Section 2 General Information .................................................................................................................................... 5
2.1 Safety Information .............................................................................................................................................. 5
2.1.1 Use of Hazard Information........................................................................................................................ 5
2.2 General Product Information .............................................................................................................................. 5
3.3.1 Installation in Conduit ............................................................................................................................. 13
3.3.2 Installation Using a Power Cord ............................................................................................................. 13
3.3.3 Wiring for Power at the Controller .......................................................................................................... 14
3.4 Alarms and Relays ........................................................................................................................................... 17
3.4.1 Connecting the Relays ........................................................................................................................... 17
3.4.2 Connecting the Analog Outputs.............................................................................................................. 18
3.5 Connecting/Wiring the sc Sensor..................................................................................................................... 19
3.5.1 Connecting the sc Sensor in a Non-hazardous Location ....................................................................... 19
3.6 Wiring the Digital Gateway............................................................................................................................... 22
3.7 Connecting the Optional Digital Output............................................................................................................ 22
4.1 Using the Keypad............................................................................................................................................. 25
4.2 Controller Display Features ............................................................................................................................. 26
4.2.1 Important Key Presses ........................................................................................................................... 26
4.3 System Setup ................................................................................................................................................. 27
4.3.2 Specifying the Displayed Language ....................................................................................................... 27
4.2.2 Software Text Abbreviations................................................................................................................... 27
4.3.3 Setting the Time and Date...................................................................................................................... 28
4.4 Setting up System Security .............................................................................................................................. 29
4.4.1 Setting the Passcode.............................................................................................................................. 29
4.4.2 Editing the Passcode.............................................................................................................................. 29
4.6.1 Navigating to the Relay Options Menu ................................................................................................... 31
4.7 Data Event Logging Options ............................................................................................................................ 31
4.8 Digital Network Options ................................................................................................................................... 32
4.9 System Setup Menu......................................................................................................................................... 32
4.10 Test/Maint Menu ............................................................................................................................................ 36
5.1 Cleaning the Controller..................................................................................................................................... 37
Microprocessor-controlled measuring unit with measured value display, temperature display,
and menu-driven system
–20 to 60 °C (–4 to 140 °F); 95 % relative humidity, non-condensing with sensor/network
card load <7 W; –20 to 40 °C (–4 to 104 °F) with sensor /network card load <25 W
AC Powered sc100 model: 100–230 V AC ±10 %, 50/60 Hz; Power 15 W with 7 W
sensor/network card load, 37 W with 25 W sensor/network card load
24 V DC powered sc100 model: 24 V DC –15 % / +20 %; Power 16 W with 7 W
sensor/network card load, 34 W with 25 W sensor/network card load
II; II
Two (Analog (4–20 mA)) outputs, maximum impedance 500 Ohm. Optional digital network
connection. IrDA digital connection.
Three SPDT, user-configured contacts rated 100–230 V AC, 5 Amp resistive maximum for the
ac powered sc100 and 24 V DC, 5 A resistive maximum for the dc powered sc100.
CE approved (with all sensor types)
Listed for use in general locations to UL and CSA safety standards by ETL
(with all sensor types)
Specifications
3
Specifications
Specifications
4
Section 2General Information
2.1Safety Information
Please read this entire manual before unpacking, setting up, or operating this equipment. Pay
attention to all danger and caution statements. Failure to do so could result in serious injury to the
operator or damage to the equipment.
To ensure that the protection provided by this equipment is not impaired, do not use or install this
equipment in any manner other than that specified in this manual.
2.1.1 Use of Hazard Information
DANGER
Indicates a potentially or imminently hazardous situation which, if not avoided, could result
in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that may result in minor or moderate injury.
Important Note: Information that requires special emphasis.
Note: Information that supplements points in the main text.
2.1.2 Precautionary Labels
Read all labels and tags attached to the instrument. Personal injury or damage to the instrument
could occur if not observed
This symbol, if noted on the instrument, references the instruction manual for operation
and/or safety information.
This symbol, when noted on a product enclosure or barrier, indicates that a risk of electrical shock and/or
electrocution exists.
This symbol, if noted on the product, indicates the need for protective eye wear.
This symbol, when noted on the product, identifies the location of the connection for Protective Earth
(ground).
This symbol, when noted on the product, identifies the location of a fuse or current limiting device.
Electrical equipment marked with this symbol may not be disposed of in European public disposal systems
after 12 August of 2005. In conformity with European local and national regulations (EU Directive
2002/96/EC), European electrical equipment users must now return old or end-of life equipment to the
Producer for disposal at no charge to the user.
Note: For all electrical products (marked or unmarked) which are supplied or produced by Hach-Lange, please contact
the local Hach-Lange sales office for instructions for proper disposal.
General Information
5
General Information
2.2General Product Information
The controller enclosure is NEMA4X/IP66-rated and has a corrosion-resistant finish designed to
withstand corrosive environmental constituents such as salt spray and hydrogen sulfide. The
controller display shows the current reading plus a secondary measurement such as temperature
if connected to a single sensor, or two readings with their corresponding secondary measurement
readings when two sensors are connected.
Installation instructions for the controller are presented in this manual. If a system with a sensor
and a controller has been purchased, complete information for installation and operation is also
presented in the sensor system manual.
General Product Information
6
Section 3Installation
DANGER
Only qualified personnel should conduct the installation tasks described in this section of
the manual.
DANGER
Do not replace any component unless power has been switched off or the area is known to
be non-hazardous.
4.Gasket for panel mounting, Neoprene,
Cat. No. 1000A4F3249-101
5.Hex nut, M6 (4), Cat. No. 586730010. Pan head screws (4), M6 x 1,0 x 150 mm,
3
2
4
8.Pan head screws (4), M6 x 1,0 x 20 mm,
Cat. No. 5867400
9.Pan head screws (4), M6 x 1,0 x 100 mm,
Cat. No. 5867500
Cat. No. 5867600
5
6
7
8
9
10
Table 1 Customer-supplied Items
Item
14-AWG wire for electrical power connections in conduit or 115 or 230 V ac power cord plus a IP65 / NEMA 4X-rated strain
relief
High-quality, shielded instrumentation cable for connecting the analog outputs plus a IP65 / NEMA 4X-rated strain relief.
Mounting hardware for the sensor (available from the manufacturer, order separately). See the sensor manual.
Sun shield for mounting configurations where the sun strikes the front of the display.
Common hand tools
Installation
7
Installation
3.1Mechanical Installation
Install in an environment that is protected from corrosive fluids.
3.1.1 Controller Dimension Illustrations
Figure 2Controller Dimensions
144.0 mm (5.67 inches)150.0 mm (5.91 inches)
sc100
Figure 3Controller Mounting Dimensions
144.02 mm (5.67 inches)
72.01 mm
(2.84 inches)
72.01 mm
(2.84 inches)
144.02 mm
(5.67 inches)
144.0 mm (5.67 inches)
40.14 mm
(1.58 inches)
80.27 mm
(3.16 inches)
40.14 mm (1.58 inches)
Mechanical Installation
8
M6 x 1.0
80.27 mm
(3.16 inches)
Figure 4Panel Mount Cut-out Dimensions
75 mm (2.955)inches
(ref only)
Installation
144 mm (5.67)inches
ref only()
144 mm
(5.67)
inches
()
ref only
72 mm
(2.835)inches
ref only()
66.67 mm (2.625)inches
Figure 5Conduit Hole Dimensions
75.07 mm (2.955 inches)
28.57 mm (1.125 inches)
135 mm
(5.31)inches
67.4 mm
(2.65)inches
133 mm (5.25)inches
144 mm (5.67 inches)
68.96 mm (2.715 inches)
28.57 mm (1.125 inches)
25.4 mm (1.00 inch)
25.4 mm (1.00 inch)
99.31 mm
(3.91 inches)
50.8 mm
(2.00 inches)
6.35 mm (0.25 inch)
15.24 mm (0.60 inch)
(5.00 inches)
Mechanical Installation
150 mm
(5.91 inches)
(ref only)
127 mm
9
Installation
3.1.2 Mounting the Controller
Attach the controller to a rail or wall or mount it in a panel. Supplied mounting hardware is shown in
Figure 6, Figure 7, and Figure 8.
