GSI PNEG-1797 User Manual

PNEG-1797
CE Approved T-Series Tower Dryer
Operation Manual
PNEG-1797
Date: 06-11-12
2 PNEG-1797CE CE Approved T-Series Tower Dryer
Tower Dryer Gas Train Commissioning Check List and Sign-Off
Name: _______________________Signed: _______________________ Date: ____________
All information, illustrations, photos and specifications in this manual are based on the latest information available at the time of publication. The right is reserved to make changes at any time without notice.
Function
Component Set Point
Pass/Fail/NA
Check Fuel Supply Shut Off Valve Check Main Fuel Supply Pressure Set/Test Main Gas Regulator Pressure Set/Test Over Pressure Shut Off (OPSO) Pressure Set/Test Pressure Relief V a lve Set/Test Maximum Gas Pressure Switch Set/Test Minimum Gas Pressure Switch Set Pilot Burner Pressure Set Burner High Flame Pressure Set Burner Low Flame Pressure Test Pilot Line Manual Shut Off Valve Test Main Gas Manual Shut Off Valve Set/Test Plenum High-Limit Carry Out Leak Test Check Purge Time Check Pilot Ignition Check Main Flame Ignition Check Modulating Valve Operation Check Burner Shut Down
4 PNEG-1797CE CE Approved T-Series Tower Dryer
Table of Contents

Contents

Chapter 1 Safety .....................................................................................................................................................7
Safety Guidelines .................................................................................................................................. 7
Tower Dryer Operations and Service .................................................................................................... 8
Safety Precautions .............................................. ... ... .... ... ... ... .... ... ........................................................ 8
Working at Heights ................................................................................................................................ 9
Entering Grain Dryers ............................ ... ... ....................................................................................... 10
Precautions to Reduce Risk of Fire ..................................................................................................... 12
Chapter 2 Decals ..................................................................................................................................................13
Chapter 3 Specifications .....................................................................................................................................20
Electrical .................................... ................ ................ ................. ................ ......................................... 20
Fuel ..................................................................................................................................................... 21
Dimensions ......................................................................................................................................... 23
Chapter 4 Dryer Installation ................................................................................................................................26
Dryer Layout ........................................................................................................................................ 26
Foundation .......................................................................................................................................... 26
Standard Base for Models 1050, 1260, 1575, 1875 and 20100 .......................................................... 27
Standard Base for Model 24100 ......................................................................................................... 28
Fuel Connections ................................................................................................................................ 29
Electrical Connection .......................................................................................................................... 29
Connecting Auxiliary Conveyors ......................................................................................................... 29
Chapter 5 Operating Controls .............................................................................................................................30
Vision Control Panel Layout ................................................................................................................ 30
Chapter 6 Vision Touch Screen Display ........................................................................... .... .............................32
Select Data Log Sample Time ............................................................................................................ 33
Optional Operation Screen ............... ... ... ... ... .... ... ... ... .... ... .......................................... ... ...................... 34
Setting the Timers ............................................................................................................................... 35
Setting the Temperatures .................................................................................................................... 36
The Setup Screen ............................................................................................................................... 37
Viewing the Owner’s Manuals on the Display Screen ......................................................................... 40
Viewing the Dryer Shut Down History ................................................................................................. 41
Chapter 7 Dryer Start-Up .....................................................................................................................................42
Dryer Commissioning .......................................................................................................................... 42
Pre-Season Checks ............................................................................................................................ 46
Chapter 8 Dryer Start-Up and Operation ...........................................................................................................53
Drying Temperatures .......................... ... ... ... .......................................... .... ... ... ... .... ............................ 53
Initial Setup Parameters ............................ ............................................. ............................................. 53
Start-Up .................................. ............................................. ................................................................ 53
