English (GB) Installation and operating instructions
English (GB)
Original installation and operating instructions
CONTENTS
Page
1.Grundfos RSI
1.1Specific functions of Grundfos RSI
2.Safety
2.1Danger
2.2Warnings
3.Startup
3.1First Start-up
3.2Description of the applications
3.2.1 Standard application10
3.2.2 Local/Remote application11
3.2.3 Multi-step application11
3.2.4 PID Control application12
3.2.5 Multi-purpose application14
3.2.6 Motor potentiometer application16
4.User Interfaces
4.1Keypad of the drive
4.1.1 Buttons17
4.1.2 Display17
4.1.3 Navigation on keypad17
4.1.4 RSI graphical keypad18
4.1.5 RSI Text keypad24
4.2Grundfos PC tool
4.2.1 Quick setup28
4.2.2 Monitor28
4.2.3 Parameters29
4.2.4 Diagnostics29
4.2.5 I/O and hardware32
4.2.6 User settings42
4.2.7 Favorites43
4.2.8 User levels43
4.3Example of control connections
4.3.1 Relay and thermistor input terminals45
4.3.2 Safe Torque off (STO) terminals45
5.Monitoring Menu
5.1Monitor group
5.1.1 Multi-monitor46
5.1.2 Trend curve46
5.1.3 Basic48
5.1.4 I/O48
5.1.5 Extras & advanced49
5.1.6 Timer functions51
5.1.7 PID Controller51
5.1.8 ExtPID Controller51
5.1.9 Mainten. counters52
5.1.10 Fieldbus data52
5.1.11 Solar53
5.1.12 Flow53
6.Parameters
6.1Application parameter lists
6.1.1 Column explanations55
6.1.2 Group 3.1: Motor settings55
2
6.1.3 Group 3.2: Start/Stop setup59
6.1.4 Group 3.3: References60
6.1.5 Group 3.4: Ramps And Brakes62
6.1.6 Group 3.5: I/O Config63
6.1.7 Group 3.6: Fieldbus DataMap70
3
6.1.8 Group 3.7: Prohibit Frequencies71
3
6.1.9 Group 3.8: Supervisions71
4
6.1.10 Group 3.9: Protections72
4
6.1.11 Group 3.10: Automatic reset78
4
6.1.12 Group 3.11: Appl. Settings78
6.1.13 Group 3.12: Timer functions79
5
6.1.14 Group 3.13: PID Controller83
5
6.1.15 Group 3.14: ExtPID Controller91
7
6.1.16 Group 3.16: Maintenance Counters94
6.1.17 Group 3.21: Pump Control94
6.1.18 Group 3.22: Solar95
6.1.19 Group 3.23: Flow meter96
6.2Additional parameter information
6.2.1 Motor Control96
6.2.2 Open Loop101
17
6.2.3 Start/Stop Setup103
17
6.2.4 References106
6.2.5 Preset Freqs106
6.2.6 Motor Potentiometer107
6.2.7 Ramps And Brakes108
6.2.8 Flux Braking108
6.2.9 Digital inputs109
27
6.2.10 Analog inputs109
6.2.11 Digital Outputs114
6.2.12 Analog outputs116
6.2.13 Prohibit Freq118
6.2.14 Protections120
6.2.15 Automatic Reset125
6.2.16 Feedbacks126
6.2.17 FeedForward127
6.2.18 Sleep Function128
44
6.2.19 Feedback Superv.129
6.2.20 Press.Loss.Comp130
6.2.21 Soft fill132
46
6.2.22 Auto-Cleaning132
46
6.2.23 Solar133
7.Fault
7.1Fault Tracing
7.2Fault appears
7.3Fault History
7.4Fault codes
54
54
96
136
136
136
137
138
1. Grundfos RSI
The Grundfos RSI contains a preloaded Grundfos
motor library for instant use.
1.1 Specific functions of Grundfos RSI
The dedicated application software was developed
to drive a Solar Pump with an optimized MPPT
(Maximum Power Point Tracking) for RSI supplied by
Solar Panels.
The MPPT is based on 4 parallel algorithms:
• Feed-Forward Controller (to follow the radiation
variations)
• Correction Controller (to compensate the
temperature variations)
• Oscillation Damping Regulator (to prevent the
panel entering in the "current source" branch of
the characteristic)
• Local Maxima logic (to prevent the regulator from
being trapped in a local maximum lower than
absolute maximum)
Features
• The MPP Tracker controls DC voltage reference
in order to find the maximum power.
• Extensive wizards for start-up, PID-control used
to facilitate commissionin g
• "Funct" button for easy change between Local
(keypad) and Remote control place. The remote
control place is selectable by parameter (I/O or
Fieldbus)
• 8 preset frequencies
• Motor potentiometer functions
• 2 programmable ramp times, 2 supervisions and
3 ranges of prohibited frequencies
• Control page for easy operation and monitoring
of the most essential values.
• Fieldbus data mapping
• Automatic reset
• Different pre-heat modes used to avoid
condensation problems
• Maximum output frequency 320 Hz
• Real-time clock and timer functions available
(optional battery required). Possible to program 3
time channels to achieve different functions on
the drive (e.g. Start/Stop and Preset frequencies)
• External PID-controller available. Can be used to
control e.g. a valve using the AC drive's I/O
• Sleep mode function which automatically enables
and disables drive running with user defined
levels to save energy.
• 2-zone PID-controller (2 different feedback
signals; minimum and maximum control)
• Two setpoint sources for the PID-control.
Selectable with digital input
• PID setpoint boost function
• Feedforward function to improve the response to
the process changes
• Process value supervision
• Maintenance counter
• Underload protection can be managed by
measuring Motor torque (standard sensorless
mode) or by measuring the water flow with a flow
meter sensor. This sensor can be an analogue
signal or a digital input. With this sensor it is
possible to measure the water flow [litres/min]
and the total volume of the water flow [m
• Sleep mode can be enabled or disabled with a
parameter.
Digital inputs can be used to measure water levels
(minimum and maximum).
3
].
English (GB)
3
2. Safety
English (GB)
This manual contains clearly marked warning
information which is intended for your personal
safety and to avoid any unintentional damage to the
product or connected appliances.
Before installing, commissioning or using the
frequency converter, please read the warning
information contained in RSI Installation Manual.
Please read the following additional safety
instructions carefully.
Only authorized, trained and qualified personnel are
allowed to install, operate and maintain the drive.
