GSI PNEG-1912 User Manual

PNEG-1912
6', 7' and 9' Tall BFT Series and GHT Series
Assembly Manual
PNEG-1912
Date: 01-29-13
2 PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series
Table of Contents

Contents

Chapter 1 Introduction .......................................................................................................................................... 5
Chapter 2 Safety ..................................................................................................................................................... 6
Safety Guidelines .................................................................................................................................. 6
General Safety Statement ..................................................................................................................... 7
Safety Instructions ..................... ... .... .......................................... ... ... ..................................................... 8
Safety Sign-Off Sheet ......................................................................................................................... 10
Proper Storage of Grain Bin/Silo Materials Prior to Construction ....................................................... 11
Chapter 3 Decals .................................................................................................................................................. 12
Chapter 4 General Information ........................................................................................................................... 13
Bulk Feed Tank Assembly Manual General Instructions .............................. ... ... ................................ 13
BFT/GHT Series Usage and Stored Product Considerations ............................................................. 14
Chapter 5 Foundation .......................................................................................................................................... 15
Chapter 6 Sidewall Assembly ............................................................................................................................. 23
Tank Sidewalls ....................................... ... ... .... ... .......................................... ... ... .... ............................ 23
Caulking Detail .................................................................................................................................... 24
Sidewall Sheet Orientation ..................... ... ... .... ... ... .......................................... ... .... ... ......................... 25
Chapter 7 Roof ..................................................................................................................................................... 28
Sealed Roof Panels Installation .......................................................................................................... 28
Peak Ring Collar to Roof Panels ......................................................................................................... 30
Chapter 8 Optional BFT Ladder Assembly ........................................................................................................ 31
Starter Bracket Installation .................................................................................................................. 32
Sidewall and Roof Ladder Installation ................................................................................................. 33
Roof Ladder Support Bracket Installation ........................................................................................... 34
Ladder Standoff Installation ................................................................................................................ 38
Ladder Section Assembly ................................................................................................................... 39
Ladder Support Detail ......................................................................................................................... 40
Chapter 9 Safety Cage ......................................................................................................................................... 41
Ladder System With Safety Cage ....................................................................................................... 41
Safety Cage Hoop Assembly .............................................................................................................. 43
Safety Cage Installation ......... ... ... .... ... .......................................... ... ... ... .... ... ... ... .... ... ... ... .......... ... ... ... 45
Chapter 10 Roof Cap and Ground Control ........................................................................................................ 48
Roof Cap and Ground Control Instructions ....................................................................................... 48
Chapter 11 Hopper Assembly ............................................................................................................................. 54
Hopper Sheets ................................................................................................................................... 54
Reinforcement Angles ..........................................................................................................
Hopper Collar .................................................................................................................................... 57
Chapter 12 Legs and Leg Bracing ...................................................................................................................... 59
Tank Legs and Leg Braces ............................. ... ... ... .... ... ... ... .... ... ... ... ... ............................................. 59
Bracing Hole Layout .......... .......................................... ... ... ... .......................................... ... .... ... ... ... ... 60
Hopper to Leg Horizontal Bracing ..................................................................................................... 62
Leg Anchors ......... ... ... ... .... ... ... ... .......................................... .................................................... ... ... ... 65
............. 56
Chapter 13 Raising Bin ........................................................................................................................................ 67
Raising Bin to Set on Foundation ...................................................................................................... 67
Lifting with Jacks ......................................................................................................................... ... ... 68
Lifting with Crane ............................................................................................................................... 69
Anchoring Tank ................................................................................................................................. 70
Tank Grounding Instructions ............................................................................................................. 71
PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series 3
Table of Contents
Chapter 14 Pneumatic Fill Kit ............................................................................................................................. 72
Pneumatic Fill Kit Assembly .................................. ... .... ... ... ... .......................................... ... .... ........... 72
Roof Panel ......................................................................................................................................... 73
Chapter 15 Parts List ........................................................................................................................................... 75
6' Diameter 60° Hopper Tank Specifications ..................................................................................... 76
6' Diameter 60° Hopper Tank Hardware Specifications .................................................................... 78
7' Diameter 67° Hopper Tank Specifications ..................................................................................... 80
7' Diameter 67° Hopper Tank Hardware Specifications .................................................................... 82
7' Diameter 45° Hopper Tank Specifications ..................................................................................... 84
7' Diameter 45° Hopper Tank Hardware Specifications .................................................................... 86
9' Diameter 60° Hopper Tank Specifications ..................................................................................... 88
9' Diameter 60° Hopper Tank Hardware Specifications .................................................................... 90
9' Diameter 45° Hopper Tank Specifications ..................................................................................... 92
9' Diameter 45° Hopper Tank Hardware Specifications .................................................................... 94
Chapter 16 Warranty ............................................................................................................................................ 97
4 PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series

