3.1 Installation of the RTC Module ......................................................................................................... 15
3.1.1 Power supply to the RTC module ............................................................................................15
3.2 Connection of process measuring instruments (for NH
3.2.1 Power supply of the sc sensors and the sc1000 controller...................................................... 15
3.3 Connecting the sc 1000 controller .................................................................................................... 16
3.4 Connection to the automation unit on the plant side.........................................................................16
-N, TSS and O2) ........................................ 15
4
Section 4 Parameterization and operation ......................................................................................... 21
4.1 Operating the sc controller................................................................................................................ 21
4.2 System setup .................................................................................................................................... 21
4.3 Menu structure.................................................................................................................................. 21
6.3 Wear parts ........................................................................................................................................ 55
Section 7 Replacement parts and accessories .................................................................................. 57
7.1 Replacement Parts ........................................................................................................................... 57
Section 8 Contact information ............................................................................................................ 59
Section 9 Warranty and liability........................................................................................................... 61
Appendix A MODBUS address setting ............................................................................................... 63
Index ...................................................................................................................................................... 65
5
Table of Contents
6
Section 1Technical data
These are subject to change without notice.
Embedded PC (compact industrial PC)
Processor
Flash memory2 GB compact flash card
Internal working memory256 MB DDR-RAM (not expandable)
Interfaces1× RJ 45 (Ethernet), 10/100 Mbit/s
Diagnostic LED
Expansion slot1× CompactFlash type II slot with ejector mechanism
Clock
Operating systemMicrosoft Windows
Control softwareTwinCAT PLC Runtime or TwinCAT NC PTP Runtime
System bus16 bit ISA (PC/104 standard)
Power supplyVia system bus (through power supply module CX1100-0002)
Max. power loss6 W (including the system interfaces CX1010-N0xx)
Equipment properties
Dimensions (L × W × H)
WeightApproximately 0.9 kg (1.98 lb)
Pentium®1, MMX compatible, 500 MHz clock rate
1× power, 1× LAN speed, 1× LAN activity, TC status,
1× flash access
Internal, battery-buffered clock for time and date (battery can be
replaced)
®2
CE or Microsoft Windows Embedded Standard
350 mm × 120 mm × 96 mm
(13.78 in. × 4.72 in. × 3.78 in.)
Analog input0/4 to 20 mA for flow rate measurement
Internal resistance80 ohm + diode voltage 0.7 V
Signal current0 to 20 mA
Common mode voltage (U
Measurement error (for entire measurement
range)
Electrical surge resistance35 V DC
Electrical isolation500 V
Digital outputsAeration and alarm activation
Number of outputs2 (KL2032), 4 (KL2134), 8 (KL2408), 16 (KL2809)
Nominal load voltage24 V DC (–15 % / +20 %)
Load typeohmic, inductive lamp load
Max. output current0.5 A (short-circuit proof) per channel
Reverse polarity protectionYes
Electrical isolation500 V
)35 V max.
CM
< ± 0.3 % (from measurement range end value)
(K-bus/signal voltage)
eff
(K-bus/field voltage)
eff
7
Technical data
Analog outputOutputs for DO setpoint or VFD control
Number of outputs
Supply voltage
Signal current0/4 to 20 mA
Working resistance< 500 Ohm
Measurement error
Resolution12 bit
Conversion timeApproximately 1.5 ms
One-channel: 1 (KL4011); 1 (KL4012) VFD control
Two-channel: 1 (KL4012); 2 (KL4012) VFD control
24 V DC via the power contacts
(Alternatively, 15 V DC with bus termination KL9515)
± 0.5 LSB linearity error
± 0.5 LSB offset error
± 0.5 % (relative to the measuring range end value)
Electrical isolation500 V
(K-bus/field voltage)
eff
Environmental conditions
Working temperature0 to 50 °C (32 to 122 °F)
Storage temperature–25 to +85 °C (–13 to 185 °F)
Relative humidity95 %, non-condensing
Miscellaneous
Pollution degree
Protection class
Installation category
Maximum altitude
3
III
I
2000 m (6.562 ft.)
Degree of protectionIP20
InstallationDIN rail EN 50022 35 × 15
1
Pentium is a registered trademark of the Intel Corporation.
2
Microsoft Windows is a brand name for operating systems of the Microsoft Corporation.
8
Section 2General Information
2.1Safety information
Please read this entire manual before unpacking, setting up, or operating this equipment.
Pay attention to all danger and caution statements. Failure to do so could result in serious
injury to the operator or damage to the equipment.
To prevent damage to or impairment of the device's protection equipment, the device may
only be used or installed as described in this manual.