2.1 Danger
These warnings are intended to personnel
responsible for grounding the frequency converter.
Ignoring the following instructions can
be extremely dangerous and may
cause death or severe injury.
Ground the frequency converter to
ensure personnel safety and to
reduce electromagnetic interference.
After disconnecting the AC drive from
the mains or from the DC input supply,
wait until the indicators on the keypad
go out (if no keypad is attached, see
the indicators on the cover). Wait an
additional 30 seconds before starting
any work on the connections of RSI.
After expiration of this time, use
measuring equipment to absolutely
ensure that no voltage is present.
Always ensure absence of voltage
before starting any electrical work!
2.2 Warnings
The touch current of RSI exceeds 3.5
mA AC. According to standard
EN61800-5-1, a reinforced protective
ground connection must be ensured.
See RSI Installation Manual for further
information.
Never work on the photovoltaic
generator or frequency converter and
its input/output cables when the
frequency converter is connected to
the mains or to the photovoltaic
generator.
Before performing any measurement
on the frequency converter,
disconnect or isolate the mains supply
voltage or the DC input supply.
Do not touch the components on the
frequency converter or on the string
box cabinet that have high DC
voltage.
The photovoltaic generator cells
exposed to light supply DC voltage
even at low light intensity.
4
3. Startup
3.1 First Start-up
In the Startup Wizard, you will be prompted for
essential information needed by the drive so that it
can start controlling your process. In the Wizard, you
will need the following keypad buttons:
Left/Right arrows. Use these to easily
move between digits and decimals.
Up/Down arrows. Use these to move
between options in menu and to
change value.
OK button. Confirm selection with this
button.
Back/Reset button. Pressing this
button, you can return to the previous
question in the Wizard. If pressed at
the first question, the Startup Wizard
will be cancelled.
Once you have connected power to your RSI, follow
these instructions to easily set up your drive.
NOTE: You can have your AC drive equipped with a
keypad with either a graphical or a text keypad.
1Language selection (P6.1)Depends on language package
Push the OK button unless you want to set all
parameter values manually.
Russia
US
EU
OFF
Yes
No
5
English (GB)
7
8
9
10
11
12
13
14
15Set value for P3.3.1.2 MaxFreqReferenceRange: 0.00...320.00 Hz
16Set value for P3.4.1.2 Accel Time 1Range: 0.1...300.0 s
17Set value for P3.4.1.3 Decel Time 1Range: 0.1...300.0 s
If you set Motor Type to Induction Motor, you see the
next question. If your selection is PM Motor, the
value of parameter P3.1.1.5 Motor Cos Phi is set to
1.00 and the wizard goes directly to question 18.
18Set value for P3.3.1.1 MinFreqReferenceRange: 0.00...50.00 Hz
19Set value for P3.3.1.2 MaxFreqReferenceRange: 0.00...320.00 Hz
20Set value for P3.4.1.2 Accel Time 1Range: 0.1...300.0 s
21Set value for P3.4.1.3 Decel Time 1Range: 0.1...300.0 s
22Run the Application wizard?
To continue to the application wizard, set the
selection to Yes and push the OK button.
After these selections, the Start-up wizard is
completed. To start the Start-up wizard again, you
have 2 alternatives. Go to the parameter P6.5.1
Restore Factory Defaults or to the parameter B1.1.2
Start-up Wizard. Then set the value to Activate.
Make a selection of an application (P1.2
Application,ID212)
Set a value for P3.1.2.2 Motor Type (so that
it agrees with the nameplate)
Set value for P3.1.1.1 Motor Nom Voltg
(according to nameplate)
Set value for P3.1.1.2 Motor Nom Freq
(according to nameplate)
Set value for P3.1.1.3 Motor Nom Speed
(according to nameplate)
Set value for P3.1.1.4 Motor Nom Currnt
(according to nameplate)
Set value for P3.1.1.5 Motor Cos Phi
(according to nameplate)
Set value for P3.3.1.1 Minimum frequency
reference
Standard
Local/Remote
Multi-step speed
PID control
Multi-purpose
Motor potentiometer
PM motor
Induction motor
Range: Varies
8.00...320.00 Hz
Range: 24...19.200 rpm
Range: Varies
Range: 0.30...1.00
Range: 0.00...50.00 Hz
Yes
No
6
3.2 Description of the ap pli catio ns
Use the parameter P1.2 (Application) to make a
selection of an application for the drive. Immediately
when the parameter P1.2 changes, a group of
parameters get their preset values.
M1 Quick setup parameter group
In the Quick Setup parameter group you will find the
different wizards of the RSI Solar Pump Application.
The wizards help you to quickly set up your drive for
use prompting you for a number of essential data.
CodeParameterMinMax Unit DefaultIDDescription
0 = Do not activate
B1.1Startup wizard0101170
P1.2Application050212
1 = Activate
Choosing Activate initiates the Startup
Wizard (see chapter 3.1 First Start-up).
0 = Standard
1 = Local/Remote
2 = Multi-Step Speed
3 = PID Control
4 = Multi-Purpose
5 = Motor
Potentiometer
P1.3 MinFreqReference 0.00P1.4Hz0.00101 Minimum allowed frequency reference
P1.4 MaxFreqReference P1.3 320.00 Hz50.00102 Maximum allowed frequency reference
P1.5Accel Time 10.1300.0s5.0103
P1.6Decel Time 10.1300 .0s5.0104
Defines the time required for the output
frequency to increase from zero
frequency to maximum frequency
Defines the time required for the output
frequency to decrease from maximum
frequency to zero frequency
P1.7Current limitVaries VariesAVaries107 Maximum motor current from AC drive
P1.8Motor type010650
P1.9Motor Nom Voltg Varies VariesVVaries110
P1.10 Motor Nom Freq8.00 320.00 HzVaries111
P1.11 Motor Nom Speed2419200 rpm Varies112
P1.12 Motor Nom Currnt Varies VariesAVaries113
P1.13Motor Cos Phi0.301.000.74120
0 = Induction motor
1 = PM motor
Find this value U
the motor. Note also used connection
(Delta/Star).
Find this value f
motor.
Find this value n
the motor.
Find this value I
motor.
Find this value on the rating plate of the
motor
on the rating plate of
n
on the rating plate of the
n
on the rating plate of
n
on the rating plate of the
n
The drive searches for the minimum
motor current in order to save energy and
P1.14
Energy
optimization
010666
to lower the motor noise. This function
can be used e.g. in fan and pump
applications
0 = Disabled
1 = Enabled
The identification run calculates or
measures the motor parameters that are
necessary for a good control of the
motor and speed.
