alarm that has
been activated in the
TB_DETAILED_STATUS
parameter.
A directory that specifies the
R36
number, starting indices, and
DD item of IDs of the data
collection in each transducer
within a transducer block. Used
by the host for efficient transfer
R/W 2 uns16
of information.
Selects the connection of the
sensor
Table 19 Transducer block bus parameters (continued)
TRANSDUCER_
DIRECTORY
Parameter Description R/W Bytes
TRANSDUCER_TYPE Identifies the transducer type. R 2
XD_ERROR
COLLECTION_
DIRECTORY
Output
INPUT_RANGE
POLARIZATION_VOLTAGE Sets the polarization voltage R/W 4 float –1000–0
SENSOR_TYPE Selects the used sensor type. R/W 2 uns16
57
Page 60
Operation—Foundation Fieldbus
0 = Dissolved
oxygen
1 = Measurement in
Range
Data
type
gases
0 = DO_%
1 = DO_mg/l
2 = DO_μg/l
3 = DO_ppm
4 = DO_ppb
5 = GAS_ppm
6 = GAS_%
DS_65
4
1
0–120
Default: 0s
58
Selects the measurement
R/W 2 uns16
method
R
(DO/ GAS)
Shows the primary value and
status
Val ue
Status
Selects the displayed primary
value depending
R/W 2 uns16
on the selected measuring
method in APPLICATION
R/W 2 uns16
R4 float
R4 float
parameter
Sets the filter time of the input
filter
Shows the impedance of the
sensor
Shows the momentary current
of the sensor
Table 19 Transducer block bus parameters (continued)
APPLICATION
Parameter Description R/W Bytes
PRIMARY_VALUE
PRIMARY_VALUE_TYPE
FILTER_TIME
IMPEDANCE
SENSOR_CURRENT
Temperature
Page 61
Operation—Foundation Fieldbus
Range
Data
type
4
R
Process temperature value and
status
DS_65
1001 = °C
1002 = °F
1000 = NTC30
1002 = NTC22
1
R
R/W 2 uns16
R/W 2 uns16
Val ue
Status
Degree C or degree F. Changes
the unit of temperature being
displayed and transmitted.
Type of temperature sensor.
The value entered must
correspond to the temp. sensor
being used.
Sets the wire impedance of the
R/W 4 float Default: 0Ω
temp. sensor. Typically 0 unless
the wire of the sensor gets too
long
–10–10K
Default: 0
1133 = kPA
1137 = BAR
114 1 = PSI
R/W 4 float
Desired temperature reading,
used for temperature
measurement calibration.
R/W 2 uns16
Selects the process pressure
measurement unit
Table 19 Transducer block bus parameters (continued)
SECONDARY_VALUE_2
Parameter Description R/W Bytes
SECONDARY_VALUE_
UNIT_2
TEMP_SENSOR_TYPE
TEMP_WIRE_IMPEDANCE
TEMP_SENSOR_CAL
Concentration/Saturation
PROCESS_PRESSURE_
UNIT
59
Page 62
Operation—Foundation Fieldbus
0–9.999 BAR
0–999.9 kPa
0–145 PSI
Default: 1.013 BAR
0–45 g/kg
Default: 0 g/kg
0 = Sat
1 = Conc
30–110 Sensor A
220–525 Sensor B
Default: 60 E-9A
–2–2
Ampere
Default: 0 E-9A
R/W 4 float
The zero offset resulting from a
calibration in Ampere
Range
Data
type
R/W 4 float
The slope of the Oxy sensor in
Table 19 Transducer block bus parameters (continued)
R4 floatDefault: 0 s
Shows the settling time in
seconds
R4 float
Shows the relative humidity in
R4 float
%
Shows the temperature which
was used during calibration
60
PROCESS_PRESSURE Sets the process pressure R/W 4 float
Parameter Description R/W Bytes
SALINITY Sets the salinity value R/W 4 float
Calibration
CALIBRATION_MODE Sets the calibration mode R/W 1 uns8
CAL_HIGH
CAL_ZERO
CAL_SETTLINGTIME
CAL_RH
CAL_PRESSURE Shows the pressure R 4 float
CAL_TEMP
Page 63
Operation—Foundation Fieldbus
000–9999h
Default: 0000 h =
disable
0 = Nop
1 = Sample
Default: 0 if step 1 of
product calibration
product calibration.
Shows the stored value of the
was not started
Rfloat
first step of Oxy product
calibration
Range
Data
type
R4 float
Shows the value of saturation
calibration
Shows the value of
R4 float
concentration calibration
Sets the calibration timer (time
R/W 4 float
R/W 1 uns8
in which the device should be
calibrated).
Starts the 1st part of Oxy
Table 19 Transducer block bus parameters (continued)
0 = Off
1 = On
0 = Off
1 = On
0 = Off
1 = On
0...100
Default: 0 = None
R/W 4 float
Sets the value for the 2nd part
of Oxy product calibration.
R/W 1 uns8
Enables or disables
Sensocheck.
CAL_VALUE_SAT
CAL_VALUE_CONC
CALIBRATION_TIMER
CAL_SAMPLE_PRD
CAL_SAMPLE_PRD_
STORED_VAL
CAL_PRODUCT
Alert
HOLD Sets the device to HOLD mode. R/W 1 uns8
SENSOCHECK
ALARM_LED_MODE Sets the LED to HOLD mode. R/W 1 uns8
Parameter Description R/W Bytes
LAST_ERROR Shows the last error. R 2 uns16
61
Page 64
Operation—Foundation Fieldbus
0 = Good
2 = Bad
Range
Data
type
R 1 uns8
Shows the current status of the
Sensoface.
Table 19 Transducer block bus parameters (continued)
62
SENSOFACE_STATUS
Identification and local parameter setting
SW_REV_LEVEL Software revision number R 2 uns16
Parameter Description R/W Bytes
HW_REV_LEVEL Hardware revision number R 1 uns8
Page 65
Operation—Foundation Fieldbus

