GSI PNEG-824 User Manual

Series 2000 Downwind Heater
Downwind Series 2000
Centrifugal Heater
Installation And
Operating Instructions
MODEL # CH__ - __ __ - __ __ - 2 __ (HIGH)
MODEL # CL__ - __ __ - __ __ - 2 __ (LOW)
Owner's Manual
1
Series 2000 Downwind Heater
THIS EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE CURRENT
INSTALLATION CODES FOR GAS BURNING APPLIANCES AND EQUIPMENT, CAN1-B149.1 AND B149.2, OR APPLICABLE PROVINCIAL REGULATIONS WHICH
SHOULD BE CAREFULLY FOLLOWED IN ALL CASES. AUTHORITIES HAVING JURISDICTION SHOULD BE CONSULTED BEFORE INSTALLATIONS ARE MADE.
2
Series 2000 Downwind Heater
_____ 1. Check all wire connections
_____ 2. Spark plug and flame sensor tightness set plug gap to 1/8"
_____ 3. Check plug in terminal strips on back of circuit board to be sure they are plugged into
proper position.
_____ 4. Software settings correct for type of heater (hi-low, on-off)
_____ 5. Dip switch settings correct for heater model (slave, master)
_____ 6. Most current software version installed
_____ 7. Turn heater toggle switch on. Most current software version should be displayed first, fol-
lowed by temperature. Screen should read "NO AIRFLOW".
_____ 8. Turn fan on. Screen should read "AIRFLOW".
_____ 9. Program hi-limit set point to 140 degrees F.
_____ 10. Program cycle set point to 120 degrees F (only on hi-lo units).
_____ 11. Program differential to 10 degrees F/
_____ 12. Turn gas on to heater unit.
_____ 13. Press start switch on heater. Screen should flash "PURGE".
_____ 14. After 10 second purge heater should light screen, and should read "HI-FLAME".
"FLAME" should appear on lower right hand corner of screen.
_____ 15. Adjust pressure to 10 psi (lp units) 5 psi (ng units).
_____ 16. Check pipe train for leaks with soapy water.
_____ 17. Temperature should rise to 120 degrees. Screen should read "LO-FLAME" and unit
should cycle to lo-flame. (hi-lo units only)
_____ 18. Adjust pressure with ball valve to 2 psi (lp units) 1 psi (ng units). (hi-lo units only)
_____ 19. On standard units temperature will rise to 140 degrees. Screen will read "OFF-CYCLE".
Heater will shut off at this point.
_____ 20. Temperature will drop 10 degrees and unit will cycle back to hi-flame. Screen should read
"HI-FLAME".
_____ 21. Observe unit go through 3 cycles.
_____ 22. Pull wire off of housing hi-limit switch. Screen should read "ERROR 000" and "HOUSING
TEMP HI-LIMIT". Heater should shut down and lock out. Fan should shut off.
_____ 23. Turn heater toggle switch on. Most current software version should be displayed first,
followed by temperature. Screen should read "NO AIRFLOW".
_____ 24. Turn fan on. Screen should read "AIRFLOW".
_____ 25. Press start switch on heater. Screen should flash "PURGE".
_____ 26. After 10 second purge heater should light. Screen should read "HI-FLAME". "FLAME"
should appear on lower right hand corner of screen.
_____ 27. Shut gas off to heater and allow gas to burn out of system.
_____ 28. 2-4 seconds after flame goes out on heater, "FLAME" in lower right hand corner of screen
should go out. Unit should begin to spark.
_____ 29. After 10 seconds fan and heater should shut down and lock out. Screen should read
"ERROR 000" and "FLAME OUT".
_____ 30. Check heater visually to see that all decals are in place and correctly located.
_____ 31. Place owners manual in control box.
CHECKLIST
Tester Signature___________________________________________
Date____________________________________
3
Series 2000 Downwind Heater
4
Series 2000 Downwind Heater
Safety 6 Series 2000 Heater Installation
High Temperature Heater Specifications 8 Low Temperature Heater Specifications 8 Temperature Sensor Box 9 Transition Hi-Limit Installation 9 Bin Configuration/Operating Temperature Table 10 Heater Unit Wiring 11 Secondary Heater Unit Wiring 11 Machine To Earth Ground 12 Proper Installation Of The Ground Rod 12 Previously Installed Units 12 Fuel Connection For Liquid Propane Models 13 Fuel Connection For Propane Vapor Models 13 Fuel Connection For Natural Gas Models 13 Installing Optional Humidity Sensor 14
Series 2000 Operating Procedure
Power Up 15 Normal Operating Displays With Heater Not Running 16 Starting The Dryer 17 Setting Gas Pressure 17 BTU's Per Gauge Pressure (PSI) 10-15 hp Models (Approximate) 19 BTU's Per Gauge Pressure (PSI) 20-40 hp Models (Approximate) 20 BTU's Per Gauge Pressure (PSI) Lo-temp Models (Approximate) 22 Adjusting The Vaporizer 23 Running The Dryer 23 Programming Set Points 24 Programming Hours To Shutdown 25 Drying Grain In The Hours To Shutdown Mode 25 Run Hours Display 25 Multiple Heater Notes 25 Modulating Valve Operation 26
Factory Configuration
Configuration Dip Switches 27
Error Conditions
Limit Switches 28 Multiple Heater Error Conditions 28
Misc Error Numbers 28 Series 2000 Heater Service 29 Series 2000 Wiring Diagram 30 Warranty 32
TABLE OF CONTENTS
5
SAFETY
SAFETY FIRST
General Safety Statements
The GSI Group Inc’s Principal concern is your safety and the safety of others associated with grain handling equipment. We want to keep you as a customer. This manual is to help you under­stand safe operating procedures and some prob­lems which may be encountered by the operator and other personnel.