2.1.1Use of hazard information
DANGER
Indicates a potentially or imminently hazardous situation that, if not avoided, can result in death or
serious injury.
WARNING
Indicates a potentially or imminently dangerous situation that, if it is not avoided, can lead to
death or to serious injuries.
CAUTION
Indicates a possible dangerous situation that can have minor or moderate injuries as the result.
Indicates a situation that, if it is not avoided, can lead to damage to the device. Information that
requires special emphasis.
Note: Information that supplements points in the main text.
2.1.2Precautionary labels
Read all labels and tags attached to the instrument. Personal injury or damage to the
instrument could occur if not observed.
This symbol is a warning triangle. Follow all safety notes that follow this symbol to prevent possible injuries. If
this symbol is located on the device, it refers to information in the operating- and/or safety notes of the user
manual.
This symbol can be attached to a housing or a barrier in the product and shows that electric shock risk and/or
the risk of a death through electric shock exists.
Electrical equipment marked with this symbol may not be disposed of in European domestic or public disposal
systems after 12 August 2005. In conformity with European local and national regulations, European electrical
equipment users must now return old or end-of life equipment to the manufacturer for disposal at no charge to
the user.
Note: You obtain instructions on the correct disposal of all (marked and not marked) electrical products that
were supplied or manufactured by Hach-Lange at your relevant Hach-Lange sales office.
NOTICE
CAUTION
The manufacturer is not responsible for any damages due to misapplication or misuse of this
product including, without limitation, direct, incidental and consequential damages, and disclaims
such damages to the full extent permitted under applicable law. The user is solely responsible to
identify critical application risks and install appropriate mechanisms to protect processes during a
possible equipment malfunction.
9
General Information
2.2Areas of application
The RTC103 N-Module is an universally applicable control unit which optimizes
nitrification processes in wastewater treatment plants. In addition, the RTC103 N-Module
can optionally be equipped with a closed-loop controller for setting the dissolved oxygen
concentration (O
module controls one activated sludge tank. The two-channel version controls two
activated sludge tanks simultaneously.
The use of an RTC module (Real-Time Controller) does not release the operator from the
responsibility of maintaining the system.
In particular, the operator must make sure that instruments connected to the RTC
open/closed-loop controller are always fully functional.
To make sure these instruments supply correct, reliable measurement values, regular
maintenance work (for example, cleaning of the sensors and laboratory comparative
measurements) is essential! (Refer to the user manual for the relevant instrument.)
2.3Scope of delivery
The combination of pre-assembled components supplied by the manufacturer does not represent
a standalone functional unit. In accordance with EU guidelines, this combination of
pre-assembled components is not supplied with a CE mark, and there is no EU declaration of
conformity for the combination.
However, the conformity of the combination of components with the guideline can be proved
through technical measurements.
) in the activated sludge tank. The single-channel version of the RTC
2
NOTICE
NOTICE
Each RTC103 N-Module is supplied with:
•A SUB-D connector (9 pin)
•Ferrite core, foldable
•User manual
Check that the order is complete. All listed components must be present. If anything is
missing or damaged, contact the manufacturer or distributor immediately.
10
2.4Instrument overview
Figure 1 Base module RTC 100-240 V version
General Information
1L(+)7Automatic circuit breaker (ON/OFF switch for item 10
and 11 without fuse function)
2N(–)8sc 1000 connection: RS485 (CX1010-N041)
3Input AVC 100–240 V / Input DC 95–250 V9Battery compartment
4PE (protective earth)10 CPU base module, consisting of Ethernet port with
battery compartment (CX1010-N000), CPU module with
CF card (CX1010-0021) and passive aeration element.
524 V transformer (Specifications refer section 3.1.1,
page 15)
6Output DC 24 V, 0.75 A
Note: All components are pre-wired.
11 Power supply module, consisting of bus coupler
(CX1100-0002) and terminal module 24V.
11
General Information
2
1
Figure 2 Design of the analog and digital input and output modules
1Analog or digital input or output module
or bus termination module
Note: The number of LEDs indicates the number of channels.
2LED area with installed LEDs or free LED installation
spaces.
2.5Theory of operation
2.5.1Theory of operation of the RTC103 N-Module
The RTC103 N-Module (Real-Time Controller for Nitrification) optimises nitrification
processes in waste water treatment plants which are continuously aerated (e.g. plug flow
nitrification tanks or pre-denitrification).
The RTC103 N-Module consists of an open-loop controller, based on NH
concentration, flow rate, and the temperature in the aeration tank. Optionally, the Total
Suspended Solids concentration in the aeration tank (MLSS) can be taken into account.