6.2.4 Calibration via Foundation Fieldbus

The transmitter can be calibrated via Foundation Fieldbus using the comparison or grab sample method.
1. Make sure the system is configured for the value that is measured:
Dissolved oxygen: PRIMARY_VALUE_TYPE = DO_mg/l, DO_ppm, DO_µg/l, DO_ppb or DO_% APPLICATION = Dissolved oxygen CALIBRATION_MODE = Conc or Sat
Gaseous oxygen: PRIMARY_VALUE_TYPE = GAS_ppm or GAS_% APPLICATION = Measurement in gases CALIBRATION_MODE = Conc or Sat
2. Collect a grab sample and set CAL_SAMPLE_PRD to sample. The measured value of the sample is stored. After writing, the parameter is automatically reset to NOP (no operation).
3. Read the parameter CAL_SAMPLE_PRD_STORED_VAL. It contains the stored value.
4. Measure the grab sample and write the lab value in CAL_PRODUCT. The device is now calibrated. CAL_SAMPLE_PRD_STORED_VAL is reset to zero.
Note: The calibration values can also be entered directly in the parameters CAL_ZERO and CAL_HIGH.
63
Page 66
Operation—Foundation Fieldbus
64
Page 67
Section 7 Operation—Profibus PA
The following section describes how to navigate and operate the si792x D-PA transmitter. The transmitter can be operated as follows:
• direct interface with the transmitter (section 7.1)
• remote operation from the control station (section 7.2 on
page 67)
Note: Calibration must be completed by direct interface with the transmitter.

7.1 Configuration

Use the configuration mode to specify the sensor, range and other parameters for the system.

7.1.1 Configuration steps

1. Press MEAS + CAL and enter 1200 to enter the configuration
mode.
2. Use the arrow and enter keys to change the settings. All settings and options are shown in section 7.1.2.
To exit the configuration mode at any time, press MEAS + CAL and
ENTER. The Hold mode will be active for 20 seconds and then the
then measured value will be displayed.
Note: During configuration the transmitter remains in the Hold mode for safety reasons. The Sensoface icon is inactive. The configuration mode indicator is displayed (Figure 12 on page 33).
65
Page 68
Operation—Profibus PA

7.1.2 Configuration menu

Select the sensor
Type A (standard; default). See Table 2 on page 24. Type B (trace measurements). See Table 2 on page 24.
Select the range
Lo-Level Hi-Level (default)
Select the units
µg/L
Lo-Level
Hi-Level
Select the temperature unit
Auto °C (default) Auto °F man °C man °F Bus °C –20–150 °C Bus °F –4–302 °F
If Auto is selected >select the temperature sensor
NTC 22 kΩ (default) NTC 30 kΩ
Select the pressure measurement unit
BAR (default) KPA PSI
Enter the process pressure
0–9.999 bar (default: 1.013 BAR)
ppb mg/L ppm % (default) mg/L ppm % (default)
66
Page 69
Operation—Profibus PA
m
T
7.1.2 Configuration menu (continued)
Enter the salinity
0–45.00 SAL (default: 00.00)
Enter polarization voltage
U-Pol 0 mV to 800 mV (default: 675 mV, 0mV = Off)
Select Sensocheck
CHECK ON CHECK OFF (default)
Select the calibration mode
CAL
Enter cal timer interval
Enter Profibus address
Edit 0001–0126 (default: 0126)
Saturation (Sat) Concentration (Conc) (default)
0000–9999 h (default: 0000 h (Off))
Continuous Sensocheck evaluation of sensor function