1. Introduction

READ THIS MANUAL carefully to learn how to properly use and install equipment. Failure to do so could result in personal injury or equipment damage.
INSPECT the shipment immediately upon arrival. The customer is responsible for ensuring that all quantities are correct. The customer should report and note any damage or shortage on the bill of lading to justify their claim to the transport company.
THIS MANUAL SHOULD BE CONSIDERED a permanent part of your equipment and should be easily accessible when needed.
This warranty provides you the assurance that the company will back its products when defects appear within the warranty period. In some circumstances, the company also provides field improvements, often without charge to the customer, even if the product is out of warranty. Should the equipment be abused, or modified to change its performance beyond the factory specifications, the warranty will become void and field improvements may be denied.
PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series 5

2. Safety

This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
WARNING indicates a hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION, used with the safety alert symbol, indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE is used to address practices not related to personal injury.
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
Safety Guidelines
This manual contains information that is important for you, the owner/operator, to know and understand. This information relates to protecting personal safety and preventing equipment problems. It is the responsibility of the owner/operator to inform anyone operating or working in the area of this equipment of these safety guidelines. To help you recognize this information, we use the symbols that are defined below. Please read the manual and pay attention to these sections. Failure to read this manual and its safety instructions is a misuse of the equipment and may lead to serious injury or death.
DANGER
WARNING
CAUTION
NOTICE
6 PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series
2. Safety
This product has sharp edges, which may cause serious injury. To avoid injury, handle sharp edges with caution and always use proper protective clothing and equipment.
General Safety Statement
Our foremost concern is your safety and the safety of others associated with grain handling equipment. This manual is to help you understand safe operating procedures and some problems that may be encountered by the operator and other personnel.
As owner and/or operator, you are responsible to know what requirements, hazard s, and precautions exist and inform all personnel associated with the equipment or in the area. Safety precautions may be required from the personnel. Avoid any alterations to the equipment, which may produce a very dangerous situation, where SERIOUS INJURY or DEATH may occur.
You should consider the location of the bin site relative to power line locations or electrical transmission equipment. Contact your local power company to review your installation plan or for information concerning required equipment clearance. Clearance of portable equipment that may be taken to the bin site should also be reviewed and considered. Any electrical control equipment in contact with the bin should be properly grounded and installed in accordance with National Electric Code provisions and other local or national codes.
This product is intended for the use of grain storage only. Any other use is a misuse of the product.
Sidewall bundles or sheets must be stored in a safe manner. The safest method of storing sidewall bundles is laying horizontally with the arch of the sheet upward, like a dome. Sidewall sheets stored on edge must be secured so that they cannot fall over and cause injury. Use care when handling and moving sidewall bundles.
Personnel operating or working around equipment should read this manual. This manual must be delivered with equipment to its owner. Failure to read this manual and its safety instructions is a misuse of the equipment.
PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series 7
2. Safety
Follow Safety Instructions
Carefully read all safety messages in this manual and safety signs on your machine. Keep signs in good condition. Replace missing or damaged safety signs. Be sure new equipment components and repair parts include the current safety signs. Replacement safety signs are available from the manufacturer.
Learn how to operate the machine and how to use controls properly. Do not let anyone operate without instruction.
Keep your machinery in proper working condition. Unauthorized modifications to the machine may impair the function and/or safety and affect machine life.
If you do not understand any part of this manual or need assistance, contact your dealer.
Read and Understand Manual
Practice Safe Maintenance
Understand service procedures before doing work. Keep area clean and dry.