Based on that information, a DO set-point is calculated which is required to reach the
desired NH
control, there is also a closed-loop PID based on the NH
the nitrification zone that can be applied to improve control performance. The PID-output
values are combined with the open-loop output to calculate the required DO set point
(Figure 3).
-N set-point at the effluent of the aeration tank. In addition to open-loop
4
-N influent
4
-N concentration at the end of
4
12
Figure 3 Principle operation mode of RTC103 N-Module
General Information
Basic RTC103 N-Module
For each lane the calculated DO set point is delivered either by analog output or via the
sc1000 ProfiBus communication card to the PLC. The DO control algorithm has to be
implemented on the PLC.
Option 2: RTC103 N-Module with DO aeration stages controller
The RTC103 N-Module is equipped with an additional DO controller adjusting the aeration
intensity to reach the calculated DO concentration. The DO control can have up to
6 different aeration stages per channel (e.g. in order to activate blower or activate discrete
aeration intensities). These aeration stages are activated by a min limit DO concentration
and the calculated DO set-point.
Option 3: RTC103 N-Module with analog DO controller
The RTC103 N-Module is equipped with an additional DO controller which, using
6 different aeration stages, adjusts the aeration intensity to reach the calculated DO
concentration. This option has two analog outputs per lane, to control up to two variable
speed drive blowers per lane.
All the above options for the RTC103 N-Module are available as single-channel (for
control of one lane) or dual-channel (for control of two lanes).
13
General Information
14
Section 3Installation
Only qualified experts may perform the tasks described in this section of the manual, while
adhering to all locally valid safety regulations.
Always lay cables and hoses so that they are straight and do not pose a tripping hazard.
Before switching on the power supply, you must refer to the instructions in the relevant operating
manuals.
3.1Installation of the RTC Module
Only install the RTC Module on a DIN rail. The module must be attached horizontally, with
at least 30 mm (1.2 in.) space at the top and bottom to make sure that the passive aeration
element can function correctly.
When used indoors, the RTC Module must be installed in a control cabinet.
When used outdoors, the RTC Module requires a suitable enclosure that supplies the
following technical specifications (see Section 1 Technical data, page 7).
DANGER
CAUTION
CAUTION
The RTC Module is only operated via the sc1000 controller (see the user manual for the
sc1000 controller).
Note: The software version of the sc1000 controller must be V3.20 or above.
3.1.1Power supply to the RTC module
WARNING
Alternating current may destroy the direct current system and therefore jeopardize user safety.
Never connect an alternating current voltage to the 24 V direct current model.
Table 1 Supply voltage of the RTC Module
Voltage24 V DC (–15 % / +20 %), max. 25 W
Recommended fuseC2
With 110–230 V option230 V, 50–60 Hz, approximately 25 VA
Note: An external deactivation switch is recommended for all installations.
3.2Connection of process measuring instruments (for NH4-N, TSS and
O
)
2
The measurement signals of the sc sensors for measuring NH4-N, TSS, Dissolved
Oxygen and Temperature (e.g. AMTAX sc, AN-ISE sc, AISE sc, SOLITAX sc, LDO2 sc,...)
are supplied to the RTC module via the RTC communication card (YAB117) in the sc1000.
3.2.1Power supply of the sc sensors and the sc1000 controller
See operating instructions of the respective sc sensors and the sc1000 controller.
15
Installation
3.3Connecting the sc 1000 controller
The supplied SUB-D connector is attached to a two-wire, shielded data cable (signal or
bus cable). For additional information regarding the data cable connection, refer to the
enclosed assembly instructions.
3.4Connection to the automation unit on the plant side
Depending on the variant (1-channel or 2-channel RTC103 N-Module, with or without DO
control) the RTC103 N-Module is equipped with various components that have to be
connected to the automation unit of the plant:
Output signals from RTC103 N-Module:
BasicFor each lane, a single DO set-point 0/4 to 20 mA or ProfiBus / ModBus via
sc1000 communication card
Option 2For each lane, Aeration intensity (1 to 6 stages) for the aeration system
(0/24 V per stage or ProfiBus / MODBUS) via sc1000 communication card
Option 3For each lane, 2 additional analog outputs (0/4 to 20 mA or ProfiBus /
MODBUS) via sc1000 communication card
Input signals to RTC103 N-module:
•Flow rate, overall wastewater (Q_in, 0/4 to 20 mA)
•IRC flow rate input (Q_IRC, 0/4 to 20 mA)
or
IRC flow = C1 * Q_in with minimum and maximum values
•RAS flow rate (Q_RAS 0/4 to 20 mA)
or
RAS flow = C2 * Q_in with minimum and maximum values
Note: 0/4 to 20 mA input can be used either for Q_IRC or for Q_RAS. The other value has to be
calculated (C*Q_xxx with minimum and maximum values).