7.2 Profibus PA communication

Profibus PA uses a master/slave data exchange technique. The master (typically a PLC) generates queries to individual slaves. The slaves, in turn, reply back with a response to the master. A Profibus message contains the information required to send a query or request, including the slave address, function code, data, and a checksum. See Table 20
on page 67 for Profibus communication parameters.
Table 20 PROFIBUS PA communication
Cause
Factory settings defective
Configuration data defective, Gaincheck
No. of
binary
message
1 0000 11xx Failure ERR SYSTEM
2 0000 11xx Failure ERR PARAME
Analog input status
Physical Block (PB)
Global status
Text of binary (default)
67
Page 70
Operation—Profibus PA
Logbook
(default)
Text of binary message
(default)
Failure ERR SAT VALUE Yes
Failure ERR CONC VALUE Yes
Failure ERR TEMP VALUE Yes
0100 0111
0100 1111
0100 0111
0100 1111
5
6
Table 20 PROFIBUS PA communication (continued)
Physical Block
Analog input
No. of
(PB)
Global status
status
binary
message
0100 0111
0100 1111
3 0000 11xx Failure ERR MEMORY Yes
4
CHK ZERO/SLOPE Yes
CHK EL. RESPONSE Yes
CAL REQUIRED Yes
Failure ERR SENSOCHECK Yes
Maintenance
req.
Maintenance
req.
Maintenance
req.
Function check CAL RUNNING Yes
0100 0111
0100 1111
10 0101 00xx
0100 0111
0100 1111
68
Cause
Memory error
(RAM, ROM,
EPROM)
Measurement range
violation
Measurement range
violation
Temp range violation
Temperature sensor
Membrane defective 7
Zero point/Slope 8 0101 00xx
Sensor response time 9 0101 00xx
Calibration timer
Cal prompt
Calibration 9
Configuration 10 1010 00xx Function check CONF RUNNING Yes
Page 71
Table 20 PROFIBUS PA communication (continued)
Logbook
Text of binary message
Physical Block
No. of
(default)
(default)
(PB)
Analog input
status
binary
Global status
message
Operation—Profibus PA
HI_HI_LIMIT OXY
HI_LIMIT OXY
LO_LIMIT OXY
LO_LO_LIMIT OXY
HI_HI_LIMIT TEMP
HI_LIMIT TEMP
LO_LIMIT TEMP
LO_LO_LIMIT TEMP
Function check HOLD Yes
Limit 1
Bit 1
Limit 1
Bit 2
Limit 1
Bit 3
Limit 1
Bit 4
Limit 2
Bit 1
Limit 2
Bit 2
Limit 2
Bit 3
Limit 2
Bit 4
0100 0111
0100 1111
11
14 1000 1110
15 1000 1010
16 1000 1001
17 1000 1101
18 1000 1110
19 1000 1010
20 1000 1001
21 1000 1101
Cause
HOLD
(Device state =
Maintenance)
HI_HI_LIM
FB analysis
HI_LIM
FB analysis
LO_LIM
FB analysis
LO_LO_LIM
FB analysis
HI_HI_LIM
FB temperature
HI_LIM
FB temperature
LO_LIM
FB temperature
LO_LO_LIM
FB temperature
Logbook empty 22 Function check EMPTY LOGBOOK
69
Page 72
Operation—Profibus PA
70
Page 73

Section 8 Calibration

8.1 Calibration

The transmitter is adjusted to the sensor through the calibration. The available calibration methods are shown in Table 21. Calibrate the sensor in air when the sensor can be removed from the process. The sensor will stabilize more quickly in air.
When the sensor cannot be removed from the process (e.g. sterile processes), the process medium must be aerated during calibration (e.g. after sterilization).
Table 21 Calibration methods and passcodes
Method Passcode
Zero calibration 1001 Temperature probe adjustment 1015 Zero/slope display 0000 Calibration in air or water 1100 Calibration by product comparison 1105
During calibration the transmitter remains in the Hold mode for safety reasons. The loop current is frozen at the value specified in the o1.HoLD menu option. The Sensoface icon is inactive. The calibration mode indicator is displayed (Figure 12 on page 33).
To exit the calibration mode at any time, press The output current will be held for 20 seconds and the measured value will be displayed.
Note: Calibrations must be performed by trained personnel. Incorrectly set parameters may result in errors in sample measurements.
CAL and then ENTER.
71
Page 74
Calibration

