Hach-Lange RTC113 User Manual

DOC023.52.90386
RTC113 ST-Module
Real Time Controller – Sludge Thickening-Module
User manual
12/2012, Edition 2A
© HACH-LANGE GmbH, 2012. All rights reserved. Printed in Germany.
Table of contents
Section2 General information .................................................................................................................. 9
2.1 Safety information............................................................................................................................... 9
2.1.1 Hazard notices in this manual.................................................................................................... 9
2.1.2 Warning labels ...........................................................................................................................9
2.2 Areas of application .......................................................................................................................... 10
2.3 Scope of delivery .............................................................................................................................. 10
2.4 Instrument overview.......................................................................................................................... 11
2.5 Theory of operation...........................................................................................................................13
2.5.1 Theory of operation of the RTC Module................................................................................... 13
2.5.2 Input signals............................................................................................................................. 13
2.5.3 Parameters for configuration.................................................................................................... 13
2.5.4 Operating modes ..................................................................................................................... 14
Section3 Installation...............................................................................................................................17
3.1 Installation of the RTC Module ......................................................................................................... 17
3.1.1 Supply voltage of the RTC Module ..........................................................................................17
3.2 Connection of process measurement instruments for the TSS concentration of solids ................... 17
3.2.1 Power supply of the sc sensors and the sc1000 controller...................................................... 17
3.3 sc1000 controller connection............................................................................................................ 17
3.4 Connection to the automation unit on the plant side.........................................................................18
Section4 Parameterization and operation ............................................................................................. 21
4.1 Operating the sc controller................................................................................................................21
4.2 sc1000 setup ....................................................................................................................................21
4.3 Menu structure.................................................................................................................................. 21
4.3.1 DIAGNOSIS............................................................................................................................. 21
4.4 Configuration of RTC113 ST-Module parameters on the sc1000 controller..................................... 21
4.4.1 RTC113 ST-Module open and closed-loop controller.............................................................. 21
4.5 Select sensors .................................................................................................................................. 26
4.6 PRESELECT PROG......................................................................................................................... 28
4.6.1 POLYMER DOSING CONTROL.............................................................................................. 28
4.6.2 FEED FLOW CONTROL .........................................................................................................28
4.6.3 CLOSED LOOP EFFLUENT CONTROL................................................................................. 28
3
Table of contents
4.7 CONTROL PARAMETER .................................................................................................................28
4.7.1 FACTOR POLYMER DOSING.................................................................................................28
4.7.2 POLYMER CONCENTRATION ...............................................................................................28
4.7.3 MANUAL POLYMER DOSING.................................................................................................29
4.7.4 MANUAL FEED FLOW ............................................................................................................29
4.7.5 MAX DECREASE CLOSED L ..................................................................................................29
4.7.6 MAX INCREASE CLOSED L ...................................................................................................29
4.7.7 SET-POINT TSS ......................................................................................................................29
4.7.8 P GAIN TSS .............................................................................................................................29
4.7.9 INTEGRAL TIME TSS..............................................................................................................29
4.7.10 DERIVATIVE TIME TSS ........................................................................................................30
4.8 INPUT/OUTPUT LIMITS ...................................................................................................................30
4.8.1 FEED FLOW LOW ...................................................................................................................30
4.8.2 FEED FLOW HIGH ..................................................................................................................30
4.8.3 FEED FLOW SMOOTHING .....................................................................................................30
4.8.4 LIMIT TSS IN LOW ..................................................................................................................30
4.8.5 LIMIT MAX TSS IN HIGH.........................................................................................................30
4.8.6 TSS IN SMOOTHING...............................................................................................................30
4.8.7 LIMIT TSS OUT LOW ..............................................................................................................31
4.8.8 LIMIT TSS OUT HIGH..............................................................................................................31
4.8.9 TSS OUT SMOOTHING...........................................................................................................31
4.8.10 POLYMER DOSING MINIMUM .............................................................................................31
4.8.11 POLYMER DOSING MAXIMUM ............................................................................................31
4.9 INPUTS .............................................................................................................................................31
4.9.1 MIN FEED FLOW.....................................................................................................................31
4.9.2 MAX FEED FLOW....................................................................................................................31
4.9.3 0/4...20 mA...............................................................................................................................31
4.9.4 MIN POLYMER FLOW.............................................................................................................32
4.9.5 MAX POLYMER FLOW............................................................................................................32
4.9.6 0/4...20 mA...............................................................................................................................32
4.10 OUTPUTS .......................................................................................................................................32
4.10.1 MIN FEED FLOW...................................................................................................................32
4.10.2 MAX FEED FLOW..................................................................................................................32
4.10.3 0/4...20 mA.............................................................................................................................32
4.10.4 MIN POLYMER FLOW.........................................
4.10.5 MAX POLYMER FLOW..........................................................................................................32
4.10.6 0/4...20 mA.............................................................................................................................32
4.10.7 CONTROL CYCLE.................................................................................................................32
4.10.8 MIN RUNTIME .......................................................................................................................33
4.11 Displayed measurement values and variables................................................................................33
..................................................................32
Section5 Maintenance............................................................................................................................35
5.1 Maintenance schedule ......................................................................................................................35
4
Table of contents
Section6 Troubleshooting...................................................................................................................... 37
6.1 Error messages ................................................................................................................................ 37
6.2 Warnings........................................................................................................................................... 37
6.3 Wear parts ........................................................................................................................................ 37
Section7 Replacement parts and accessories ...................................................................................... 39
7.1 Replacement parts............................................................................................................................39
Section8 Contact information ................................................................................................................ 41
Section9 Warranty and liability .............................................................................................................. 43
AppendixA Modbus address setting ...................................................................................................... 45
AppendixB Configuration of the network modules................................................................................. 47
B.1 RTC113 ST-Module Profibus/Modbus telegram ............................................................................. 47
Index....................................................................................................................................................... 49
5
Table of contents
6
Section1 Technical data
These are subject to change without notice.
Embedded PC (compact industrial PC)
Processor
Flash memory 2 GB compact flash card
Internal working memory 256 MB DDR-RAM (not expandable)
Interfaces 1× RJ 45 (Ethernet), 10/100 Mbit/s
Diagnostic LED
Expansion slot 1× CompactFlash type II slot with ejector mechanism
Clock
Operating system Microsoft Windows
Control software TwinCAT PLC Runtime or TwinCAT NC PTP Runtime
System bus 16 bit ISA (PC/104 standard)
Power supply Via system bus (through power supply module CX1100-0002)
Max. power loss 6 W (including the system interfaces CX1010-N0xx)
Analog inputs 0/4 to 20 mA for input of the feed flow rate and the polymer flow rate
Number of inputs
Internal resistance 80 ohm + diode voltage 0.7 V
Pentium®1, MMX compatible, 500 MHz clock rate
1× power, 1× LAN speed, 1× LAN activity, TC status, 1× flash access
Internal, battery-buffered clock for time and date (battery can be replaced)
®2
CE or Microsoft Windows Embedded Standard
One-channel: 2 (KL3011) Two-channel: 4 (KL3011)
Signal current 0/4 to 20 mA
Common mode voltage (UCM) 35 V max.
Measurement error (for entire measurement range)
Voltage surge resistance 35 V DC
Electrical isolation 500 V
Digital inputs Enabling of the open-loop control (thickened sludge pump on/off)
Number of inputs 2 (KL1002)
Nominal voltage 24 V DC (-15 % / +20 %)
Signal voltage "0" –3 to +5 V
Signal voltage "1" 15 to 30 V
Input filter 30 ms
Input current 5mA (typ.)