Series 2000 Downwind Heater
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
As owner and/or operator, it is your respon­sibility to know what requirements, hazards and precautions exist and inform all personnel associ­ated with, or in the area of the product. Safety precautions may be required from the personnel. This product is ideal for the conditioning of corn, soy beans or other select grains. Avoid any alter­ation to the equipment, such alterations may pro­duce a very dangerous situation, where serious in­jury or death may occur.
This is the safety alert symbol. It is used to alert you to poten­tial personal injury hazards.
Obey all safety messages that follow this symbol to avoid possible in­jury or death.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury
CAUTION
CAUTION used without the safety alert symbol indi­cates a potentially hazardous situation which, if not avoided, may result in property damage.
If a decal is damaged or missing contact:
The GSI Group Inc. 1004 E. Illinois St. Assumption, IL 62510 217-226-4421
A free replacement will be sent to you.
BE ALERT!
Danger!
Personnel operating or working around electrical
equipment should read this manual. This manual must be delivered with equipment to its owner. Failure to read this manual and its safety instructions is a misuse of the equipment.
WARNING
WARNING indicates a potentially hazardous situation which , if not avoided, could result in death or serious injury.
6
The GSI Group Inc. recommends that you contact your local power company and have a rep­resentative review your installation so your wir­ing will be compatible with their system and so that you will have adequate power supplied to your unit.
Series 2000 Downwind Heater
Roof Damage Warning And Disclaimer
SAFETY
GSI DOES NOT WARRANT ANY ROOF DAMAGE
CAUSED BY EXCESSIVE VACUUM OR INTERNAL PRES-
SURE FROM FANS OR OTHER AIR MOVING SYSTEMS.
ADEQUATE VENTILATION AND/OR "MAKEUP AIR" DE-
VICES SHOULD BE PROVIDED FOR ALL POWERED AIR
HANDLING SYSTEMS. GSI DOES NOT RECOMMEND
THE USE OF DOWNWARD FLOW SYSTEMS (SUCTION).
SEVERE ROOF DAMAGE CAN RESULT FROM ANY
BLOCKAGE OF AIR PASSAGES. RUNNING FANS DUR-
ING HIGH HUMIDITY/COLD WEATHER CONDITIONS
CAN CAUSE AIR EXHAUST OR INTAKE PORTS
7
SPECIFICATIONS
Series 2000 Downwind Heater
Centrifugal Heater Specifications
Hi-Temp Hi-Temp Lo-Temp Model
10-15HP 20-40HP All units
All Models BTU Rating 2225000 4500000 500000
Weight 145 145 135
Liquid Mo dels Maximum Fuel flow (GPH) 24 49 N/A
Orifice size 0.2188 0.3125 N/A
Mod Valve Bypass Orifice Blue Aluminum Yellow
Minimum operating pre ssure 1 1 N/A
Maximum operating pressure 15 15 N/A
Minimum line size 3/8" 3/8" N/A
Vapor Models Maximum Fuel flow (CFH) 931 1898 210
Orifice size 0.2188 0.3125 0.109
Mod Valve Bypass Orifice Blue Aluminum Yellow
Minimum operating pre ssure 1 1 1
Maximum operating pressure 15 15 15
Minimum line size 3/8" 3/8" 1/2"
Natural Gas Maximum Fuel flow (CFH) 2496 4643 500
Models Orifice size 0.3438 0.4688 0.156
Mod Valve Bypass Orific e Aluminum Aluminum Gre en
Minimum operating pre ssure 0.5 0.5 1
Maximum operating pressure 7 7 7
Minimum line size 1.1/4" 1.1/4" 1"
Heater Dimensional Specifications
Heater Size
Inside Height
Inside Width
Inside length
8
10-15
30.1/4"
19.1/2"
24"
20-30
33.1/4"
21.3/4"
24"
40
33.1/4"
23.11/16"
24"
Series 2000 Downwind Heater
PLENUM TEMPERATURE
SENSOR MOUNTING
The plenum temperature sensor is
the white PVC junction box with bolt
extending from outside attached by
a cord to the fan/heater control box.
1. 24" to the right side of the transi
tion, drill one 3/8" hole in the cen
ter of the plenum in a valley on
the bin sidewall.
2. Insert the probe through the hole.
3. Position the housing so that the
tabs are vertical, and the cord
exits the housing horizontally.
HEATER INSTALLATION
4. Use two self drilling screws to
mount the housing to the bin
sidewall.
5. Caulk between the housing and
the sidewall to seal.
TRANSITION HI-LIMIT INSTALLATION
1. Mark location on transition one
(1) foot up from the bottom
(entrance collar) and centered
in the transition.
2. Drill or knock out 7/8" diameter
hole on marked location.
3. Install transition hi-limit using
supplied self drilling screws.
Plenum temperature sensor installation.
Figure 1: The transition connecting the heater to the bin with the plenum
thermostat in place.
9
HEATER INSTALLATION
Bin Configuration
Series 2000 Downwind Heater
IMPORTANT! When mounting (2) heaters on a bin it is imperative that they be situated as illustrated in this draw­ing. Plenum thermostat must be to the right of master heater and master heater must be to the right of slave heater.
THIS TABLE IS NOT INTENDED AS A DRYING GUIDE.
IT SHOULD BE USED AS A REFERENCE FOR SETTING MAXIMUM PLENUM
TEMPERATURE FOR SAFE OPERATION.
Operating Temperature Table
PMET-OL
HCTAB
0
02-5
NROC
ECIR
SNAEB
&
TAEHW
EVOBA
TNEIBMA
PMET
0
01-5
EVOBA
TNEIBMA
PMET
0
02-5
EVOBA
TNEIBMA
PMET
-HGIH
PMET
YRDHCTAB
GNIRRITSON
0
021
0
001
0
011
-HGIH
PMET
HTIW
GNIRRITS
0
041
SUOUNITNOC
WOLF
)GNITALUCRICER(
0
061
IMPORTANT!