8.1.1 Zero calibration

Perform a zero calibration as the first point whenever a 2-point calibration is required.
Note: The DO sensor models SE 704, SE 705 and InPro6000 have a very low zero current. Therefore a zero calibration is only recommended for measurement of oxygen traces.
Allow the sensor to stabilize in the calibration medium for at least 10 to 30 minutes (InPro6900 at least 60 minutes). A drift check will not be made. The zero current of a properly functioning sensor is notably less than 0.5% of the current in air.
The display will not change until an input current is entered for the zero point. When measuring in an oxygen-free medium, the displayed current can be taken directly.
Complete the following steps to set the zero point.
1. Press
2. Place the sensor in an oxygen-free medium.
3. Press
4. The slope of the sensor will be shown in the main display. The new
5. Return the sensor to the process. The oxygen value will be shown in
CAL, enter passcode: 1001, ENTER. The main display will
show CAL ZRO and then the entered value (in nA) for the zero point. The secondary display shows the measured current.
ENTER to accept the value or correct the value and then
ENTER.
press
zero point will be shown in the secondary display. Press end the calibration.
the main display alternately with Hold. Press measure mode.
ENTER to return to the
ENTER to
72
Page 75
Calibration

8.1.2 DO calibration (default)

Make sure that DO is selected in the configuration menu (Table 9 on
page 36). For a 2-point calibration, calibrate the zero point first
(section 8.1.1 on page 72).
8.1.2.1 Calibration in air (recommended)
1. Press
2. Remove the sensor from the process and place in air.
3. Enter the actual relative humidity and press
4. Enter the barometric pressure and press
5. Accept the calculated value for the concentration or adjust the value
6. Press
7. Press
CAL, enter passcode: 1100, ENTER. The display will briefly
show CAL and then the entered (or default) humidity value.
show the entered (or default) barometric pressure.
begin. The drift check may take some time. When complete, the display will show the concentration in the units specified in the configuration menu.
Note: To exit the drift check after, 10 seconds, press will be reduced).
as necessary and then press slope and zero (relative to 25 °C and 1.013 mbar).
ENTER to end the calibration. Return the sensor to the
process. The measured value will be shown in the display alternately with Hold.
ENTER to return to the measure mode.
ENTER. The display will show the new
ENTER. The display will
ENTER. A drift check will
CAL (accuracy
73
Page 76
Calibration
8.1.2.2 Calibration in water
The water must be in equilibrium with air (percent saturation for water is 100%). The exchange between air and water is very slow. To speed up the calibration, make sure that there is a steady flow during calibration.
1. Press
2. Remove the sensor from the process and place in the calibration
3. Enter the actual relative humidity (for water always 100% relH) and
4. Enter the barometric pressure and press
5. Accept the calculated value for the concentration or adjust the value
6. Press
7. Press

8.1.3 Gas calibration (volume concentration)

Make sure that GAS is selected in the configuration menu (Table 9 on
page 36).
1. Press
CAL, enter passcode: 1100, ENTER. The display will briefly
show CAL and then the entered (or default) humidity value.
water.
ENTER. The display will show the entered (or default)
press barometric pressure.
ENTER. A drift check will
begin. The drift check may take some time. When complete, the display will show the concentration in the units specified in the configuration menu.
Note: To exit the drift check after > 10 seconds, press (accuracy will be reduced).
as necessary and then press slope and zero (relative to 25 °C and 1.013 mbar).
ENTER to end the calibration. Return the sensor to the
process. The measured value will be shown in the display alternately with Hold.
ENTER to return to the measure mode.
CAL, enter passcode: 1100, ENTER. The display will briefly
show CAL and then the entered (or default) humidity value.
ENTER. The display will show the new
CAL
74
Page 77
Calibration
2. Remove the sensor from the process and place in air or other
(gaseous) calibration medium.
3. Enter the actual relative humidity and press show the entered (or default) barometric pressure.
4. Enter the barometric pressure and press begin. The drift check may take some time. When complete, the display will show the new slope and zero (relative to 25 °C and
1.013 mbar).
Note: To exit the drift check after > 10 seconds, press (accuracy will be reduced).
5. Press
6. Press
ENTER to end the calibration. Return the sensor to the
process. The measured value will be shown in the display alternately with Hold.
ENTER to return to the measure mode.