Figure 6Vertical or Horizontal Pipe Mounting the Controller
4.Mounting Foot (2), Cat. No. 1000B4F322210. Pan head screw, M6 x 1,0 x 150 mm (4),
5.Mounting bracket, controller, Cat. No. 1000C4F3217-101 11. It may be necessary to remove the sensor connectors.
6.Pan head screw (4), Cat. No. 5867400
/8 inch))9.Flat washer (4), Cat. No. 8H1346
8.Hex nut (4), Cat. No. 5867300
Cat. No. 5867600
see procedure below.
10
To remove the sensor connectors before inserting the controller enclosure into the panel cut-out:
1. Disconnect the wires at terminal block J5, see Figure 19 on page 21.
2. Loosen and remove the nut securing the sensor connector inside the enclosure. Remove the
sensor connector and wires. Repeat step 1 and 2 for the other sensor connector.
3. After the controller is in place in the panel, reinstall the sensor connectors and reconnect the
wiring to terminal J5 as shown in Figure 19 on page 21.
Mechanical Installation
11
Installation
3.2Wiring Safety Information
When making any wiring connections to the sc100 Controller, the following warnings and must be
adhered to, as well as, any warnings and notes found throughout the individual installation
sections. For more safety information refer to Safety Information on page 5.
DANGER
Always disconnect power to the instrument when any making electrical connections.
3.2.1Electrostatic Discharge (ESD) Considerations
Important Note: To minimize hazards and ESD risks, maintenance procedures not requiring
power to the analyzer should be performed with power removed.
Delicate internal electronic components can be damaged by static electricity, resulting in degraded
instrument performance or eventual failure.
The manufacturer recommends taking the following steps to prevent ESD damage to
your instrument:
•Before touching any instrument electronic components (such as printed circuit cards and the
components on them) discharge static electricity from your body. This can be accomplished by
touching an earth-grounded metal surface such as the chassis of an instrument, or a metal
conduit or pipe.
•To reduce static build-up, avoid excessive movement. Transport static-sensitive components in
anti-static containers or packaging.
•To discharge static electricity from your body and keep it discharged, wear a wrist strap
connected by a wire to earth ground.
•Handle all static-sensitive components in a static-safe area. If possible, use anti-static floor
pads and work bench pads.
3.3Electrical Installation
High-voltage wiring for the controller is conducted behind the high voltage barrier in the controller
enclosure. The barrier must remain in place unless a qualified installation technician is installing
wiring for power, alarms, or relays. See Figure 9 for barrier removal information.
Wiring Safety Information
12
Installation
RELAYA
+
DATA
+
OUT 2
+
V
+
OUT 1
PCB
CONNECTOR
FIELD WIRING
INSULATION MUST
BE RATED TO
80° C MINIMUM
NCNCNC
COMCOMCOM
NO
F1
F2
NONO
RELAYCRELAYBRELAYARELAYA
1
1
+
DATA+DATA
+
OUT 2+OUT 2
– DATA
– OUT 2
SERVICE REQUEST
SHIELD/CHASSIS GND
+V+
V
+
OUT 1+OUT 1
GND
– OUT 1
2
2
3
3
4
4
5
5
6
PROBES
ANALOG OUTPUTS
PCB
CONNECTOR
PCB
CONNECTOR
FIELD WIRING
INSULATION MUST
BE RATED TO
80° C MINIMUM
FIELD WIRING
INSULATION MUST
BE RATED TO
80° C MINIMUM
DANGER- EXPLOSION HAZARD
DANGER- RISQUE D'EXPLOSION
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE
UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS.
NE PAS DEBRANCHER TANT QUE LE EST SOUS
TENSION, A MONIS QU'IL NE S'AGISSE D'UN
EMPLACEMENT NON-DANGEROUX
J1
J2
J4
NETWORK
INTERFACE
CARD
J3
J5
J6
U5
U9
S1
Figure 9Removing Voltage Barrier
J1
S1
J2
U5
J4
U9
NETWORK
INTERFACE
CARD
1.High voltage barrier2.Unsnap the barrier latch then pull out to remove the barrier.
J3
1
+
DATA
– DATA
2
SERVICE REQUEST
34
+
5
6
1
234
5
NCNCNC
NONO
COMCOMCOM
RELAYCRELAYBRELAYA
FIELD WIRING
INSULATION MUST
BE RATED TO
80° C MINIMUM
V
GND
F1
+
OUT 2
– OUT 2
SHIELD/CHASSIS GND
+
OUT 1
– OUT 1
NO
F2
PROBES
J5
PCB
CONNECTOR
DANGER- EXPLOSION HAZARD
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE
UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS.
J6
DANGER- RISQUE D'EXPLOSION
NE PAS DEBRANCHER TANT QUE LE EST SOUS
TENSION, A MONIS QU'IL NE S'AGISSE D'UN
EMPLACEMENT NON-DANGEROUX
ANALOG OUTPUTS
1
2
3.3.1 Installation in Conduit
In hard-wired electrical applications, the power and safety ground service drops for the instrument
must be 18 to 12 AWG. See Figure 10 on page 13 for strain relief and conduit opening sealing plug
information. See section 3.3.3 on page 14 for wiring information.
3.3.2 Installation Using a Power Cord
A sealing-type strain relief to maintain the NEMA 4X/IP66 environmental rating and a power cord
less than 3 meters (10 feet) in length with three 18-gauge conductors (including a safety ground
wire) can be used, see Replacement Parts on page 39. See Figure 10 on page 13 for strain relief
and conduit opening sealing plug assembly. See section 3.3.3 on page 14 for wiring information.
Figure 10Using the Optional Strain Relief and Conduit Plug
DANGER
Explosion hazard. Do not connect or disconnect electrical components or circuits to the
equipment unless power has been switched off or the area is known to be non-hazardous.
DANGER
Do not connect AC power to a sc100 24 V DC powered model.
The sc100 can be purchased as either an 100–230 V AC powered model or a 24 V DC powered
model. Follow the appropriate wiring instructions per the purchased model.
Important Note: A protective earth (PE) ground connection is required by the sc100 for both
100–230 V AC and 24 V DC wiring applications. Failure to connect a good PE ground connection
can result in shock hazards and poor performance due to electromagnetic interferences. ALWAYS
connect a good PE ground to the sc100 terminal.
The controller can be wired for line power by hard-wiring in conduit or wiring to a power cord.
Regardless of the wire used, the connections are made at the same terminals. A local disconnect
designed to meet local electrical code is required and must be identified for all types of installation.
See Figure 13 and Figure 14 on page 16 for suggested local disconnect configurations.
1. Obtain appropriate fittings with NEMA 4X/IP66 environmental rating.
2. Loosen the screws using a phillips-head screwdriver and open the hinged controller cover.
3. Remove the high-voltage barrier (see Figure 9 on page 13).
4. Insert the wires through the strain relief fitting or conduit hub located in the right-rear access
hole in the bottom of the enclosure. Tighten the strain relief if used, to secure the cord.
5. Properly prepare each wire (Figure 11) and insert each wire into the terminal according to
Table 2 or Table 3. Tug gently after each insertion to ensure the connection is secure.
6. Seal any unused openings in the controller box with conduit opening sealing plugs.
7. Reinstall the high-voltage barrier and latch to secure.
Figure 11Proper Wire Preparation and Insertion
1
2
1.Strip ¼-inch of insulation.2.Seat insulation against connector with no bare wire exposed.