DO NOT EXCEED
PLENUM
TEMPERATURES
0
001
0
021
TON
DEDNEMMOCER
TON
DEDNEMMOCER
LISTED IN TABLE
10
Series 2000 Downwind Heater
HEATER INSTALLATION
Heater Unit
1. Be sure fan unit is installed and
wired to meet local codes. Be
sure equipment is well grounded
(see page 10).
2. A separate neutral is required
for 120 volt heater circuit in 220
volt 1PH and 3PH fan units. For
460 volt fan units a separate 120
volt power supply or transformer
is required.
3. Run 5-wire black cord from
heater unit to fan unit and se-
cure to fan.
4. Orange and red wires should be
connected in series with coil in
fan. When contacts in heater be-
tween these wires open fan
Wiring
Figure 2: Wiring diagram for the fan and heater unit.
shuts down. Recommended wiring is shown in Figure 2.
5. Black and white wires should be connected to a fused 120V
power supply as shown. Green wire should be connected to
ground in fan. Heater should have power, even with fan off.
Figure 3: Secondary heater wiring diagram.
SECONDARY HEATER UNIT
1. Secondary heater unit runs as a slave of heater
unit #1 and requires no plenum temperature
sensor.
2. Run (2) 20 gauge (minimum) wires from sec-
ondary heater unit (slave) to heater unit #1
(master).
3.
Connect wires as shown in Figure 3.
4. Third heater unit may also be added to system.
If adding third unit, run connections to master
unit #1 and connect them in parallel with sec
ondary heater unit.
11
HEATER INSTALLATION
Machine To Earth
Ground
It is very important that a machine
to earth ground rod be installed at
the fan. This is true even if there is
a ground at the pole 15 feet away.
This ground needs to be as close to
the fan as possible, but no more than
8 feet away. The ground rod should
be connected to the fan control panel
with at least a #6 solid bare copper
ground wire, or in accordance with
local requirements. The machine to
earth ground provides additional
safety if there is a short. It also pro-
vides the grounding necessary for
long life and operation of the solid
state circuit boards used on control
circuits and the electronic ignition
systems.
(Ground rods and wires are not supplied by Airstream). It is recommended that
the rod not be driven into dry ground. The following steps ensure proper ground
rod installation:
1. Dig a hole large enough to hold 1 to 2 gallons of water.
2. Fill hole with water.
Series 2000 Downwind Heater
Figure 4: Use a #6 or approved size bare copper ground wire. Install a 5/8" diameter 8' long copper-clad ground rod, 2' away from the foundation and 1' below the surface of the ground or in accordance with local requirements.
Proper Installation Of The Ground Rod
Dig a hole large enough to hold 1
or 2 gallons of water. Work the
ground rod into the earth until it is
completely in the ground.
3. Insert rod through water and jab it into the ground.
4. Continue jabbing the rod up and down, the water will work its way
down the hole, making it possible to work the rod completely
into the ground. This method of installing the rod gives a good
conductive bond with the surrounding soil.
5. Connect the bare copper ground wire to the rod with the proper
ground rod clamp.
6. Connect the bare ground wire to the fan control boxes with a
grounding lug. See figure 4.
7. Ground wire must not have any breaks or splices. Insulated
wire is not recommended for grounding.
Previously Installed Units
It is recommended that previously installed units be checked to see
that a machine to earth ground has been installed by an electrician.
12
Series 2000 Downwind Heater
HEATER INSTALLATION
Standard electrical safety prac-
tices and codes should be used
when working with a heater.
Refer to the National Electric
ALWAYS DISCONNECT AND LOCK OUT POWER
WARNING
BEFORE WORKING ON OR
Code Standard Handbook by
the National Fire Protection
Association. A qualified elec-
trician should make all wiring
installations.
AROUND HEATER
Fuel Connection
Liquid Propane Models
1. L.P. models are designed to run on liquid pro
pane with liquid draw from the propane tank.
Avoid using propane supply tanks that have been
used for vapor draw for long periods of time.
When using liquid draw systems any moisture
that may be present in tank or lines may freeze
when system is used in cold weather. To avoid
this situation, purge the system with methanol.
2. Run proper size line (see specification on page
7) to liquid pipetrain on heater. Have a qualified
gas service person inspect installation to be sure
that everything is installed according to local
codes and ordinances.
IMPORTANT! Do not use pro-
pane tanks that have previ-
ously been used for ammonia
unless they have been purged
according to procedures of the
National L.P. Association.
Fuel supply system must
comply with local codes for L.P.
gas installation.
external vaporizer.
2. Run proper size line (see specifications on page
7) to pipetrain on heater. Have a qualified gas
service person inspect installation to be sure that
everything is installed according to local codes
and ordinances.
3. After installation is complete check all connec-
tions for leaks. DO NOT USE FLAME FOR
LEAK TESTING.
Natural Gas Models
1. Natural gas models are designed to run directly
off of a supply tank or from a separate
external vaporizer.
3. After installation is complete check all connec-
tions for leaks with liquid detergent or compa-
rable. Wear rubber gloves and eye protection.
Avoid contact with liquid propane. DO NOT
USE FLAME FOR LEAK TESTING.
Propane Vapor Models
1. Propane vapor models are designed to run di-
rectly off of a supply tank or from a separate
2. Run proper size line (see specification on page 7)
to pipetrain on heater. Have a qualified gas
service person inspect installation to be sure ev-
erything is installed according to local codes
and ordinances.
3. After installation is complete check all connec-
tions for leaks. DO NOT USE FLAME FOR
LEAK TESTING.