Never lubricate, service, or adjust machine while it is in operation. Keep hands, feet, and clothing away from rotating parts.
Keep all parts in good condition and properly installed. Fix damage immediately . Replace worn or broken p arts. Remove any built-up grease, oil, and debris.
Maintain Equipment and Work Area
Safety Instructions
Our foremost concern is your safety and the safety of others associated with this equipment. We want to keep you as a customer. This manual is to help you understand safe operating procedures and some problems that may be encountered by the operator and other personnel.
As owner and/or operator, it is your responsibility to know what requirements, hazards, and precautions exist, and to inform all personnel associated with the equipment or in the area. Safety precautions may be required from the personnel. Avoid any alterations to the equipment. Such alterations may p roduce a very dangerous situation where SERIOUS INJURY or DEATH may occur.
This equipment shall be installed in accordance with the current installation codes and applicable regulations, which should be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made.
8 PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series
2. Safety
Prepare for Emergencies
Be prepared if fire starts. Keep a first aid kit and fire extinguisher handy. Keep emergency numbers for doctors, ambulance service,
hospital, and fire department near your telephone.
Keep Emergency Equipment Quickly Accessible
Wear Protective Clothing
Wear close-fitting clothing and safety equipment appropriate to the job.
Remove all jewelry.
Tie long hair up and back.
Wear safety glasses at all times to protect eyes from debris.
Wear gloves to protect your hands from sharp edges on plastic or steel parts.
Wear steel toed-boots to help protect your feet from falling debris. Tuck in any loose or dangling shoestrings.
A respirator may be needed to prevent breathing potentially toxic fumes and dust.
Wear a hard hat to help protect your head.
Wear appropriate fall protection equipment when working at elevations greater than six feet (6').
Eye Protection
Gloves
Steel-Toed Boots
Respirator
Hard Hat
Fall Protection
PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series 9
2. Safety
Safety Sign-Off Sheet
As a requirement of O.S.H.A., it is necessary for the employer to train the employee in the safe operating and safety procedures for this equipment. This sign-off sheet is provided for your convenience and personal record keeping. All unqualified persons are to stay out of the work area at all times. It is strongly recommended that another qualified person who knows the shut down procedure be in the area in the event of an emergency.
Date Employee Name Supervisor Name
10 PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series
2. Safety
Proper Storage of Grain Bin/Silo Materials Prior to Construction
Wet storage stain (rust) will develop when closely packed bundles of galvanized material, such as sidewall and roof sheets, have moisture present. Inspect roof and sidewall bundles on arrival for any moisture. If moisture is present, it must not be allowed to remain between the sheets. Separate the sheets or panels immediately and wipe them down. Spray with a light oil or diesel fuel.
If possible, sidewall bundles, roof sheets and other closely packed galvanized materials should be stored in a dry, climate controlled building. If outdoor storage is unavoidable, the materials should be stored so that they are raised above the ground and vegetation. Any stacking and spacing materials should not be corrosive or wet. Be sure to protect materials from the weather, but permit air movement around the bundles if possible.
Storing roof bundles and sidewall sheets at a slight incline can also help minimize the presence of moisture. Storing the bundles with the center of the dome up (like an arch) is one option for minimizing moisture during storage. Sidewall bundles can also be stored on edge but must be secured so that they do not fall over and cause injury.
If “white rust” or “wet storage stain” occurs, contact the manufacturer immediately about ways to minimize the adverse effect upon the galvanized coating.
PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series 11

3. Decals

GSI Decals
1004 E. Illinois St. Assumption, IL. 62510 Phone: 1-217-226-4421
For replacement decals, contact:
Rotating flighting will
kill or dismember.
Flowing material will
trap and suffocate.
Crusted material will
collapse and suffocate.
Keep clear of all augers. DO NOT ENTER this bin!
Failure to heed these warnings will result in serious injury or death.
4. Avoid the center of the bin.
5. Wear proper breathing equipment or respirator.
DC-2123
1. Shut off and lock out all power.
2. Use a safety harness and safety line.
3. Station another person outside the bin.
If you must enter the bin:
12 PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series