Electrical isolation 500 V
< ± 0.3 % (from end value of measurement range)
(K-bus/signal voltage)
eff
(K-bus/field voltage)
eff
7
Technical data
Analog outputs Output of the polymer dosing, output of the feed flow rate
Number of outputs
Supply voltage
Signal current 0/4 to 20 mA
Working resistance <500 ohm
Measurement error
Resolution 12 bit
Conversion time Approximately 1.5 ms
One-channel: 2 (KL4012) Two-channel: 4 (KL4012)
24 V DC via the power contacts (Alternatively, 15 V DC with bus termination KL9515)
± 0.5 LSB linearity error ± 0.5 LSB offset error ± 0.1 % (relative to the measuring range end value)
Electrical isolation 500 V
(K-bus/field voltage)
eff
Digital outputs Control of polymer pump: feed flow rate and fault messages
Number of outputs
One-channel: 4 (KL2134) Two-channel: 8 (KL2408)
Nominal load voltage 24 V DC (–15 % / +20 %)
Load type ohmic, inductive lamp load
Max. output current 0.5 A (short-circuit proof) per channel
Reverse polarity protection Yes
Electrical isolation 500 V
(K-bus/field voltage)
eff
Equipment properties
Dimensions (W x× H x× D)
One-channel: 191 × 120 × 96 mm (7.52 × 4.72 × 3.78 in) Two-channel: 227 × 120 × 96 mm (8.94 × 4.72 × 3.78 in)
Mass Approximately 0.9 kg (approximately 1.98 lb)
Environmental conditions
Working temperature 0 to 50 °C (32 to 122 °F)
Storage temperature –25 to +85 °C (–13 to 185 °F)
Relative humidity 95 %, non-condensing
Miscellaneous
Pollution Degree Protection Class Installation Category Maximum Altitude
2 1 II 2000 m (6.562 ft.)
Protection class IP20
Installation DIN rail EN 50022 35 × 15.0
1
Pentium is a registered trademark of the Intel Corporation.
2
Microsoft Windows is a brand name for operating systems of the Microsoft Corporation.
8
Section2 General information
2.1 Safety information
Please read the entire manual carefully before unpacking, assembling or operating the instrument. Pay attention to all hazard and warning notices. Failure to do so could result in serious injury to the operator or damage to the instrument.
To prevent damage to or impairment of the device's protection equipment, the device may only be used or installed as described in this manual.
2.1.1 Hazard notices in this manual
Indicates a potentially or imminently hazardous situation that, if not avoided, can result in death or serious injury.
Indicates a potentially or imminently dangerous situation that, if it is not avoided, can lead to death or to serious injuries.
Indicates a possible dangerous situation that can have minor or moderate injuries as the result.
DANGER
WARNING
CAUTION
Indicates a situation that, if it is not avoided, can lead to damage to the device. Information that requires special emphasis.
Note: Information that supplements points in the main text.
2.1.2 Warning labels
Observe all labels and tags attached to the instrument. Failure to do so may result in personal injury or damage to the instrument.
This symbol may be attached to the device and refers to operation and/or safety notes in the user manual.
This symbol may be found on an enclosure or barrier within the product and indicates a risk of electric shock and/or death by electrocution.
Electrical equipment marked with this symbol may no longer be disposed of in unsorted domestic or industrial waste in Europe after August 12, 2005. In conformity with the provisions in force (EU Directive 2002/96/EC), consumers in the EU must return old electrical devices to the manufacturer for disposal from this date, at no charge to the consumer.
Note: You obtain instructions on the correct disposal of all (marked and not marked) electrical products that were supplied or manufactured by Hach-Lange at your relevant Hach-Lange sales office.
NOTICE
9
General information
2.2 Areas of application
The RTC113 ST-Module (Real Time Controller, Sludge Thickening-Module) is an open and closed-loop control unit for universal applications. It can be used by mechanical sludge thickening devices, for example belt thickeners or drum thickeners in wastewater treatment plants.
The RTC113 ST-Module
Optimizes polymer consumption and
Uniformly manages the concentration of solids in the thick sludge
1-channel Open/closed-loop controller for one thickener 2-channel Open/closed-loop controller for two thickeners
The use of an RTC Module does not release the operator from the duty of care to the system. No guarantees as to the functionality or operational safety of the system.
In particular, the operator must make sure that instruments connected to the RTC open/closed-loop controller are always fully functional.
To make sure these instruments supply correct, reliable measurement values, regular maintenance work (for example, cleaning of the sensor and laboratory comparative measurements) is essential! (Refer to the user manual for the relevant instrument.)
Table1 Versions of the RTC113 ST-Module
NOTICE
2.3 Scope of delivery
The combination of pre-assembled components supplied by the manufacturer does not represent a standalone functional unit. In accordance with EU guidelines, this combination of pre-assembled components is not supplied with a CE mark, and there is no EU declaration of conformity for the combination.
However, the conformity of the combination of components with the guidelines can be proved through technical measurements.
Each RTC Module is supplied with:
SUB-D connector (9 pin)
user manual
ferrite core Check that the order is complete. All listed components must be present. If anything is
missing or damaged, contact the manufacturer or distributor immediately.
NOTICE
10
2.4 Instrument overview
Figure1 Base module RTC 24 V version .
General information
1 PE (protective earth) 5 sc 1000 connection: RS485 (CX1010-N031) 2 24 V 6 Battery compartment 3 0 V 7 CPU base module, consisting of Ethernet port with
battery compartment (CX1010-N000), CPU module with CF card (CX1010-0021) and passive aeration element.
4 Automatic circuit breaker (ON/OFF switch for item 7 and
8 without fuse function).
Note: All components are pre-wired.
8 Power supply module, consisting of bus coupler
(CX1 100-0002) and terminal module 24V.
11
General information
Abbildung 2 Base module RTC 100-240 V version
1 L(+) 7 Automatic circuit breaker (ON/OFF switch for item 10
and 11 without fuse function).
2 N(–) 8 sc 1000 connection: RS485 (CX1010-N041) 3 Input AC 100–240 V / Input DC 95 V–250 V 9 Battery compartment 4 PE (protective earth) 10 CPU base module, consisting of Ethernet port with
battery compartment (CX1010-N000), CPU module with CF card (CX1010-0021) and passive aeration element.
5 24 V transformer (Specification section 3.1.1, page 17) 11 Power supply module, consisting of bus coupler 6 Output DC 24 V, 0,75 A
(CX1100-0002) and terminal module 24V.
Note: All components are pre-wired.
12
Figure3 Design of the analog and digital input and output modules
2
1
General information
1 Input- or Output- Module or Bus Termination Module
analog or digital
Note: The number of LEDs indicates the number of channels.
2.5 Theory of operation
2.5.1 Theory of operation of the RTC Module
The RTC113 RTC Module outputs analog (0/4–20 mA) and digital (0/24 V) signals for the polymer dosing rate or the feed flow rate of mechanical sludge thickening devices. Digital fieldbus signals from sc1000 communication cards can also be used.
2.5.2 Input signals
The most important input signals are:
Sludge influent TSS concentration (concentration of solids)
Feed flow rate of the machine-controlled sludge thickening
2.5.3 Parameters for configuration
Thickened sludge TSS concentration (optional)
Status of the thickened sludge pump (on/off)
The most important parameters for configuration are:
2 LED area with installed LEDs or free LED installation
spaces
The required specific polymer dosing [g polymer/kg TSS]
The target TSS concentration in thickened sludge
Note: In a closed-loop circuit, TSS measurement is required in thickened sludge.
13
General information
2.5.4 Operating modes
The RTC113 ST-Module can be operated as a combined open-loop and closed-loop controller. Several variants can be configured.
1. Configuration of a specified polymer rate [L/h] with a specified feed flow rate [m
2. Configuration of a specified specific polymer dosing rate [g polymer/kg TSS]. One of the following settings is adjusted:
a. The polymer flow rate according to the TSS concentration and the feed flow rate
Based on the actual feed flow rate [L/h] and TSS concentration [g/L] in the feed
Or: b. The feed flow rate according to the specified polymer dosing rate and the
3
/h].
(Figure4).
flow, the polymer dosing rate [L/h] is calculated for the required specific dosing rate.
measured TSS concentration of the influent (Figure5).