Continuous Flow Drying Mode Using Advanced Moisture Control ..................................... .... ... ... ... ... 54
How the Advanced Moisture Control Works ....................................................................................... 58
Chapter 9 Drying Time Tables ............................................................................................................................59
Chapter 10 Service ...............................................................................................................................................65
Pre-Seasonal Inspection and Service ..................... .... ... ... ... .......................................... ... .... ... ... ...... 65
Seasonal Inspection and Service ...................................................................................................... 65
In Case of Fire ................................................................................................................................... 66
End of Season Service ...................................................................................................................... 66
Pre-Season Service Check List ......................................................................................................... 67
End of Season Shut Down Procedure ............................... ... .... ... ... ... ... .... ... ... ................................... 67
Chapter 11 Lubrication ........................................................................................................................................68
Table of Contents
Chapter 12 Error Messages ................................................................................................................................69
Safety Circuit Shut Down Messages ................................................................................................. 69
Input/Output Generated Errors .......................................................................................................... 70
Master Display Generated Errors ...................................................................................................... 71
Chapter 13 Wiring Diagrams for Pactrol Burner Control .................................................................................72
Upper Terminal Strip Wiring .............................................................................................................. 72
Burner/Fan Control Wiring ................................................................................................................. 73
Lower Terminal Strip Wiring .............................................................................................................. 74
Safety Relay Wiring ........................................................................................................................... 75
Upper Terminal Strip Field Connections ............................................................................................ 76
Lower Terminal Strip Field Connections ............................................................................................ 77
Chapter 14 Wiring Diagrams for Honeywell Burner Control ............................................................................78
Upper Terminal Strip Wiring .............................................................................................................. 78
Burner/Fan Control Wiring ................................................................................................................. 79
Lower Terminal Strip Wiring .............................................................................................................. 80
Safety Relay Wiring ........................................................................................................................... 81
Upper Terminal Strip Field Connections ............................................................................................ 82
Lower Terminal Strip Field Connections ............................................................................................ 83
Chapter 15 Warranty ............................................................................................................................................85
6 PNEG-1797CE CE Approved T-Series Tower Dryer

1. Safety

DANGER
WARNING
CAUTION
NOTICE
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
WARNING indicates a hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION, used with the safety alert symbol, indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE is used to address practices not related to personal injury.
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
Safety Guidelines
This manual contains information that is important for you, the owner/operator, to know and understand. This information relates to protecting personal safety and preventing equipment problems. It is the responsibility of the owner/operator to inform anyone operating or working in the area of this equipment of these safety guidelines. To help you recognize this information, we use the symbols that are defined below. Please read the manual and pay attention to these sections. Failure to read this manual and its safety instructions is a misuse of the equipment and may lead to serious injury or death.
1. Safety
Tower Dryer Operations and Service
This manual contains important information that all owners/operators must understand, relating to:
1. Personal safety.
2. Preventing equipment problems.
The owner/operator must inform anyone operating or working around this equipment of these safety guidelines.
Failure to read this manual and it’s safety instructions is a misuse of the equipment and may lead to serious injury or death.
Safety Precautions
1. Read the operating manual.
2. Electrical installation must be in accordance with relevant IEC standards, EU Directives and Local Codes/Regulations.
3. The entire dryer must be electrically earthed.
4. Gas/liquid fuel supply must be in accordance with European Standards, EU Directives and Local Codes/Regulations.
5. NEVER operate the dryer without guards in place.
6. DISCONNECT and LOCK OUT all power and fuel before adjusting, servicing, accessing or e ntering the dryer or associated equipment. The ONLY safe place to do this is at the main power panel. TURN OFF the incoming power at the main disconnect, LOCK the handle and TAG it to prevent inadvertent re-start. Be sure to lock out any other equipment attached to the dryer such as elevators and conveyors.
NEVER rely on the ON/OFF controls at the PLC interface. These are not safety shut offs. In addition, ensure the gas supply has been locked out at the main gas valve feeding the dryer.