Table 2 AC Power Wiring Information (sc100 AC powered model only)
Terminal NumberTerminal Description Wire Color Code for North AmericaWire Color Code for Europe
Table 3 DC Power Wiring Information (sc100 24 V DC powered model only)
RELAYA
+24
VDC
–24
VDC
Terminal NumberTerminal Description Wire Color Code for North AmericaWire Color Code for Europe
1+24 V dcRedRed
224 V dc returnBlackBlack
3Protective Earth (PE)GreenGreen w/yellow tracer
The DC power source that supplies power to the 24 V DC powered sc100 must maintain voltage
regulation within the specified 24 V DC –15 % / +20 % voltage limits. The DC power source must
also provide adequate protection against line transients.
Figure 12sc100 Wiring Connections
312
45
J1
J3
14
S1
J2
Installation
CARD
U5
U9
1110
F1
J5
NONO
J6
F2
NCNCNC
NO
COMCOMCOM
RELAYCRELAYBRELAYA
–24 VDC
+24 VDC
89
13
12
J4
NETWORK
INTERFACE
1.J1—Network connector8.Sensor connector
2.J2—Header for optional network interface card9.Sensor connector
3.J5—Relay A connector10. J6—Analog output (4–20 mA) connector
4.J6—Relay B connector11. J5—Sensor connector for hard-wiring
5.J7—Relay C connector12. Position for network interface card
6.Fuses (F1, F2)13. Service port
7.J8—Power connections14. Sensor terminator selector/service port configuration
a.AC Power connection (AC powered sc100 model only)
b. DC Power connection (24 V DC sc100 model only)
6
7
7a
7b
Electrical Installation
15
Installation
RELAYA
Figure 13Local Disconnect for Power Cord
J1
S1
J2
J3
1
CARD
U5
U9
J5
J6
F1
NCNCNC
NONO
NO
COMCOMCOM
RELAYCRELAYBRELAYA
J4
NETWORK
INTERFACE
1.Power terminal2.Power cord strain relief
Figure 14Local Disconnect for Hard-wired Line Power
J1
S1
J2
J3
F2
2
1
CARD
U5
U9
J5
NCNCNC
NONO
COMCOMCOM
RELAYCRELAYBRELAYA
J6
J4
NETWORK
INTERFACE
1.Power terminal2.Conduit strain relief
Electrical Installation
16
F1
F2
2
NO
3.4Alarms and Relays
DANGER
Explosion hazard. Do not connect or disconnect electrical components or circuits to the
equipment unless power has been switched off or the area is known to be non-hazardous.
DANGER
Exposure to some chemicals may degrade the sealing properties of materials used in the
following devices: Relays K1, K2, and K3. Periodic inspection of these devices is
recommended to check for degradation.
The controller is equipped with three unpowered relays rated 100–230 V AC, 50/60 Hz, 5 Amp
resistive maximum. See the sensor manual for relay setup details.
3.4.1 Connecting the Relays
DANGER
Relay loads must be resistive. User must externally limit current to the relays to 5 Amps by
use of a fuse or breaker.
DANGER
Power and relay terminals are designed for only single wire termination. Do not use more
than one wire in each terminal.
Installation
The relay connector accepts 18–12 AWG wire (as determined by load application). Wire gauge
less than 18 AWG is not recommended.
The Normally Open (NO) and Common (COM) relay contacts will be connected when an alarm or
other condition is active. The Normally Closed (NC) and Common relay contacts will be connected
when an alarm or other condition is inactive or when power is removed from the controller.
AC Line (100–230 V) Powered sc100’s
AC line powered sc100 controllers contain three relays designed for use with high voltage (greater
than 30 V-RMS, 42,2 V-PEAK or 60 V DC). Refer to Figure 15 for connection information. The
relay wiring compartment is not designed for voltage connections below these levels. Relays must
not be powered from the same wiring used to power the controller.
24 V DC Powered sc100
The 24 V DC sc100 controller contains three relays designed for use with only low voltage (less
than 30 V-RMS, 42,2 V-PEAK or 60 V DC). Refer to Figure 15 for connection information. The
wiring compartment is not designed for voltage connections above these levels. Relay must not be
powered from the same wiring used to power the controller.
Alarms and Relays
17
Installation
NCNCNC
COMCOMCOM
NO
F1
F2
NONO
RELAYCRELAYBRELAYA
J1
J2
J4
S1
NETWORK
INTERFACE
CARD
J3
J5
J6
U5
U9
J5J5
Figure 15Alarm and Relay Connections
J1
S1
J4
J2
U5
U9
J3
J5J5
J5
NCCOMNO
J5J6J7
3
2
1
RELAY ARELAY BRELAY C
F1
F2
NETWORK
INTERFACE
CARD
J6
3.4.2Connecting the Analog Outputs
DANGER
Explosion hazard. Do not connect or disconnect electrical components or circuits to the
equipment unless power has been switched off or the area is known to be non-hazardous.
Two isolated analog outputs (1 and 2) are provided, see Figure 16. Each output can be set to 0–20
or 4–20 mA, and can be assigned to represent the measured parameter or secondary
measurement such as temperature. Make connections with twisted-pair shielded wire and connect
the shield at the controlled component end or at the control loop end. Do not connect the shield at both ends of the cable. Use of non-shielded cable may result in radio frequency emission or
susceptibility levels higher than allowed. Maximum loop resistance is 500 Ohm. Refer to the
sensor manual for output software setup.
NCNCNC
NONO
NO
COMCOMCOM
RELAYCRELAYBRELAYA
Disconnect
Power
Alarms and Relays
18
Make wiring connections at the analyzer end as shown in Figure 16.
Table 4 Output Connections at Terminal Block J6
Recorder WiresCircuit Board Position
Output 2 +1
Output 2 –2
Shield3
Output 1 +4
Output 1 –5
Figure 16Analog Output Connections
+
DATA
+
OUT 2
+
V
+
OUT 1
ANALOG OUTPUTS
PCB
CONNECTOR
FIELD WIRING
INSULATION MUST
BE RATED TO
80° C MINIMUM
NCNCNC
COMCOMCOM
NO
F1
F2
NONO
RELAYCRELAYBRELAYA
J1
J2
J4
S1
NETWORK
INTERFACE
CARD
J3
J5
J6
U5
U9
1
1
+
DATA+DATA
+
OUT 2+OUT 2
– DATA
– OUT 2
SERVICE REQUEST
SHIELD/CHASSIS GND
+V+
V
+
OUT 1+OUT 1
GND
– OUT 1
2
2
3
3
4
4
5
5
6
PROBES
ANALOG OUTPUTSANALOG OUTPUTS
PCB
CONNECTOR
PCB
CONNECTOR
FIELD WIRING
INSULATION MUST
BE RATED TO
80° C MINIMUM
FIELD WIRING
INSULATION MUST
BE RATED TO
80° C MINIMUM
DANGER - EXPLOSION HAZARD
DANGER - RISQUE D'EXPLOSION
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE
UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS.
NE PAS DEBRANCHER TANT QUE LE EST SOUS
TENSION, A MONIS QU'IL NE S'AGISSE D'UN
EMPLACEMENT NON-DANGEROUX
J5J5
J1
S1
J2
U5
J4
U9
NETWORK
INTERFACE
CARD
J3
J5J5
J5
J6
Installation
1
+
DATA
– DATA
2
SERVICE REQUEST
34
+
56
1
2345
NCNCNC
NONO
COMCOMCOM
RELAYCRELAYBRELAYA
FIELD WIRING
INSULATION MUST
BE RATED TO
80° C MINIMUM
V
GND
F1
+
OUT 2
– OUT 2
SHIELD/CHASSIS GND
+
OUT 1
– OUT 1
NO
F2
PROBES
PCB
CONNECTOR
DANGER- EXPLOSION HAZARD
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE
UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS.