Based on the measurement value of the TSS concentration from the influent [g/L]
and the configurable specified polymer dosing rate [L/h], the feed flow rate [m is calculated such that it corresponds to the pre-defined specific polymer dosing rate [g/kg].
3. Both variants 2a and 2b can be combined with the closed-loop controller described below:
a. Closed-loop control of the TSS concentration in the thickened sludge
The specific polymer dosing rate is adjusted according to the difference between
the target and actual TSS concentration in the outlet.
3
/h]
14
Figure4 Adjustment of the polymer dosing rate to the feed flow rate
General information
1 Static thickener 8 Pump for open-loop control of the polymer dosing rate 2 Measurement of the feed flow rate 9 Pump for the feed flow rate 3 Open-loop control of the polymer dosing rate (feed flow
rate measurement value) 4 TSS measurement from the influent 11 TSS measurement in the thickened sludge outlet 5 Open-loop control of the polymer dosing rate (influent
TSS concentration measurement value) 6 RTC113 ST-Module 13 Thickened sludge pump 7 Polymer supply 14 Digester
10 Mechanical sludge thickener
12 Closed-loop control of the polymer dosing rate
15
General information
Figure5 Adjustment of the feed flow rate to the specified polymer dosing rate
1 Static thickener 8 Pump for polymer dosing: constant here 2 Influent 9 Mechanical sludge thickener 3 TSS measurement from the influent 10 TSS measurement in the thickened sludge outlet 4 Open-loop control for the feed flow rate 11 Closed-loop control for the feed flow rate 5 RTC113 ST-Module 12 Thickened sludge pump 6 Pump for open-loop control of the feed flow rate 13 Digester 7 Polymer supply
16
Section3 Installation
Only qualified experts may perform the tasks described in this section of the manual, while adhering to all locally valid safety regulations.
Always lay cables and hoses so that they are straight and do not pose a tripping hazard.
Before the power supply is switched on, refer to the instructions in the relevant manuals.
3.1 Installation of the RTC Module
Only install the RTC Module on a DIN rail. The module must be attached horizontally, with at least 30 mm (1.2 in.) space at the top and bottom to make sure that the passive aeration element can function correctly.
When used indoors, the RTC Module must be installed in a control cabinet. When used outdoors, the RTC Module requires a suitable enclosure that follows the technical specifications.
DANGER
CAUTION
CAUTION
The RTC Module is only operated via the sc1000 controller (see the user manual for the sc1000 controller).
Note: The software version of the sc1000 controller must be V3.14 or above.
3.1.1 Supply voltage of the RTC Module
Table2 Supply voltage of the RTC Module
Voltage 24 V DC (–15 % / +20 %), max. 25 W Recommended fuse C2 With 110–230 V option 110–230 VAC, 50-60 Hz, approximately 25 VA
Note: An external deactivation switch is recommended for all installations.
3.2 Connection of process measurement instruments for the TSS concentration of solids
The measurement signals of the sc sensors for the measurement of the concentration of solids (e. g. SOLITAX sc) are provided to the RTC113 ST-Module via the RTC communication card (YAB117) in the sc1000.
3.2.1 Power supply of the sc sensors and the sc1000 controller
See operating instructions of the respective sc sensors and the sc1000 controller.
3.3 sc1000 controller connection
Connect the SUB-D plug supplied to a dual-core, sheathed data cable (signal or bus cable). For additional information regarding the data cable connection, refer to the enclosed assembly instructions.
17
Installation
3.4 Connection to the automation unit on the plant side
The one-channel and two-channel versions of the ST-Module are equipped with various modules that must be connected to the plant automation system.
The feed flow rate must be provided to the ST-Module as a 0/4 to 20 mA signal.
The polymer flow rate must be provided (on both versions) to the ST-Module as a 0/4 to 20 mA signal.
The status signal of the thickened sludge pump (on/off) must be a digital input signal (24 V/0 V).
The polymer pump can be operated in pulse/pause mode (PWM).
The status signals and fault indications are output as 0 V/24 V signals.
Measurement errors are shown 5 minutes after the error occurs. In the event of a new startup (return of power supply), the unit is set back to ON (24 V) after approximately 1 minute and 40 seconds if there are no measurement errors.
In the event of a new startup (return of power supply), the RTC operating signal is set back to ON (24 V) after approximately 1 minute and 25 seconds.
Table3 Connections for the 1-channel RTC113 ST-Module
Module Name Connection Signal Function
2x digital input KL1002
4x digital output
2x analog output KL4012
1x analog input KL3011 1(+) - 2(-) 0/4 to 20 mA Input of the feed flow rate 1x analog input KL3011 1(+) - 2(-) 0/4 to 20 mA Input of the polymer flow rate Bus termination KL9010 Bus termination
1
KL2134
1 Input + 24 V/0 V Status of thickened sludge pump (on/off) 2 Source + 24 V 24 V for relay 1 +24 V/0 V Polymer pump on/off (24 V/0 V)
5+24V/0V
4 +24 V/0 V Input signals OK (24 V), input signal faulty (0 V) 8 +24 V/0 V RTC operational (24 V), RTC faulty (0 V) 1(+) - 3(-) 0/4 to 20 mA Output of the polymer pump flow rate 5(+) - 7(-) 0/4 to 20 mA Output of the feed flow rate
Closed-loop control of the feed flow rate active/inactive (24 V/0 V)
1
Ground to connection 3 and 7 or to the supply voltage connections
Table4 Connections for the 2-channel RTC113 ST-Module
Module Name Connection Signal Channel Function
1 Input + 24 V/0 V 1 Status of thickened sludge pump (on/off)
4x digital input KL1002
2 Source + 24 V 1 24 V for relay 5 Input + 24 V/0 V 2 Status of thickened sludge pump (on/off) 6 Source + 24 V 2 24 V for relay
18
Table4 Connections for the 2-channel RTC113 ST-Module
Module Name Connection Signal Channel Function
1 +24 V/0 V 1 Polymer pump on/off (24 V/0 V)
5+24V/0V1
2 +24 V/0 V 1 Input signals OK (24 V), input signal faulty (0 V)
8x digital
1
output
2x analog output
2x analog output
1x analog input KL3011 1(+) - 2(-) 0/4 to 20 mA 1 Input of the feed flow rate 1x analog input KL3011 1(+) - 2(-) 0/4 to 20 mA 1 Input of the polymer flow rate 1x analog input KL3011 1(+) - 2(-) 0/4 to 20 mA 2 Input of the feed flow rate 1x analog input KL3011 1(+) - 2(-) 0/4 to 20 mA 2 Input of the polymer flow rate Bus termination KL9010 Bus termination
KL2408
KL4012
KL4012
6 +24 V/0 V 1 RTC operational (24 V), RTC faulty (0 V) 3 +24 V/0 V 2 Polymer pump on/off (24 V/0 V)
7+24V/0V2
4 +24 V/0 V 2 Input signals OK (24 V), input signal faulty (0 V) 8 +24 V/0 V 2 RTC operational (24 V), RTC faulty (0 V) 1(+) - 3(-) 0/4 to 20 mA 1 Output of the polymer pump flow rate 5(+) - 7(-) 0/4 to 20 mA 1 Output of the feed flow rate 1(+) - 3(-) 0/4 to 20 mA 2 Output of the polymer pump flow rate 5(+) - 7(-) 0/4 to 20 mA 2 Output of the feed flow rate
Closed-loop control of the feed flow rate active/inactive (24 V/0 V)
Closed-loop control of the feed flow rate active/inactive (24 V/0 V)
Installation
1
Ground to connection 3 and 7 or to the supply voltage connections
19
Installation
20
Section4 Parameterization and operation
4.1 Operating the sc controller
The RTC Module can only be operated via the sc1000 controller in conjunction with the RTC communication card. Before the RTC Module is used, the user must be familiar with the functionality of the sc1000 controller. Learn how to navigate through the menu and perform the relevant functions.