7. NEVER bypass any safety device.
8. Whilst the dryer is running no-one should be inside or on the dryer.
9. Observe recommended drying temperatures.
10. Keep the dryer clean throughout.
11. Use CAUTION. The dryer and associated equipment may START AUTOMATICALLY.
12. Keep fan inlets clear of any foreign objects.
13. Auxiliary equipment capacity must be matched to the dryer.
14. Keep drive belts correctly tensioned.
15. Dry clean grain only for optimum performance.
16. Dryer operators must be trained and competent.
17. Follow required maintenance procedures and intervals.
8 PNEG-1797CE CE Approved T-Series Tower Dryer
1. Safety
Working at Heights
Whilst the equipment has been designed to operate primarily at ground level, at some stages during the life cycle it will be necessary to operate at heights. For this reason the equipment has been provided with access ladders, platforms and walkways. These have been designed to recognized safety standards to minimize the risk to health and safety to operators and technicians working on them. In addition attention should be paid to the following safety requirements.
1. The ladders, platforms and walkways are for use by competent and trained personnel only. NEVER allow children or members of the general public to gain access to the equipment, its ladders or access platforms.
2. Where the equipment is sited in an unsecured location, access must be restricted by use of security fencing and lockable gates.
3. Lower sections of ladders on the equipment should be fitted with a lockable safety gate, to prevent unauthorized access.
4. Ensure any hot surfaces have had adequate time to cool before working on or in the equipment. This may require running the equipment fans only to cool off external screens and internal burner components.
5. The equipment should be OFF and all power LOCKED OFF before work on or in the equipment. Ensure the power isolator is OFF and LOCKED and TAGGED to prevent inadvertent re-start. This must include all equipment attached to the dryer/bin on which you are working. (See Figure 1A.)
Figure 1A
6. Ensure the fuel supply is OFF and LOCKED. (See Figure 1B.)
Figure 1B
1. Safety
7. NEVER attach lifting equipment to ladders or platforms.
8. When working on the equipment, NEVER go outside the safety rails provided.
9. NEVER walk on the roof of the equipment.
10. Do not work at heights during high winds, heavy rain, snow, ice or storm.
The majority of routine cleaning and service can be carried out from the service platforms provided. However in exceptional circumstances it may be necessary to access other parts of the equipment. In particular, in the rare event that access is required to repair or r eplace the g rain level switches. On th ese occasions additional access and safety equipment may be required. Wherever possible we recommend the use of powered access lift platforms or ‘cherry pickers’. In exceptional circumstances access may require the use of safety harness. Such work must only be carried out b y specialist technicians trained and qualified in working at heights and only after a complete risk assessment has been carried out and safe working methods established.
Entering Grain Dryers
Wherever possible it is recommended not to enter grain dryers. However, if you have to enter the, observe the following minimum
precautions:
1. NEVER
2. Make sure you are aware of all the possible hazards
3. Complete a risk assessment
4. You may need to complete a permit to work approved by the dryer owner or supervisor.
5. Ensure the dryer has been purged of any products of combustion. Shut off the burner but leave the fans running for at least 30 minutes before entry.
6. Do not smoke or use naked flames in or around the dryer.
7. Where there is a risk of harmful gases or vapors, check the atmosphere with a suitable analyzer. If necessary, run the fans for longer to provide a safe breathable atmosphere. If in doubt do not enter
8. Switch OFF, lock and tag equipment feeding and emptying the dryer. This will require turning the main power isolator to OFF, LOCKING it and apply a TAG to prevent inadvertent re-start. (See Figure 1C on Page 11.)
allow a child or untrained, inexperienced person to enter a grain dryer at any time.
present within the dryer.
and identify any control measures that may be required, including:
Personal protective equipment, such as hand, eye, foot, hearing, head and respiratory protection.
Safe access equipment.
Safety equipment, such as safety line and harness.
Supplementary lighting.
and prepare a safe system of work and have it
power supplies to ALL equipment associated with the dryer. Include
.