8.1.4 Calibration by comparison

The sensor can be calibrated for DO (or gas volume concentration) by entering the sample value from a measurement in an instrument such as a laboratory or portable meter. The sensor does not need to be removed from the process during calibration. The sample temperature should correspond to the measured process temperature for accurate results.
1. Press
2. Collect a grab sample for measurement in the lab. Press
3. Measure the grab sample with a laboratory or portable meter.
CAL, enter passcode: 1105, ENTER. The display will briefly
show CAL PRD and then StorE.
store the sample value in the transmitter.
The cal mode indicator will flash to indicate that calibration is not complete. The transmitter will continue to measure and display the current sample values.
ENTER. The display will
ENTER. A drift check will
CAL
ENTER to
75
Page 78
Calibration
4. Press
5. Edit the displayed value to match the value measured by the
6. Press
7. Press
Note: For comparison calibration via Foundation Fieldbus, see
section 6.2.4 on page 63.
CAL, enter passcode: 1105, ENTER to access the product
calibration once more. The display will briefly show CAL PRD and then CALC.
laboratory or portable meter and press zero point will be shown.
ENTER to end the calibration. Return the sensor to the
process. The measured value will be shown in the display alternately with Hold.
ENTER to return to the measure mode.
ENTER. The new slope and

8.2 Temperature sensor adjustment

Complete the following steps to calibrate the temperature sensor.
1. Press
2. Measure the process temperature with an external thermometer.
3. Use the
4. Press
5. The transmitter remains in HoLD mode. Press
Note: Repeat input of the process temperature value when “Err” is displayed.
CAL, enter passcode: 1015, ENTER. CAL TMP will be
displayed for 3 seconds. The process temperature will be shown.
UP ARROW and RIGHT ARROW to enter the value of the
temperature from the external thermometer.
ENTER to save the value.
ENTER again.
The transmitter remains in HoLD mode for approximately 20 seconds after calibration and returns to the measure mode.
76
Page 79

Section 9 Maintenance

DANGER
Explosion hazard. Only qualified personnel should conduct the tasks described in this section of the manual.
DANGER Electrostatic hazard. Follow the instructions in section on page 20 before conducting any maintenance tasks.

9.1 Cleaning the instrument

Use only a moistened antistatic, lint-free cloth to remove dust, dirt and spots from the external surfaces of the transmitter. Use a mild household cleaner if necessary.

9.2 Sensor maintenance

Refer to the user manual supplied with each sensor for specific cleaning requirements.
77
Page 80
Maintenance
78
Page 81

Section 10 Troubleshooting

10.1 Sensoface

The Sensoface feature is active whenever Sensocheck is active. This feature monitors the sensor for defects in the sensor or cable, and indicates the maintenance status of the sensor (Table 22).
Table 22 Sensoface description
Sensoface Description
The sensor is functioning properly.
The functionality of the sensor is acceptable, but will require replacement soon.
The functionality of the sensor is not longer acceptable. Replace the sensor.

10.2 Sensocheck

Important Note: Sensocheck must be switched off for Type B sensors.
The Sensocheck feature monitors the sensor electrodes and wires for open circuits. When problems are detected, the error message “Err 33” is displayed, along with an icon corresponding to the type of problem.
Table 23 shows the sensor types that Sensocheck monitors.
Sensocheck can be switched off in the configuration menu.
Note: For confirmation a Sensoface is displayed after calibration.
79
Page 82
Troubleshooting
Table 23 Sensocheck limits for Type A sensors
Slope Zero Response time Cal timer
Adm.
range
25–130 nA –2–2 nA
35–90 nA –0.5–0.5 nA
30–35 nA –1.0–0.5 nA
90–110 nA 0.5–1.0 nA
< 30 nA < –1.0 nA > 600 seconds timer expired
> 110 nA > 1.0 nA > 600 second timer expired
720 seconds
maximum
300 seconds 80% expired
300–600
seconds
300–600
seconds

10.3 Error codes

Table 24 describes the error codes.
Table 24 Error codes
Code Description Corrective action
Make sure that the correct sensor is connected to the transmitter.
Replace sensor and cable. Make sure that the correct
sensor is connected to the transmitter.
Replace sensor and cable.
ERR 01
ERR 02
Measured value (SAT range) flashes; value is above or below the range limit.
Measured value (Conc range) flashes; value is above or below the range limit.
80–100%
expired
80–100%
expired
80
Page 83
Troubleshooting
Table 24 Error codes (Continued)
Code Description Corrective action
Check the temperature sensor wiring.
Make sure that the correct temperature sensor is selected in the configuration menu.
Measure resistance of the temperature sensor in the sensor to check for correct reading.
Check the loop power supply voltage to the transmitter.
Make sure of the current output selection.
Check the range settings.
Make sure of the configuration settings.
Replace sensor and cable.
Reconfigure and calibrate the device.
Return to the factory for repair and calibration.
ERR 03
ERR 11
ERR 12
ERR 13
ERR 33
ERR 98
ERR 99
Temperature sensor icon flashes; open or short circuit; temperature range exceeded
Current output icon flashes; current is below 3.8 mA
Current output icon flashes; current is above 20.5 mA
Current output icon flashes; reading range value set too large or too small
Sensocheck icon flashes; error with sensor
CONF flashes; configuration or calibration data is defective. Memory error in the program.
FAIL flashes; EEPROM or RAM defective
81
Page 84
Troubleshooting