4.2 sc1000 setup
1. Open the MAIN MENU.
2. Select
3. Select
4. Select
RTC MODULES / PROGNOSYS and confirm. RTC MODULES and confirm. RTC and confirm.
4.3 Menu structure
4.3.1 DIAGNOSIS
DIAGNOSIS
RTC
ERROR LIST
WARNING LIST
REMINDER LIST
Possible error messages: RTC MISSING, RTC CRC, CHECK CONFIG, RTC FAILURE
Possible warning messages: MODBUS ADDRESS, PROBE SERVICE
Note: Refer to Section6 Troubleshooting, page37 for a list of all possible error and warning messages together with a description of all necessary countermeasures to be taken.
4.4 Configuration of RTC113 ST-Module parameters on the sc1000 controller
The following menu items are in the SC1000 SETUP menu.
4.4.1 RTC113 ST-Module open and closed-loop controller
RTC MODULES / PROGNOSYS
RTC MODULES
RTC
CONFIGURE
SELECT SENSOR
Select the sensors installed for the open/closed-loop controller (refer to section4.5, page26).
21
Parameterization and operation
4.4.1 RTC113 ST-Module open and closed-loop controller (Continued)
RTC MODULES / PROGNOSYS
RTC MODULES
RTC
PRESELECT PROG.
CHANNEL 1
Based on the feed flow rate [m³/h] and measured TSS POLYMER DOSING CONTROL
FEED FLOW CONTROL
CLOSED LOOP EFFLUENT CONTROL
CHANNEL 2 As per channel one
concentration [g/L] from the influent, the polymer dosing rate
[L/h] is calculated such that it corresponds to the target specific
polymer dosing rate [g/kg].
Based on the measured TSS concentration [g/L] and a fixed
polymer dosing rate [L/h], the feed flow [m
that it corresponds to the specific polymer dosing rate [g/kg].
If activated, the specific polymer dosing rate FACTOR
POLYMER DOSING is adjusted based on the difference
between the target and actual TSS concentration in the
thickened sludge.
The change in the specific dosing rate affects the polymer
dosing rate [L/h] in the POLYMER DOSING CONTROL module
and affects the feed flow rate in the FEED FLOW CONTROL
module.
3
/h] is calculated such
Activation/ deactivation
Activation/ deactivation
Activation/ deactivation
22
Parameterization and operation
4.4.1 RTC113 ST-Module open and closed-loop controller (Continued)
RTC MODULES / PROGNOSYS
RTC MODULES
RTC
CONTROL PARAMETER
CHANNEL 1
FACTOR POLYMER DOSING
POLYMER CONCEN­TRATION
MANUAL POLYMER DOSING
MANUAL FEED FLOW
MAX DECREASE CLOSED L
MAX INCREASE CLOSED L
SET-POINT TSS
P GAIN TSS
INTEGRAL TIME TSS
DERIVATIVE TIME TSS
CHANNEL 2 As per channel one
Required specific polymer dosing [g/kg]. This parameter determines how many grams of polymer per kilogram of TSS are fed by the machine.
Polymer concentration [g/L] fed via the polymer pump. g/L
The RTC outputs the polymer flow rate [L/h] if
FEED FLOW CONTROL is activated
No open-loop control mode (see above) is activated
The TSS measurement from the influent reports an error, or
The flow measurement from the influent reports an error. The RTC outputs the feed flow rate [m³/h] if
POLYMER DOSING CONTROL is activated
No open-loop control mode (see above) is activated
The TSS measurement from the influent reports an error, or
The flow measurement from the influent reports an error This value defines the maximum decrease of the specific
polymer dosing rate FACTOR POLYMER DOSING [g/kg] if CLOSED LOOP EFFLUENT CONTROL is selected.
This value defines the maximum increase of the specific polymer dosing rate FACTOR POLYMER DOSING [g/kg] if CLOSED LOOP EFFLUENT CONTROL is selected.
Required setpoint of the TSS concentration in the thickened sludge.
Note: This parameter is only considered if CLOSED LOOP EFFLUENT CONTROL is activated.
Proportional gain for the PID closed-loop controller for the TSS concentration in the thickened sludge.
Note: P GAIN TSS [L/g] is divided by 100 before it is multiplied by the deviation of the actual TSS concentration from the required TSS setpoint.
Integral time for the PID closed-loop controller for the TSS concentration in the thickened sludge.
Note: INTEGRAL TIME TSS is set to "0" to deactivate the integral part of the PI open-loop controller.
Derivative time for the PID closed-loop controller for the TSS concentration in the thickened sludge.
g/kg
L/h
m³/h
g/kg
g/kg
g/L
L/g
min
min
23
Parameterization and operation
4.4.1 RTC113 ST-Module open and closed-loop controller (Continued)
RTC MODULES / PROGNOSYS
RTC MODULES
RTC
INPUT/OUTPUT LIMITS
CHANNEL 1
3
FEED FLOW LOW
FEED FLOW HIGH
FEED FLOW SMOOTHING
LIMIT TSS IN LOW
LIMIT MAX TSS IN HIGH
TSS IN SMOOTHING
LIMIT TSS OUT LOW
LIMIT TSS OUT HIGH
TSS OUT SMOOTHING
Feed flow rate input signals below this value [m
this value (to avoid low flow peaks).
Feed flow rate input signals above this value [m
this value (to avoid high flow peaks).
Feed flow measurement values are smoothed in line with this
parameter.
TSS measurement values from the influent that are below this
value [g/L] are set to this value (to avoid low peaks).
TSS measurement values from the influent that are above this
value [g/L] are set to this value (to avoid high peaks).
The TSS measurement values from the influent are smoothed in
line with this parameter.
The TSS values of the thickened sludge that are below this
value [g/L] are set to this value (to avoid low peaks).
The TSS values of the thickened sludge that are above this
value [g/L] are set to this value (to avoid high peaks).
The TSS measurement values from the effluent are smoothed in
line with this parameter.
When FEED FLOW CONTROL is activated, measurement POLYMER DOSING MINIMUM
values for the polymer dosing rate that are below this value
[m³/h] are set to this value (to avoid low peaks in the dosing
flow).
Any RTC calculation above this value [g/L] is set to this value
and delivered to the polymer pump. POLYMER DOSING
MAXIMUM
When FEED FLOW CONTROL is activated, measurement
values for the polymer dosing rate that are above this value
[m³/h] are set to this value (to avoid high peaks in the dosing
flow).
CHANNEL 2 As per channel one
INPUTS
CHANNEL 1
MIN FEED FLOW
MAX FEED FLOW
0/4...20mA
MIN POLYMER FLOW
MAX POLYMER FLOW
0/4...20mA
Minimum flow rate [m³/h] from the influent in accordance with
the 0/4 mA measurement signal.
Maximum flow rate [m³/h] from the influent in accordance with
the 20 mA measurement signal.
Transfer range of 0/4 to 20 mA current loop (as set in connected
flow measuring instrument).
Minimum polymer dosing in [L/h] in accordance with the 0/4 mA
measurement signal.
Maximum polymer dosing in [L/h] in accordance with the 20 mA
measurement signal.
Transfer range of 0/4 to 20 mA current loop (as set on
connected flow measuring instrument).
CHANNEL 2 As per channel one
/h] are set to
3
/h] are set to
3
m
3
m
min
g/L
g/L
min
g/L
g/L
min
L/h
L/h
m³/h
m³/h
L/h
L/h
/h
/h
24
Parameterization and operation
4.4.1 RTC113 ST-Module open and closed-loop controller (Continued)
RTC MODULES / PROGNOSYS
RTC MODULES
RTC
OUTPUTS
CHANNEL 1
MIN FEED FLOW Minimum feed flow rate [m³/h] in accordance with 0/4 mA. m³/h MAX FEED FLOW Maximum feed flow rate [m³/h] in accordance with 20 mA. m³/h
0/4...20mA
MIN POLYMER FLOW
MAX POLYMER FLOW
0/4...20mA
CONTROL CYCLE
MIN RUNTIME
CHANNEL 2 As per channel one
MODBUS
ADDRESS
DATA ORDER
DATALOG INTRVL Indicates the interval in which the data is saved in the log file. [min] SET DEFAULTS Restores the factory settings.