DANGER- RISQUE D'EXPLOSION
NE PAS DEBRANCHER TANT QUE LE EST SOUS
TENSION, A MONIS QU'IL NE S'AGISSE D'UN
EMPLACEMENT NON-DANGEROUX
ANALOG OUTPUTS
1
2
3
4
5
J6
3.5Connecting/Wiring the sc Sensor
DANGER
Explosion hazard. Do not connect or disconnect electrical components or circuits to the
equipment unless power has been switched off or the area is known to be non-hazardous.
3.5.1 Connecting the sc Sensor in a Non-hazardous Location
3.5.1.1 Attaching a sc Sensor with a Quick-connect Fitting
The sensor cable is supplied with a keyed quick-connect fitting for easy attachment to the
controller, see Figure 17. Retain the connector cap to seal the connector opening in case the
sensor must be removed. Optional extension cables may be purchased to extend the sensor cable
length. If the total cable length exceeds 100 m (300 ft), a termination box must be installed. When
used with the termination box, the maximum cable length is 400 m (1300 ft). See the Replacement
Parts section in the sensor manual for part number information.
Connecting/Wiring the sc Sensor
19
Installation
Figure 17Attaching the Sensor using the Quick-connect Fitting
sc100
Figure 18Quick-connect Fitting pin assignment
5
4
3
ItemDesignationWire Color
1Pin 1 (+12 V DC) Brown
2Pin 2 (Circuit Common)Black
3Pin 3 (Data (+))Blue
4Pin 4 (Data (–))White
5Pin 5 (Shield)Shield (grey wire in existing quick-disconnect fitting)
6Groove
3.5.1.2 Hard-wiring a sc Sensor to the Controller
6
1
2
1. Open the controller cover.
2. Disconnect and remove the existing wires between the quick connect and terminal block J5,
see Figure 19 on page 21.
3. Remove the quick connect fitting and wires and install the threaded plug on the opening to
maintain the environmental rating.
Connecting/Wiring the sc Sensor
20
4. Strip the insulation on the cable back 1-inch. Strip ¼-inch of each individual wire end.
+
DATA
+
OUT 2
+
V
+
OUT 1
ANALOG OUTPUTS
PCB
CONNECTOR
FIELD WIRING
INSULATION MUST
BE RATED TO
80° C MINIMUM
+
DATA
+
OUT 2
+
V
+
OUT 1
ANALOG OUTPUTS
PCB
CONNECTOR
FIELD WIRING
INSULATION MUST
BE RATED TO
80° C MINIMUM
1
1
+
DATA+DATA
+
OUT 2+OUT 2
– DATA
– OUT 2
SERVICE REQUEST
SHIELD/CHASSIS GND
+V+
V
+
OUT 1+OUT 1
GND
– OUT 1
2
2
3
3
4
4
5
5
6
PROBES
ANALOG OUTPUTSANALOG OUTPUTS
PCB
CONNECTOR
PCB
CONNECTOR
FIELD WIRING
INSULATION MUST
BE RATED TO
80° C MINIMUM
FIELD WIRING
INSULATION MUST
BE RATED TO
80° C MINIMUM
DANGER- EXPLOSION HAZARD
DANGER- RISQUE D'EXPLOSION
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE
UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS.
NE PAS DEBRANCHER TANT QUE LE EST SOUS
TENSION, A MONIS QU'IL NE S'AGISSE D'UN
EMPLACEMENT NON-DANGEROUX
NCNCNC
COMCOMCOM
NO
F1
F2
NONO
RELAY3RELAY2RELAY1
1
1
+
DATA+DATA
+
OUT 2+OUT 2
– DATA
– OUT 2
SERVICE REQUEST
SHIELD/CHASSIS GND
+V+
V
+
OUT 1+OUT 1
GND
– OUT 1
2
2
3
3
4
4
5
5
6
PROBES
ANALOG OUTPUTSANALOG OUTPUTS
PCB
CONNECTOR
PCB
CONNECTOR
FIELD WIRING
INSULATION MUST
BERATED TO
80° CMINIMUM
FIELD WIRING
INSULATION MUST
BERATED TO
80° CMINIMUM
J1
J2
J4
NETWORK
INTERFACE
CARD
J3
U5
U9
S1
DANGER- EXPLOSION HAZARD
DANGER - RISQUE D'EXPLOSION
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE
UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS.
NE PAS DEBRANCHER TANT QUE LE EST SOUS
TENSION, A MONIS QU'IL NE S'AGISSE D'UN
EMPLACEMENT NON-DANGEROUX
5. Pass the cable through conduit and a conduit hub or a strain relief fitting and an available
access hole in the controller enclosure. Tighten the fitting.
6. Wire as shown in Table 5.
7. Close and secure the cover.
Figure 19Hard-wiring the sensor
J1
S1
J4
NETWORKINTERFACE
CARD
J2
U5
J5J5
J5
U9
J5
J6
Installation
J3
1
1
+
DATA
+
DATA
– DATA
– DATA
2
2
SERVICE REQUEST
SERVICE REQUEST
3
34
4
+
V
+
5
5
GND
GND
6
6
1
1
+
+
– OUT 2
– OUT 2
2
2
SHIELD/CHASSIS GND
SHIELD/CHASSIS GND
3
34
4
+
+
5
5
– OUT 1
– OUT 1
NCNCNC
NONO
COMCOMCOM
RELAY3RELAY2RELAY1
FIELD WIRING
FIELD WIRING
INSULATION MUST
INSULATION MUST
BE RATED TO
BE RATED TO
80° C MINIMUM
80° C MINIMUM
V
F1
F2
OUT 2
OUT 2
OUT 1
OUT 1
NO
PCB
PCB
CONNECTOR
CONNECTOR
DANGER- EXPLOSION HAZARD
DANGER- EXPLOSION HAZARD
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE
UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS.
UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS.
DANGER- RISQUE D'EXPLOSION
DANGER- RISQUE D'EXPLOSION
NE PAS DEBRANCHER TANT QUE LE EST SOUS
NE PAS DEBRANCHER TANT QUE LE EST SOUS
TENSION, A MONIS QU'IL NE S'AGISSE D'UN
TENSION, A MONIS QU'IL NE S'AGISSE D'UN
EMPLACEMENT NON-DANGEROUX
EMPLACEMENT NON-DANGEROUX
PROBES
PROBES
ANALOG OUTPUTS
ANALOG OUTPUTS
From Probe
Table 5 Wiring the Sensor at Terminal Block J5
Terminal NumberTerminal DesignationWire Color
1Data (+)Blue
2Data (–)White
3Service RequestNo Connection
4+12 V dcBrown
5Circuit CommonBlack
6ShieldShield (grey wire in existing quick disconnect fitting)
Disconnect
Power
Connecting/Wiring the sc Sensor
21
Installation
3.6Wiring the Digital Gateway
The digital gateway is designed to provide a digital interface to the sc100 controller (or other
appropriate digital controller). The non-sensor end is connected to the controller as described in
section 3.5.1 on page 19 for non-hazardous locations.
3.7Connecting the Optional Digital Output
DANGER
Explosion hazard. Do not connect or disconnect electrical components or circuits to the
equipment unless power has been switched off or the area is known to be non-hazardous.
At this time, the manufacturer supports Modbus RS485, Modbus RS232, and Profibus DP
communication protocols. The optional digital output card is installed in the location indicated in
Figure 21 on page 23. Terminal block J1 provides user connection to the optional network card.
The terminal connection is based on the selected network card. Refer to the instructions supplied
with the network card for more details.
Note: The sc100/1720E system also supports the AquaTrend Network.