13
HEATER INSTALLATION
Figure A
Series 2000 Downwind Heater
Installing Optional Humidity Sensor
1. Humidity sensor should be mounted 6-8" right of the airswitch/temperature sensor box. See Figure A.
2. Using sensor as a guide drill or knock-out 7/8" diameter hole in the center of the plenum on the bin sidewall. If you are using sensor to sense drying air humidity.
3. Insert pipe nipple from sensor housing through hole in side wall and use self­drilling screws to mount to sidewall. Figure B
4. Do not caulk sensor box openings on side of box, they are for air escape.
14
Figure B
Series 2000 Downwind Heater
OPERATING PROCEDURE
The control panel display showing initial start up.
Standard electrical safety practices and codes should
be used when working with a heater. Refer to the
National Electric Code Standard Handbook by
the National Fire Protection Association. A quali-
fied electrician should make all wiring installa-
tions.
WARNING
ALWAYS DISCONNECT AND LOCK OUT POWER BEFORE WORKING ON OR AROUND HEATER
Power Up
All safety and high limit switches are checked upon
power up. If a safety or limit is open, the control dis-
plays it. The control cannot operate with a safety switch
error, and the fan cannot turn on with an error condi-
tion. There is no way to bypass an error condition. It
must be fixed. (See errors on page 21)
The air switch is also checked on power up.
The air switch must indicate no airflow. This is
necessary to check the function of the air switch.
However, if the operator forgets and turns the fan
on before the controller has been powered up,
The controller locks up with the main display alter-
nating between a "FAN" and "ON" message. This
may be bypassed by depressing and holding the
"FAN BYPASS" switch (lower right switch). Nor-
mal operating procedure should be to power up the
controller with the fan off.
If multiple heaters are tied together, and the
master detects that the slave fan is on (the air
switch stuck?), the master will lock up display-
ing "SLA ERROR". This condition may be by-
passed with the "FAN BYPASS" switch.
15
OPERATING PROCEDURE
Normal Operating Displays With Heater Not Running
Series 2000 Downwind Heater
The main display shows the plenum temperature. If
the dryer has not been running, the display should
show outside temperature. The control is preset at
the factory to display temperature in centigrade or
fahrenheit.
"AIRFLOW" or "NO AIRFLOW" is displayed
if air is flowing or not flowing. "RX TX" (receive,
transmit) is displayed if multiple heaters are con-
nected.
All safeties or high limits are continuously
checked during the off mode. A limit switch open,
or any other error condition will cause the display
to show the limit or error condition.
When drying is not occurring, and the limit
or error condition is corrected, the display returns
to its normal output. This is not the case with an
error or limit condition during the drying opera-
tion. This causes the display to lock up in the er-
ror display mode. This is to keep the display
locked up with the condition illuminated. ( see
section on "Running the Dryer" for mode expla-
nation on page 17).
16
The heater display with fan on (airflow).
Series 2000 Downwind Heater
Starting The Dryer
After heater power is turned on, the fan must be
turned on. Attempting to start the dryer without the
air switch indicating there is airflow will cause an air-
flow alarm to go off when the start switch is depressed.
The airflow alarm is simply the entire display going
blank, and the "NO AIRFLOW" message flashing for
a few seconds. The display must show "AIRFLOW"
before the dryer can be started.
To start the dryer, just push the "START" switch.
The first message to come up will be the "PURGE"
message--the drying process begins with a 10 sec-
ond purge.
When multiple heaters are connected together,
drying may be started from any heater control.
OPERATING PROCEDURE
Programming the temperature differential.
7. Press the "PROGRAM TEMPERATURE" but
ton to continue to set the "TEMPERATURE
DIFFERENTIAL".
8. Use the increase or decrease buttons to set the
"TEMPERATURE DIFFERENTIAL" to 10°*.
Setting Gas Pressure
1. At heater turn toggle switch to "ON" position.
2. Press the "PROGRAM TEMPERATURE" but-
ton.
3. Use the increase or decrease button to set the
"PLENUM HIGH LIMIT SET POINT" to de-
sired setting (100°-160°*).
4. Press the "PROGRAM TEMPERATURE" but-
ton to continue to set the "CYCLE SETPOINT".
(hi-lo units only)
5. Use the increase or decrease buttons to set the
"CYCLE SET POINT" to desired setting (90°-
150°*) (hi-lo units only).
9. Press "progam temperature" button to continue
to set "relative humidity differential". Use ar-
row keys to adjust to 5%. ( Hudidity sensor units
only).
10. Open all manual gas shut off valves, on and to
the heater unit.
11 Start the fan unit.
12. Make sure that the blade is spinning in the right
direction. If not place the toggle switch in the
"OFF" position and correct the problem.
13. After the fan reaches full speed the display should
read "AIRFLOW" in the upper right hand corner.
If not adjust air switch. (See page 19)
14. Press the start button on the heater control.
6. Press "programs temperature" button to continue
to set the desired "relative humidity" setting,
lower setting will run heater longer. (humidity
sensor units only) Use arrow keys to set.
15. After 10 seconds the burner should ignite. If not,
turn "OFF" the toggle switch and then back "ON".
Repeat 12-15.
*Temperatures are fahrenheit.
17
OPERATING PROCEDURE
Series 2000 Downwind Heater
16. When the burner ignites the display should read
"HI-FLAME " at the left of the display. Loosen
the nut on the main regulator and turn screw in, to
increase pressure and out to decrease pressure.
