2.1 Applications
S pumps, range 72, 74 and 78, are designed for the pumping of
sewage and wastewater in a wide range of municipal and
industrial applications.
Depending on the installation type, the pumps can be used for
submerged or dry, horizontal or vertical, installation.
Maximum solids size: 90-145 mm, depending on impeller type.
2.2 Potentially explosive environments
In potentially explosive environments, use only Ex-approved
apparatus. All range-72 pumps are available as Ex versions.
Range 72 Ex pumps can be used in hazardous areas classified
as Zone 1 or Zone 2.
Warning
Special conditions for safe use of S pumps,
range 72 Ex, 74 and 78:
1. Make sure the moisture switches and thermal
switches are connected in two separate circuits
and have separate alarm outputs (motor stop) in
case of high humidity or high temperature in the
motor.
2. Bolts used for replacement must be class A4-80
or A2-80 according EN/ISO 3506-1.
3. The flame path gaps of the motor are specified by
the manufacturer and are narrower than
standard. Please see the manufacturer's
installation, operation and maintenance
document for guidance.
4. During operation, the cooling jacket, when fitted,
must be filled with pumped liquid.
5. The level of pumped liquid must be controlled by
level switches connected to the motor control
circuit. The minimum level depends on the
installation type and is specified in these
installation and operating instructions.
6. Dry-running is not allowed.
7. Make sure the permanently attached cables are
suitably mechanically protected and terminated in
a suitable terminal board.
8. The sewage pumps have an ambient temperature
range of 0-40 °C and a maximum process
temperature 40 °C.
9. The control unit must protect the WIO against the
short circuit current of the supply to which it is
connected. The maximum current from the
control unit must be limited to 350 mA.
10.The maximum submersion depth is 20 m.
Warning
Special conditions for safe use of WIO sensor
1. The control unit must protect the sensor against
the short-circuit current of the current supply to
which it is connected.
2. The sensor must be installed in such a way that
danger of mechanical impact is avoided.
3. The WIO sensor must not be used in oil with a
flash point below 250 °C.
4. The WIO sensor is approved according to
EN/IEC 60079-18:2004. In Ex and IEC Ex
applications, the maximum current supplied to the
sensor must be limited to 350 mA according to
EN/IEC 60079-18:2004.
Installation
type
Description Accessories
S
Sewage pump without
cooling jacket for
submerged installation on
auto coupling.
Auto coupling
C
Sewage pump with
cooling jacket for
submerged installation on
auto coupling.
Auto coupling
D
Sewage pump with
cooling jacket for dry
vertical installation.
Base plate for vertical
installation
H
Sewage pump with
cooling jacket for dry
horizontal installation.
Base plate for
horizontal installation
ST
Sewage pump without
cooling jacket for
installation in vertical
column pipe.
Seat ring