4. General Information

Bulk Feed Tank Assembly Manual General Instructions
First, read the Assembly Manual completely before starting to assemble your Bulk Feed Tank. Check your shipment with the packing list to be sure there are no shortages.
1. Decal protective mask must be removed when assembling tank. Mask may become difficult to remove if left exposed to sunlight.
2. Vertical seams must be staggered on all sidewall rings.
3. When legs extend up 2 rings, the leg holes must be in alignment in the bottom 2 rings.
4. All hopper seams and the hopper collar use truss head bolts. The heads of the bolts must be on the inside of the tank.
5. Hex head bin bolts are used on all sidewall and roof seams with the bolt heads on the outside of the bin.
6. Hex head bolts are to be used on all leg to sidewall connections with the bolt heads on the inside of the tank.
7. All bolts are to be tightened from the nut side only. Do not allow bolt heads to spin.
8. 7' Diameter sidewall sheets must be bolted together so there is 65-5/8" between leg holes.
(See Page 80.)
9. Drift punches can be used to align holes.
10. All vertical sidewall sheet seams must be overlapped in the same direction.
11. A hole spacing of 3-1/8" is used at the top of all top sidewall sheets and at the bottom of all bottom sidewall sheets.
Selecting the Proper Site
The selected site should be level, firm and free from underlying debris. The tank can be installed satisfactorily on slopes, but as the slope increases, additional labor and materials are required for the foundation. The concrete foundation surfaces must be level and tamped thoroughly to prevent uneven settling from the weight of the tank. Good water dra inage should be provided to prevent water collecting under or aro und the tank. The site must allow convenient access for loading and unloading and provide additional space for future units. Also, consider the positioning of handling equipment, availability of electricity, etc.
. If some fill is required, it should be watered
Tools
Tools recommended for assembly of Bulk Feed Tanks.
1. Assorted sizes of combination wrenches
2. Hammer
3. 3-12" Long drift punches
4. 1 Large flathead screwdriver
5. 1 Pair of slip joint pliers
6. Two (2) adjustable wrenches
7. Ratchet and sockets
8. Impact wrenches and sockets (if available)
PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series 13
4. General Information
BFT/GHT Series Usage and Stored Product Considerations
6', 7' and 9' diameter tall tanks covered in this manual are designed for the storage of free flowing materials not weighing more than 40 lb/cubic ft.
Bulk feed materials that are not free flowing will require appropriate agitiation and possible tank modifications or may not be suitable for storage in these units. Consult with GSI technical services or engineering on the storage of such products.
Tanks Sizes Covered By this Manual
This manual is intended to cover the following:
1. 6' Diameter, 5-8 ring BFT/GHT tanks
2. 7' Diameter, 7-8 ring BFT/GHT tanks
3. 9' Diameter, 7-11 ring BFT/GHT tanks
For tanks shorter than the listed heights consult PNEG-1460.
14 PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series