MAINTENANCE
RTC DATA
RTC MEASUREMEN
RTC ACTUAT VAR
DIAG/TEST
EEPROM Hardware test RTC COMM TO Communication time-out RTC CRC Communication check sum
MODBUS ADDRESS
Transfer range of 0/4 to 20 mA current loop (as set on connected flow measuring instrument).
Minimum polymer pump delivery rate in accordance with 0/4 mA.
Maximum polymer pump delivery rate in accordance with 20 mA.
Transfer range of 0/4 to 20 mA current loop (as set on connected flow measuring instrument).
Pulse/pause mode for the polymer pump open-loop control for dosing rates beneath the minimum polymer flow rate (MIN POLYMER FLOW). The on/off duration in pulse/pause mode can be affected by the duration of the CONTROL CYCLE. For example, with a CONTROL CYCLE of 100 seconds and a dosing control value of 60 %, the polymer pump is regularly switched on for 60 seconds and switched off for 40 seconds. Short cycle times increase the switching frequency but enable more precise adaptation to individual requirements. CONTROL CYCLE should be divisible by MIN RUNTIME and produce a whole number.
The minimum ON time in pulse/pause dosing mode. The pump is not activated for periods shorter than this. The MIN RUNTIME must be shorter than the duration of the CONTROL CYCLE.
Start address of an RTC within the Modbus network. Default setting: 41–61
Specifies the register order within a double word. Presetting: NORMAL
Specifies the value measured by the RTC, e. g. the influent measurement.
Specifies the variable calculated by the RTC, e. g. whether the aeration should be switched on or off.
Here, the address is displayed where the communication actually takes place. Presetting: 41
L/h
L/h
s
s
25
Parameterization and operation
4.5 Select sensors
Figure6 Select sensor
1. To select sensors and their sequence for the RTC Module, press RTC > CONFIGURE > SELECT SENSOR.
1ENTER — Saves the setting and returns to the
CONFIGURE menu.
2CANCEL — Returns to the CONFIGURE menu without
saving.
3ADD — Adds a new sensor to the selection.
2. Press A selection list of all subscribers to the sc1000 network
opens.
3. Press the required sensor for the RTC Module and confirm by pressing
Sensors in black type are available for the RTC Module. Sensors in red type are not available for the RTC Module.
Note: Sensors marked (p) are available for PROGNOSYS if these sensors have been selected in conjunction with an RTC (refer to the PROGNOSYS user manual).
4 DELETE — Removes a sensor from the selection.
5UP/DOWN — Moves the sensors up or down.
ADD (Figure6, item 3).
ENTER below the selection list.
26
Parameterization and operation
4. The selected sensor is shown in the sensor list. Press
ADD (Figure6, item 3) to open the selection list again.
5. Select the second sensor for the RTC Module and confirm by pressing
Note: Previously selected sensors are shown in gray.
The selected sensors are shown in the sensor list.
ENTER below the selection list.
6. To sort the sensors in the order specified for the RTC Module, press the sensor and use the arrow keys to move it (Figure6, item 5). Press
DELETE (Figure6, item 4) to remove an incorrect
sensor from the sensor list again.
7. Press ENTER (Figure6, item 1) to confirm the list once it is finished.
27
Parameterization and operation
4.6 PRESELECT PROG
4.6.1 POLYMER DOSING CONTROL
4.6.2 FEED FLOW CONTROL
Based on the measured feed flow rate [m³/h] and the measured TSS concentration [g/L] from the influent, the polymer dosing rate [L/h] is calculated such that the setpoint corresponds to the specific polymer dosing rate [g/kg].
Note: This open-loop control mode can only be activated if FEED FLOW CONTROL is deactivated.
Note: The polymer flow rate is controlled via the RTC.
Based on the measured TSS concentration [g/L] and the specified polymer dosing rate [L/h], the feed flow rate is calculated such that it corresponds with the specific polymer dosing rate [g/kg] (FACTOR POLYMER DOSING).
Note: This open-loop control mode can only be activated if POLYMER DOSING CONTROL is deactivated.
Note: The feed flow rate is controlled via the RTC.
4.6.3 CLOSED LOOP EFFLUENT CONTROL
If activated, the specific polymer dosing rate FACTOR POLYMER DOSING is adjusted based on the difference between the target and actual TSS concentration in the thickened sludge.
If FEED FLOW CONTROL is activated, the TSS load fed with the sludge thickening is adjusted based on the difference between the target and actual TSS concentration in the filtrate.
Note: This closed-loop control can only be activated if POLYMER DOSING CONTROL (section4.6.1) or FEED FLOW CONTROL (section4.6.2) is activated.
4.7 CONTROL PARAMETER
4.7.1 FACTOR POLYMER DOSING
Required specific polymer dosing [g/kg]. This parameter determines how many grams of polymer per kilogram of TSS are fed by the machine.
4.7.2 POLYMER CONCENTRATION
28
Polymer concentration [g/L] fed via the polymer pump.
4.7.3 MANUAL POLYMER DOSING
4.7.4 MANUAL FEED FLOW
4.7.5 MAX DECREASE CLOSED L
Parameterization and operation
The RTC outputs the polymer dosing rate [L/h] if
FEED FLOW CONTROL is activated
No open-loop control mode (section4.6.1 to section4.6.3) is activated
The TSS measurement from the influent reports an error, or
The flow measurement from the influent reports an error.
The RTC outputs the feed flow rate [m3/h] if
POLYMER DOSING CONTROL is activated
No open-loop control mode (section4.6.1 to section4.6.3) is activated
The TSS measurement at the inlet reports an error, or
The flow measurement from the influent reports an error.
4.7.6 MAX INCREASE CLOSED L
4.7.7 SET-POINT TSS
4.7.8 P GAIN TSS
This value defines the maximum decrease of the specific polymer dosing rate FACTOR POLYMER DOSING [g/kg] if CLOSED LOOP EFFLUENT CONTROL is selected.
This value defines the maximum increase of the specific polymer dosing rate FACTOR POLYMER DOSING [g/kg] if CLOSED LOOP EFFLUENT CONTROL is selected.
Required setpoint of the TSS concentration in the thickened sludge.
Note: · This parameter is only considered if CLOSED LOOP EFFLUENT CONTROL (section4.6.3) is activated.
Proportional gain for the PID closed-loop controller for the TSS concentration in the thickened sludge.
Note: P GAIN TSS [L/g] is divided by 100 before it is multiplied by the deviation of the actual TSS concentration from the required TSS setpoint.
4.7.9 INTEGRAL TIME TSS
Integral time for the PID closed-loop controller for the TSS concentration in the thickened sludge.
Note: INTEGRAL TIME TSS is set to "0" to deactivate the integral part of the PI open-loop controller.
29
Parameterization and operation
4.7.10 DERIVATIVE TIME TSS
4.8 INPUT/OUTPUT LIMITS
4.8.1 FEED FLOW LOW
4.8.2 FEED FLOW HIGH
4.8.3 FEED FLOW SMOOTHING
Derivative time for the PID closed-loop controller for the TSS concentration in the thickened sludge.
Feed flow rate input signals below this value [m3/h] are set to this value. This means that very low feed flow rates can be avoided.
Feed flow rate input signals above this value [m3/h] are set to this value. This avoids load peaks.
Feed flow measurement values are smoothed in line with this parameter.
SMOOTHING = 1: The signal for the flow rate measurement is not smoothed.