The pressure gauges should be set at 10-15 lbs.
for LP units, or 4-6 lbs.. for natural gas units. (use
the charts on the following pages to set pressure)
17. Press the "PROGRAM TEMPERATURE" but-
ton to change the high limit set point. Press it
again to change the "CYCLE SET POINT". (hi-
lo units only)
18. Decrease the "CYCLE SET POINT TEM
PERATURE" until the heater cycles to low
flame. (hi-lo units only)
19. Open or close the low cycle ball valve until
the gas pressure is 3-5 lbs. for LP, or 1-2 lbs.
for natural gas. (hi-lo units only)
20. Increase the cycle set point to return to high
flame. (hi-lo units only)
21. Watch heater run several minutes to make
sure it cycles between hi and lo flame or on
and off properly.
22. Hi-flame pressure should be adjusted so ple-
num reaches cycling temperature easily.
23. Adjust pressure on on/off units so that unit is
on approximately 75% of the time.
18
Series 2000 Downwind Heater
g
)
(°F)
)
g
g
)
(°F)
)
BTUs Per Gauge Pressure (psi) PROPANE MODELS (Approximate
Hi
2 4 6 8 10 12 14 15
ALL MODELS
816,013 1,148,640 1,409,477 1,632,026 1,825,859 1,995,762 2,153,700 2,227,883
Gau
e Pressure (psi) Required to Maintain Temperature (Approximate
(10-15 hp High Temperature Propane Units Only)
OPERATING PROCEDURE
10-15 hp Units
h Temperature 10-15hp 7/32" (0.219") Orifice
OPERATING PRESSURE (psi)
Fan Static
Model Pressure 60 80 100 120 140 160 180
2"24681013
10 hp4"135681114
6"11356810
2" 3 6 9 12 15
15 hp 4" 3 5 7 10 13
6"235691114
Heat Rise
10-15 hp Units
BTUs Per Gauge Pressure (psi) NATURAL GAS MODELS (Approximate
High Temperature 10-15hp 11/32" (0.344") Orifice
OPERATING PRESSURE (psi)
1234567
ALL MODELS
859,104 1,218,432 1,489,296 1,718,208 1,921,584 2,107,632 2,276,352
Gau
e Pressure (psi) Required to Maintain Temperature (Approximate
(10-15 hp High Temperature Natural Gas Units Only)
Fan Static
Model Pressure 60 80 100 120 140 160 180
2" 1 1.75 2.5 3.5 4.75 6
10 hp 4" 0.75 1.25 2 2.75 3.75 4.75 6
6" 0.5 1 1.5 2 2.75 3.5 4.25
2" 1.5 2.5 3.75 5.5
15 hp 4" 1.25 2 3 4.25 5.75
6" 0.75 1.25 2 2.75 3.75 5 6
Heat Rise
19
OPERATING PROCEDURE
g
)
(°F)
)
g
BTUs Per Gauge Pressure (psi) PROPANE MODELS (Approximate
Hi
h Temperature 20-40hp 5/16" (0.313") Orifice
OPERATING PRESSURE (psi)
2 4 6 8 10 12 14 15
ALL MODELS
1,663,135 2,345,140 2,878,779 3,328,663 3,721,115 4,068,100 4,393,548 4,541,914
Gau
e Pressure (psi) Required to Maintain Temperature (Approximate
(20-40 hp High Temperature Propane Units Only)
Series 2000 Downwind Heater
20-40 hp Units
Fan Static
Model Pressure 60 80 100 120 140 160 180
2"22457810
20 hp 4" 1 2 3 4 5 7 8
6"1234567
2" 2 3 5 7 9 12 15
25 hp 4" 2 3 4 6 8 10 13
6"22456810
2"24681115
30 hp 4" 2 4 5 7 10 13
6" 2 3 4 6 8 10 13
2" 3 6 8 12
40 hp 4" 3 5 7 11 14
6"347912
Heat Rise
20
Series 2000 Downwind Heater
g
)
(°F)
)
BTUs Per Gauge Pressure (psi) NATURAL GAS MODELS (Approximate
High Temperature 20-40hp 15/32" (0.469") Orifice
OPERATING PRESSURE (psi)
1234567
ALL MODELS
1,597,824 2,266,320 2,770,656 3,195,648 3,573,216 3,919,776 4,234,416
Gau
e Pressure (psi) Required to Maintain Temperature (Approximate
(20-40 hp High Temperature Natural Gas Units Only)
OPERATING PROCEDURE
20-40 hp Units
Fan Static
Model Pressure 60 80 100 120 140 160 180
2" 0.75 1.25 1.75 2.5 3.25 4.25 5.5
20 hp 4" 0.5 1 1.5 2 2.75 3.5 4.5
6" 0.5 0.75 1.25 1.75 2.25 3 3.75
2" 1 1.75 2.25 3.5 4.75 6.25
25 hp 4" 0.75 1.5 2.25 3.25 4 5.25 6.25
6" 0.5 1.25 1.75 2.5 3.25 4.25 5.5
2" 1.25 2 3 4.5 6
30 hp 4" 1 1.75 2.75 3.75 5 7
6" 0.75 1.5 2.25 3 4 5.25 7
2" 1.75 3 4.5 6.25
40 hp 4" 1.5 2.5 4 5.5
6" 1.25 2.25 3.5 4.75 6.75
Heat Rise
21
OPERATING PROCEDURE
)
(App
)
p
g
)
(App
)
Lo-Temp Units
BTUs Per Gauge Pressure (psi
PROPANE MODELS
Series 2000 Downwind Heater
roximate
ALL MODELS
Low Tem
2 4 6 8 10 12 14 15
203,405 287,160 351,771 409,203 457,063 497,744 538,425 555,176
erature All hp 7/64" (0.109") Orifice
OPERATING PRESSURE (psi)
Lo-Temp Units
BTUs Per Gau
NATURAL GAS MODELS
e Pressure (psi
roximate
22
Low Temperature All hp 5/32" (0.156") Orifice
OPERATING PRESSURE (psi)
1234567
ALL MODELS
177,840 251,712 308,256 355,680 397,632 435,936 470,592
Series 2000 Downwind Heater
OPERATING PROCEDURE
Adjusting The Vaporizor
1. Vaporizer should be adjusted so
the vapor pipetrain runs warm
to the touch (100°-120°F).