10 PNEG-1797CE CE Approved T-Series Tower Dryer
Figure 1C
9. You may also need to lock out any associated equipment attached to the dryer.
1. Safety
10. Shut OFF, lock and tag
the fuel supply at the main incoming valve. (See Figure 1D,)
Figure 1D
11. Never work alone, it is recommended to work in teams of at least three (3) so help is immediately available in the event of emergency.
12. On completion of the work, check all team members are out of the dryer and all work tools have been recovered.
13. Close and lock all dryer accesses.
14. Do not re-connect power or fuel supplies until approved by the dryer owner or supervisor.
PNEG-1797CE CE Approved T-Series Tower Dryer 11
1. Safety
WARNING
Keep the dryer clean. Do not allow fine material to accumulate in the plenum chamber or surrounding the outside of the dryer.
Precautions to Reduce Risk of Fire
Whilst the dryer has been designed to minimize the risk of ignition of combustible dust and dirt, this can only be ensured by regular inspection and cleaning. At least every five (5) days.
1. Refer to Page 10 for required precautions before entering the dryer. The dryer must be locked out and tagged at the main power and fuel supply before entering.
2. Open the dryer access hatches and check for any significant build-up of dust or particles of grain.
3. Using an industrial vacuum cleaner, clean the plenum. Do not use compressed air.
4. Check inside other dryer accesses and clean as required.
5. Check all personnel are out of the dryer, close and lock all accesses before re-starting drying.
6. This procedure may be carried out more regularly in conditions of extreme dust and dirt.
Exercise greater caution when drying highly flammable grains and seeds. For example rapeseed, can ola, linseed, sunflower and milo.
All grain and seed must be whole (minimal cracked or crushed), clean and dust free. Dry at low temperatures (< 40°C). Avoid dust and chaff being drawn into the fan and heater. Keep the fan, heater, drying plenum and ducts clean at all times. In the event of a fire (or suspected fire).
Shut down the entire dryer.
Turn OFF fuel at the tank or supply valve.
Shut off and lock electrical power.
Evacuate the area.
Call the fire department.
Use Caution in the Operation of this Equipment
This dryer is designed and manufactured with operator safety in mind. However, the very nature of a grain dryer having a gas burner, high voltage electrical equipment and high speed rotating parts, presents hazards to personnel which cannot be completely safeguarded against withou t interfering with the efficient operation of the dryer and reasonable access to its components.
Use extreme caution at all times when working on or around the dryer.
Continued safe, dependable operation of automatic equipment depends, to a great degree, upon the owner. Follow the recommendations within the Owner’s Manual and make it a practice to regularly inspect the unit for any developing problems or unsafe conditions.
Take special note of the safety precautions on Page 8 before attempting to operate the dryer.
12 PNEG-1797CE CE Approved T-Series Tower Dryer

2. Decals

Safety decals must be read and understood by all people in and around the dryer area. If a ny safety decals are not displayed on the dryer or if they are damaged, contact The GSI Group, Inc. for replacement:
International Decals
International, translated versions of the decals fitted to the equipment are available as part of the Language Pack that was supplied with the product. If you need further copies or a different language, please contact GSI or you dealer.
The international decals have been designed to be placed directly over the USA standard versions. Normally these will be factory fitted, but if you need to change them, please refer to the decal cross reference sheet, provided with the Language Pack and the decal locations given in the user’s manual.