5. Foundation

# of
Rings
Slab
Thickness (D)
Concrete
Volume
Wire Mesh
Area
# of Column
Legs
1-5 11" 2.2 Cu. Yards 60 Sq. Ft. 4
6 13" 2.6 Cu. Yards 60 Sq. Ft. 4
7 15" 3.0 Cu. Yards 60 Sq. Ft. 4
8 18" 3.6 Cu. Yards 60 Sq. Ft. 4
# of
Rings
Slab
Thickness (D)
Concrete
Volume
Wire Mesh
Area
# of Column
Legs
1-5 279 mm 1.68 Cu. Meters 5.57 Sq. Meters 4
6 330 mm 1.99 Cu. Meters 5.57 Sq. Meters 4
7 381 mm 2.29 Cu. Meters 5.57 Sq. Meters 4
8 457 mm 2.75 Cu. Meters 5.57 Sq. Meters 4
All instructions shall be construed as recommendations only. The actual
installation may vary according to local conditions. The GSI Group assumes
no liability for results arising from the use of such recommendations.
GENERAL NOTES:
1. Foundation recommendations are based on 3500 lbs./ft.^2 allowable
soil bearing capacity.
2. Foundation recommendations are based on a minimum compressive
strength of 3000 PSI at 28 days.
3. The foundation site must be well drained and free of vegetation
and debris or well drained.
4. The foundation should be level within 1/4" overall and within
± 1/8" in any 10' length along the anchor bolt circle.
5. Material estimates do not include allowance for shrinkage and waste.
6. These layouts are recommendations for GSI tanks only. Consult GSI
engineering for special tank foundations.
Figure 5A 6' 1-8 Rings Square Pad
PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series 15
5. Foundation
# of
Rings
Slab
Thickness (D)
Concrete
Volume
Wire Mesh
Area
# of Column
Legs
1-5 11" 1.7 Cu. Yards 55 Sq. Ft. 4
6 13" 2.0 Cu. Yards 55 Sq. Ft. 4
7 15" 2.4 Cu. Yards 55 Sq. Ft. 4
8 18" 2.8 Cu. Yards 55 Sq. Ft. 4
# of
Rings
Slab
Thickness (D)
Concrete
Volume
Wire Mesh
Area
# of Column
Legs
1-5 279 mm 1.31 Cu. Meters 5. 11 Sq. Meters 4
6 330 mm 1.54 Cu. Meters 5.11 Sq. Meters 4
7 381 mm 1.78 Cu. Meters 5.11 Sq. Meters 4
8 457 mm 2.13 Cu. Meters 5.11 Sq. Meters 4
All instructions shall be construed as recommendations only. The actual
installation may vary according to local conditions. The GSI Group assumes
no liability for results arising from the use of such recommendations.
GENERAL NOTES:
1. Foundation recommendations are based on 3500 lbs./ft.^2 allowable
soil bearing capacity.
2. Foundation recommendations are based on a minimum compressive
strength of 3000 PSI at 28 days.
3. The foundation site must be well drained and free of vegetation
and debris and well drained.
4. The foundation should be level within 1/4" overall and within
± 1/8" in any 10' length along the anchor bolt circle.
5. Material estimates do not include allowance for shrinkage and waste.
6. These layouts are recommendations for GSI tanks only. Consult GSI
engineering for special tank foundations.
Figure 5B 6' 1-8 Rings BFT/ GHT Round Pad
16 PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series
5. Foundation
# of
Rings
Slab
Thickness (D)
Concrete
Volume
Wire Mesh
Area
# of Column
Legs
1-6 13" 3.3 Cu. Yards 80 Sq. Ft. 4
7 14" 3.5 Cu. Yards 80 Sq. Ft. 4
8 17" 4.3 Cu. Yards 80 Sq. Ft. 4
# of
Rings
Slab
Thickness (D)
Concrete
Volume
Wire Mesh
Area
# of Column
Legs
1-6 330 mm 2.52 Cu. Meters 7.43 Sq. Meters 4
7 356 mm 2.68 Cu. Meters 7.43 Sq. Meters 4
8 432 mm 3.29 Cu. Meters 7.43 Sq. Meters 4
All instructions shall be construed as recommendations only. The actual
installation may vary according to local conditions. The GSI Group assumes
no liability for results arising from the use of such recommendations.
GENERAL NOTES:
1. Foundation recommendations are based on 3500 lbs./ft.^2 allowable
soil bearing capacity.
2. Foundation recommendations are based on a minimum compressive
strength of 3000 PSI at 28 days.
3. The foundation site must be well drained and free of vegetation