4.8.4 LIMIT TSS IN LOW
4.8.5 LIMIT MAX TSS IN HIGH
4.8.6 TSS IN SMOOTHING
SMOOTHING = 2: Smoothing is performed over 3 minutes. SMOOTHING = 3: Smoothing is performed over 5 minutes. SMOOTHING = 5: Smoothing is performed over 12 minutes. SMOOTHING = 10: Smoothing is performed over
25 minutes. Example: With the setting SMOOTHING = 2, it takes 3 minutes for the
smoothed value to reach 95 % of the final value after an abrupt change in the feed flow rate.
TSS measurement values from the influent that are below this value [g/L] are set to this value (to avoid low peaks).
Measurement values from the influent that are above this value [g/L] are set to this value (to avoid high peaks).
TSS measurement values from the influent are smoothed in line with this parameter.
30
SMOOTHING = 1: The signal is not smoothed.
SMOOTHING = 2: Smoothing is performed over 3 minutes.
SMOOTHING = 3: Smoothing is performed over 5 minutes.
SMOOTHING = 5: Smoothing is performed over 12 minutes.
SMOOTHING = 10: Smoothing is performed over
25 minutes.
4.8.7 LIMIT TSS OUT LOW
4.8.8 LIMIT TSS OUT HIGH
Parameterization and operation
TSS measurement values for the thickened sludge that are below this value [g/L] are set to this value (to avoid low peaks).
4.8.9 TSS OUT SMOOTHING
4.8.10 POLYMER DOSING MINIMUM
TSS measurement values for the thickened sludge that are above this value [m
TSS measurement values from the effluent are smoothed in line with this parameter.
SMOOTHING = 1: The signal is not smoothed. SMOOTHING = 2: Smoothing is performed over 3 minutes. SMOOTHING = 3: Smoothing is performed over 5 minutes. SMOOTHING = 5: Smoothing is performed over 12 minutes. SMOOTHING = 10: Smoothing is performed over
25 minutes.
RTC calculations below this value [g/L] are set to this value and transferred to the polymer pump.
Note: When FEED FLOW CONTROL is activated, measurement values for the polymer dosing rate that are below this value [m value (to avoid low peaks in the dosing flow).
3
/h] are set to this value (to avoid high peaks).
3
/h] are set to this
4.8.11 POLYMER DOSING MAXIMUM
4.9 INPUTS
4.9.1 MIN FEED FLOW
4.9.2 MAX FEED FLOW
4.9.3 0/4...20 mA
RTC calculations above this value [g/L] are set to this value and transferred to the polymer pump.
Note: When FEED FLOW CONTROL is activated, measurement values for the polymer dosing rate that are above this value [m value (to avoid high peaks in the dosing flow).
Minimum flow rate [m³/h] from the influent in accordance with the 0/4 mA measurement signal.
Maximum flow rate [m³/h] from the influent in accordance with the 20 mA measurement signal.
Transfer range of the 0/4 to 20 mA current loop (as set in connected flow measuring instrument).
3
/h] are set to this
31
Parameterization and operation
4.9.4 MIN POLYMER FLOW
4.9.5 MAX POLYMER FLOW
4.9.6 0/4...20 mA
4.10 OUTPUTS
4.10.1 MIN FEED FLOW
4.10.2 MAX FEED FLOW
Minimum polymer dosing in [L/h] in accordance with the 0/4 mA measurement signal.
Maximum polymer dosing in [L/h] in accordance with the 20 mA measurement signal.
Transfer range of the 0/4 to 20 mA current loop (as set in connected flow measuring instrument).
Minimum feed flow rate [m³/h] in accordance with 0/4 mA.
Maximum feed flow rate [m³/h] in accordance with 20 mA.
4.10.3 0/4...20 mA
4.10.4 MIN POLYMER FLOW
4.10.5 MAX POLYMER FLOW
4.10.6 0/4...20 mA
4.10.7 CONTROL CYCLE
Transfer range of 0/4 to 20 mA current loop (as set in connected flow measuring instrument).
Minimum polymer pump delivery rate in accordance with 0/4 mA.
Maximum polymer pump delivery rate in accordance with 20 mA.
Transfer range of 0/4 to 20 mA current loop (as set in connected flow measuring instrument).
Pulse/pause mode for the polymer pump open-loop control for dosing rates beneath the minimum polymer flow rate (MIN POLYMER FLOW). The on/off duration in pulse/pause mode can be affected by the duration of the CONTROL CYCLE. For example, with a CONTROL CYCLE of 100 seconds and a dosing control value of 60 %, the polymer pump is switched on for 60 seconds and switched off for 40 seconds. Short cycle times increase the switching frequency but enable more precise adaptation to individual requirements.
32
Note: CONTROL CYCLE must be divisible by MIN RUNTIME and produce a whole number.
Parameterization and operation
4.10.8 MIN RUNTIME
Minimum ON time in pulse/pause dosing mode. The pump is activated for this runtime at the very least. The MIN RUNTIME must be shorter than the duration of the CONTROL CYCLE.
4.11 Displayed measurement values and variables
The following measurement values and variables are shown on the sc1000 display and transferred via fieldbus (refer to
sectionAppendixB).
RTC113 ST-Module, one-channel Parameter Unit Description
3
Measurement 1 Qin 1 m Measurement 2 Qavg 1 m Measurement 3 Qdos1 L/h Polymer flow rate Measurement 4 TSin 1 g/L TSS concentration from the influent Measurement 5 TSef 1 g/L TSS concentration from the effluent Actuat var 6 Pdos1 L/h Polymer dosing Actuat var 7 Fact 1 g/kg Specific polymer dosing Actuat var 8 Feed 1 m
/h Flow rate from the influent
3
/h Average flow rate
3
/h Feed flow rate
RTC113 ST-Module, two-channel Parameter Unit Description
3
Measurement 1 Qin 1 m Measurement 2 Qavg 1 m Measurement 3 Qdos 1 L/h Polymer flow rate 1 Measurement 4 TSin 1 g/L TSS concentration from the influent 1 Measurement 5 TSef 1 g/L TSS concentration in the effluent 1 Measurement 6 Qin 2 m Measurement 7 Qavg 2 m Measurement 8 Qdos 2 L/h Polymer flow rate 2 Measurement 9 TSin 2 g/L TSS concentration from the influent 2 Measurement 10 TSef 2 g/L TSS concentration in the effluent 2 Actuat var 11 Pdos 1 L/h Polymer dosing 1 Actuat var 12 Fact 1 g/kg Specific polymer dosing 1 Actuat var 13 Feed 1 m Actuat var 14 Pdos2 L/h Polymer dosing 2 Actuat var 15 Fact 2 g/kg Specific polymer dosing 2 Actuat var 16 Feed 2 m
/h Flow rate from the influent 1
3
/h Average flow rate
3
/h Flow rate from the influent 2
3
/h Average flow rate
3
/h Feed flow rate 1
3
/h Feed flow rate 2
33
Parameterization and operation
34
Section5 Maintenance
Multiple hazards Only qualified personnel must conduct the tasks described in this section of the manual.
5.1 Maintenance schedule
Interval Maintenance task
DANGER
Visual inspection
CF card 2 years
Battery 5 years
Application-specific Check for contamination and corrosion
Replacement by manufacturer's service department (Section8,
page41)
Replacement by manufacturer's service department (Section8,
page41)
35
Maintenance
36
Section6 Troubleshooting
6.1 Error messages
Possible RTC errors are displayed by the sc controller.
Table5
Displayed errors Cause Resolution
Supply RTC with voltage
RTC MISSING
RTC CRC
CHECK CONFIG
RTC FAILURE
INFLOW1 NOT G. Influent measurement signal faulty Test sensor, check cable connections INFLOW2 NOT G. Influent measurement signal faulty Test sensor, check cable connections
No communication between RTC and RTC communication card
Interrupted communication between RTC and RTC communication card
The sensor selection of the RTC was deleted by deleting or selecting a new sc1000 participant.
Brief general read/write error on the CF card, mostly caused by a brief interruption to the power supply.
Test connection cable Reset the sc1000 and the RTC (switch so it is
completely voltage free and switch back on) Make sure +/- connections of the connector
cable between RTC and RTC communication card in the sc1000 are installed correctly.
