Grasslin DTMV40 Series, DTMV40, DTQMV40, DTMV40-IM, DTMV40-M Operating Instructions Manual

...
• Disconnectpoweratthecircuitbreaker(s)ordisconnectswitch(es)beforebeginning installationorservicing.
• Morethanonecircuitbreakerordisconnectswitchmayberequiredtode-energizethe equipmentbeforeservicing.
• Donotusethemanualoffpositionofthetimerforequipmentservicing.Alwaysdiscon­nectthepoweratthecircuitbreaker(s)ordisconnectswitch(es).
• UseCOPPERconductorsONLY.
• Wireinaccordancewithnationalandlocalelectricalcoderequirements.
DTMV40 Series
TimeInitiated,Temperature,
PressureorTimeTerminatedMulti-Voltage 40ADefrostTimers
WARNING
Risk of Fire or Electric Shock
• Rotatetimerdialclockwiseonly.
CAUTION
Risk of Damage to Timer
1
Paragon Precision
TIME INITIATED, TIME TERMINATED
Grasslin
Mode Selection Wiring Diag.
TIME INITIATED, PRESSURE TERMINATED
(Separate Pressure Switch Required (see instructions)
TIME INITIATED, REMOTE TEMPERATURE OR
PRESSURE TERMINATED
STARTUP PROCEDURE
1. Determine model to be replaced (Grasslin or Competitors) from table below.
2. Set Mode Selection (S1 BLUE DIP Switch – Fig. A) See table below and instructions on page 5.
3. Apply corresponding Terminal Identification and Door labels –see retrofit kit instructions.
4. Set correct input voltage (S2 RED DIP Switch – Fig. B).
5. Follow installation and programming instructions.
The DTMV40 can be configured for either 120 or 208/240VAC. Locate RED DIP Switch to the right of timer module. For:
120VAC slide DIP switch UP
208/240VAC slide DIP switch DOWN
TImer Mechanism
Step 2
Interior Protective Cover
Step 1
Ground Lug
2-1/2”
6-1/8”
INSTALLATION
Note: For outdoor locations, raintight, or wet location conduit hubs that comply with requirements of UL 514B (standard for fittings for conduit and outlet boxes) are to be used.
1. Open door and then remove interior protective cover by releasing spring clip on bottom.
2. Remove timer mechanism by releasing spring clip on bot­tom.
3. Select knockouts to be used. Remove inner 1/2” knockout by inserting a screwdriver in the slot and carefully punch knockout loose. Remove slug. If 3/4” knockout is required, remove the outer ring with pliers after removing the 1/2” knockout. Smooth edges with knife if necessary.
4. Place enclosure in desired mounting location and mark the three mounting holes (refer to diagram below). Start by placing set screw on top and attaching enclosure over keyhole: then screw in remaining two screws on bottom.
5. Connect conduit hubs to conduit before connecting the hubs to the enclosure. After inserting hubs into enclosure, carefully tighten hub lock nut. Do not over-torque.
6. Verify voltage selection. 120VAC – position switch UP; 208/240VAC – position switch DOWN (refer to Fig. B).
7. Wire in accordance with National and Local
Codes.
8. Gr
ounding: Terminate all ground wires to ground lug on
bottom of enclosure.
9. Replace interior pro­tective cover.
UL TYPE 3R Enclosure
Bracket Mount
Input Voltage Switch (S2)
Mode Selection Switch (S1)
http://waterheatertimer.org/Intermatic-Defrost-timers-and-manuals.html
8
7
A
M
Models Non-Enclosure Mount
DTMV40-M 24-hour, Mechanism Only
DTQMV40-M 24-hour w/Battery Backup, Mechanism Only
DTMV40-P 24-hour, Panel Mount
DTMV40-B 24-hour, Bracket Mount
DTQMV40-B 24-hour w/Battery Backup, Bracket Mount
PROGRAMMING (Synchronous and Quartz
Models)
Setting the Time:
Turn the minute hand clockwise until the time of day (and AM or PM) on the outer dial is aligned with the triangle marker on the inner dial.
Note: All units with Battery Backup provide up to a week of reserve carryover.
Setting Defrost Initiation Time:
Move a white tab (tripper) on the outer dial outward at each desired initiation time. For example, to set defrost initiation times at 6:00AM, 11:30AM, 4:30PM and 11:00PM, move the tab adjacent to the “M” in AM on the dial (6:00AM), the tab that lies between 11:30AM and 11:45 AM, the tab between 4:30PM and 4:45PM, and the tab adjacent to the 11:00–11:15PM marks. (See note for 8243/6243 replacement.)
Setting Maximum Defrost Duration:
Different defrost durations may be set for each defrost initiation setting. Each white tab (tripper) provides a 15 minute interval. The tabs that set the initiation time provide a minimum of 15 min­utes of defrost. For longer defrost duration, move additional tabs (following in time) from the initiation tab. For example, if a 45 minute defrost is to start at 7:00AM, move the tab outward that lies between 7:00 and 7:15
on the AM side of the dial, and the tabs adjacent to 7:15-7:30 and 7:30-7:45. (3 tabs moved outward). The defrost will initiate at 7:00AM and time terminate at 7:45AM (if temperature termination does not occur first.)
For electronic models, refer to sepa­rate programming instructions.
DO NOT ROTATE MINUTE HAND COUNTER-CLOCKWISE
Model Designation
Models Enclosure Mount
DTMV40 24-hour, Outdoor UL TYPE 3R Enclosure
DTQMV40 24-hour w/Battery Backup,
Outdoor UL TYPE 3R Enclosure
DTMV40-IM 24-hour, Indoor Metal UL TYPE 1 Enclosure
Note: It is necessary to apply power across terminals 1&N in order to perform electrical test.