Surge Protection Recommendation for Profibus DP
Many industrial environments are vulnerable to power transients and lightning. Water and
wastewater plants are notorious lightning targets. Lightning has become a leading cause of
instrument failure at these facilities. Surge protectors limit the magnitude of over-voltage transients
and protect equipment from damage. To be effective on Data lines, at a minimum, a surge
protector should provide two stages of protection with sub-nanosecond response time. Data line
surge protection should be installed on a Profibus DP network where it might be susceptible to
lightning or transients. The purpose of the surge protector is to protect the device (instrument) it is
located next to, not the network cable.
For the best performance/protection connect the surge protector as close as possible to the device
to be protected and connect the device (instrument) ground connection through the surge
protector’s ground to the local protective earth ground. Contact your local Profibus network
component supplier for their recommendation as to which surge protectors may be best for your
system.
The AquaTrend Network only applies to sc100/1720E systems
AquaTrend
Network
1
Modbus RS485
2-wire
Modbus RS485
4-wire
Modbus RS232Profibus DP
Wiring the Digital Gateway
22
Installation
RELAYA
+
DATA
+
OUT 2
+
V
+
OUT 1
PCB
CONNECTOR
FIELD WIRING
INSULATION MUST
BE RATED TO
80° C MINIMUM
NCNCNC
COMCOMCOM
NO
F1
F2
NONO
RELAYCRELAYBRELAYARELAYA
J1
J2
J4
S1
NETWORKINTERFACE
CARD
J3
J5
J6
U5
U9
1
1
+
DATA+DATA
+
OUT 2+OUT 2
– DATA
– OUT 2
SERVICE REQUEST
SHIELD/CHASSIS GND
+V+
V
+
OUT 1+OUT 1
GND
– OUT 1
2
2
3
3
4
4
5
5
6
PROBES
ANALOG OUTPUTS
PCB
CONNECTOR
PCB
CONNECTOR
FIELD WIRING
INSULATION MUST
BE RATED TO
80° C MINIMUM
FIELD WIRING
INSULATION MUST
BE RATED TO
80° C MINIMUM
DANGER - EXPLOSION HAZARD
DANGER - RISQUE D'EXPLOSION
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE
UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS.
NE PAS DEBRANCHER TANT QUE LE EST SOUS
TENSION, A MONIS QU'IL NE S'AGISSE D'UN
EMPLACEMENT NON-DANGEROUX
J5J5
Figure 20RS232 Connection to Customer-supplied Computer 9-pin D Subminiature Connector
Common 5
Not used 4
Rx 3
Tx 2
Not used 1
Figure 21Network Card Position in the Controller
21
J1
S1
J2
U5
J4
U9
NETWORK
INTERFACE
CARD
J3
J5J5
J5
DANGER- EXPLOSION HAZARD
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE
UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS.
J6
DANGER- RISQUE D'EXPLOSION
NE PAS DEBRANCHER TANT QUE LE EST SOUS
TENSION, A MONIS QU'IL NE S'AGISSE D'UN
PCB
CONNECTOR
EMPLACEMENT NON-DANGEROUX
PROBES
ANALOG OUTPUTS
123456
12345
NCNCNC
NONO
COMCOMCOM
RELAYCRELAYBRELAYA
FIELD WIRING
INSULATION MUST
BE RATED TO
80° C MINIMUM
+
DATA– DATASERVICE REQUEST
+
V
GND
F1
+
OUT 2– OUT 2SHIELD/CHASSIS GND
+
OUT 1
– OUT 1
NO
9
8
7
6
F2
3
4
5
1.J2—Network card header4. Mounting hole (3)
2.J2 Pin 15.Network card placement
3.J1 Terminal
Connecting the Optional Digital Output
23
Installation
Connecting the Optional Digital Output
24
Section 4Operation
4.1Using the Keypad
The front of the controller is shown in Figure 22. The keypad consists of the eight keys described in
Tab le 7 .
Figure 22Front of the Controller
1
sc100
5
2
3
4
1.Instrument display5.IrDA Port
2.BACK key6.HOME key
3.MENU key7.ENTER key
4.RIGHT, LEFT, UP and DOWN keys
Table 7 Controller Key Functions/Features
NumberKeyFunction
2Moves back one level in the menu structure.
3
Moves to the main menu from other menus. This key is not active in menus where a selection or other
input must be made.
6
7
4Navigates through the menus, changes settings, and increments and decrements digits.
6
7Accepts an input value, updates, or accepts displayed menu options.
Moves to the Main Measurement screen from any other screen. This key is not active in menus where a
selection or other input must be made.
Operation
25
Operation
4.2Controller Display Features
When a sensor is connected and the controller is in measurement mode, the controller
automatically identifies the connected sensors and displays associated measurements.
The display will flash on startup, when a sensor error has occurred, when the hold outputs function
has been activated, and when a sensor is being calibrated. An active system warning will cause
the warning icon (a triangle with an exclamation point inside) to be displayed on the right side of
the display. See Figure 23.
Figure 23Display Example
1
2
3
1.Status bar. Indicates the sensor name and status of relays. The relay
letter is displayed when the relay is energized.
2.Main measurement5.Warning icon area
3.Secondary measurement (if applicable)6.Measurement units
SENSOR NAME:
7.00
pH
TEMP: 23.0°C
4.Parameter
4.2.1 Important Key Presses
•Press HOME then RIGHTorLEFTto display two readings when two sensors are connected.
Continue to press
RIGHT orLEFT to toggle through the available display options:
4
5
6
•Press
display the secondary measurement (temperature) and output information.
•When in Menu mode, an arrow may appear on the right side of the display to indicate that
more menus are available. Press UP or DOWN (corresponding to the arrow direction) to
display additional menus.
MAIN MENU
SENSOR DIAG
SENSOR SETUP
SYSTEM SETUP
TEST/MAINT
Controller Display Features
26
UP and DOWN to toggle the status bar at the bottom of the measurement display to
SENSOR NAME:
7.00
TEMP: 23.0°C
SYSTEM SETUP
OUTPUT SETUP
RELAY SETUP
NETWORK SETUP
DISPLAY SETUP
SENSOR NAME:
7.00
OUTPUT1: 12.00 mA
SYSTEM SETUP
DISPLAY SETUP
SECURITY SETUP
LOG SETUP
CALCULATION
SENSOR NAME:
pHpHpH
7.00
pH
OUTPUT2: 12.00 mV
pHpH
SYSTEM SETUP
SECURITY SETUP
LOG SETUP
CALCULATION
ERROR HOLD MODE
Operation
4.2.2 Software Text Abbreviations
AbbreviationMeaningAbbreviationMeaning
AdjAdjustP/FPass/Fail
CalCalibrationPassPassword
ContContinuePrepedPrepared
DfltDefaultSNSerial Number
DiagDiagnosticStdStandard
FreqFrequencyTempTemperature
IntInternalVersVersion
MeasMeasurementXferTransfer
4.3System Setup
4.3.1 Adjusting Display Contrast
StepSelectMenu Level/InstructionsConfirm
1
2
3
4
—ADJUST CONTRAST
5
6
Main Menu or Main Measurement Screen—
MAIN MENU—
SYSTEM SETUP
DISPLAY SETUP
(+0–50)
4.3.2 Specifying the Displayed Language
StepSelectMenu Level/InstructionsConfirm
1
2
MAIN MENU—
SYSTEM SETUP
3
4
5
6
Select the language from displayed options.
Main Menu or Main Measurement Screen—
DISPLAY SETUP
LANGUAGE
System Setup
27
Operation
4.3.3 Setting the Time and Date
4.3.3.1 Setting the Time (24-hr format)
StepSelectMenu Level/InstructionsConfirm
1
2
3
4
5
MAIN MENU—
SYSTEM SETUP
DISPLAY SETUP
SET DATE/TIME
Highlight TIME
Select the character to edit.