2. Loosen 5/16" bolt on adjust-
ment bracket.
3. Swivel vaporizer away from
flame if running too hot, closer
to flame if too cold.
4. Move vaporizer only 1" at a time
and allow a few minutes for
tem perature to equalize.
Adjusting the vaporizer coil on a liquid propane model. The top photo
shows the setting in, and the bottom photo shows the coil out.
5. Tighten 5/16" bolt and watch
heater run for several minutes
to verify adjustment.
Running The Dryer
The display will indicate "FLAME"
when flame is sensed. If no flame
is sensed, the "FLAME" message
will be off. The display indicates
what part of the cycle it is in. If the
unit is a hi-lo dryer, the display will
indicate whether it is in the "HI-
FLAME" or "LO-FLAME" part of
the cycle. (See "programming set
points" page 21 for setting the hi-lo
flame temperature). If the tempera-
ture is above the high temperature set-
ting, the flame will be off, the
"FLAME" message will be out and the
display will be flashing "OFF-
CYCLE".
If the flame is shut off because
of the humidity sensor (humidistat),
the display flashes "OFF-CYCLE
HUMIDISTAT".
23
OPERATING PROCEDURE
Series 2000 Downwind Heater
The limits are continuously
checked during the drying operation.
A limit switch open or any other er-
ror condition will cause the dryer to
shutdown, and the fan will be shut-
down. If a limit opens, or an er-
ror condition occurs during dry-
ing, the control will lockup in the
error display mode. Power must
be shut off and back on to the con-
trol to clear the error condition--
even if the error or limit that
caused the shutdown has been
corrected. This is to keep the dis-
play locked up with the condition
that caused the error, allowing the
operator time to determine what
caused the shutdown.
Multiple heaters may be done at any heater control console. The informa-
tion programmed is automatically transmitted to all other heaters when the
programming is complete.
Hi Limit Set Point--The upper left cursor is flashing indicating the
mode. If the plenum temperature increases above this point, the flame is
shut off--"OFF-CYCLE" is displayed on screen.
Cycle Set Point--The upper 2nd from left cursor is flashing indicating
the mode. If the dryer is not a hi-lo dryer, this function is skipped. If
the plenum temperature increases above this point, the flame reduces to
"LO-FLAME".
Humidity Set Point--The upper 2nd from right cursor is flashing indi-
cating the mode. If the humidity is above this point the dryer operates
normally--flame on and off at the high limit and cycle set points. If the
humidity is below this point the dryer goes into the "OFF-CYCLE" mode.
Temperature Differential--The upper right cursor is flashing indicating
the mode. If the flame shuts off because the temperature is greater than the
high limit set point, the temperature must fall below the (Set Point minus
Temperature Differential) for the flame to come back on.
Programming Set Points
Depressing the "PROGRAM"
switch (lower left) causes the dis-
play to enter the program mode.
Each item below is programmed by
using the up and down arrow
switches. Holding down these up
and down arrow switches for about
2 seconds will cause the numbers to
increase/decrease rapidly until the
switch is released. When finished
programming an item, depressing
the "PROGRAM" switch again will
cause the new setting to be entered
into memory, and the display will
advance to the next function to be
programmed.
Programming may be done at
anytime (unless an error condition
exists) even while the dryer is in
operation.
Programming a system with
Programming the high-limit set point.
24
Series 2000 Downwind Heater
OPERATING PROCEDURE
On hi-lo units when the unit reaches cycle set point, the flame will
switch to lo-flame and unit will not cycle back to hi-flame until (Set
Point minus Temperature Differential) is reached.
Temperature differential would normally be set for 10-15 degrees F
for high temp units, and 2-5 degrees F for lo-temp units.
Humidity Differential--The upper right cursor is flashing indicat-
ing the mode. If the flame shuts off because the humidity set point, the
humidity must rise above the ( Set Point plus Humidity Differential) for
the flame to come back on. (Normally set to 5%)
Programming Hours To Shutdown
To change the hours to shutdown, depress and hold the "SHUTDOWN
HOURS" switch. While holding in on the switch, depress the up and
down arrow switches to alter the
hours. Setting range is 0 to 200
hours.
Drying Grain In The
Hours To Shutdown
Mode
While drying grain, depress and
hold the "SHUTDOWN HOURS"
switch. While holding in on that
switch, depress the "START"
switch. After depressing the start
switch one time, the heater is in the
shutdown mode. Then, the fan and
heater shutdown when the time ex-
pires. This is indicated by the lower
left cursor flashing.
Depressing the start switch
again (while holding in on the
"SHUTDOWN HOURS" switch)
will cause only the heater to shut off.
This leaves the fan on when the time
expires. This is indicated by the 2nd
from lower left cursor flashing. De-
pressing the start switch one more
time returns the heater into the con-
tinuous--non-shutdown mode.
Setting the cycle set point.
Run Hours Display
Run hours are recorded when the
controller detects that the fan is on
(airflow). The hours may be viewed
by depressing the "HOURS" to get
hours and "HOURS X 1000" to get
the number of 1000 hours accumu-
lated.
Multiple Heater Notes
When multiple heaters are con-
nected together, the temperature and
humidity sensors must be connected
to the master.
25
OPERATING PROCEDURE
Modulating Valve Operation
Series 2000 Downwind Heater
1. The modulating valve regulates gas flow through the heater based on sensing unit in the plenum, and maintains a constant drying air temperature.