and debris and well drained.
4. The foundation should be level within 1/4" overall and within
± 1/8" in any 10' length along the anchor bolt circle.
5. Material estimates do not include allowance for shrinkage and waste.
6. These layouts are recommendations for GSI tanks only. Consult GSI
engineering for special tank foundations.
PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series 17
Figure 5C 7' 1-8 Rings BFT/ GHT 45° and 67° Square Pad
5. Foundation
# of
Rings
Slab
Thickness (D)
Concrete
Volume
Wire Mesh
Area
# of Column
Legs
1-6 13" 2.6 Cu. Yards 65 Sq. Ft. 4
7 14" 2.8 Cu. Yards 65 Sq. Ft. 4
8 17" 3.4 Cu. Yards 65 Sq. Ft. 4
# of
Rings
Slab
Thickness (D)
Concrete
Volume
Wire Mesh
Area
# of Column
Legs
1-6 330 mm 1.91 Cu. Meters 6.04 Sq. Meters 4
7 356 mm 2.10 Cu. Meters 6.04 Sq. Meters 4
8 432 mm 2.55 Cu. Meters 6.04 Sq. Meters 4
All instructions shall be construed as recommendations only. The actual
installation may vary according to local conditions. The GSI Group assumes
no liability for results arising from the use of such recommendations.
GENERAL NOTES:
1. Foundation recommendations are based on 3500 lbs./ft.^2 allowable
soil bearing capacity.
2. Foundation recommendations are based on a minimum compressive
strength of 3000 PSI at 28 days.
3. The foundation site must be well drained and free of vegetation
and debris.
4. The foundation should be level within 1/4" overall and within
± 1/8" in any 10' length along the anchor bolt circle.
5. Material estimates do not include allowance for shrinkage and waste.
6. These layouts are recommendations for GSI tanks only. Consult GSI
engineering for special tank foundations.
18 PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series
Figure 5D 7' 1-8 Rings BFT/ GHT 45° and 67° Round Pad
5. Foundation
# of
Rings
Slab
Thickness (D)
Concrete
Volume
Wire Mesh
Area
# of Column
Legs
2-6 13" 4.9 Cu. Yards 125 Sq. Ft. 6
7 16" 6.0 Cu. Yards 125 Sq. Ft. 6
8 17" 6.4 Cu. Yards 125 Sq. Ft. 6
9 17" 6.4 Cu. Yards 125 Sq. Ft. 6
# of
Rings
Slab
Thickness (D)
Concrete
Volume
Wire Mesh
Area
# of Column
Legs
2-6 330 mm 4.85 Cu. Meters 11.61 Sq. Meters 6
7 406 mm 4.85 Cu. Meters 11.61 Sq. Meters 6
8 432 mm 5.14 Cu. Meters 11.61 Sq. Meters 6
9 432 mm 5.14 Cu. Meters 11.61 Sq. Meters 6
All instructions shall be construed as recommendations only. The actual
installation may vary according to local conditions. The GSI Group assumes
no liability for results arising from the use of such recommendations.
GENERAL NOTES:
1. Foundation recommendations are based on 3500 lbs./ft.^2 allowable
soil bearing capacity.
2. Foundation recommendations are based on a minimum compressive
strength of 3000 PSI at 28 days.
3. The foundation site must be well drained and free of vegetation
and debris.
4. The foundation should be level within 1/4" overall and within
± 1/8" in any 10' length along the anchor bolt circle.
5. Material estimates do not include allowance for shrinkage and waste.
6. These layouts are recommendations for GSI tanks only. Consult GSI
engineering for special tank foundations.
* Applies to 45° hopper Tank only.
*
*
PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series 19
Figure 5E 9' 2-9 Rings BFT/ GHT 45° and 60° Square Pad
5. Foundation
# of
Rings
Slab
Thickness (D)
Concrete
Volume
Wire Mesh
Area
# of Column
Legs
2-6 13" 3.8 Cu. Yards 100 Sq. Ft. 6
7 16" 4.7 Cu. Yards 100 Sq. Ft. 6
8 17" 5.0 Cu. Yards 100 Sq. Ft. 6
9 17" 5.0 Cu. Yards 100 Sq. Ft. 6
# of
Rings
Slab
Thickness (D)
Concrete
Volume
Wire Mesh
Area
# of Column
Legs
2-6 330 mm 2.91 Cu. Meters 9.29 Sq. Meters 6
7 406 mm 3.59 Cu. Meters 9.29 Sq. Meters 6
8 432 mm 3.82 Cu. Meters 9.29 Sq. Meters 6
9 432 mm 3.82 Cu. Meters 9.29 Sq. Meters 6