6
Scroll to appropriate number.
7
Main Menu or Main Measurement Screen—
4.3.3.2 Setting the Date Format and Date
StepSelectMenu Level/InstructionsConfirm
1
2
3
4
5
6
—Highlight DATE FORMAT
Choose the appropriate date format from the displayed options.
7
MAIN MENU—
SYSTEM SETUP
DISPLAY SETUP
SET DATE/TIME
Highlight DATE
Select the character to edit.—
8
Scroll to the appropriate number.
9
Main Menu or Main Measurement Screen—
System Setup
28
Operation
4.4Setting up System Security
The passcode feature of the sc100 restricts unauthorized access to configuration and calibration
settings. The passcode is factory set to sc100 (the five digits must be followed by a space to
remove the trailing asterisk). The following two options are available:
Disabled: All configuration settings and calibrations can be changed. This is the default setting.
Enabled: Certain calibration and Test/Maint settings/operations cannot be accessed without
the passcode. If the passcode is enabled, it may be edited (see section 4.4.2). The passcode can
consist of up to six digits (alpha and/or numeric and available characters). If the instrument is reset
using the Configure/Default Setup menu selection, the passcode will return to the factory default. If
a changed passcode is forgotten, obtain the Master passcode from the Technical Consulting
Services Department.
4.4.1 Setting the Passcode
StepSelectMenu Level/InstructionsConfirm
1
2
3
4
—SET PASSCODE
5
6
Main Menu or Main Measurement Screen—
MAIN MENU—
SYSTEM SETUP
SECURITY SETUP
Highlight ENABLE
4.4.2 Editing the Passcode
StepSelectMenu Level/InstructionsConfirm
1
2
3
Highlight SECURITY SETUP
MAIN MENU—
SYSTEM SETUP
4
5
EDIT PASSCODE select character (shown in brackets)—
ENTER PASSCODE
EDIT PASSCODE
6
EDIT PASSCODE move to the next character
7
Main Menu or Main Measurement Screen—
Setting up System Security
29
Operation
4.5Output Options
Refer to the System Setup on page 27 for more information on the output options menu.
4.5.1 Navigating to the Output Options Menu
StepSelectMenu Level/InstructionsConfirm
1
2
3
4
5
6
Main Menu or Main Measurement Screen when Output options are configured.—
Customize the options, refer to System Setup on page 27.
MAIN MENU—
SYSTEM SETUP
OUTPUT SETUP
SELECT OUTPUT
The analyzer provides two isolated analog outputs (Output 1 and Output 2).
4.5.2 Hold/Transfer Outputs
During normal measurement operation, the analog outputs can be held at the last measured value
or transferred to a preset value. To hold or transfer the output until released:
StepSelectMenu Level/InstructionsConfirm
1
2
3
4
5
6
7
8
9
10
MAIN MENU—
TEST/MAINT
HOLD OUTPUTS
SET OUTMODE
Select HOLD OUTPUTS or XFER OUTPUTS
SET CHANNELS
Select ALL or one of the connected sensors.—
ACTIVATION
Select LAUNCH
Main Menu or Main Measurement Screen
reading will
flash
Output Options
30
Operation
During calibration, analog outputs can remain active, held, or transferred to a preset mA value.
4.5.3 Release Outputs
StepSelectMenu LevelConfirm
1
2
3
4
5
6
Main Menu or Main Measurement Screen—
MAIN MENU—
TEST/MAINT
HOLD OUTPUTS
ACTIVATION
RELEASE
4.6Relay Options
Refer to System Setup on page 27 for more information on the relay options menu.
4.6.1 Navigating to the Relay Options Menu
StepSelectMenu Level/InstructionsConfirm
1
MAIN MENU—
2
3
4
5
6
Main Menu or Main Measurement Screen when Relay options are configured.—
Customize the options, refer to System Setup on page 27.
4.7Data Event Logging Options
The sc100 provides three data logs (one for each sensor and one for calculated values) and three
event logs (one for each sensor and one for the controller). The data logs store the measurement
data at selected intervals. The event log stores a variety of events that occur on the devices such
as configuration changes, alarms, and warning conditions. The data logs are stored in a packed
binary format and the event logs are stored in a CSV format. The logs can be downloaded through
the digital network port or through the service port using the service cable LZX887.
SYSTEM SETUP
RELAY SETUP
SELECT RELAY
Relay Options
31
Operation
4.8Digital Network Options
The sc100 provides two digital communication methods with the controller (the digital network port
and the IrDA port). Either of the digital ports can be used to access setup data, measurement data,
or data/event logs. For the features available for each individual digital network port, refer to the
instruction sheet supplied with the selected network card.
4.9System Setup Menu
OUTPUT SETUP (see section 4.5.1 on page 30 for expanded menu information)
SELECT OUTPUT 1 OR 2
SELECT SOURCE
Press
ENTER to access a list of all connected sensors and select the sensor that will drive the output.
SET PARAMETER
Press ENTER to select from the displayed parameters. Highlight the appropriate displayed parameter and press ENTER.
SET FUNCTION
Select LINEAR CONTROL for current output to track the measurement valve. Select PID CONTROL for the sc100 to operate
as a PID controller.
SET TRANSFER
Each analog output is normally active, responding to the measured value of its assigned parameter. However, during
calibration, each output can be transferred to this preset transfer value.
SET FILTER
Average measurements over time (0–999 seconds). Default is 0 seconds. The higher the value, the longer the sensor signal
response time will be to a change in the actual process value.
SCALE 0 mA/4 mA
Select 0 mA or 4 mA for minimum current (outputs will be set to 0–20 mA or 4–20 mA).
ACTIVATE
Dependent on Function selected previously. See section 4.5.1 on page 30 for additional information.
FUNCTION set to LINEAR CONTROL
If LINEAR CONTROL was selected in SET FUNCTION, set the low and the high values for the current output here.
FUNCTION set to PID CONTROL
1.SET MODE: AUTO or MANUAL
2.PHASE: DIRECT or REVERSE controller operation.
3.SET SETPOINT: enter the setpoint the PID control will control the process to.
4.PROP BAND: control the proportional band for the PID control.
5.INTEGRAL: control the integral action time period in minutes.
6.DERIVATIVE: control the settings for the rate control.
Digital Network Options
32
Operation
4.9System Setup Menu (continued)
RELAY SETUP
Select Relay A, B, or C
SELECT SOURCE
Select from none, a connected sensor, or the real time clock (RTC)
SET PARAMETER
ENTER to select from the displayed parameters.
Press
SET FUNCTION
Source set to sensor
Alarm: Operates relays in response to the measured parameter. Contains separate High and Low Alarm points, deadbands,
and ON/OFF delay.
Feeder Control: Operates in response to the measured parameter. Can be set for phasing, setpoint, deadband, overfeed
timer, and ON/OFF delay.
Event Control: Controls a cleaning system (or equivalent) on a timed basis.
Warning: Activated when the analyzer detects a sensor warning.
PWM Control: Allows the relay to provide a duty cycled output.
Freq Control: Allows the relay to cycle at a frequency between the minimum pulse per minute and maximum pulse per minute.
Source set to RTC
Timer: Sets the timer for a cleaning system (or equivalent). Controls the output hold, interval, duration, and off delay.
SET TRANSFER
Sets the relay to Energize or De-energize (user-selectable). Normally, each control or alarm relay is active, responding to the
measured value of its assigned parameter. During calibration, however, the relay can be transferred to a preset on/off state to
suit the application requirements. Select Energize or De-energize and press ENTER.
FAILSAFE
Allows the user to create a state where the normal condition is energized. The relay is de-energized when an error condition is
experienced. Select YES (Energized) or NO (De-energized) and press ENTER. YES sets the relay normal condition to
energized resulting in the relay becoming de-energized when an error condition is experienced.