Input signals from sc1000 via RTC communication card to RTC103 N-module
•Common or individual NH4-N – concentration inlet aeration
(Measuring points: 1. Inflow 2. Settled Sewage and RAS Mixing / Distribution
Chamber 3. aeration tank after IRC input)
•Common or individual NH4-N – concentrations at the end of each lane
•DO concentration for each lane
•TSS concentration aeration tank (option)
•Temperature (coming from a connected sensor DO or NH
Main Input parameters:
, or via analog input card)
4
16
•Parameters for open-loop control
•Parameters for PID control (closed-loop)
•Min/max DO concentration, max. rate of change
•Control parameters for DO control
Installation
1-Channel RTC103 N-Module
ModuleNameTerminal SignalChannelFunction
2 fold digital output
1
KL2032
1 fold analog outputKL4011 1 - 30/4 to 20 mAOutput DO set point
1 fold analog intputKL3011 1 - 20/4 to 20 mAFlow rate aeration lane
1 fold analog inputKL3011 1 - 20/4 to 20 mAFlow rate internal recirculation or return sludge
Bus terminationKL9010Bus termination
1
Ground Connector 3 and 7, 24 V Connector 6.
2-Channel RTC103 N-Module
ModuleNameTerminal SignalChannelFunction
4 fold digital output1KL2134
2 fold analog outputKL4012
1 fold analog intputKL3011 1 - 20/4 to 20 mA1Flow rate aeration lane 1
1 fold analog inputKL3011 1 - 20/4 to 20 mA2
1 fold analog intputKL3011 1 - 20/4 to 20 mA1Flow rate aeration lane 2
1 fold analog inputKL3011 1 - 20/4 to 20 mA2
Bus terminationKL9010Bus termination
1+24 V/0 VInput Signals ok (24V), Input signal faulty (0V)
5+24 V/0 VRTC operating (24V), RTC failure (0V)
1+24 V/0 V1Input Signals ok (24V), Input signal faulty (0V)
5+24 V/0 V1RTC operating (24V), RTC failure (0V)
4+24 V/0 V2Input Signals ok (24V), Input signal faulty (0V)
8+24 V/0 V2RTC operating (24V), RTC failure (0V)
1 - 30/4 to 20 mA1Output DO set point lane 1
5 - 70/4 to 20 mA2Output DO set point lane 2
Flow rate internal recirculation or return sludge
lane 1
Flow rate internal recirculation or return sludge
lane 2
1
Ground Connector 3 and 7, 24 V Connector 6.
1-Channel RTC103 N-Module DO aeration stages control
ModuleNameTerminal SignalChannelFunction
1+24 V/0 VInput Signals ok (24V), Input signal faulty (0V)
2+24 V/0 VAeration step 1 ON / OFF
3+24 V/0 VAeration step 2 ON / OFF
8 fold digital output
1
KL2408
4+24 V/0 VAeration step 3 ON / OFF
5+24 V/0 VAeration step 4 ON / OFF
6+24 V/0 VAeration step 5 ON / OFF
7+24 V/0 VAeration step 6 ON / OFF
8+24 V/0 VRTC operating (24V), RTC failure (0V)
1 fold analog outputKL4011 1 - 30/4 to 20 mAOutput DO set point
1 fold analog intputKL3011 1 - 20/4 to 20 mAFlow rate aeration lane
1 fold analog inputKL3011 1 - 20/4 to 20 mAFlow rate internal recirculation or return sludge
Bus terminationKL9010Bus termination
1
Ground Connector 3 and 7, 24 V Connector 6.