All instructions shall be construed as recommendations only. The actual
installation may vary according to local conditions. The GSI Group assumes
no liability for results arising from the use of such recommendations.
GENERAL NOTES:
1. Foundation recommendations are based on 3500 lbs./ft.^2 allowable
soil bearing capacity.
2. Foundation recommendations are based on a minimum compressive
strength of 3000 PSI at 28 days.
3. The foundation site must be well drained and free of vegetation
and debris.
4. The foundation should be level within 1/4" overall and within
± 1/8" in any 10' length along the anchor bolt circle.
5. Material estimates do not include allowance for shrinkage and waste.
6. These layouts are recommendations for GSI tanks only. Consult GSI
engineering for special tank foundations.
* Applies to 45° hopper tank only.
*
*
20 PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series
Figure 5F 9' 2-9 Rings BFT/ GHT 45° and 60° Round Pad
5. Foundation
# of
Rings
Slab
Thickness (D)
Concrete
Volume
Wire Mesh
Area
# of Column
Legs
9 17" 6.4 Cu. Yards 120 Sq. Ft. 9
10 17" 6.4 Cu. Yards 120 Sq. Ft. 9
11 18" 6.7 Cu. Yards 120 Sq. Ft. 9
# of
Rings
Slab
Thickness (D)
Concrete
Volume
Wire Mesh
Area
# of Column
Legs
9 432 mm 4.85 Cu. Meters 11.15 Sq. Meters 9
10 432 mm 4.85 Cu. Meters 11.15 Sq. Meters 9
11 457 mm 5.14 Cu. Meters 11.15 Sq. Meters 9
All instructions shall be construed as recommendations only. The actual
installation may vary according to local conditions. The GSI Group assumes
no liability for results arising from the use of such recommendations.
GENERAL NOTES:
1. Foundation recommendations are based on 3500 lbs./ft.^2 allowable
soil bearing capacity.
2. Foundation recommendations are based on a minimum compressive
strength of 3000 PSI at 28 days.
3. The foundation site must be well drained and free of vegetation
and debris.
4. The foundation should be level within 1/4" overall and within
± 1/8" in any 10' length along the anchor bolt circle.
5. Material estimates do not include allowance for shrinkage and waste.
6. These layouts are recommendations for GSI tanks only. Consult GSI
engineering for special tank foundations.
* Applies to 45° hopper tank only.
*
*
PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series 21
Figure 5G 9' 9-11 Rings BFT/ GHT 45° and 60° Square Pad
5. Foundation
# of
Rings
Slab
Thickness (D)
Concrete
Volume
Wire Mesh
Area
# of Column
Legs
9 17" 5.0 Cu. Yards 100 Sq. Ft. 9
10 17" 5.0 Cu. Yards 100 Sq. Ft. 9
11 18" 5.3 Cu. Yards 100 Sq. Ft. 9
# of
Rings
Slab
Thickness (D)
Concrete
Volume
Wire Mesh
Area
# of Column
Legs
9 432 mm 3.82 Cu. Meters 9.29 Sq. Meters 9
10 432 mm 3.82 Cu. Meters 9.29 Sq. Meters 9
11 457 mm 4.04 Cu. Meters 9.29 Sq. Meters 9
All instructions shall be construed as recommendations only. The actual
installation may vary according to local conditions. The GSI Group assumes
no liability for results arising from the use of such recommendations.
GENERAL NOTES:
1. Foundation recommendations are based on 3500 lbs./ft.^2 allowable
soil bearing capacity.
2. Foundation recommendations are based on a minimum compressive
strength of 3000 PSI at 28 days.
3. The foundation site must be well drained and free of vegetation
and debris.
4. The foundation should be level within 1/4" overall and within
± 1/8" in any 10' length along the anchor bolt circle.
5. Material estimates do not include allowance for shrinkage and waste.
6. These layouts are recommendations for GSI tanks only. Consult GSI
engineering for special tank foundations.
* Applies to 45° hopper tank only.
*
*
22 PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series
Figure 5H 9' 9-11 Rings BFT/ GHT 45° and 60° Round Pad
Tank Sidewalls