ACTIVATION
Function set to ALARM
LOW ALARM—Sets the value where the relay will turn on in response to decreasing measured value. For example, if the low
alarm is set for 1,0 and the measured value drops to 0,9, the relay will be activated.
HIGH ALARM—Sets the value where the relay will turn on in response to increasing measured value. For example, if the
high alarm is set for 1,0 and the measured value increases to 1,1 the relay will be activated.
LOW DEADBAND—Sets the range where the relay remains on after the measured value increases above the low alarm
value. Default is 5 % of the range. For example, if the low alarm is set for 1,0 and the low deadband is set for 0,5, then the
relay remains on between 1,0 and 1,5.
HIGH DEADBAND—Sets the range where the relay remains on after the measured value decreases below the high alarm
value. Default is 5 % of the range. For example, if the high alarm is set for 4,0 and the high deadband is set for 0,5, then the
relay remains on between 3,5 and 4,0.
OFF DELAY—Sets a time (0–300 seconds) to delay the relay from normally turning off.
ON DELAY—Sets a time (0–300 seconds) to delay the relay from normally turning on.
LOW ALARM—Sets the value where the relay will turn on in response to decreasing measured value. For example, if the low
alarm is set for 1,0 and the measured value drops to 0,9, the relay will be activated.
System Setup Menu
33
Operation
4.9System Setup Menu (continued)
Function set to FEEDER CONTROL
PHASE—“High” phase assigns the relay setpoint to respond to an increasing measured value; conversely, a “Low” phase
assigns the relay setpoint to respond to a decreasing measured value.
SET SETPOINT—Sets the value where the relay will turn on.
DEADBAND—Sets the range where the relay remains on after the measured value decreases below the setpoint value (high
phase relay) or increases above the setpoint value (low phase relay).
OVERFEED TIMER—Sets the time (0–999,9 minutes) to limit how long the relay can remain on.
OFF DELAY—Sets a time (0–999 seconds) to delay the relay from normally turning off.
ON DELAY—Sets a time (0–999 seconds) to delay the relay from normally turning on.
Function set to EVENT CONTROL
SET SETPOINT—Sets the value where the relay will turn on.
DEADBAND—Sets the range where the relay remains on after the measured value decreases below the setpoint value (high
phase relay) or increases above the setpoint value (low phase relay).
OnMax TIMER—Sets the time (0–999 minutes) to limit the time the relay can remain on.
OffMax TIMER—Sets a time (0–999 minutes) to delay the relay from normally turning off.
OnMin TIMER—Sets the time (0–999 minutes) to limit the time the relay can remain on.
OffMin TIMER—Sets the time (0–999 minutes) to limit the time the relay can remain off.
Function set to TIMER (RTC selected in SELECT SOURCE)
HOLD OUTPUTS—Set OUTMODE to select output hold operation and select channels that cause the outputs to be held.
INTERVAL—Set the off time for the relay.
DURATION—Set the on time for the relay.
OFF DELAY—Set the time for additional hold/output time after the relay has been turned off.
Function set to WARNING CONTROL
WARNING LEVEL—Set the warning level that will trigger a relay. Range: 0–32. For example: If warnings 1–9 are active on
the instrument, set the warning level to 0 to allow all warnings to trigger the relay; set the warning level to 5 to allow warnings
6 and above to trigger the relay. Set the warning level to 9 or greater to not trigger the relay on any warning.
Function set to PWM CONTROL
SET MODE—Auto or Manual
PHASE—Direct or Reverse
SET SETPOINT—Control Setpoint
DEAD ZONE—Zone around setpoint where output is off
PERIOD—3–60 second PMW period
MIN WIDTH—Minimum pulse width in 0,1 seconds
MAX WIDTH—Maximum pulse width in 0,1 seconds
PROP BAND—Proportional control band
INTEGRAL—Integral control setting (minutes)
Function set to FREQ CONTROL
SET MODE—Auto or Manual
PHASE—Direct or Reverse
SET SETPOINT—Control Setpoint
DEAD ZONE—Zone around setpoint where output is off
MIN WIDTH—0,001–200 pulses per minute
MAX WIDTH—0,001–200 pulses per minute
PROP BAND—Proportional control band (this is outside of the dead zone)
INTEGRAL—Integral control setting (minutes)
System Setup Menu
34
4.9System Setup Menu (continued)
NETWORK SETUP (this menu appears only if a network card is installed in the controller)
SET MODE
Auto or Manual
MODBUS ADDRESS
Highlight sc100 Analyzer, or either connected sensor then press
(each source must have a different address) then press
BAUD RATE
Select a baud rate of 9600, 19200, 38,4 K, 57,6 K, or 115,2 K. Default: 19200
STOP BITS
Select 1 or 2 stop bits. Default: 1
MODBUS MODE
Select RTU or ASCI. Default: RTU
DATA ORDER
Select Normal or Swapped. Default: Swapped
DISPLAY SETUP
ENTER.
ENTER. Choose a number between 1 and 247 as the address
Operation
ADJUST CONTRAST
Use the UP and DOWN keys to increase or decrease the contrast, see section 4.3.1 on page 27.
LANGUAGE
The default is English. Choose Spanish, German or French to allow all menus to appear in the selected language.
SET DATE/TIME
Use this menu to select the date format and to set the date and time (24-hour (military) format), see section 4.3.3 on page 28.
SECURITY SETUP (Enter a 6-digit passcode)
SET PASSCODE
DISABLE
Disables system security. See section 4.4 on page 29.
ENABLE
Enables system security. See section 4.4 on page 29.
LOG SETUP
DATALOG SETUP
Setup datalogging of displayed sensor measurements
CALCULATION
SET VARIABLE X
Select the sensor corresponding to the variable set as “X”.
SET VARIABLE Y
Select the sensor corresponding to the variable set as “Y”.
SET PARAMETER
Select the parameter to be associated with the variable.
SET FORMULA
Select the formula of the calculation to be performed on “X” and “Y”.
System Setup Menu
35
Operation
4.9System Setup Menu (continued)
ERROR HOLD MODE
HOLD OUTPUTS
Holds outputs when unable to communicate with the sensor.
XFER OUTPUTS
Goes to transfer state when unable to communicate with the sensor.
4.10 Test/Maint Menu
STATUS
Indicates the status of each relay and indicates which sensors are connected to the controller.
OUTPUT CAL
SELECT OUTPUT 1 OR 2
Calibrate Analog Output by specifying values to correspond to 4 mA and 20 mA using the
HOLD OUTPUTS
SET OUTMODE
Choose Hold Outputs or Xfer Outputs
SET CHANNELS
Choose any individual attached sensor or all attached sensors to be held or transferred.
ACTIVATION
Select Launch or Release.
OVERFEED RESET
Reset the overfeed time out.
TEST OUTPUT
SELECT OUTPUT 1 OR 2
Set the analog output to a desired current level. Range: 0–20
TEST RELAY
SELECT RELAY A, B, OR C
Energize or de-energize the selected relay.
RESET CONFIG
UP and DOWN arrow keys.
Reset to default configuration
SIMULATION
SELECT SOURCE, SET PARAMETER, SET SIM VALUE
Simulate sensor measurement value for testing the outputs and relays.
SCAN SENSORS
Manually scans for sensors to determine if sensors have been added or removed.
MODBUS STATS
Indicates the communication statistics for use with an external network.
CODE VERSION
Indicates the controller software version.
Test/Maint Menu
36
Section 5Maintenance
DANGER
Only qualified personnel should conduct the maintenance tasks described in this section
of the manual.
DANGER
Do not replace any component unless power to all electrical circuits to the Controller have
been switched off and the area is known to be non-hazardous.
5.1Cleaning the Controller
With the enclosure securely closed, wipe the exterior with a damp cloth.