P1.15Identification010631
P1.16Start function010505
0 = No action
1 = At standstill
2 = With rotatio n
Before you do the identification run, you
must set the motor nameplate
parameters.
0 = Ramping
1 = Flying start
English (GB)
7
English (GB)
CodeParameterMinMax Unit DefaultIDDescription
P1.17Stop function010506
P1.18Automatic reset010731
P1.19External fault032701
P1.20AI Low Fault050700
P1.21Rem.Ctrl. Place010172
P1.22I/O A Ref sel195117
P1.23Keypad Ref sel192121
P1.24 Fieldbus Ref sel193122
P1.25 AI1 signal range010379
P1.26 AI2 signal range011390
0 = Coasting
1 = Ramping
0 = Disabled
1 = Enabled
0 = No action
1 = Alarm
2 = Fault (Stop according to stop mode)
3 = Fault (Stop by coasting)
Response when an analogue signal in
use goes below 50 % of the minimum
signal range. 0 = No action
1 = Alarm
2 = Alarm, Preset Freq
3 = Alarm, Previous Freq
4= Fault (Stop according to stop mode)
5 = Fault (Stop by coasting)
Selection of remote control place (start/
stop). Can be used to change back to
remote control e.g. in case of a broken
panel.
0 = I/O control
1 = Fieldbus control
Selection of ref source when control place
is I/O A
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1 + AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
Selection of ref source when control place
is keypad:
See P1.22
Selection of ref source when control place
is Fieldbus:
See P1.22
0 = 0…10 V / 0…20 mA
1 = 2…10 V / 4…20 mA
0 = 0…10 V / 0…20 mA
1 = 2…10 V / 4…20 mA
8
CodeParameterMinMax Unit DefaultIDDescription
Function selection for Basic R01:
0 = None
1 = Ready
2 = Run
3 = General fault
4 = General fault inverted
5 = General alarm
6 = Reversed
7 = At speed
8 = Thermistor fault
9 = Motor regulator active
10 = Start signal active
11 = Keypad control active
12 = I/O B control activated
13 = Limit supervision 1
14 = Limit supervision 2
15 = No fucntion
16 = No fucntion
17 = Preset speed active
18 = No fucntion
19 = PID in Sleep mode
20 = PID soft fill active
21 = PID supervision limits
22 = Ext. PID superv. limits
23 = Input press. alarm/fault
24 = Frost prot. alarm/fault
25 - 30 = No fucntion
P1.27RO1 function051211001
P1.28 Basic R02 function046311004 See P1.27
31 = RTC time chnl 1 control
32 = RTC time chnl 2 control
33 = RTC time chnl 3 control
34 = FB ControlWord B13
35 = FB ControlWord B14
36 = FB ControlWord B15
37 = FB ProcessData1.B0
38 = FB ProcessData1.B1
39 = FB ProcessData1.B2
40 = Maintenance alarm
41 = Maintenance fault
42 = No fucntion
43 = No fucntion
44 = Block Out. 1
45 = Block Out. 2
46 = Block Out. 3
47 = Block Out. 4
48 = Block Out. 5
49 = Block Out. 6
50 = Block Out. 7
51 = Block Out. 8
52 = Block Out. 9
53 = Block Out.10
54 = No function
55 = No function
56 = Auto-cleaning active
57 = Motor Switch Open
58 = TEST (Always Closed)
59 = No function
English (GB)
9
English (GB)
CodeParameterMinMax Unit DefaultIDDescription
P1.30AO1 function019210050
3.2.1 Standard application
You can use the Standard application in speedcontrolled processes where no special functions are
necessary, for example pumps, fans, or conveyors.
It is possible to control the drive from the keypad,
Fieldbus or I/O terminal.
When you control the drive with the I/O terminal, the
frequency reference signal is connected to AI1
(0…10 V) or AI2 (4…20 mA). The connection
depends the type of the signal. There are also 3
preset frequency references available. You can
activate the preset frequency references with DI4
and DI5. The start/stop signals of the drive are
connected to DI1 (start forward) and DI2 (start
reverse).
It is possible to configure all the drive outputs freely
in all the applications. There are 1 analogue output
(Output Frequency) and 3 relay outputs (Run, Fault,
Ready) available on the basic I/O board.
M1.31 Standard
0 = TEST 0 % (Not used)
1 = TEST 100 %
2 = Output freq (0 -fmax)
3 = Freq reference (0-fmax)
4 = Motor speed (0 - Motor nominal
speed)
5 = Output current (0-I
6 = Motor torque (0-T
7 = Motor power (0-P
8 = Motor voltage (0-U
9 = DC link voltage (0-1000 V)
10 = PID1 output (0-100 %)
11 = Ext.PID output (0-100 %)
12 = ProcessDataIn1 (0-100 %)
13 = ProcessDataIn2 (0-100 %)
14 = ProcessDataIn3 (0-100 %)
15 = ProcessDataIn4 (0-100 %)
16 = ProcessDataIn5 (0-100 %)
17 = ProcessDataIn6 (0-100 %)
18 = ProcessDataIn7 (0-100 %)
nMotor
nMotor
nMotor
nMotor
)
)
)
)
19 = ProcessDataIn8 (0-100 %)
CodeParameterMin Max Un it Default ID Description
P1.31.1 Preset Freq 1 P1.3 P1.4 Hz10.0105
P1.31.2 Preset Freq 2 P1.3 P1.4 Hz15.0106
P1.31.3 Preset Freq 3 P1.3 P1.4 Hz20.0126
Make the selection of a preset frequency with the
digital input DI4.
Make the selection of a preset frequency with the
digital input DI5.
Make the selection of a preset frequency with the
digital input DI4 and DI5.
10
3.2.2 Local/Remote application
Use the Local/Remote application when, for
example, it is necessary to switch between 2
different control places.
To change between the Local and the Remote
control place, use DI6. When Remote control is
active, you can give the start/stop commands from
Fieldbus or from I/O terminal (DI1 and DI2). When
Local control is active, you can give the start/stop
commands from the keypad, Fieldbus or I/O terminal
(DI4 and DI5).
For each control place, you can make a selection of
the frequency reference from the keypad, Fieldbus or
I/O terminal (AI1 or AI2).