Decals
1004 E. Illinois St. Assumption, IL. 62510 Phone: 1-217-226-4421
PNEG-1797CE CE Approved T-Series Tower Dryer 13
2. Decals
DC-2163
DC-2163 is located on outside and inside of the main power panel doors. Quantity: 3
DC-2161
DC-2161 is located on inside and outside of the roof access hatches. Quantity: 2
No entry to
unauthorised
personnel
Suffocation and
Entrapment Hazard
Do not walk directly
on stored material
No smoking or
naked flames
Automatic Machinery
Isolate and lock all power
before entering this bin
Respirators
must be worn
in this area
Before entering:
Permit required for entry into confined space
Disconnect and lock all electrical power
Disconnect and lock fuel supply
Use safety harness and safety line
Ensure someone else is outside the bin
DC-2161
High
Voltage
Isolate and lock from power before removing guards or opening enclosure
Replace all guards and lock enclosure before reconnecting to power
DC-2163
14 PNEG-1797CE CE Approved T-Series Tower Dryer
2. Decals
Do not stand on
rotating drum
Serious injury
may result
DC-2212
Rotating drum
below
DC-2212
DC-2212 is located on the outside of the hopper service access hatch. Quantity: 2
Do not operate with guards removed
Isolate and lock from power before removing guards
Replace all guards before reconnection to power
Automatic Machinery
DC-2164
DC-2165
DC-2165 is located on the heat section inner and outer access hatches. Quantity: 2
DC-2164
Background: White Colors: Black, ANSI Yellow and ANSI Blue Size: 3.940" x 1.970"
DC-2165
Do not open door while drier is running
Disconnect and lock electric and gas supply before opening
Close and lock door before reconnecting
High Temperature
and Pressure
Equipment Can Start
Unexpectedly
PNEG-1797CE CE Approved T-Series Tower Dryer 15
2. Decals
Confined Space
High Temperature
Exposed fan and belt drive
Automatic machinery
No unauthorized access No smoking No exposed flames
Lock out all electrical power before entering Lock out fuel supply before entering Refer to owners manual before entering Wear respiratory protection
DC-2216
DC-2216
DC-2216 is located on the cool section (intake plenum) access hatch. Quantity: 1
Confined Space
High Temperature
Powered machinery can kill or dismember
Flowing material will bury and suffocate
No unauthorized access No smoking No exposed flames
Lock out all electrical power before entering Lock out fuel supply before entering Refer to owners manual before entering Wear respiratory protection
DC-2215
DC-2215
DC-2215 is located on upper and middle level access hatches. Quantity varies with size of dryer.
DC-2214
DC-2214 is located on the grain sampling access hatch. Quantity: 1
Automatic conveying equipment
Do not remove
guarding
Grain Sampling Point
below
DC-2214
16 PNEG-1797CE CE Approved T-Series Tower Dryer
2. Decals
Electrical Lockout
DC-2217
BEFORE working on or in the dryer
SWITCH OFF, LOCK and TAG
to prevent accidental start-up
DC-2217
DC-2217 is located adjacent to the electrical lock out handle on the main power panel. Quantity: 1
DC-2230
Background: White Colors: Black, ANSI Y ellow and ANSI Blue Size: 6.000" x 3.000"
DC-2231
DC-2231 is located on the outside of the main power panel doors. Quantity: 2
DC-2230
Lock out all electrical power before entering
Auto equipment can
start at any time
Rotating auger will
crush and cut
DC-2231
Secure legs to foundation prior to opening doors
Crush
Hazard
PNEG-1797CE CE Approved T-Series Tower Dryer 17
2. Decals
DC-2233
If an overload or a fault current interruption occurs, circuits must be checked to determine the cause of the interruption
If a fault condition exists, the current-carrying components should be examined and replaced if damaged, and the integral current sensors must be replaced
Electric shock and
fire hazard
DC-2234
To maintain overcurrent short circuit and ground fault protection, the manufacturer’s instructions for selecting overload relays and setting the instantaneous trip circuit breaker must be followed
Electric shock and
fire hazard
DC-2234
DC-2234 is located on inside main power panel door. Quantity: 1
DC-2233
DC-2233 is located on inside main power panel door. Quantity: 1
DC-2232
DC-2232 is located on roof panels adjacent to roof steps. Quantity: 4
Slip and fall hazard
Can cause severe
injuries
Do NOT step or stand
in this area
DC-2232
18 PNEG-1797CE CE Approved T-Series Tower Dryer
DC-2235
High Voltage
Insure that the incoming AC power and all separate power sources are turned off and locked before working on this equipment
Failure to observe practice below may result in severe injury, death, and/or equipment damage
All maintenance
DC-2235
DC-2235 is located on inside and outside main power panel door. Quantity: 2
DC-2236
DC-2236 is located on inside main power panel door. Quantity: 1
DC-2237
DC-2237 is located on inside main power panel door. Quantity: 1
procedures must be performed by qualified personnel who are familiar with the operation of this equipment.