10.4 Calibration errors

Table 25 describes the calibration error messages.
Table 25 Calibration error messages
Display Description Corrective action
Make sure that the specified values in the configuration menu are correct.
Slope error icon Slope is out of range
CAL ERR with calibration timer icon
Calibration canceled due to large drift in mV reading.
Make sure of the temperature specification in configuration.
Replace the sensor. Make sure that the
temperature does not change during calibration.
Make sure that the cable is sufficiently shielded from strong electric fields.
Make sure that the sensor has electrolyte.
Clean the sensor. Replace the sensor.
82
Page 85

10.5 Diagnostic functions

Table 26 lists the diagnostic functions.
Table 26 Diagnostic functions
Function Description
View the output current
View calibration data
View the last error message
View the sensor current (sensor monitor)
Specify output current
From the measuring mode, press current will show in the main display for five seconds, then return to measuring mode.
From the measuring mode, press ‘0000’. The slope will show in the main display and the zero current will show in the secondary display. After 20 seconds, the transmitter will return to the measuring mode, or press
ENTER to return immediately to the measuring mode.
From the measuring mode, press ‘0000’. The last error message will show for 20 seconds, or
ENTER to return immediately to the measuring mode.
press After viewing the error, the message will be deleted.
From the measuring mode, press ‘2222’. The measured (uncorrected) current will show in the main display. Press mode.
From the measuring mode, press ‘5555’. The measured current will show in the secondary display. The output current in the main display can be modified.
To change the output current:
1. Select the current value with the
2. Edit the number using the
ENTER to confirm. The entered value will show in
3. Press
the secondary display. The transmitter will remain in Hold mode.
4. To exit Hold mode, press measuring mode.
ENTER to return to the measurement
Troubleshooting
ENTER. The output
CAL and enter passcode
CONF and enter passcode
CONF and enter passcode
CONF and enter passcode
RIGHT ARROW key.
UP ARROW key.
CONF, then ENTER to return to
83
Page 86
Troubleshooting
84
Page 87

Section 11 Parts and accessories

11.1 si792 D series versions

Description Catalog number
si792 D, Dissolved Oxygen, C1D2 LXV504.99.70002 si792x D, Dissolved Oxygen, C1D1, ATEX Zone 1 LXV504.99.70102 si792x D-PA, Dissolved Oxygen, C1D1, ATEX Zone 1 LXV504.99.76102 si792x D-FF, Dissolved Oxygen, C1D1, ATEX Zone 1 LXV504.99.77102

11.2 Accessories

Description Catalog number
Installation Kit, si792, LZY486 Panel-Mount Installation Kit, si792 LZY484 Pipe-Mount Installation Kit, si792 LZY483 Protective Hood, si792 LZY485 Rear Housing, si792, LZY487 si792 D, Dissolved Oxygen Manual, English DOC026.52.00797 si792 Series Complete Documentation on CD DOC086.98.00794
85
Page 88
Parts and accessories
86
Page 89