It is possible to configure all the drive outputs freely
in all the applications. There are 1 analogue output
(Output Frequency) and 3 relay outputs (Run, Fault,
Ready) available on the basic I/O board.
M1.33 Local/Remote
CodeParameterMin Max UnitDefaultID Description
Selection of ref source when control place
P1.32.1I/O B Ref sel199131
P1.32.2I/O B Ctrl forceDigIN SlotA.6 343
P1.32.3I/O B Ref forceDigIN SlotA.6 411 Force control to fieldbus
P1.32.4Ctrl signal 1 BDigIN SlotA.4 423 Start signal 1 when control place is I/O B
P1.32.5Ctrl signal 2 BDigIN SlotA.5 424 Start signal 2 when control place is I/O B
P1.32.6 Keypad Ctrl forceDigIN Slot0.1 410 Force control to keypad
P1.32.7 Fieldbus Ctrl forceDigIN Slot0.1 411 Force control to fieldbus
P1.32.8Ext fault closeDigIN SlotA.3 405
P1.32.9Ext fault openDigIN Slot0.2 406
3.2.3 Multi-step application
You can use the Multi-step speed application with
processes where more than 1 fixed frequency
reference is necessary (for example test benches).
It is possible to use 1 + 7 frequency references: 1
basic reference (AI1 or AI2) and 7 preset references.
Make a selection of the preset frequency references
with digital signals DI4, DI5 and DI6. If none of these
inputs are active, the frequency reference is
removed from the analogue input (AI1 or AI2). Give
the start/stop commands from the I/O terminal (DI1
and DI2).
It is possible to configure all the drive outputs freely
in all the applications. There are 1 analogue output
(Output Frequency) and 3 relay outputs (Run, Fault,
Ready) available on the basic I/O board.
is I/O B. See above.
NOTE: I/O B control place can only be
forced active with digital input (P3.5.1.7).
TRUE = Used frequency reference is
specified by I/O reference B parameter
(P3.3.1.6).
You can use the PID control application with
processes where you control the process variable
(for example pressure) through control of the speed
of the motor.
In this application, the internal PID controller of the
drive is configured for 1 setpoint and 1 feedback
signal.
It is possible to use 2 control places. Make the
selection of the control place A or B with DI6. When
control place A is active, the start/stop commands
are given by DI1, and the PID controller gives the
frequency reference. When control place B is active,
start/stop commands are given by DI4, and AI1 gives
the frequency reference.
It is possible to configure all the drive outputs freely
in all the applications. There are 1 analogue output
(Output Frequency) and 3 relay outputs (Run, Fault,
Ready) available on the basic I/O board.
0 = Binary coded
1 = Number of inputs. Preset frequency is
selected according to how many of preset
speed digital inputs are active
FALSE = OK
TRUE = External fault
FALSE = External fault
TRUE = OK
12
M1.34 PID Control
CodeParameterMinMaxUnit Default IDDescription
If the value of the paramet er is set to
P1.34.1Gain0.00 1000.00%100.00 118
P1.34.2 Integration Time 0.00600.00s1.00119
P1.34.3 Derivation Time 0.00100.00s0.00132
P1.34.4FB 1 Source0202334
100 % a change of 10 % in the error
value causes the controller output to
change by 10 %.
If this parameter is set to 1,00 s a
change of 10 % in the error value
causes the controller output to change
by 10.00 %/s.
If this parameter is set to 1,00 s a
change of 10 % in the error value during
1.00 s causes the controller output to
change by 10.00 %.
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = AI5
6 = AI6
7 = ProcessDataIn1
8 = ProcessDataIn2
9 = ProcessDataIn3
10 = ProcessDataIn4
11 = ProcessDataIn5
12 = ProcessDataIn6
13 = ProcessDataIn7
14 = ProcessDataIn8
15 = Temperature input 1
16 = Temperature input 2
17 = Temperature input 3
18 = Temperature input 4
19 = Temperature input 5
20 = Temperature input 6
AI's and ProcessDataIn are handled as
% (0.00-100.00 %) and scaled
according to Feedback min and max.
NOTE: ProcessDataIn use two
decimals.
You can use the Multi-purpose application for
different processes (for example conveyors) where a
wide range of motor control functions is necessary.
It is possible to control the drive from the keypad,
Fieldbus or I/O terminal. When you use I/O terminal
control, the start/stop commands are given through
DI1 and DI2, and the frequency reference from AI1
or AI2.
There are 2 acceleration/deceleration ramps
available. The selection between Ramp1 and Ramp2
is made by DI6.
It is possible to configure all the drive outputs freely
in all the applications. There are 1 analogue output
(Output Frequency) and 3 relay outputs (Run, Fault,
Ready) available on the basic I/O board.
SP 1 Sleep
Delay
SP 1
WakeUpLevel
03000s01017
Varies 0.001018
0 = Not used
1 = Keypad setpoint 1
2 = Keypad setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 = ProcessDataIn1
10 = ProcessDataIn2
11 = ProcessDataIn3
12 = ProcessDataIn4
13 = ProcessDataIn5
14 = ProcessDataIn6
15 = ProcessDataIn7
16 = ProcessDataIn8
17 = Temperature input 1
18 = Temperature input 2
19 = Temperature input 3
20 = Temperature input 4
21 = Temperature input 5
22 = Temperature input 6
AI's and ProcessDataIn are handled as
percent (0.00-100.00 %) and scaled
according to Setpoint minimum and
maximum.
NOTE: ProcessDataIn signals use 2
decimals.
Drive goes to sleep mode when the
output frequency stays below this limit
for a time greater than that defined by
parameter Sleep delay.
The minimum amount of time the
frequency has to remain below the
Sleep level before the drive is stopped.
Defines the level for the PID feedback
value wake-up supervision. Uses
selected process units.
P1.35.7 Field WeakngPnt 8.00 P3.3.1.2 Hz Varies 602
P1.35.8Voltage at FWP 10.00 200.00%100.00 603
P1.35.9U/f Mid Freq0.00 P3.1.4.2 HzVaries 604
P1.35.10U/f Mid Voltg0.0100.0%100.0605
P1.35.11 Zero Freq Voltg0.0040.00%Varies 606
P1.35.12 StartMagnCurrent 0.00VariesAVaries 517
P1.35.13 StartMagnTime0,00600,00s0,00516
P1.35.14 DC Brake Current Varies VariesAVaries 507
P1.35.15DC BrakeTime0,00600,00s0,00508
P1.35.16DC Start Freq0,1010,00Hz1,50515
P1.35.17Load drooping0.0050.00%0.00620
P1.35.18
Start Acceleration
Time
Load drooping
time
0.13000.0s2.0502 Start Acceleration Time
0.002.00s0.00656
0 = U/f Freq ctrl open loop
1 = Speed control open loop
Automatic torque boost can be used in
application where starting torque due to
starting friction is high.