2. Decals
For precise location of all safety decals, please refer to manual provided with the language pack for the dryer.
PNEG-1797CE CE Approved T-Series Tower Dryer 19
Failure to observe this warning can result in serious or even fatal injury and/or equipment damage.
DC-2236
Be sure that charge light and all LED’s are out before touching any components.
All test equipment should be connected and disconnected with power off.
Ground test equipment, such as Insure that the incoming AC
oscilloscopes, may damage the power and all separate power
inverter. sources are turned off and
locked before working on this Isolate all instruments from
equipment ground before using. The DC bus
remains charged for several minutes after power is removed.
DC-2237

3. Specifications

Dryer Specifications
Models 1050 1260 1575 1875 20100 24100
Blower Size 43" Axial 43" Axial 8490 8542 8542 8600 Blower RPM 1750 1750 1035 856 981 818 Blower kW 37.50 45.00 56.25 56.25 75.00 75.00 Metering kW 0.75 0.75 0.75 0.75 0.75 0.75
Drying m3/s
3
Cooling m Grain Column 324 mm 324 mm 324 mm 324 mm 324 mm 324 mm Tower Diameter 3.65 m 3.65 m 3.65 m 3.65 m 3.65 m 3 .65 m Overall Height 13.9 m 15.9 m 18.0 m 21.0 m 23.1 m 26.1 m Wet Holding (T) 7.677.677.677.677.677.67 Heat Holding (T) 15.49 19.20 23.22 29.41 31.90 38.07 Cool Holding (T) 5.56 6.81 7.75 8.99 11.46 12.70 Dryer Holding (T) 31.29 36.25 41.20 48.64 53.59 60.99 Outside Catwalks 001223 T/H (20%-15%) 25 30 38 46 51 61 T/H (25%-15%) 151823273037
/s
19.98 22.86 36.42 38.63 46.57 51.15
6.85 8.27 18.21 19.32 23.28 25.58
Electrical
Standard voltages are:
1. 240V, 480V or 575V, 60 Hz
2. 380V, 400V or 415V, 50 Hz
The power panel includes:
1. Main power disconnect.
2. Motor starters and overloads (standard direct on line, star/delta and soft start are options).
3. Control circuit breakers for the individual blower motors.
4. Auxiliary 7.5 kW motor starters for dry and wet grain handling equipment.
5. A correctly designed power supply is required, including safety earth connection.
Please note that the figures given on Page 72 are minimum figures and do not take into account starting currents. Please allow for these when designing the required power supply for the dryer.
20 PNEG-1797CE CE Approved T-Series Tower Dryer
3. Specifications
Minimum Electrical Power Requirements
3 Phase Power Requirements (A)
Supply Voltage
230 380 400 415 440 460 575
Model #
T-1050 204 123 117 113 106 102 81 T-1260 226 136 130 125 118 113 90 T-1575 258 156 148 143 135 129 103
T-1875 258 156 148 143 135 129 103 T-20100 316 191 181 175 165 158 126 T-24100 316 191 181 175 165 158 126
F-1050 204 123 117 113 106 102 81
F-1260 226 136 130 125 118 113 90
F-1575 258 156 148 143 135 129 103
F-1875 258 156 148 143 135 129 103 F-20100 316 191 181 175 165 158 126 F-24100 316 191 181 175 165 158 126
Fuel
1. Fuel types are LPG or natural gas vapor.
2. Minimum supply pressure is, a. 350 mBar natural gas at full burner flow rate. b. 350 mBar LPG vapor at full burner flow rate. Higher pressures may be required to obtain
maximum burner output.