17
Installation
2-Channel RTC103 N-Module DO aeration stages control
ModuleNameTerminal SignalChannelFunction
1+24 V/0 V1Input Signals ok (24V), Input signal faulty (0V)
2+24 V/0 V1Aeration step 1 ON / OFF
3+24 V/0 V1Aeration step 2 ON / OFF
4+24 V/0 V1Aeration step 3 ON / OFF
5+24 V/0 V1Aeration step 4 ON / OFF
6+24 V/0 V1Aeration step 5 ON / OFF
7+24 V/0 VAeration step 6 ON / OFF
16 fold digital output1KL2809
2 fold analog outputKL4012
1 fold analog intputKL3011 1 - 20/4 to 20 mA1Flow rate aeration lane 1
1 fold analog inputKL3011 1 - 20/4 to 20 mA2
1 fold analog intputKL3011 1 - 20/4 to 20 mA1Flow rate aeration lane 2
1 fold analog inputKL3011 1 - 20/4 to 20 mA2
Bus terminationKL9010Bus termination
8+24 V/0 VRTC Channel 1 operating (24V), RTC failure (0V)
9+24 V/0 V2Input Signals ok (24V), Input signal faulty (0V)
10+24 V/0 V2Aeration step 1 ON / OFF
11+24 V/0 V2Aeration step 2 ON / OFF
12+24 V/0 V2Aeration step 3 ON / OFF
13+24 V/0 V2Aeration step 4 ON / OFF
14+24 V/0 V2Aeration step 5 ON / OFF
15+24 V/0 VAeration step 6 ON / OFF
16+24 V/0 VRTC Channel 2 operating (24V), RTC failure (0V)
1 - 30/4 to 20 mA1Output DO set point lane 1
5 - 70/4 to 20 mA2Output DO set point lane 2
Flow rate internal recirculation or return sludge
lane 1
Flow rate internal recirculation or return sludge
lane 2
1
Ground Connector 3 and 7, 24 V Connector 6.
1-Channel RTC103 N-Module connectors DO aeration stages / analog control
ModuleNameTerminal SignalChannelFunction
1+24 V/0 VInput Signals ok (24V), Input signal faulty (0V)
2+24 V/0 VAeration step 1 ON / OFF (VFD)
3+24 V/0 VAeration step 2 ON / OFF (VFD)
8 fold digital output
1
KL2408
4+24 V/0 VAeration step 3 ON / OFF
5+24 V/0 VAeration step 4 ON / OFF
6+24 V/0 VAeration step 5 ON / OFF
7+24 V/0 VAeration step 6 ON / OFF
8+24 V/0 VRTC operating (24V), RTC failure (0V)
2 fold analog outputKL4012
1 - 30/4 to 20 mAOutput 1 VFD for DO control
5 - 70/4 to 20 mAOutput 2 VFD for DO control
1 fold analog intputKL3011 1 - 20/4 to 20 mAFlow rate aeration lane
1 fold analog inputKL3011 1 - 20/4 to 20 mAFlow rate internal recirculation
Bus terminationKL9010Bus termination
1
Ground Connector 3 and 7, 24 V Connector 6.
18
2-Channel RTC103 N-Module connectors DO aeration stages / analog control
ModuleNameTerminal SignalChannelFunction
1+24 V/0 V1Input Signals ok (24V), Input signal faulty (0V)
2+24 V/0 V1Aeration step 1 ON / OFF (VFD)
3+24 V/0 V1Aeration step 2 ON / OFF (VFD)
4+24 V/0 V1Aeration step 3 ON / OFF
5+24 V/0 V1Aeration step 4 ON / OFF
6+24 V/0 V1Aeration step 5 ON / OFF
7+24 V/0 V1Aeration step 6 ON / OFF
16 fold digital output1KL2809
2 fold analog outputKL4012
2 fold analog outputKL4012
1 fold analog intputKL3011 1 - 20/4 to 20 mA1Flow rate aeration lane
1 fold analog inputKL3011 1 - 20/4 to 20 mA1Flow rate internal recirculation
1 fold analog intputKL3011 1 - 20/4 to 20 mA2Flow rate aeration lane
1 fold analog inputKL3011 1 - 20/4 to 20 mA2Flow rate internal recirculation
Bus terminationKL9010Bus termination
8+24 V/0 V1RTC Channel 1 operating (24V), RTC failure (0V)
9+24 V/0 V2Input Signals ok (24V), Input signal faulty (0V)
10+24 V/0 V2Aeration step 1 ON / OFF (VFD)
11+24 V/0 V2Aeration step 2 ON / OFF (VFD)
12+24 V/0 V2Aeration step 3 ON / OFF
13+24 V/0 V2Aeration step 4 ON / OFF
14+24 V/0 V2Aeration step 5 ON / OFF
15+24 V/0 V2Aeration step 6 ON / OFF
16+24 V/0 V2RTC Channel 2 operating (24V), RTC failure (0V)
0/4 to 20 mA1Output 1 VFD for DO control
0/4 to 20 mA1Output 2 VFD for DO control
0/4 to 20 mA2Output 1 VFD for DO control
0/4 to 20 mA2Output 2 VFD for DO control
Installation
1
Ground Connector 3 and 7, 24 V Connector 6.
19
Installation
20
Loading...
+ 46 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.