0 = Disabled
1 = Enabled
Type of U/f curve between zero
frequency and the field weakening
point.
0 = Linear
1 = Squared
2 = Programmable
The field weakening point is the output
frequency at which the output voltage
reaches the field weakening point
voltage
Voltage at field weakening point in % of
motor nominal voltage
Provided that the programmable U/f
curve has been selected (par. P3.1.4.1),
this parameter defines the middle point
frequency of the curve.
Provided that the programmable U/f
curve has been selected (par. P3.1.4.1),
this parameter defines the middle point
voltage of the curve.
This parameter defines the zero
frequency voltage of the U/f curve. The
default value varies according to unit
size.
Defines the DC current fed into motor at
start. Disabled if set to 0.
This parameter defines the time for how
long DC current is fed to motor before
acceleration starts.
Defines the current injected into the
motor during DC-braking.
0 = Disabled
Determines if braking is ON or OFF and
the braking time of the DC-brake when
the motor is stopping.
The output frequency at which the DCbraking is applied.
The drooping function enables speed
drop as a function of load. Drooping will
be defined in percent of nominal speed
at nominal load.
Load drooping is used in order to
achieve a dynamic speed drooping
because of changing load. This
parameter defines the time during which
the speed is restored to the level it was
before the load increase.
English (GB)
15
English (GB)
CodeParameterMinMaxUnit Default ID Description
P1.35.19
3.2.6 Motor potentiometer application
Use the Motor potentiometer application for the
processes where the frequency reference of the
motor is controlled (that is, increased and
decreased) through digital inputs.
In this application, the I/O terminal is set to the
default control place. the start/stop commands are
given with DI1 and DI2. The frequency reference of
the motor is increased with DI5 and decreased with
DI6.
It is possible to configure all the drive outputs freely
in all the applications. There are 1 analogue output
(Output Frequency) and 3 relay outputs (Run, Fault,
Ready) available on the basic I/O board.
M1.36 Motor Potentiom
CodeParameterMin Max Unit Default ID Description
P1.36.1 MotPot ramp time 0.1 500.0 Hz/s10.0331
P1.36.2MotPot Reset021367
P1.36.3Preset Freq 1P1.3 P1.4Hz20.0105
Load drooping
mode
0101534
0 = Normal; Load drooping factor is
constant through the whole frequency
range
1 = Linear removal; Load drooping is
removed linearly from nominal
frequency to zero frequency
Rate of change in the motor potentiometer
reference when increased or decreased with
parameters P3.3.4.1 or P3.3.4.2.
Motor potentiometer frequency reference reset
logic.
0 = No reset
1 = Reset if stopped
2 = Reset if powered down
Make the selection of a preset frequency with
the digital input DI4 and DI5.
16
4. User Interfaces
Graphical display
Back button / reset faults
Move cursor left
Scroll menu up / Increase value
Home button
Move cursor right
On button
Scroll menu down /
decrease value
Confirm selection
Off button
4.1 Keypad of the drive
The control keypad is the interface between the RSI
and the user. With the control keypad it is possible to
control the speed of a motor, to supervise the state
of the equipment and to set the AC drive's
parameters.
There are two keypad types you can choose for your
user interface: Keypad with graphical display and
Text keypad.
4.1.1 Buttons
The button section of the keypad is identical for both
keypad types.
English (GB)
Fig. 1Keypad buttons
4.1.2 Display
The keypad display indicates the status of the motor
and the drive and any irregularities in motor or drive
functions. On the display, the user sees information
about the drive and his present location in the menu
structure and the item displayed.
4.1.3 Navigation on keypad
The data on the control keypad are arranged in
menus and submenus. Use the Up and Down arrows
to move between the menus. Enter the group/item by
pressing the OK button and return to the former level
by pressing the Back/Reset button.
The Location field indicates your current location.
The Status field gives information about the present
status of the drive. See Figure 1.
17
4.1.4 RSI graphical keypad
9159.emf
Main Menu
Quick Setup
( 17 )
Parameters
( 12 )
STO PRE ADYI/ O
ID:M1
( 5 )
Monitor
Status fieldSTOP/RUN
Direction
ALARM
Status fieldREADY/NOT READY/FAULT
Control place:PC/IO/KEYPAD/FIELDBUS
Activated group/item:Press OKtoenter
Number ofitemsin the group
Location field(Parameter ID numberandcurrent menulocation
Status field
STOP/RUN
Status field
READY/NOT READY/FAULT
Direction
ALARM
Control place
PC/IO/KEYPAD/FIELDBUS
Location field
(Parameter ID number and current
menu location)
Activated group/item:
Press OK to enter
Number of items in the group
English (GB)
Fig. 2Main menu
Using the graphical keypad
Editing values
The selectable values can be accessed and edited in
two different ways on the graphical keypad.
Parameters with one valid value
Typically, one parameter is set one value. The value
is selected either from a list of values (see example
below) or the parameter is given a numerical value
from a defined range (e.g. 0.00...50.00 Hz).
18
Change value of a parameter following the
Start/Stop Setup
Rem Control Place
I/O Control
KeypadStopButton
Yes
Start Function
Ramping
STOPREADYI/ O
ID:172M3.2.1
Edit
Help
Add to favorites
Rem Control Place
STOPREADYI/ O
ID:M3.2.1
Rem Control Place
STO PREADYI/ O
M3.2.1
I/O Control
FieldbusCTRL
Start/Stop Setup
Rem Control Place
I/O Control
KeypadStopButton
Yes
Start Function
Ramping
STO PREADYI/ O
ID:172M3.2.1
Rem Control Place
STOPREADYI/ O
M3.2.1
I/O Control
FieldbusCTRL
OKOK
OK
BACK
RESET
OR:
9160.emf
9257.emf
OK
procedure below:
1. Locate the parameter.
2. Enter the Edit mode.
3. Set new value with the arrow buttons up/down.
You can also move from digit to digit with the
arrow buttons left/right if the value is numerical
and then change the value with the arrow buttons
up/down.
4. Confirm change with OK button or ignore change
by returning to previous level with Back/Reset
button.