Section 12 Contact information

HACH Company World Headquarters
P.O. Box 389 Loveland, Colorado 80539-0389 U.S.A. Tel (800) 227-HACH (800) 227-4224 (U.S.A. only) Fax (970) 669-2932 orders@hach.com www.hach.com
Repair Service in Latin America, the Caribbean, the Far East, Indian Subcontinent, Africa, Europe, or the Middle East:
Hach Company World Headquarters, P.O. Box 389 Loveland, Colorado, 80539-0389 U.S.A. Tel +001 (970) 669-3050 Fax +001 (970) 669-2932 intl@hach.com
HACH LANGE LTD
Unit 1, Chestnut Road Western Industrial Estate IRL-Dublin 12 Tel. +353(0)1 46 02 5 22 Fax +353(0)1 4 50 93 37 info@hach-lange.ie www.hach-lange.ie
Repair Service in the United States:
HACH Company Ames Service 100 Dayton Avenue Ames, Iowa 50010 Tel (800) 227-4224 (U.S.A. only) Fax (515) 232-3835
HACH LANGE GMBH
Willstätterstraße 11 D-40549 Düsseldorf Tel. +49 (0)2 11 52 88-320 Fax +49 (0)2 11 52 88-210 info@hach-lange.de www.hach-lange.de
DR. BRUNO LANGE GES. MBH
Industriestraße 12 A-3200 Obergrafendorf Tel. +43 (0)27 47 74 12 Fax +43 (0)27 47 42 18 info@hach-lange.at www.hach-lange.at
Repair Service in Canada:
Hach Sales & Service Canada Ltd. 1313 Border Street, Unit 34 Winnipeg, Manitoba R3H 0X4 Tel (800) 665-7635 (Canada only) Tel (204) 632-5598 Fax (204) 694-5134 canada@hach.com
HACH LANGE LTD
Pacific Way Salford GB-Manchester, M50 1DL Tel. +44 (0)161 872 14 87 Fax +44 (0)161 848 73 24 info@hach-lange.co.uk www.hach-lange.co.uk
DR. BRUNO LANGE AG
Juchstrasse 1 CH-8604 Hegnau Tel. +41(0)44 9 45 66 10 Fax +41(0)44 9 45 66 76 info@hach-lange.ch www.hach-lange.ch
87
Page 90
Contact information
HACH LANGE FRANCE S.A.S.
33, Rue du Ballon F-93165 Noisy Le Grand Tél. +33 (0)1 48 15 68 70 Fax +33 (0)1 48 15 80 00 info@hach-lange.fr www.hach-lange.fr
HACH LANGE APS
Åkandevej 21 DK-2700 Brønshøj Tel. +45 36 77 29 11 Fax +45 36 77 49 11 info@hach-lange.dk www.hach-lange.dk
HACH LANGE S.L.U.
Edif. Arteaga Centrum C/Larrauri, 1C- 2ª Pl. E-48160 Derio/Vizcaya Tel. +34 94 657 33 88 Fax +34 94 657 33 97 info@hach-lange.es www.hach-lange.es
HACH LANGE S.R.O.
Lešanská 2a/1176 CZ-141 00 Praha 4 Tel. +420 272 12 45 45 Fax +420 272 12 45 46 info@hach-lange.cz www.hach-lange.cz
HACH LANGE SA
Motstraat 54 B-2800 Mechelen Tél. +32 (0)15 42 35 00 Fax +32 (0)15 41 61 20 info@hach-lange.be www.hach-lange.be
HACH LANGE AB
Vinthundsvägen 159A SE-128 62 Sköndal Tel. +46 (0)8 7 98 05 00 Fax +46 (0)8 7 98 05 30 info@hach-lange.se www.hach-lange.se
HACH LANGE LDA
Av. do Forte nº8 Fracção M P-2790-072 Carnaxide Tel. +351 214 253 420 Fax +351 214 253 429 info@hach-lange.pt www.hach-lange.pt
HACH LANGE KFT.
Hegyalja út 7-13. H-1016 Budapest Tel. +36 (06)1 225 7783 Fax +36 (06)1 225 7784 info@hach-lange.hu www.hach-lange.hu
DR. LANGE NEDERLAND B.V.
Laan van Westroijen 2a NL-4003 AZ Tiel Tel. +31(0)344 63 11 30 Fax +31(0)344 63 11 50 info@hach-lange.nl www.hach-lange.nl
HACH LANGE S.R.L.
Via Riccione, 14 I-20156 Milano Tel. +39 02 39 23 14-1 Fax +39 02 39 23 14-39 info@hach-lange.it www.hach-lange.it
HACH LANGE SP.ZO.O.
ul. Opolska 143 a PL-52-013 Wrocław Tel. +48 (0)71 342 10-83 Fax +48 (0)71 342 10-79 info@hach-lange.pl www.hach-lange.pl
HACH LANGE S.R.L.
Str. Leonida, nr. 13 Sector 2 RO-020555 Bucuresti Tel. +40 (0) 21 201 92 43 Fax +40 (0) 21 201 92 43 info@hach-lange.ro www.hach-lange.ro
88
Page 91
HACH LANGE
8, Kr. Sarafov str. BG-1164 Sofia Tel. +359 (0)2 963 44 54 Fax +359 (0)2 866 04 47 info@hach-lange.bg www.hach-lange.bg
ΗΑCH LANGE E.Π.Ε.
Αυλίδος 27 GR-115 27 Αθήνα Τηλ . +30 210 7777038 Fax +30 210 7777976 info@hach-lange.gr www.hach-lange.gr
Contact information
HACH LANGE SU ANALİZ SİSTEMLERİ LTD .ŞTİ.
Hilal Mah. 75. Sokak Arman Plaza No: 9/A TR-06550 Çankaya/ ANKARA Tel. +90 (0)312 440 98 98 Fax +90 (0)312 442 11 01 bilgi@hach-lange.com.tr www.hach-lange.com.tr
HACH LANGE E.P.E.
27, Avlidos str GR-115 27 Athens Tel. +30 210 7777038 Fax +30 210 7777976 info@hach-lange.gr www.hach-lange.gr
HACH LANGE D.O.O.
Fajfarjeva 15 SI-1230 Domžale Tel. +386 (0)59 051 000 Fax +386 (0)59 051 010 info@hach-lange.si www.hach-lange.si
89
Page 92