From MAIN MENU > RTC MODULES / PROGNOSYS > RTC MODULES > RTC > CONFIGURE > SELECT SENSOR, select the correct sensor for the RTC again and confirm.
Acknowledge error. If this message is shown frequently, eliminate the cause of the power disruptions. If necessary, inform the service team of the manufacturer (Section8, page41).
6.2 Warnings
Possible RTC sensor warnings are displayed by the sc controller.
Table6
Displayed warnings Cause Resolution
The RTC menu SET DEFAULTS was opened.
MODBUS ADDRESS
PROBE SERVICE A configured sensor is in service status. The sensor must exit service status.
This deleted the Modbus address of the RTC in the sc1000.
Go to MAIN MENU > RTC MODULES / PROGNOSYS > RTC MODULES > RTC > CONFIGURE > MODBUS > ADDRESS and set the correct MODBUS address.
6.3 Wear parts
Table7
Designation Number Service life
CF card, type RTC module 1 piece Battery 1 piece
~2years ~5years
37
Troubleshooting
38
Section7 Replacement parts and accessories
7.1 Replacement parts
Description Cat. No
DIN rail NS 35/15, punched according to DIN EN 60715 TH35, made of galvanized steel. Length: 35 cm (13.78 in.)
Transformer 90–240 V AC/24 V DC 0.75 A, module for DIN rail assembly LZH166 Terminal for 24 V connection without power supply LZH167 Terminal for protective earth LZH168 SUB-D connector LZH169 C2 circuit breaker LZH170 CPU base module with Ethernet port, passive ventilation element. (CX1010-0021) and
RS422/485 connection module (CX1010-N031) Power supply module, consisting of a bus coupler and a 24 V terminal module (CX1100-0002) LZH172 Digital output module 24 V DC (4 outputs) (KL2134) LZH174 Analog output module (2 outputs) (KL4012) LZH176 Analog input module (1 input) (KL3011) LZH177 Digital input module 24 V DC (2 inputs) (KL1002) LZH204 Digital output module 24 V DC (8 outputs) (KL2408) LZH205 Bus termination module (KL9010) LZH178 RTC communication card YAB117 CF card type RTC-Module LZY748-00
LZH165
LZH171
39
Replacement parts and accessories
40
Section8 Contact information
HACH Company World Headquarters
P.O. Box 389 Loveland, Colorado 80539-0389 U.S.A. Tel (800) 227-HACH (800) -227-4224 (U.S.A. only) Fax (970) 669-2932 orders@hach.com www.hach.com
HACH LANGE GMBH Willstätterstraße 11
D-40549 Düsseldorf Tel. +49 (0)2 11 52 88-320 Fax +49 (0)2 11 52 88-210 info@hach-lange.de www.hach-lange.de
HACH LANGE GMBH Rorschacherstrasse 30a
CH-9424 Rheineck Tel. +41 (0)848 55 66 99 Fax +41 (0)71 886 91 66 info@hach-lange.ch www.hach-lange.ch
HACH LANGE APS Åkandevej 21
DK-2700 Brønshøj Tel. +45 36 77 29 11 Fax +45 36 77 49 11 info@hach-lange.dk www.hach-lange.dk
Repair Service in the United States:
HACH Company Ames Service 100 Dayton Avenue Ames, Iowa 50010 Tel (800) 227-4224 (U.S.A. only) Fax (515) 232-3835
HACH LANGE LTD Pacific Way
Salford GB-Manchester, M50 1DL Tel. +44 (0)161 872 14 87 Fax +44 (0)161 848 73 24 info@hach-lange.co.uk www.hach-lange.co.uk
HACH LANGE FRANCE S.A.S.
8, mail Barthélémy Thimonnier Lognes F-77437 Marne-La-Vallée cedex 2 Tél. +33 (0) 820 20 14 14 Fax +33 (0)1 69 67 34 99 info@hach-lange.fr www.hach-lange.fr
HACH LANGE AB Vinthundsvägen 159A
SE-128 62 Sköndal Tel. +46 (0)8 7 98 05 00 Fax +46 (0)8 7 98 05 30 info@hach-lange.se www.hach-lange.se
Repair Service in Canada: Hach Sales & Service
Canada Ltd. 1313 Border Street, Unit 34 Winnipeg, Manitoba R3H 0X4 Tel (800) 665-7635 (Canada only) Tel (204) 632-5598 Fax (204) 694-5134 canada@hach.com
HACH LANGE LTD Unit 1, Chestnut Road
Western Industrial Estate IRL-Dublin 12 Tel. +353(0)1 460 2522 Fax +353(0)1 450 9337 info@hach-lange.ie www.hach-lange.ie
HACH LANGE NV/SA Motstraat 54
B-2800 Mechelen Tel. +32 (0)15 42 35 00 Fax +32 (0)15 41 61 20 info@hach-lange.be www.hach-lange.be
HACH LANGE S.R.L. Via Rossini, 1/A
I-20020 Lainate (MI) Tel. +39 02 93 575 400 Fax +39 02 93 575 401 info@hach-lange.it www.hach-lange.it
Repair Service in Latin America, the Caribbean, the Far East, Indian Subcontinent, Africa, Europe, or the Middle East:
Hach Company World Headquarters, P.O. Box 389 Loveland, Colorado, 80539-0389 U.S.A. Tel +001 (970) 669-3050 Fax +001 (970) 669-2932 intl@hach.com
HACH LANGE GMBH Hütteldorfer Str. 299/Top 6
A-1140 Wien Tel. +43 (0)1 912 16 92 Fax +43 (0)1 912 16 92-99 info@hach-lange.at www.hach-lange.at
DR. LANGE NEDERLAND B.V.
Laan van Westroijen 2a NL-4003 AZ Tiel Tel. +31(0)344 63 11 30 Fax +31(0)344 63 11 50 info@hach-lange.nl www.hach-lange.nl
HACH LANGE S.L.U. Edificio Seminario
C/Larrauri, 1C- 2ª Pl. E-48160 Derio/Vizcaya Tel. +34 94 657 33 88 Fax +34 94 657 33 97 info@hach-lange.es www.hach-lange.es
HACH LANGE LDA Av. do Forte nº8
Fracção M P-2790-072 Carnaxide Tel. +351 214 253 420 Fax +351 214 253 429 info@hach-lange.pt www.hach-lange.pt
HACH LANGE KFT. Vöröskereszt utca. 8-10. H-1222 Budapest XXII. ker.
Tel. +36 1 225 7783 Fax +36 1 225 7784 info@hach-lange.hu www.hach-lange.hu
HACH LANGE SP. ZO.O. ul. Krakowska 119
PL-50-428 Wrocław Tel. +48 801 022 442 Zamówienia: +48 717 177 707 Doradztwo: +48 717 177 777 Fax +48 717 177 778 info@hach-lange.pl www.hach-lange.pl
HACH LANGE S.R.L. Str. Căminului nr. 3,
et. 1, ap. 1, Sector 2 RO-021741 Bucureşti Tel. +40 (0) 21 205 30 03 Fax +40 (0) 21 205 30 17 info@hach-lange.ro www.hach-lange.ro
HACH LANGE S.R.O. Zastrčená 1278/8
CZ-141 00 Praha 4 - Chodov Tel. +420 272 12 45 45 Fax +420 272 12 45 46 info@hach-lange.cz www.hach-lange.cz
HACH LANGE 8, Kr. Sarafov str.
BG-1164 Sofia Tel. +359 (0)2 963 44 54 Fax +359 (0)2 866 15 26 info@hach-lange.bg www.hach-lange.bg
HACH LANGE S.R.O. Roľnícka 21
SK-831 07 Bratislava – Vajnory Tel. +421 (0)2 4820 9091 Fax +421 (0)2 4820 9093 info@hach-lange.sk www.hach-lange.sk
HACH LANGE SU ANALİZ SİSTEMLERİ LTD.ŞTİ.