Fig. 3Typical editing of values on graphical keypad (text value)
English (GB)
Fig. 4Typical editing of values on graphical keypad (numerical value)
19
Parameters with check box selection
9256.emf
...
OK
Symbol for checkbox selection
English (GB)
Some parameters allow selecting several values.
Make a check box selection at each value you wish
to activate as instructed below.
Fig. 5Applying the check box value selection on graphical keypad
Resetting fault
Instructions for how to reset a fault can be found in
chapter 7. Fault.
Function button
The FUNCT button is used for four functions:
1. to quickly access the Control page,
2. to easily change between the Local (Keypad) and
Remote control places,
3. to change the rotation direction and
4. to quickly edit a parameter value.
Control places
The control place is the source of control where the
drive can be started and stopped. Every control
place has its own parameter for selecting the
frequency reference source. The Local control place
is always the keypad. The Remote control place is
determined by parameter P3.2.1 (I/O or Fieldbus).
The selected control place can be seen on the status
bar of the keypad.
Remote control place
I/O A, I/O B and Fieldbus can be used as remote
control places. I/O A and Fieldbus have the lowest
priority and can be chosen with parameter P3.2.1
(Rem Control Place). I/O B, again, can bypass the
remote control place selected with parameter P3.2.1
using a digital input. The digital input is selected with
parameter P3.5.1.7 (I/O B Ctrl Force).
Local control
Keypad is always used as control place while in local
control. Local control has higher priority than remote
control. Therefore, if, for example, bypassed by
parameter P3.5.1.7 through digital input while in
Remote, the control place will still switch to Keypad if
Local is selected. Switching between Local and
Remote Control can be done by pressing the
FUNCT-button on the keypad or by using the "Local/
Remote" (ID211) parameter.
20
Changing control places
Main Menu
Parameters
( 15 )
Diagnostics
ST O PREADYKeypad
ID:M1
( 7 )
Monitor
( 6 )
ID:
Choose action
ST O PReadyKeypad
ID:1805
Local/Remote
Control page
Change direction
?
Remote
ID:
Local/Remote
ST OPREA DYKey pad
ID:211
Remote
Local
Main Menu
Parameters
( 15 )
Diagnostics
STO PREADYI/ O
ID:M1
( 7 )
Monitor
( 6 )
FUNCT
OK
OK
9161.emf
Main Menu
Parameters
( 15 )
Diagnostics
STOPREADYI/ O
ID:M1
( 7 )
Monitor
( 6 )
ID:
Choose action
STOPReadyKeypad
ID:1805
Local/Remote
Control page
Change direction
STOPREADYKeypad
( 6 )
Keypad Reference
0.00 Hz
Output Frequency
0.00Hz
Motor Current
0.00A
Motor Torque
0.00%
0.00%
Motor Power
ID:184
Keypad
0.00 Hz
Output Frequency
0.00Hz
Motor Current
0.00A
Motor Torque
0.00%
0.00%
Motor Power
ST O PREADYKeypad
( 6 )
ID:168
Keypad Reference
0.00 Hz
Output Frequency
0.00Hz
Motor Current
0.00A
Motor Torque
0.00%
0.00%
Motor Power
FUNCT
OK
OK
OK
9162.emf
Change of control place from Remote to Local
(keypad).
1. Anywhere in the menu structure, push the
FUNCT button.
2. Push the Arrow up or the Arrow down button to
select Local/Remote and confirm with the OK
button.
Fig. 6Changing control places
Accessing the control page
The Control page is meant for easy operation and
monitoring of the most essential values.
1. Anywhere in the menu structure, push the
FUNCT button.
2. Push the Arrow up or the Arrow down button to
select Control page and confirm with the OK
button.
3. On the next display, select Local or Remote and
again confirm with the OK button.
4. The display will return to the sam e location as it
was when the FUNCT button was pushed.
However, if the Remote control place was
changed to Local (Keypad) you will be prompted
for keypad reference.
3. The control page appears
If keypad control place and keypad reference are
selected to be used you can set the Keypad
Reference after having pressed the OK button. If
other control places or reference values are used
the display will show Frequency reference which
is not editable. The other values on the page are
Multimonitoring values. You can choose which
values appear here for monitoring (for this
procedure, see page 28).
English (GB)
Fig. 7Accessing Control page
21
Changing direction
Main Menu
Parameters
( 15 )
Diagnostics
STO PREADYI/ O
ID:M1
( 7 )
Monitor
( 6 )
ID:
Choose action
RUNRea dyKeypad
ID:1805
Local/Remote
Control page
Change direction
ID:
Choose action
RU NR eadyKeypad
ID:1805
Forward
Reverse
Main Menu
Parameters
( 15 )
Diagnostics
STO PREADYI/ O
ID:M1
( 7 )
Monitor
( 6 )
FUNCT
OKOK
9163.ai
English (GB)
Rotation direction of the motor can quickly be
changed by applying the FUNCT button.
Note! Changing direction command is not visible in
the menu unless the selected control place is Local.
1. Anywhere in the menu structure, push the Fu nct
button.
2. Push the Arrow up or the Arrow down button to
select Change direction and confirm with the OK
button.
Quick edit
Through the Quick edit functionality you can quickly
access the desired parameter by entering the
parameter's ID number.
1. Anywhere in the menu structure, push the
FUNCT button.
2. Push the Arrow up or the Arrow down buttons to
select Quick Edit and confirm with the OK button.
3. Then enter the ID number of parameter or
monitoring value you wish to access. Press OK
button to confirm.
4. Requested Parameter/Monitoring value appears
on the display (in editing/monitoring mode.)
3. Then choose the direction you wish to ru n the
motor to. The actual rotation direction is blinking.
Confirm with the OK button.
4. The rotation direction changes immediately and
the arrow indication in the status field changes.
22
Copying parameters
ST OPREA D YKe ypad
Main Menu
Favourites
( 0 )
( 4 )
ID:M6
User settings
I/O and Hardware
( 8 )
STOPREADYKeypad
Drive name
( 3 )
ID:
User settings
Application selection
HVAC
M6.5M6.5
Parameter backup
Drive
ST OPREA DYKey pad
Restore from keypad
ID:
Restore factory defaults
M6.5M6.5.1
Save to keypad
Parameter backup
OKOK
9164.emf
note: This feature is available in graphical keypad
only.
The parameter copy function can be used to copy
parameters from one drive to another.