6. Sidewall Assembly

Sidewall Sheet Gauge Chart
Model Gauge
BFT 6'-5 Ring 17-17-18-20-20 BFT 6'-6 Ring 15-15-16-18-20-20 BFT 6'-7 Ring 13-13-15-16-18-20-20 BFT 6'-8 Ring 13-13-13-15-16-18-20-20 BFT 7'-7 Ring 13-13-14-16-18-20-20 BFT 7'-8 Ring 13-13-13-14-16-18-20-20 BFT 9'-7 Ring 13-13-15-16-18-20-20 BFT 9'-8 Ring 13-13-13-14-16-18-20-20
BFT 9'-9 Ring 12-12-13-13-14-16-18-20-20 BFT 9'-10 Ring 11-11-11-12-13-14-16-18-20-20 BFT 9'-11 Ring 10-10-11-11-12-13-14-16-18-20-20
How to use charts on this page:
The chart labeled “Sidewall Sheet Gauge Chart” is for the reference when building the tank. This chart tells you what gauges your rings of the specific tank must have. To read the chart find up the tank size you are building, for example, a 7' diameter tank with 7 rings is referred to as BFT 7'-7 ring. The side labeled “Gauge” will indicate which sidewall sheets to use. The sheets are color coded, simply match the gauge number with the color. (Use “Sheet Gauge Color Code Chart” below.)
NOTE: Sidewall sheets are color coded on edges for gauge identification.
Sheet Gauge Color Code Chart
Code # Color Code
20 Red 18 Orange 16 Blue 15 Brown/Red 14 Green 13 Yellow/Blue 12 Black 11 Pink 10 Light Blue
PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series 23
6. Sidewall Assembly
Caulking is applied to all BFT parts before assembly.
Caulking Detail
Figure 6A Caulking Detail
NOTE: Rope caulking is applied before each sheet is assembled. Wipe sheet clean where it will be
applied. Apply caulking on each side of the holes of the vertical seams and on each side of the horizontal row of holes.
Figure 6B
24 PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series
6. Sidewall Assembly
Sidewall Sheet Orientation
IMPORTANT: Ple ase note sheet orientation when assembling the bin sidewall. The upper right corner will
have a slot or identifying sticker. This corner should be on the inside of the tank when assembled. (See Figure 6C.)
Figure 6C
Sidewall Assembly
Start by assembling the top ring of the Bulk Feed Tank. The top row of bolt holes has 3-1/8" spacing in the top ring. Before bolting the sidewall sheets together, check that you have the proper gauge steel for the top ring. The higher gauge number denotes thinner materia l. For example, 20 gauge material is thinner than 14 gauge. In assembling all Bulk Feed Tanks the thinnest material always go on top. The heaviest corrugated sidewall sheets will be located on the bottom of the tank. Check the various gauges of the tank with the “Sheet Gauge Color Code Chart” and “Sidewall Sheet Gauge Chart”, on Page 23. Begin by putting the rings together on the edge of the sheets. After the first ring is complete, the roof must be assembled as described on Pages 26-27. After the roof is assembled, the tank can be rolled on its side for easier sidewall assembly. (See Figure 6F on Page 27.)
Tighten all bolts from the nut side only.
PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series 25
6. Sidewall Assembly
First ring assembly. Tighten bolts from the nut side only.
Continue to add rings with lighter gauges first, then heavier gauges. Each subsequent row of sidewall sheets goes to the inside of the previous row of sidewall panels. Remember to place the caulking between every ring. See Figure 6D for illustration of proper sidewall overlap and caulking detail.
Be sure to stagger all vertical seams between rows.
Figure 6D Ring Overlap Detail
Figure 6E
26 PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series
6. Sidewall Assembly
IMPORTANT: Begin bolting in the center of sheets when connecting sidewall rings to one another.
When bolting sidewall rings to one another, always begin bolting in the center of the sh eet and work toward the outside edges (horizontal seams). This allows the sidewall to draw up evenly.
Figure 6F Sidewall Assembly
It is easier to add more sidewall sheets with the tank on its side. It can be rolled easily from side-to-side to allow the bolts and nuts to be put in the proper holes. NOTE: The roof must be assembled on the first ring before rolling it over to its side. This will not be practical on taller tanks where jacks should be used.
PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series 27

7. Roof

Sealed Roof Panels Installation
NOTE: The roof and sidewall ladders are centered on a roof panel. Be sure to apply two (2) strips of
caulking on either side of bolt holes at the seams. Roof panel edges allow for the roof to be assembled in either the clockwise or counterclockwise manner. (See roof sheet overlap detail on Page 29.) Be sure to lap sheets in the same manner around the entire tank.
Figure 7A
On bins that will be equipped with a pneumatic fill system (See Page 72), the two (2) roof panels with fill hole and exhaust hole must be located opposite each other on the Bulk Feed Tank. The peak ring may now be installed.
28 PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series
Figure 7B Lining Up Holes and Placing Bolts
7. Roof
Figure 7C Roof Sheet Overlap Detail
PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series 29
7. Roof
Caulking
Peak ring
Caulking
5/16" x 3/4" Bin bolt
Peak Ring Collar to Roof Panels
Apply two (2) strips of caulking between peak ring and roof panels, Se e Figure 7D. Note that the peak ring goes on the outside of the roof panels.
Figure 7E
Figure 7D
Figure 7F Peak Ring Collar Detail
30 PNEG-1912 6', 7' and 9' Tall BFT Series and GHT Series
Loading...
+ 68 hidden pages