2. The sensing bulb of the modulating valve should be mounted through the bin wall with the side reading "top" up. The bulb reacts to tempera­ture. It changes the amount of gas (increase or decrease), burning warmer or cooler depending on the position of the valve SET POINT. If the bulb is cooler than it was at the SET POINT, the bulb senses the cooler temperature and opens the valve further so more heat is applied to the drying air. If the bulb is warmer than it was at the SET POINT, the valve closes further and re­duces the temperature until the air is at the valve SET POINT.
3. It is important that the pressure regulator be set high enough to allow the modulating valve to deliver enough gas to maintain the plenum tem­perature necessary. The regulator is normally factory set at 15 psi (propane units). To set the regulator, run the heater and turn the modulat ing valve T-handle in. This gets full line pres­sure to the burner. Then adjust regulator to read 15 psi (depending on the plenum temperature needed).
4. Turn the fan and heater on. To set the modulat­ing valve, turn the T-handle out (counterclockwise) until loose and wait a few minutes for the ple­num temperature to equalize. When the tempera­ture under the bin has equalized, gradually turn T-handle in (clockwise) about 1/2 turn at a time.
Wait until temperature under bin has equalized as before. If temperature under bin is less than the desired temperature, continue turning T-handle in, increasing gas flow and waiting for plenum temperature to equalize until the desired tem­perature is the stable temperature of the ple num. If temperature under bin is the same 10 minutes after you last made any adjustments to the T-handle you can be certain that the temperature under the bin is the SET POINT of the valve. 1 turn of the T-handle equals
approximately 7 degrees F of temperature.
5. The valve will now keep the plenum tempera­ture at the set point regardless of ambient conditions as long as humidistat or thermostat do not shut down the heater. A bypass orifice is used to maintain a small flame when out­side temperature is near or above the set point of the valve. The bypass insures steady appli­cation of heat at minimum gas flow operation. Bypass orifice will only operate correctly if pressure regulator is set correctly.
6. To observe how the modulating valve increases the efficiency of bin drying, check the gas pres­sure of the unit in the morning and compare to the pressure read mid-afternoon. If the ambi­ent (outside) temperature is significantly greater later in the day (as normal), the gas pres sure will be less. Since less heat is required to maintain the same temperature in the plenum, the modulating valve will have reduced the amount of gas used by the heater.
26
Series 2000 Downwind Heater
FACTOR Y CONFIGURATION
Configuration Dip
Switches (Normally Done
At GSI)
These switches are used to config-
ure the heater control for various
types of heaters.
Stand alone heater
with no slaves, all
dip switches in the
off state.
Multiple heaters connected together through the serial link.
Master with one
slave-dip switch 7
on/all others off.
Master with two
slaves-dip switch 8
on/all others off.
Slave #1-dip switch
one and three on/all
others off.
Slave #2-dip switch
two and three on/all
others off.
Master with 3
slaves-dip switch 7
& 8 on/all others
off.
Slave #3-dip switch
one, two and three
on/all others off.
The backside of the control board, showing the dip switch placement.
27
ERROR CONDITIONS
Limit Switches
Series 2000 Downwind Heater
The following limit switch errors light up individually on the heaters
LCD screen: PLENUM, HOUSING, VAPOR, TEMP HI LIMIT.
Note: When a shutdown does occur due to an error condition, the amount
of time elapsed since the shutdown can be viewed by pressing the down
arrow switch (up to 218 Hours).
"SLA" on the main display
and the "RX" "TX" symbols will be
flashing.
If a limit switch error or one of
the error numbers 1 through 8
occurs, that error is displayed on
Multiple Heater Error Conditions
If two or more heaters are connected together through the serial link, and the
master cannot communicate with a slave controller, the master will display
the slave where the error origi-
nates. The master displays
"SLA ERROR".
Misc Error Numbers
1 2 3 4 5 6
Temperature probe 1 open.
7
Temperature probe 1 short.
8 9 10 11 12
Temperature probe 2 open.
Temperature probe 2 short.
Airflow open.
Airflow short.
Illegal flame sense.
Error 7 is most likely caused by stuck open solenoid. Error 7 will not shutdown fan until loss of flame is detected by control.
13
+11 volt DC shorted to ground.
The heater
control display
showing error
#7.
Flame probe short error.
000
This indicates that one of the other on screen errors (vapor, plenum or housing temp hi­limit or flame out or no airflow has occurred).
Slave #1 incon­sistent with mas­ter with either the drying grain flag or the LP main solenoid or cycle solenoid.
Most likely the slave got re­set powering up with the sole­noids off.
(Errors 9 through 11 are displayed only if multiple heaters are tied together through serial link).
Note: Temperature sensor connection-the temperature sensor (bolt) must always be connected to the master.
Slave #2 inconsistent.
Same as error 9 for slave #1.
Slave #3 inconsistent.
Same as error 9 for slave #1.
Wrong voltage.
Dip switch #5 is the voltage selector switch. If dip switch #5 in "ON" that se­lects 240 VAC. If the unit has only 120 VAC applied, error 12 will show up. If dip switch #5 is "OFF" that se­lects 120 VAC. If the unit has 240 VAC applied er­ror 12 will show up.
This is im­portant because if the fan heater is set up at GSI for 120 VAC and the customer connects to 240 VAC the heater control will work, but if allowed to operate the so­lenoids will have 240 VAC applied to them which will damage so­lenoids.
28
Series 2000 Downwind Heater
HEATER SERVICE
All Airstream heaters are constructed of durable
weather-resistant materials, so a minimum
amount of service should be required; however
before the unit is started for the first time each
season there are a few items that need to be
checked out. All damaged parts should be repaired
or replaced.
1. Disconnect and lock out power to fan and heater.
Open control box lid and inspect all compo-
nents for moisture, vibration or rodent damage.