The parameters are first saved to the keypad, then
the keypad is detached and connected to another
drive. Finally the parameters are downloaded to the
new drive restoring them from the keypad.
Before any parameters can successfully be copied
from the keypad to the drive, the drive has to be
stopped before the parameters are uploaded.
Fig. 8Parameter copy
Note: If the keypad is changed between drives of
different sizes, the copied values of these
parameters will not be used:
– Motor nominal current (P3.1.1.4)
– Motor nominal voltage (P3.1.1.1)
– Motor nominal speed (P3.1.1.3)
– Motor nominal power (P3.1.1.6)
– Motor nominal frequency (P3.1.1.2)
– Motor cos phii (P3.1.1.5)
– Switching frequency (P3.1.2.3)
– Motor current limit (P3.1.3.1)
– Stall current limit (P3.9.3.2)
– Stall time limit (P3.9.3.3)
– Stall frequency (P3.9.3.4)
– Maximum frequency (P3.3.1.2)
• First go into User settings menu and locate the
Parameter backup submenu. In the Parameter
backup submenu, there are three possible
functions to be selected:
• Restore factory defaults will re-establish the
parameter settings originally made at the factory.
• By selecting Save to keypad you can copy all
parameters to the keypad.
• Restore from keypad will copy all parameters
from keypad to a drive.
English (GB)
23
Help texts
( 6 )
Digital Inputs
Ctrl Signal 1 A
Ctrl Signal 1 B
STO PREADYI/ O
ID:403M3.5.1.1
Ctrl Signal 2 A
( 6 )
Add to favorites
STO PREADYI/ O
ID:403M3.5.1.1
Ctrl signal 1 A
Edit
Help
Start Signal 1 for control Place
I/O A. Start Signal 1
functionality chosen with I/O A
Logic in Start/Stop Setup Menu.
STOPREADYI/ O
Ctrl signal 1 A
ID:403
M3.5.1.1
OKOK
9165.emf
Basic Settings
Motor Nom Voltg
230.00 V
Motor Nom Speed
1430 rpm
STOPREADYI/ O
Motor Nom Freq
50.00 Hz
Edit
Help
Motor Nom Freq
STO PREADYI/ O
Add to favorites
Motor Nom Freq
was added to
favorites. Press OK
to continue.
STOPREADYI/ O
OKOK
9166.emf
English (GB)
The graphical keypad features instant help and
information displays for various items.
All parameters offer an instant help display. Select
Help and press the OK button.
Text information is also available for faults, alarms
and the startup wizard.
Fig. 9Help text example
Adding item to favorites
You might need to refer to certain parameter values
or other items often. Instead of locating them one by
one in the menu structure, you may want to add
them to a folder called Favorites where they can
easily be reached.
To remove an item from the Favorites, see chapter
4.2.7 Favorites.
Fig. 10 Adding item to Favorites
4.1.5 RSI text keypad
You can also choose a so-called Text keypad for
your user interface. It has mainly the same
functionality as the graphical keypad although some
of these are somewhat limited.
Keypad display
The keypad display indicates the status of the motor
and the drive and any irregularities in motor or drive
functions. On the display, the user sees information
about the drive and his present location in the menu
structure and the item displayed. If the text on the
text line is too long to fit in the display, the text will
scroll from left to right to reveal the whole text string.
24
Using the text keypad
9167.emf
Indicators:
Status
Indicators:
Alarm, Fault
Indicators:
Direction
Indicators:
Control place
Group or parameter name
Menu location
OKOKOK
BACK
RESET
9168.emf
Editing values
Change value of a parameter following the
procedure below:
1. Locate the parameter.
2. Enter the Edit mode by pressing OK.
3. Set new value with the arrow buttons up/down.
You can also move from digit to digit with the
arrow buttons left/right if the value is numerical
and change then the value with the arrow buttons
up/down.
4. Confirm change with OK button or ignore change
by returning to previous level with Back/Reset
button.
English (GB)
Fig. 11 Editing values
Resetting fault
Instructions for how to reset a fault can be found in
chapter 7. Fault on page 136.
Function button
The FUNCT button is used for four functions:
Control places
The control place is the source of control where the
drive can be started and stopped. Every control
place has its own parameter for selecting the
frequency reference source. The Local control place
is always the keypad. The Remote control place is
determined by parameter P3.2.1 (I/O or Fieldbus).
The selected control place can be seen on the status
bar of the keypad.
Remote control place
I/O A, I/O B and Fieldbus can be used as remote
control places. I/O A and Fieldbus have the lowest
priority and can be chosen with parameter P3.2.1
(Rem Control Place). I/O B, again, can bypass the
remote control place selected with parameter P3.2.1
using a digital input. The digital input is selected with
parameter P3.5.1.7 (I/O B Ctrl Force).
25
Local control
FUNCT
OKOK
9169.emf
9170.emf
FUNCT
OK
OK
English (GB)
Keypad is always used as control place while in local
control. Local control has higher priority than remote
control. Therefore, if, for example, bypassed by
parameter P3.5.1.7 through digital input while in
Remote, the control place will still switch to Keypad if
Local is selected. Switching between Local and
Remote Control can be done by pressing the
FUNCT-button on the keypad or by using the "Local/
Remote" (ID211) parameter.
Fig. 12 Changing control places
Accessing the control page
The Control page is meant for easy operation and
monitoring of the most essential values.
1. Anywhere in the menu structure, push the
FUNCT button.
2. Push the Arrow up or the Arrow down button to
select Control page and confirm with the OK
button.
Changing control places
Change of control place from Remote to Local
(keypad).
1. Anywhere in the menu structure, push the
FUNCT button.
2. Using the arrow buttons, select Local/Remote
and confirm with the OK button.
3. On the next display, select Local or Remote and
again confirm with the OK button.
4. The display will return to the sam e location as it
was when the FUNCT button was pushed.
However, if the Remote control place was
changed to Local (Keypad) you will be prompted
for keypad reference.
3. The control page appears
If keypad control place and keypad reference are
selected to be used you can set the Keypad
Reference after having pressed the OK button. If
other control places or reference values are used
the display will show Frequency reference which
is not editable.
Fig. 13 Accessing Control page
Changing direction
Rotation direction of the motor can quickly be
changed by applying the FUNCT button.
Note! Changing direction command is not visible in
the menu unless the selected control place is Local.
1. Anywhere in the menu structure, push the Fu nct
button.
2. Push the Arrow up or the Arrow down button to
select Change direction and confirm with the OK
button.