Section 13 Warranty, liability and complaints

The manufacturer warrants that the product supplied is free of material and manufacturing defects and undertakes the obligation to repair or replace any defective parts at zero cost.
The warranty period for instruments is 24 months. If a service contract is taken out within 6 months of purchase, the warranty period is extended to 60 months.
With the exclusion of the further claims, the supplier is liable for defects including the lack of assured properties as follows: all those parts that can be demonstrated to have become unusable or that can only be used with significant limitations due to a situation present prior to the transfer of risk, in particular due to incorrect design, poor materials or inadequate finish will be improved or replaced, at the supplier's discretion. The identification of such defects must be notified to the supplier in writing without delay, however at the latest 7 days after the identification of the fault. If the customer fails to notify the supplier, the product is considered approved despite the defect. Further liability for any direct or indirect damages is not accepted.
If instrument-specific maintenance and servicing work defined by the supplier is to be performed within the warranty period by the customer (maintenance) or by the supplier (servicing) and these requirements are not met, claims for damages due to the failure to comply with the requirements are rendered void.
Any further claims, in particular claims for consequential damages cannot be made.
Consumables and damage caused by improper handling, poor installation or incorrect use are excluded from this clause.
The manufacturer process instruments are of proven reliability in many applications and are therefore often used in automatic control loops to provide the most economical possible operation of the related process.
90
Page 93
Warranty, liability and complaints
To avoid or limit consequential damage, it is therefore recommended to design the control loop such that a malfunction in an instrument results in an automatic change over to the backup control system; this is the safest operating state for the environment and the process.
91
Page 94
Warranty, liability and complaints
92
Page 95

Appendix A Passcode editor

For applications requiring compliance with FDA 21 CFR Part 11, certain device functions must be protected with editable passcodes. If passcode protection is not required, use the preset passcodes (Table 27).
To activate the passcode editor:
1. Press CONF.
2. Enter 1989, the administrator passcode. The initial screen will show
for approximately 3 seconds, then proceed to the next function.
3. Use the ARROW keys to change the passcode.
4. Press ENTER to proceed to the next function. Press CONF to exit
the passcode editor. Refer to Table 27 for default passcodes.
Table 27 Default passcode settings
Display Function Default setting
Cal INFO Calibration information 0000 CAL 0-CAL Calibration zero 1001 CAL CAL Calibration Saturation/Concentration 1100 CAL PROD Product calibration 1105 CAL RTD Temperature sensor adjustment 1015 CFG ERR Error information 0000 CFG CONF Configuration 1200 CFG SNSR MO Probe monitor 2222 CFG OUT Current source 5555
CFG SPCL ST
NO SPCL ST
YES SPCL ST
Administrator passcode. Use select NO or YES
Do not change administrator passcode
Change administrator passcode
ARROW keys to
Press
ENTER to return to the default
passcode
CONF to exit the editor
Press
ENTER to accept the new
Press passcode
CONF to exit the editor
Press
1989
93
Page 96
Passcode editor
Important Note: The passcode editor cannot be accessed without the administrator passcode. Record changes in a secure location. It is not possible to override this system if the passwords are lost. The unit must be exchanged. Contact technical support for assistance.
94
Page 97

Index

22 mA signal ...................................................................................... 38
4–20 mA output
error notification hold mode configuration setting the range
A
averaging filter .................................................................................... 38
C
calibration
by product comparison errors
.......................................................................................... 82
temperature probe zero adjustment
calibration mode
......................................................................................... 71
exiting cleaning the transmitter configuration
.......................................................................................... 41
alarm
current output
overview
temperature
D
diagnostic functions ............................................................................ 83
dimensions display
...................................................................................19, 20
................................................................................................ 33
E
error codes ......................................................................................... 80
H
hold mode
during calibration
......................................................................... 38
............................................................. 39
........................................................................ 38
............................................................... 75
..................................................................... 76
......................................................................... 72
......................................................................77
.......................................................................44, 66
..................................................................................... 35
................................................................................ 40
........................................................................ 71
95
Page 98
Index
during output
I
icons ...................................................................................................33
L
LED
setting on or off during hold
M
measurement mode ........................................................................... 35
menu navigation
N
navigation, menu ................................................................................37
noise, reducing
S
Sensocheck
description
setting on or off Sensoface symbols, display
T
temperature compensation ................................................................40
Testing
............................................................................................... 16
time constant troubleshooting
W
wiring
2-electrode probe
sensor
Z
zero adjustment .................................................................................. 72
.............................................................................. 39
.......................................................41
.................................................................................37
...................................................................................38
.................................................................................. 79
.......................................................................... 41
..........................................................................................79
.................................................................................33
......................................................................................38
................................................................................... 83
................................................................ 24, 25
........................................................................................ 25
96
Loading...