5.2Fuse Replacement
The instrument contains two mains fuses. Failed fuses are an indication that an equipment
problem could exist. Problem resolution and fuse replacement should be performed only by
qualified service personnel. Refer to Figure 24 and the following steps to replace the fuses:
1. Disconnect power to the controller (including power to relays and other components,
if powered).
2. Open the hinged controller cover by completely loosening all four captive screws in the cover.
3. Remove the high voltage barrier; pull out on the lever of the captive fastener then pull straight
out on the barrier. Set the barrier aside for reinstallation.
4. Remove the fuses and install new fuses of the same type and rating:
•AC Powered sc100: T, 1,6 A, 250 V, slow blow
•24 V DC powered sc100: T, 3 A, 250 V, slow blow
5. Reinstall the high voltage barrier.
6. Close the controller cover and hand-tighten the four screws.
7. Reconnect power to the instrument.
Maintenance
37
Maintenance
RELAYC
Figure 24Fuse Replacement
J1
S1
J4
NETWORK
INTERFACE
J2
U5
U9
CARD
1.Fuses F1 and F2.
AC powered, T, 1,6A, 250 V, slow blow
DC powered, T, 3A, 250 V, slow blow
Digital output card for Modbus RS232 communicationeach59200-00
Digital output card for Modbus RS485 communicationeach59200-01
Locknuteach1059612
Plug, conduit openingeach58687-00
Power cord with strain relief, 115 Veach54488-00
Power cord with strain relief, 230 Veach54489-00
Sealing Washereach1033814
Strain relief, Heycoeach16664
Sun ShieldeachLZX961
DOC023.52.00032.XXXXX
XXXXX= Date of Revision
Replacement Parts
39
Replacement Parts
Accessories
40
Section 7Warranty, liability and complaints
HACH LANGE GmbH warrants that the product supplied is free of material and manufacturing
defects and undertakes the obligation to repair or replace any defective parts at zero cost.
The warranty period for instruments is 24 months. If a service contract is taken out within 6 months
of purchase, the warranty period is extended to 60 months.
With the exclusion of the further claims, the supplier is liable for defects including the lack of
assured properties as follows: all those parts that can be demonstrated to have become unusable
or that can only be used with significant limitations due to a situation present prior to the transfer of
risk, in particular due to incorrect design, poor materials or inadequate finish will be improved or
replaced, at the supplier's discretion. The identification of such defects must be notified to the
supplier in writing without delay, however at the latest 7 days after the identification of the fault. If
the customer fails to notify the supplier, the product is considered approved despite the defect.
Further liability for any direct or indirect damages is not accepted.
If instrument-specific maintenance and servicing work defined by the supplier is to be performed
within the warranty period by the customer (maintenance) or by the supplier (servicing) and these
requirements are not met, claims for damages due to the failure to comply with the requirements
are rendered void.
Any further claims, in particular claims for consequential damages cannot be made.
Consumables and damage caused by improper handling, poor installation or incorrect use are
excluded from this clause.
HACH LANGE GmbH process instruments are of proven reliability in many applications and are
therefore often used in automatic control loops to provide the most economical possible operation
of the related process.
To avoid or limit consequential damage, it is therefore recommended to design the control loop
such that a malfunction in an instrument results in an automatic change over to the backup control
system; this is the safest operating state for the environment and the process.
Warranty, liability and complaints
41
Warranty, liability and complaints
7.1Immunity
This equipment was tested for Industrial level EMC per:
EN 61326(EMC Requirements for Electrical Equipment for Measurement, Control and
Laboratory Use)
compliance by Hach Company.
Standards include:
IEC 1000-4-2:1995 (EN 61000-4-2:1995) Electrostatic Discharge Immunity (Criteria B)
IEC 1000-4-3:1995 (EN 61000-4-3:1996) Radiated RF Electromagnetic Field Immunity
(Criteria A)
IEC 1000-4-4:1995 (EN 61000-4-4:1995) Electrical Fast Transients/Burst (Criteria B)
IEC 1000-4-5:1995 (EN 61000-4-5:1995) Surge (Criteria B)
IEC 1000-4-6:1996 (EN 61000-4-6:1996) Conducted Disturbances Induced by RF Fields
(Criteria A)
IEC 1000-4-11:1994 (EN 61000-4-11:1994) Voltage Dip/Short Interruptions (Criteria B)
Additional Immunity Standard/s include:
ENV 50204:1996 Radiated Electromagnetic Field from Digital Telephones (Criteria A)
per 89/336/EEC EMC: Supporting test records by Hach Company, certified
7.2Emissions
This equipment was tested for Radio Frequency Emissions as follows:
Standards include:
EN 61000-3-2 Harmonic Disturbances Caused by Electrical Equipment
EN 61000-3-3 Voltage Fluctuation (Flicker) Disturbances Caused by Electrical Equipment
Additional Emissions Standard/s include:
EN 55011 (CISPR 11), Class “A” emission limits
Per 89/336/EEC EMC: EN 61326:1998(Electrical Equipment for measurement, control and
laboratory use—EMC requirements) Class “A” emission limits. Supporting test records by
Hewlett Packard, Fort Collins, Colorado Hardware Test Center (A2LA # 0905-01) and certified
compliance by Hach Company.
Via Riccione, 14
I-20156 Milano
Tel. +39 02 39 23 14-1
Fax +39 02 39 23 14-39
info@hach-lange.it
www.hach-lange.it
Contact
43
Contact
Contact
44
Appendix A Modbus Protocol
A.1 Modbus Troubleshooting
Table 8: Troubleshooting
ProblemPossible CausesSolution
Verify sc100 settings match the Modbus master
settings.Verify Modbus master Parity setting is set to
None.
Check all network devices for termination or biasing
settings. Only the ends of the network should have
termination turned on and only one point on the network
should be providing biasing.
Verify all addresses are unique and between 1 and 247.
Verify the requested register(s) Data Type matches the
Modbus Master Request e.g. do not access a Slave Float
value with a 2 byte Integer request. When requesting a
Float (2 registers/4 bytes), both registers must be
requested at the same time.
No Modus Response
Modbus Exception Response
Baud rate, or stop bits does not match
settings of Modbus master
Bad RS232 or RS485 cableReplace/Repair cable
No or improper network biasing and
termination.
Slave Address incorrect or duplicate
address of another bus device.
Register not supportedVerify register is supported
Data Type incorrect
A.2 sc100 Modbus Registers
Table 9: sc100 Modbus Registers
Group NameTag NameRegister # Data TypeLengthR/WDescription
Measurements
SetupLanguage40003
SetupDate Format40004
Setup
Setup/Analog Output 1Source40006
Setup/Analog Output 1Sensor Select40007
Setup/Analog Output 1
Setup/Analog Output 1Type40009
Setup/Analog Output 1Transfer Value40010Float2R/WSets the transfer value
Setup/Analog Output 1Filter40012
Setup/Analog Output 1
Setup/Analog Output
1/Linear
Calculated
Value
Error Hold
Mode
Measurement
Select
0mA - 4mA
Select
Min Setting40014Float2R/WSets the min output value
40001Float2R
40005
40008
40013
Unsigned
Integer
Unsigned
Integer
Unsigned
Integer
Unsigned
Integer
Unsigned
Integer
Unsigned
Integer
Unsigned
Integer
Unsigned
Integer
Unsigned
Integer
1R/WCurrent System Language
1R/W
1R/W
1R/W
1R/W
1R/W
1R/W
1R/W
1R/W
Value calculated from two sensor
measurements
Current Data Display Format
(0 = DD/MM/YY; 1 = MM/DD/YY;
2 = DD-MM-YY; 3 = MM-DD-YY)
Error Mode Hold State (0 = Hold outputs;
1 = Transfer outputs to predefined value)
Selects data source for this output
(0 = None; 2 = sensor; 4 = Calculation)