3. Then choose the direction you wish to ru n the
motor to. The actual rotation direction is blinking.
Confirm with the OK button.
4. The rotation direction changes immediately and
the arrow indication in the status field changes.
26
Quick edit
Through the Quick edit functionality you can quickly
access the desired parameter by entering the
parameter's ID number.
1. Anywhere in the menu structure, push the
FUNCT button.
2. Push the Arrow up or the Arrow down buttons to
select Quick Edit and confirm with the OK button.
3. Then enter the ID number of parameter or
monitoring value you wish to access. Press OK
button to confirm.
4. Requested Parameter/Monitoring value appears
on the display (in editing/monitoring mode.)
4.2 Grundfos PC tool
The PC tool is for commissioning and maintenance
of the RSI. Grundfos PC tool is an accessory
available in Grundfos Product Center.Menu structure
Click on and select the item you wish to receive more
information about (electronic manual).
Timer functions
PID Controller
ExtPID controller
Mainten. counters
Fieldbus data
Solar
Active faults
Reset faults
Fault history
Total counters
Trip counters
Software info
Basic I/O
Slot D
Slot E
Real time clock
Power unit settings
Keypad
RS-485
Ethernet
Language selections
Application selection
Parameter backup
Drive name
1
See chapter 4.2.7 Favorites.
English (GB)
27
4.2.1 Quick setup
Main Menu
Quick Setup
( 17 )
Parameters
( 12 )
ID:M1
STO PR EADYI/ O
( 5 )
Monitor
Monitor
Multimonitor
(13)
Basic
(13)
Timer functions
(10)
STO PRE ADYI/ O
ID:M2.1
0.0rpm
STO PR EADYI/ O
Multimonitor
0. 00 Hz
ID25FreqReference
Output Freq
0.00Hz
Motor Curre
0.00A
Motor Torque
0.00%
Motor Voltage
Motor Speed
Motor TemperaUnit TemperaDC-link volt
20.0 Hz
FreqReferenc
0.0V
0.0V81.9°C0.0%
ID:1M2.1.1.1
STO PReadyI / O
FreqReference
Output frequency
Motor Power
FreqReference
Motor Speed
Motor Current
Motor Torque
0.00 Hz
10.00 Hz
0.00 rpm
0.00 A
0.00 %
0.00 %
OKOK
OKOK
9171.emf
English (GB)
In the Quick Setup parameter group you will find the
different wizards of the Grundfos RSI. More detailed
information on the parameters of this group you will
find in chapter 3. Startup.
4.2.2 Monitor
Multi-monitor
Note: This menu is not available in text keypad.
On the multi-monitor page, you can collect four to
nine values that you wish to monitor.
Fig. 14 Multi-monitoring page
Change the monitored value by activating the value
cell (with arrow buttons left/right) and clicking OK.
Then choose a new item on the Monitoring values
list and click OK again. More detailed information on
the monitor items can be found in chapter
5. Monitoring Menu.
Trend curve
The Trend Curve feature is a graphical presentation
of two monitor values at a time.
Basic
The basic monitoring values are the actual values of
selected parameters and signals as well as statuses
and measurements.
I/O
Statuses and levels of various input and output
signal values can be monitored here.
Extras/Advanced
Monitoring of different advanced values, e.g. fieldbus
values.
Timer functions
Monitoring of timer functions and the Real Time
Clock.
28
PID Controller
Monitoring of PID controller values.
External PID Controller
Monitoring of external PID controller values.
Maintenance counters
Monitoring of values related to Maintenance
counters.
Fieldbus data
Fieldbus data shown as monitor values for
debugging purposes at e.g. fieldbus commissioning.
Solar
Monitoring of values related to Solar specific
application.
4.2.3 Parameters
Through this submenu, you can reach the application
parameter groups and parameters. More information
on parameters in chapter 6. Parameters.
4.2.4 Diagnostics
Under this menu, you can find Active faults, Reset
faults, Fault history, Total counters, Trip counters
and Software info.
Active faults
MenuFunctionNote
When a fault/faults appear(s), the
display with the name of the fault starts
Active faults
Reset faults
MenuFunctionNote
Reset faults
Fault history
MenuFunctionNote
Fault history
to blink. Press OK to return to the
Diagnostics menu. The Active faults
submenu shows the number of faults.
Select the fault and push OK to see the
fault-time data.
In this menu you can reset faults. For
closer instructions, see chapter 7. Fault.
40 latest faults are stored in the Fault
history.
The fault remains active until it is cleared
with the Reset button (push for 2 s) or with
a reset signal from the I/O terminal or
fieldbus or by choosing Reset faults (see
below).
The memory of active faults can store the
maximum of 10 faults in the order of
appearance.
CAUTION! Remove external Control
signal before resetting the fault to prevent
unintentional restart of the drive.
Entering the Fault history and clicking OK
on the selected fault shows the fault time
data (details).
English (GB)
29
Total counters
English (GB)
CodeParameterMin MaxUnitDefault ID Description
V4.4.1Energy counterVaries2291
V4.4.3
V4.4.4
V4.4.5
V4.4.6
V4.4.7
V4.4.8
V4.4.9
V4.4.10
V4.4.11
V4.4.12
V4.4.13
V4.4.14
V4.4.15
Operating time
(graphical keypad)
Operating time
(text keypad)
Operating time
(text keypad)
Operating time
(text keypad)
Run time
(graphical keypad)
Run time
(text keypad)
Run time
(text keypad)
Run time
(text keypad)
Power on time
(graphical keypad)
Power on time
(text keypad)
Power on time
(text keypad)
Power on time
(text keypad)
Start command
counter
a d hh:min2298 Control unit operating time
a
dControl unit operating time in total days
hh:min:ss
a d hh:min2293 Motor running time
aMotor running time in total years
dMotor running time in total days
hh:min:ss
a d hh:min2294
aPower on time in total years
dPower on time in total days
hh:min:ss
Amount of energy taken from supply
network. No reset.
note for text keypad: The highest
energy unit shown on the standard
keypad is MW. Should the counted
energy exceed 999.9 MW, no unit is
shown on the keypad.
Control unit operating time in total
years
Control unit operating time in hours,
minutes and seconds
Motor running time in hours, minutes
and seconds
Amount of time the power unit has been
powered so far. No reset.
Power on time in hours, minutes and
seconds
The number of times the power unit has
2295
been started.
30
Loading...
+ 114 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.