Inspect and tighten all loose terminal con-
nections. Replace any damaged wiring.
2. Remove burner orifice tube and inspect for dirt
or foreign material. Clean out if necessary.
3. Inspect burner for wear or foreign material in
any of the ports. Clean or replace parts if necessary.
4. Inspect the spark plug and flame probe for cor
rosion and damage. Clean or replace if necessary.
The Series 2000 control box.
29
WIRING DIAGRAM
Series 2000 Downwind Heater
30
Series 2000 Downwind Heater
______________________________________________________________________________________________________________
_____________________________________________________________________________________________________
__________________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
____________________________________________________________________________________________________________
_________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________
______________________________________________________________________________________________________________
_____________________________________________________________________________________________________
__________________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
NOTES
____________________________________________________________________________________________________________
_________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________
______________________________________________________________________________________________________________
_____________________________________________________________________________________________________
__________________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
____________________________________________________________________________________________________________
_________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________
______________________________________________________________________________________________________________
_____________________________________________________________________________________________________
__________________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
____________________________________________________________________________________________________________
_________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________
__________________________________________________________________________________________________________
31
WARRANTY
THE GSI GROUP, INC. ("GSI") WARRANTS ALL PRODUCTS MANUFACTURED BY GSI TO BE FREE
OF DEFECTS IN MATERIAL AND WORKMANSHIP UNDER NORMAL USAGE AND CONDITIONS
FOR A PERIOD OF 36 MONTHS AFTER RETAIL SALE TO THE ORIGINAL END USER OF SUCH
PRODUCTS. GSI'S ONLY OBLIGATION IS, AND PURCHASER'S SOLE REMEDY SHALL BE FOR
GSI, TO REPAIR OR REPLACE, AT GSI'S OPTION AND EXPENSE, PRODUCTS THAT, IN GSI'S SOLE
JUDGMENT, CONTAIN A MATERIAL DEFECT DUE TO MATERIALS OR WORKMANSHIP. ALL
DELIVERY AND SHIPMENT CHARGES TO AND FROM GSI'S FACTORY WILL BE PURCHASER'S
RESPONSIBILITY. EXPENSES INCURRED BY OR ON BEHALF OF THE PURCHASER WITHOUT
PRIOR WRITTEN AUTHORIZATION FROM AN AUTHORIZED EMPLOYEE OF GSI SHALL BE THE
SOLE RESPONSIBILITY OF THE PURCHASER.
EXCEPT FOR THE ABOVE STATED EXPRESS LIMITED WARRANTIES, GSI MAKES NO WARRANTY
OF ANY KIND, EXPRESSED OR IMPLIED, INCLUDING, WITHOUT LIMITATION, WARRANTIES
OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR USE IN CONNECTION
WITH (i) PRODUCT MANUFACTURED OR SOLD BY GSI OR (ii) ANY ADVICE, INSTRUCTION,
RECOMMENDATION OR SUGGESTION PROVIDED BY AN AGENT, REPRESENTATIVE OR EMPLOYEE
OF GSI REGARDING OR RELATED TO THE CONFIGURATION, INSTALLATION, LAYOUT, SUIT-
ABILITY FOR A PARTICULAR PURPOSE, OR DESIGN OF SUCH PRODUCT OR PRODUCTS.
Series 2000 Downwind Heater
IN NO EVENT SHALL GSI BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL OR CONSE-
QUENTIAL DAMAGES, INCLUDING, WITHOUT LIMITATION, LOSS OF ANTICIPATED PROFITS
OR BENEFITS. PURCHASER'S SOLE AND EXCLUSIVE REMEDY SHALL BE LIMITED TO THAT
STATED ABOVE, WHICH SHALL NOT EXCEED THE AMOUNT PAID FOR THE PRODUCT PUR-
CHASED. THIS WARRANTY IS NOT TRANSFERABLE AND APPLIES ONLY TO THE ORIGINAL
PURCHASER. GSI SHALL HAVE NO OBLIGATION OR RESPONSIBILITY FOR ANY REPRESENTA-
TIVE OR WARRANTIES MADE BY OR ON BEHALF OF ANY DEALER, AGENT OR DISTRIBUTOR
OF GSI.
GSI ASSUMES NO RESPONSIBILITY FOR FIELD MODIFICATIONS OR ERECTION DEFECTS
WHICH CREATE STRUCTURAL OR STORAGE QUALITY PROBLEMS. MODIFICATIONS TO THE
PRODUCT NOT SPECIFICALLY COVERED BY THE CONTENTS OF THIS MANUAL WILL NUL-
LIFY ANY PRODUCT WARRANTY THAT MIGHT HAVE BEEN OTHERWISE AVAILABLE.
THE FOREGOING WARRANTY SHALL NOT COVER PRODUCTS OR PARTS WHICH HAVE BEEN
DAMAGED BY NEGLIGENT USE, MISUSE, ALTERATION OR ACCIDENT. THIS WARRANTY COV-
ERS ONLY PRODUCTS MANUFACTURED BY GSI. THIS WARRANTY IS EXCLUSIVE AND IN LIEU
OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED. GSI RESERVES THE RIGHT TO MAKE
DESIGN OR SPECIFICATION CHANGES AT ANY TIME.
PRIOR TO INSTALLATION, PURCHASER HAS THE RESPONSIBILITY TO RESEARCH AND COM-
PLY WITH ALL FEDERAL, STATE AND LOCAL CODES WHICH MAY APPLY TO THE LOCATION
AND INSTALLATION.
32
Series 2000 Downwind Heater
33
Series 2000 Downwind Heater
34
1004 E. Illinois St.
Assumption, IL 62510
Phone 217-226-4421
Fax 217-226-4498
March 2000
Loading...