Ilkbahar mah. Galip Erdem Cad. 616 Sok. No:9 TR-Oran-Çankaya/ANKARA Tel. +90312 490 83 00 Fax +90312 491 99 03 bilgi@hach-lange.com.tr www.hach-lange.com.tr
41
Contact information
HACH LANGE D.O.O. Fajfarjeva 15
SI-1230 Domžale Tel. +386 (0)59 051 000 Fax +386 (0)59 051 010 info@hach-lange.si www.hach-lange.si
HACH LANGE OOO Finlyandsky prospekt, 4A
Business Zentrum “Petrovsky fort”, R.803 RU-194044, Sankt-Petersburg Tel. +7 (812) 458 56 00 Fax. +7 (812) 458 56 00 info.russia@hach-lange.com www.hach-lange.com
ΗΑCH LANGE E.Π.Ε. Αυλίδος 27
GR-115 27 Αθήνα Τηλ. +30 210 7777038 Fax +30 210 7777976 info@hach-lange.gr www.hach-lange.gr
HACH LANGE D.O.O. Ivana Severa bb
HR-42 000 Varaždin Tel. +385 (0) 42 305 086 Fax +385 (0) 42 305 087 info@hach-lange.hr www.hach-lange.hr
HACH LANGE MAROC SARLAU
Villa 14 – Rue 2 Casa Plaisance Quartier Racine Extension MA-Casablanca 20000 Tél. +212 (0)522 97 95 75 Fax +212 (0)522 36 89 34 info-maroc@hach-lange.com www.hach-lange.ma
42
Section9 Warranty and liability
The manufacturer warrants that the supplied product is free of material and manufacturing defects, and undertakes to repair or to replace any defective parts without charge.
The warranty period is 24 months. If a maintenance contract is taken out within 6 months of purchase, the warranty period is extended to 60 months.
With the exclusion of further claims, the supplier is liable for defects, including the lack of assured properties, as follows: all parts that, within the warranty period calculated from the day of the transfer of risk, can be demonstrated to have become unusable or that can only be used with significant limitations owing to circumstances prior to transfer of risk, in particular due to incorrect design, substandard materials or inadequate finish, shall be repaired or replaced at the supplier's discretion. The identification of such defects must be reported to the supplier in writing as soon as possible, but no later than 7 days after the discovery of the fault. If the customer fails to notify the supplier, the product is considered approved despite the defect. Further liability for indirect or direct damages is not accepted.
If device-specific maintenance- or inspection work prescribed by the supplier is to be performed within the guarantee period by the customer (maintenance) or by the supplier (inspection) and these requirements are not met, claims for damages that result from non-observance of these requirements are void.
Further claims, in particular for consequential damages, cannot be made. Wear and damage caused by improper handling, incorrect installation or non-designated
use are excluded from this clause. The process instruments of the manufacturer have proven their reliability in many
applications and are therefore often used in automatic control loops to enable the most economical and efficient operation of the relevant process.
To avoid or limit consequential damage, it is therefore recommended that the control loop be designed such that an instrument malfunction results in an automatic changeover to the backup control system. This guarantees the safest operating condition both for the environment and the process.
43
Warranty and liability
44
AppendixA Modbus address setting
The same slave address must be set for Modbus communication on the sc1000 controller display and in the RTC module. Since 20 slave numbers are reserved for internal purposes, the following numbers are available for assignment:
1, 21, 41, 61, 81, 101… The start address 41 is preset at the factory.
NOTICE
If this address is to be or must be changed because, for example, it has already been allocated for another RTC, the changes must be made both on the sc1000 controller and on the CF card of the RTC module.
This can only be done by the manufacturer service department (Section8)!
45
Modbus address setting
46
AppendixB Configuration of the network modules
B.1RTC113 ST-Module Profibus/Modbus telegram
Table8 RTC113 ST-Module, one-channel
Register Parameter Unit Description
3
MEASUREMENT 1 Qin 1 m MEASUREMENT 2 Qavg 1 m MEASUREMENT 3 Qdos1 L/h Polymer flow rate MEASUREMENT 4 TSin 1 g/L TSS concentration in the inflow MEASUREMENT 5 TSef 1 g/L TSS concentration in the outflow ACTUAT VAR 6 Pdos1 L/h Polymer dosing ACTUAT VAR 7 Fact 1 g/kg Specific polymer dosing ACTUAT VAR 8 Feed 1 m
Table9 RTC113 ST-Module, two-channel
Register Parameter Unit Description
MEASUREMENT 1 Qin 1 m MEASUREMENT 2 Qavg 1 m MEASUREMENT 3 Qdos 1 L/h Polymer flow rate 1 MEASUREMENT 4 TSin 1 g/L TSS concentration in inflow 1 MEASUREMENT 5 TSef 1 g/L TSS concentration in outflow 1 MEASUREMENT 6 Qin 2 m MEASUREMENT 7 Qavg 2 m MEASUREMENT 8 Qdos 2 L/h Polymer flow rate 2 MEASUREMENT 9 TSin 2 g/L TSS concentration in inflow 2 MEASUREMENT 10 TSef 2 g/L TSS concentration in outflow 2 ACTUAT VAR 11 Pdos 1 L/h Polymer dosing 1 ACTUAT VAR 12 Fact 1 g/kg Specific polymer dosing 1 ACTUAT VAR 13 Feed 1 m ACTUAT VAR 14 Pdos2 L/h Polymer dosing 2 ACTUAT VAR 15 Fact 2 g/kg Specific polymer dosing 2 ACTUAT VAR 16 Feed 2 m
/h Flow rate in the inflow
3
/h Average flow rate
3
/h Feed flow rate
3
/h Flow rate in inflow 1
3
/h Average flow rate
3
/h Flow rate from the influent 2
3
/h Average flow rate
3
/h Feed flow rate 1
3
/h Feed flow rate 2
47
Configuration of the network modules
48
Index
Numerics
1-channel version ..................................................... 18
2-channel version ..................................................... 18
A
Abmessungen .......................................................... 11
Address setting ........................................................ 45
aeration element ................................................ 11, 12
B
Battery compartment .......................................... 11, 12
C
Closed-loop controller behavior ............................... 13
Concentration of solids
SOLITAX sc .......................................................... 17
TSS ....................................................................... 17
Control cycle ............................................................ 25
D
DIN rail ..................................................................... 17
E
Embedded PC ............................................................ 7
Error messages ........................................................ 37
Ethernet port ...................................................... 11, 12
Expansion slot ............................................................ 7
F
Feed flow rate ............................................................ 7
Flash memory ............................................................ 7
I
Input
analog ..................................................................... 7
digital ...................................................................... 7
Inputmodule ............................................................. 13
Interfaces ................................................................... 7
Module
bus termination ..................................................... 13
input ...................................................................... 13
output .................................................................... 13
O
Open-loop control ..................................................... 14
feed flow ......................................................... 22, 28
Open-loop controller
polymer dosing ................................................ 22, 28
Operating system ....................................................... 7
Output
analog ..................................................................... 8
digital ...................................................................... 8
Outputmodule ........................................................... 13
P
Polymer consumption optimization .......................... 10
Polymer dosing .......................................................... 8
manual ............................................................ 23, 29
specific ...................................................... 13, 23, 28
Polymer flow rate ....................................................... 7
Polymer pump ............................................................ 8
S
Safety information ...................................................... 9
Slave address .......................................................... 45
Sludge thickening ..................................................... 10
Smoothing ................................................................ 31
Supply voltage .......................................................... 17
T
Technical data ............................................................ 7
Theory of operation .................................................. 13
Thickened sludge pump ....................................... 7, 13
TSS concentration
influent .................................................................. 13
thickened sludge ................................................... 13
M
Maintenance schedule ............................................. 35
W
Warning labels ........................................................... 9
Warnings .................................................................. 37
Warranty and liability ................................................ 43
49
Index
50
Loading...