3. Burner flow rates are as table on Page 22.
PNEG-1797CE CE Approved T-Series Tower Dryer 21
3. Specifications
T-Series and F-Series Fuel Specifications
T-Series and F-Series T/F-1050 T/F-1260 T/F-1575 T/F-1875 T/F-1054 T/F-20100 T/F-24100
Maximum Burner Output (kW)
Average Burner Output (kW)
LPG Fuel LPG Gross CV
Maximum Gas Flow LPG (m
3
/h)
Average Gas Flow
3
LPG (m
/h)
Supply Pressure (mBar1)
Regulator Setting (mBar2)
3254 3831 4882 5180 6244 6858 7722
1871 2203 2807 2979 3590 3943 4440
93.8 MJ/m
3
125 147 187 199 240 263 296
72 85 108 114 138 151 170
350-700 350-700 350-700 350-700 350-700 350-700 350-700
206 206 206 206 206 206
Regulator Spring Black Cadmium Cadmium Cadmium Cadmium Cadmium Cadmium Burner Pressure High-Fire
2
O6)
mm (H
Burner Pressure Low-Fire
2
O7)
mm (H
418 1375 807 1189 1447 972
16.7 55.0 32.3 47.5 57.9 38.9
Natural Gas Fuel NG Gross CV
Maximum Gas Flow
3
NG (m
/h)
Average Gas Flow
3
NG (m
/h)
Supply Pressure (mBar1)
Regulator Setting (mBar2)
303 357 455 483 582 640 720
174 205 262 278 335 368 414
350-700 350-700 350-700 350-700 350-700 350-700 350-700
21 206 206 206 206 206 206
39 MJ/m
3
Regulator Spring Black Cadmium Cadmium Cadmium Cadmium Cadmium Cadmium Burner Pressure High-Fire
mm (H
2
O6)
Burner Pressure Low-Fire mm (H
2
O7)
Pressure Relief Set Point (mBar
4
)
Over Pressure Valve
5
Set Point (mBar
)
500 500 500 500 500 500 500
450 450 450 450 450 450 450
719 1189 697 1009 1241 855
28.8 47.6 27.9 40.3 49.7 34.2
22 PNEG-1797CE CE Approved T-Series Tower Dryer
Dimensions
3. Specifications
Figure 3A 1050 Figure 3B 1260
PNEG-1797CE CE Approved T-Series Tower Dryer 23
3. Specifications
Dimensions (Continued)
Figure 3C 1575 Figure 3D 1875
24 PNEG-1797CE CE Approved T-Series Tower Dryer
Dimensions (Continued)
3. Specifications
Figure 3E 20100
PNEG-1797CE CE Approved T-Series Tower Dryer 25
Figure 3F 24100

4. Dryer Installation

Dryer Layout
System Layout
When considering dryer location make allowance for:
1. Grain handling systems.
2. Location of storage bins.
3. Wet grain supply.
4. Prevailing wind direction.
5. Fuel and power supply.
6. Noise.
7. Control panel location.
Site Location
Do not locate the dryer:
1. Inside a building.
2. Adjacent to combustible material which may be sucked in.
3. Within 2.0 m of other structures. Refer to specifications on Pages 20-22 and dimensions
on Pages 23-25.
You may need to obtain local permission for the dryer construction and should also consider:
1. Electrical code.
2. Fuel installation regulations.
3. Insurance requirements.
Foundation
Standard foundation details are given in Figure 4A on Page 27 and Figure 4B on Page 28. For ground conditions outside of these standards a local engineer will be required to carry out site specific foundation design.
26 PNEG-1797CE CE Approved T-Series Tower Dryer
Loading...
+ 60 hidden pages